Tensar Earth Retaining Structures Design Analysis Output from TensarSoil Version 2.04 Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading) Client: Odebrecht Project: Carretera Constanza-Jarabacoa H=2.40mts, Embedment=.60 mts, Slope at toe, Aceleración Sísmica (a) =.2g. Tensar Earth Retaining Structure Mesa Std Connector IMPORTANT NOTES (Preliminary/Conceptual Design) (1) This printout contains an Application Suggestion which has been prepared by a Tensar affiliate or by LICENSEE to enable the application of Tensar Geogrids to be evaluated by a qualified and experience professional engineer. The calculations are derived from a standardized software program which generally follows AASHTO or NCMA design methodologies and which has been modified to incorporate certain properties of Tensar® products. (2) This printout provides certain limited information for preliminary or conceptual design only, and does not itself constitute a design or plan suitable for construction. A final engineered design and plan, with drawings and installation details and construction requirements, signed and sealed by a registered professional engineer, is required prior to actual construction. (3) Any mechanically-stabilized earth structure involves various engineering, design, material, construction and end-use considerations. Many of these are site specific, such as (but not limited to) terrain and grading, watertable, the nature and strength of the foundation and backfill soils, the quality and compaction of the backfill, surface and subsurface water control and drainage, the presence of utilities and other elements in or around the structure, use of proper equipment and construction practices during installation, neighboring construction activity, load factors, other environmental factors and the like. Final determination of the suitability of any information or material for the use contemplated and the manner of use is the sole responsibility of the user and its professional advisors, who must assume all risk and liability in connection therewith. Tensar assumes no responsibility or liability to the recipient or any third party for the whole or any part of the content of any Application Suggestion or other work product. Tensar is a registered trademark. Method of analysis The calculation method used in this Design Analysis is the tie-back wedge method for MSE walls given in Chapter 4 of Mechanically Stabilized Earth Walls and Reinforced Soil Slopes, Design & Construction Guidelines, Federal Highway Administration, Demonstration Project 82, Publication No FHWA-SA-96-071 (August, 1997). Reference Date Page Apr 2 2011 1 of 9 Design analysis prepared by Designer 123 Tensar International Corporation Atlanta Office 5883 Glenridge Drive, Suite 200 Tel: +1 404 2501290 Atlanta Fax: +1 404 2509185 GA 30328 E-mail: [email protected] United States of America www.tensar-international.com

Upload: mauricio-santisteban-campos-robles

Post on 14-Apr-2016

212 views

Category:

Documents


0 download

DESCRIPTION

geo

TRANSCRIPT

Page 1: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

Output from TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Client: Odebrecht

Project: Carretera Constanza-Jarabacoa

H=2.40mts, Embedment=.60 mts, Slope at toe, Aceleración Sísmica (a)=.2g.

TensarEarth RetainingStructure

Mesa Std Connector

IMPORTANTNOTES(Preliminary/ConceptualDesign)

(1) This printout contains an Application Suggestion which has been prepared by a Tensar affiliate or by LICENSEE to enable the application of Tensar Geogrids to beevaluated by a qualified and experience professional engineer. The calculations are derived from a standardized software program which generally follows AASHTO orNCMA design methodologies and which has been modified to incorporate certain properties of Tensar® products.

(2) This printout provides certain limited information for preliminary or conceptual design only, and does not itself constitute a design or plan suitable for construction. A finalengineered design and plan, with drawings and installation details and construction requirements, signed and sealed by a registered professional engineer, is required priorto actual construction.

(3) Any mechanically-stabilized earth structure involves various engineering, design, material, construction and end-use considerations. Many of these are site specific, suchas (but not limited to) terrain and grading, watertable, the nature and strength of the foundation and backfill soils, the quality and compaction of the backfill, surface andsubsurface water control and drainage, the presence of utilities and other elements in or around the structure, use of proper equipment and construction practices duringinstallation, neighboring construction activity, load factors, other environmental factors and the like. Final determination of the suitability of any information or material for theuse contemplated and the manner of use is the sole responsibility of the user and its professional advisors, who must assume all risk and liability in connection therewith.Tensar assumes no responsibility or liability to the recipient or any third party for the whole or any part of the content of any Application Suggestion or other work product.

Tensar is a registered trademark.

Method of analysis

The calculation method used in this Design Analysis is the tie-back wedge method for MSE walls given inChapter 4 of Mechanically Stabilized Earth Walls and Reinforced Soil Slopes, Design & ConstructionGuidelines, Federal Highway Administration, Demonstration Project 82, Publication No FHWA-SA-96-071(August, 1997).

Reference Date Page Apr 2 2011 1 of 9

Design analysisprepared by

Designer

123

Tensar International Corporation Atlanta Office

5883 Glenridge Drive, Suite 200

Tel: +1 404 2501290 Atlanta

Fax: +1 404 2509185 GA 30328

E-mail: [email protected] United States of America

www.tensar-international.com

Page 2: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 2 of 9

Input data and Section Project: Carretera Constanza-Jarabacoa

1

90° 90°

26°

0.60

1.002.40

2.50

Datum

Tensar earth retaining structure Mesa Std Connector

All dimensions in metres Scale 1:50Seismic loading case

Fill/foundation propertiesDesign soilstrengthparameters arepeak values

Soil zone c' φ φ φ φ ' γ γ γ γ bulk

(kN/m²) (°) (kN/m³)

Reinforced soil 0.0 30.0 19.0

Retained soil 5.0 35.0 19.0

Foundation soil 5.0 30.0 17.6

Page 3: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 3 of 9

Seismicdesign datag =accelerationdue to gravity

Input Limiting External mechanisms Internal mechanismsdeformation

Ah = 0.20g 50 mm kh(ext) = 0.11g kh(int) = 0.25g

Av = 0.00g 50 mm kv(ext) = 0.00g kv(int) = 0.00g

Vertical accelerations may act either downwards or upwards

Soil-geogridinteractionfactors

Sliding coefficient Cds Pullout scale factor α α α α0.67 0.80

Pullout coefficient Ci is given in

reinforcement layout table

Surchargesx values aremeasured from thetop of thereinforced fillblock.

No Load acts from x (m) To x (m) Load (kN/m²) Live load/Dead load

1 0.49 99.98 18 Live load

Waterpressure data

Location Height of water level above datum (m) ru

In front of structure No water pressures

Within fill No water pressures NA

Externalstabilityresults

Mechanism Result Min/Max Critical load case OK?

Eccentricity 1.37 ft max0.050 m Static OK

Overturning OK2.00 minFS = 13.47 Static

Sliding on base 1.50 minFS = 4.55 Static OK

Bearing capacity 2.500 minFS = 8.234 Static OK

Internalstabilityresults

Mechanism OK? Mechanism OK?

Rupture check OK Pullout check OK

Internal sliding OK Connection check OK

ReinforcementlayoutStarting andfinishing levelsare related todatum

Tensar No of Starting Vertical Finishing Coverage Cigeogrid layers level (m) spacing (m) level (m) (%)

UX1400MSE 3 0.80 0.60 2.00 100 0.67

UX1400MSE 1 0.20 - - 100 0.67

Page 4: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 4 of 9

Requiredminimumfactors ofsafetyAs given in Chapter 2.7and Chapter4.3 d & e (forseismic internal& connection)

Mechanism Static loading Seismic loading

Eccentricity e<B/6 on soil, e<B/4 on rock E<B/3 all cases

Overturning FS = 2.0 FS = 1.5

Sliding on base and geogrid FS = 1.5 FS = 1.125

Bearing capacity FS = 2.5 FS = 1.875

Geogrid rupture FS = 1.5 FS = 1.125

Geogrid pullout FS = 1.5 FS = 1.125

Connection with facing FS = 1.5 FS = 1.1

Furtherinformationrelevent tothisTensarEarthRetentionSystem

Further information, specifications and bill of quantitiesdescriptions for this Tensar Earth Retaining Structureare given in the following documents which form part of this Design Analysis

System overviewInstallation guideCase histories

The current versions of these documents may be found by following the website linkto "Tensar Documentation" in the Help menu of the TensarSoil program

For program users who do Tensar International Corporationnot have a link to the internet Tel: +1 866 2664980contact your nearest Tensar Fax: +1 404 2509185representative or distributor E-mail: [email protected]

Web: www.tensarcorp.com

Page 5: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 5 of 9

Detailed calculation resultsThe following tables provide the detailed results from the design Analysis, including geogrid design data, together with bothexternal and internal analysis results.

Geogrid reinforcement design dataGeogrid strength is calculated following Chapter 3.5 Section b (geosynthetic reinforcement).Connection data given below is defined in Chapter 4.3 Section e and the values given are for the facing system indicated on Page 2.

Design temperature (°C) Design life (years)20 120

Tensar Ultimate Creep Durability Installation FS Design Connection datageogrid strength factor factor damage strength

(kN/m) (kN/m)

TaTult CRs CRuRFcr RFd RF id

UX1400MSE 70.00 1.10 1.10 1.502.60 22.28 0.27 1.00

Geogrid coordinates and design dataLevels are measured from the datum and horizontal location is measured from the toe of the wall

Tensar Level Left end Right end Length Coverage Pullout interactionGeogrid (m) (m) (m) (m) % factor Ci

UX1400MSE 2.000 0.295 3.516 3.221 100.0 0.670UX1400MSE 1.400 0.290 2.511 2.221 100.0 0.670UX1400MSE 0.800 0.285 2.506 2.221 100.0 0.670UX1400MSE 0.200 0.281 2.502 2.221 100.0 0.670

Page 6: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 6 of 9

External stability - unfactored calculated forces

Forces are calculated as per Chapter 4.2 for both static and seismic loading.

Note: negative forces are upwards

Loading direction Units Vertical Horizontal

Static force components

Forces in or above reinforced block:Soil mass kN/m 101.268Facing kN/m 8.698Dead loads kN/m 0.000Live loads kN/m 31.202

Forces behind reinforced block:From soil kN/m -0.017 2.121From dead loads kN/m 0.000 0.000From live loads kN/m -0.091 11.578

Additional force components due to seismic loading

Forces in or above reinforced block:Soil mass kN/m 0.000 4.637Facing kN/m 0.000 0.961Dead loads kN/m 0.000 0.000Live loads kN/m 0.000 0.000

Forces behind reinforced block:From soil kN/m -0.013 1.689From dead loads kN/m 0.000 0.000From live loads kN/m 0.000 0.000

External stability - eccentricity and overturning

Calculations carried out as per Chapter 4.2 Section d, to establish eccentricity for static loading and

Section h for seismic loading. In addition an overturning calculation is carried out.

Calculation Units Static loading Seismic loading

Total vertical load on base kN/m 109.858 109.936Total moment on base about centreline kNm/m 5.443 0.584Eccentricity m 0.050 0.005

Maximum permitted m 0.417 0.833

OK? OK OK

Driving moment about toe kNm/m 10.573 5.828Restoring moment about toe kNm/m 142.452 142.664FS (overturning) 13.474 24.480

Requirement 2.00 1.50

OK? OK OK

Page 7: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 7 of 9

External stability - sliding

Calculations carried out as per Chapter 4.2 Section e for static loading and Section h for seismic

loading.

Calculation Units Static loading Seismic loading

Horizontal driving force kN/m 13.699 9.407Horizontal resisting force kN/m 63.427 63.472FS (sliding) 4.630 6.747

Requirement 1.50 1.13

OK? OK OK

Additional sliding check

For inclined structures an additional sliding check is carried out with the back of the reinforced soil

block defined by a series of steeper lines until the lowest FS value is obtained.

Critical inclination of wall back deg 90.000 90.000Horizontal driving force kN/m 14.042 9.624Horizontal resisting force kN/m 63.933 63.933FS (sliding) 4.553 6.643

Requirement 1.50 1.13

OK? OK OK

External stability - bearing capacity check

Calculations carried out as per Chapter 4.2 Section f for static loading and Section h for seismic

loading, using Meyerhof load distribution to take into account eccentricity. The effect of load

inclination is omitted in accordance with Chapter 3.4 Section a.

Calculation Units Static loading Seismic loading

Total vertical load on base kN/m 141.060 109.936Total horizontal load on base kN/m 13.699 9.407Total moment on base about centreline kNm/m -7.104 0.584Factor Nc 26.240 26.240

Factor Nq 14.166 14.166

Factor Nγγγγ 15.154 15.154

Effective length L' m 2.500 2.489Ultimate bearing pressure kN/m² 464.582 463.166Applied bearing pressure kN/m² 56.424 44.162FS (bearing capacity) 8.234 10.488

Requirement 2.50 1.875

OK? OK OK

Page 8: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 8 of 9

Internal stability - static loadingCalculations carried out as per Chapter 4.3 Section b (tension check), Section c (pullout check) andSection e (connection check).

Geogrid Data Factor of safety

Tensar Level Length Sv Cov Ta Tmax FS FSpo FScon FScon

geogrid (m) (m) (m) % (kN/m) (kN/m) tension pullout rupture pullout

UX1400MSE 2.00 3.22 0.70 100 22.28 5.55 FS4.02 1.77 4.42 3.41UX1400MSE 1.40 2.22 0.60 100 22.28 6.61 FS3.37 2.53 3.71 2.86UX1400MSE 0.80 2.22 0.60 100 22.28 8.89 FS2.51 3.74 2.76 2.13UX1400MSE 0.20 2.22 0.50 100 22.28 9.31 FS2.39 5.86 2.63 2.03

Minimum requirement ≥1.5 ≥1.5 ≥1.5 ≥1.5

Internal stability - seismic loadingCalculations carried out as per Chapter 4.3 Section d (seismic check, both tension and pullout) andSection e (connection check for seismic).

Geogrid Data Factor of safety

Tensar Level Length Sv Cov Ta Tmax Tmd FS FSpo FScon FScon

geogrid (m) (m) (m) % (kN/m) (kN/m) (kN/m) tension pullout rupture pullout

UX1400MSE 2.00 3.22 0.70 100 22.28 1.77 2.20 8.505 1.972 9.64 3.81UX1400MSE 1.40 2.22 0.60 100 22.28 3.80 1.50 5.089 2.525 5.67 2.85UX1400MSE 0.80 2.22 0.60 100 22.28 6.08 1.86 3.278 3.345 3.64 1.90UX1400MSE 0.20 2.22 0.50 100 22.28 6.97 2.22 2.848 4.744 3.16 1.64

Minimum requirement ≥1.125 ≥1.125 ≥1.1 ≥1.1

Page 9: Hw=2.40_mts,_Wembedment=.6mt,_seismic

TensarEarth Retaining Structures

Design Analysis

TensarSoil Version 2.04

Calculations in accordance with: Demo 82 (FHWA 1997) (seismic loading)

Reference Date Page Apr 2 2011 9 of 9

Internal sliding check - sliding on geogrids

DEMO 82 does not include a specific requirement or definition for checking sliding on geogrids, socalculations are carried out as per the external check, Chapter 4.2 Section e for static loadingand Section h for seismic loading.

Geogrid Data Static loading Seismic loading

Tensar Level Cov Ci Driving Resisting FSSL Driving Resisting FSSL

geogrid (m) % forces forces Sliding forces forces Sliding (kN/m) (kN/m) (kN/m) (kN/m)

UX1400MSE 2.00 100 0.670 0.25 17.77 72.15 0.18 17.78 100.00UX1400MSE 1.40 100 0.670 2.14 28.97 13.52 0.29 28.98 100.00UX1400MSE 0.80 100 0.670 5.87 40.16 6.84 2.63 40.18 15.28UX1400MSE 0.20 100 0.670 11.44 51.35 4.49 7.37 51.38 6.97

Minimum requirement ≥1.5 ≥1.125