hvdc network: dc fault ride-through improvement · 5 permit the whole hvdc network to recover...

8
[email protected] HVDC Network: dc fault ride-through improvement G.P. ADAM, G.KALCON, S.J. FINNEY, D. HOLLIDAY, O.ANAYA-LARA AND B.W. WILLIAMS University of Strathclyde, UK Electronic and Electrical Engineering Department Institute of Energy and Environment SUMMARY This paper compares the transient behaviour of two HVDC networks with similar structures but which use different converter topologies, namely two-level and H-bridge modular multilevel converters. The key objective of this comparison is to show that the use of HVDC converters that inherent dc fault reversed blocking capability is beneficial to the HVDC networks in term of dc fault ride-through capability improvement (may reduce the risk of converter stations damage from over-current during dc side faults). The improvement in the HVDC network dc fault ride-through capability is achieved by stopping grid contribution to the fault current, and minimization of the transient component due to discharge of the dc side capacitors. Therefore HVDC networks that use converter stations with dc fault reversed blocking capability are expected to recover swiftly from dc side faults compared to those using converter stations without dc fault reversed blocking capability. To illustrate the outcomes of this comparison, the responses of both HVDC networks are examined when subjected to dc side faults. Issues such as lead-through and inrush currents in the ac and dc sides during and following dc faults are discussed. KEYWORDS Current source converter, dc fault ride-through capability, dc fault reversed blocking capability, high- voltage dc network and voltage source converters. CIGRÉ Canada 21, rue d’Artois, F-75008 PARIS CIGRÉ-122 Conference on Power Systems http : //www.cigre.org Halifax, September 6- 8, 2011

Upload: doanh

Post on 12-Apr-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

[email protected]

HVDC Network: dc fault ride-through improvement

G.P. ADAM, G.KALCON, S.J. FINNEY, D. HOLLIDAY, O.ANAYA-LARA AND B.W. WILLIAMS

University of Strathclyde, UK Electronic and Electrical Engineering Department

Institute of Energy and Environment

SUMMARY

This paper compares the transient behaviour of two HVDC networks with similar structures

but which use different converter topologies, namely two-level and H-bridge modular

multilevel converters. The key objective of this comparison is to show that the use of HVDC

converters that inherent dc fault reversed blocking capability is beneficial to the HVDC

networks in term of dc fault ride-through capability improvement (may reduce the risk of

converter stations damage from over-current during dc side faults). The improvement in the

HVDC network dc fault ride-through capability is achieved by stopping grid contribution to

the fault current, and minimization of the transient component due to discharge of the dc side

capacitors. Therefore HVDC networks that use converter stations with dc fault reversed

blocking capability are expected to recover swiftly from dc side faults compared to those

using converter stations without dc fault reversed blocking capability. To illustrate the

outcomes of this comparison, the responses of both HVDC networks are examined when

subjected to dc side faults. Issues such as lead-through and inrush currents in the ac and dc

sides during and following dc faults are discussed.

KEYWORDS Current source converter, dc fault ride-through capability, dc fault reversed blocking capability, high-

voltage dc network and voltage source converters.

CIGRÉ Canada 21, rue d’Artois, F-75008 PARIS CIGRÉ-122 Conference on Power Systems http : //www.cigre.org Halifax, September 6- 8, 2011

2

1. INTRODUCTION The current trend in the developed world towards increasing the penetration of intermittently available

renewable power into the power system networks represent a major concern to the transmission

system operators (TSO) regarding system stability, supply security and reliability. One way to address

these concerns is to use a large number of distributed storage systems with different time-scales,

ranging from few seconds to several hours, to balance out the impact of the renewable power

variability on the ac networks operation and improve power quality. Alternatively, large HVDC

networks may be required to accommodate increased penetration of renewable power into the power

system networks without the need for bulky storage systems and voltage stability problems at the ac

sides [1]-[4]. Such a solution is currently under consideration for accommodation of next generation

large offshore wind farms in the North Sea into UK, Norway, German and Danish power systems.

At the present, voltage source converter high-voltage dc (VSC-HVDC) transmission systems have

become competitive compared to systems that use thyristor current source converters in terms of

power handling capability, dc operating voltage, reliability and technology maturity, and

semiconductor losses [2]-[7]. These improvements have been achieved using two-level converters

with series connected insulated gate commutated bipolar transistors (IGBT), and multilevel converters

[4]-[5]. Voltage source converter systems also offer several invaluable features to the ac side networks

that are not available in current source systems such as independent control of active and reactive

power, provision of voltage support, reversal of power flow without increasing voltage stresses on dc

cables and interfacing transformers (dc link polarity reversal), and resilience to ac side faults[2]. These

features are attractive for practical realisation of HVDC networks. Some of the claimed benefits of

multi-terminal HVDC networks are increased flexibility of power flow control and dispatch,

asynchronous connection of regional networks (which prevents ac faults propagation and improves ac

system transient stability), and that the topology may facilitate connection of large offshore wind

farms dispersed over wide area [1].

However, the vulnerability of the HVDC networks to dc side faults and the absence of dc circuit

breakers capable of operating at high voltage to isolate dc fault currents represent major barriers

toward the evolution of the dc grid. The main vulnerabilities of HVDC networks during dc side faults

are:

• The risk on converter switches from over-current due to grid contribution to dc fault current

during dc side faults, and inrush current during recovery without interruption as the dc link

voltage builds up after the fault is cleared.

• DC side faults expose dc circuit breakers to high lead-through currents of the order of 40kA to

60kA, which are not easy to handle by fast semiconductor circuit breakers. The magnitude of

these lead-through-currents depends upon the amount of reservoir capacitance connected to

the dc side, and the stray capacitance of the dc cables which is line length dependent.

Several new voltage source converter topologies have been specially developed to address these

vulnerabilities. Some of these converters are H-bridge and alternative arm modular multilevel

converters, and hybrid multilevel converter with H-bridge cells in the ac side [2],[7]-[11]. These

converters inherently provide dc fault reverse blocking capability, i.e. they have the ability to stop the

active power exchange between the ac and dc sides and the reactive power flow between the converter

and ac side, and hence the current flow in the converter switches during dc side faults).

To show the potential improvement that may be achieved in HVDC network transient response during

dc side faults with converter stations which have inherent dc fault reverse blocking capability, this

paper compares the performance of the two HVDC networks using converter stations based on two-

level converters without reversed blocking capability and H-bridge modular multilevel converters with

dc fault reversed blocking capability. This comparison is focused on the HVDC network transient

response during dc side faults. The issues that influence HVDC recovery from a dc fault and the rating

of potential dc circuit breakers are discussed

3

2. REVIEW OF TWO-LEVEL AND H-BRIDGE MODULAR CONVERTERS

(A) Two-level converter

Fig. 1a shows a one-phase two-level converter. This converter is capable of generating output voltage

with two voltage levels, +½Vdc and –½Vdc between ‘a’ and an imaginary supply mid-point ‘0’ as

shown in Fig. 1a. It can be controlled using modulation strategies such as carrier based pulse width

modulation, selective harmonic elimination modulation and space vector modulation. The first two

modulation strategies are preferred in HVDC transmission systems due to their robust dynamic

performance during network disturbances. The main drawbacks of two-level converter HVDC systems

are high semiconductor losses (predominantly switching losses), exposure of converter transformers

to high voltage stresses (dv/dt) that result from fast switching of large voltage steps (therefore,

requiring expensive converter transformers to withstand high voltage stresses) and the requirement for

relatively large ac filters at the converter output. The topology also lacks dc fault reverse blocking

capability.

(B) H-bridge modular converter

Figs. 1b and 1c show one-phase and three-phase H-bridge modular converters with two and N cells

per arm respectively. H-bridge modular multilevel converters can be controlled using multilevel pulse

width modulation or amplitude modulation with one or two modulating signals per phase. A capacitor

voltage balancing mechanism is required to ensure that the voltage stresses on switching devices are

controlled. Each converter arm in Fig. 1b must be able to support the full dc link voltage. As a result,

the number of switching devices in the conduction path at any instant is twice that of the two-switch

modular converter, which results in higher on-state losses. The use of full-bridge cells instead of half-

bridge cells introduces a new set of redundant switch states in the phase voltage that allows the voltage

error in the cell capacitors to be corrected within sub-cycles of the fundamental period. This also

permits the use of smaller cell capacitors compared to the two-switch modular converter, and hence a

relatively modest reduction in converter footprint. An important inherent feature of the H-bridge

modular multilevel converter is its dc fault reverse blocking capability. This feature enables the

converter to block the current flow in the converter switches (IGBTs and their freewheeling diodes)

during dc side faults, hence no active and reactive power exchange occurs with the ac sides (zero

current, zero active and reactive power exchange). Such a feature is significant from the converter

protection point of view. However, its value is debatable from the transmission system operators

(TSO) point of view since the reduction in active power exchange between the ac networks to zero

may cause over-frequency in some ac networks that suffer from over-generation, and frequency drop

in other ac networks that experience under-generation. Nevertheless, this paper discusses the topic

from the power converter protection standpoint without consideration of the ac side dynamics.

3. HVDC NETWORK DC FAULTS Conventional voltage source converter HVDC networks rely on the converter station’s control systems

to ride-through ac and dc side faults. During dc side faults, the fault currents in the dc side comprise

the ac network’s contribution through the converter’s freewheeling diodes, and discharge currents

from the converter’s reservoir (dc link) capacitors and dc cable stray (distributed) capacitance. The

discharge current from the reservoir capacitors and cable capacitance represent transient components

of the dc fault current. The magnitudes of these currents are much larger than the grid contribution

through the converter’s freewheeling diodes. As a result, dc fault interruption may require dc circuit

breakers capable of handing high lead-through currents (the first few cycles of the transient component

of dc fault currents due to the dc side capacitor discharge), high current breaking capacity and fast

interruption time. The dc side capacitors may also influence the recovery speed of the HVDC network

from dc side faults, as they draw large currents from the ac networks during the recovery of the

collapsed dc link voltage following the fault clearance.

4

(a) One-phase two-level converter

(b) One-phase H-bridge M2C

with two cells per arm

(c) Three-phase H-bridge M2C with N cells per arm

Fig.1: Schematic diagram of two-level and H-bridge modular multilevel converters

The use of HVDC converter topologies without common dc link capacitors (with no dc link

capacitors) , such as two-switch modular multilevel converters, may completely eliminate the transient

components of the dc fault in HVDC systems connected in a back-to-back configuration, and may

achieve significant reduction in the magnitude of this component in long distance HVDC transmission

systems. Therefore, such converter topologies may permit the use of dc circuit breakers with relatively

low lead-through currents and relatively low dc current breaking capability. Additionally, the use of

such converters may improve the speed of recovery of HVDC systems from temporary dc side faults

and, since the cell capacitors do not contribute to the dc fault current when the gate signals to the

converter switches are inhibited, reduce the risk of device failure due to over-current on the converter

switches. Combining the features of elimination of the converter dc link capacitors with dc fault

reverse blocking capability, such as in the H-bridge M2C configuration of Fig. 1, may allow the use of

dc circuit breakers with relatively low lead-through currents and current breaking capacity, and

relatively slow interruption time to isolate permanent dc faults in the HVDC networks. This may

5

permit the whole HVDC network to recover without interruption from a temporary or permanent dc

side fault in a relatively short time without significant risk to the converter stations and to the stability

of the ac networks. The major drawback of this approach, beside increased semiconductor losses, is

that the power transfer capability of the whole system is reduced to zero during the entire dc fault

period.

4. TEST SYSTEM AND SIMULATIONS

Fig. 2 shows a generic four terminal HVDC network that will be used in this paper to assess the

viability of converters with dc fault reverse blocking capability in improving the resilience of the dc

grid to dc side faults. VSC1 through VSC4 represent converter stations. Converters VSC1 and VSC2

control active power injection into the dc network and regulate ac voltage magnitude at points of

common coupling B1 and B2. VSC3 and VSC4 regulate dc link voltage and ac voltage magnitude at

points of common coupling B3 and B4. In order to assess the possible improvement that can be

achieved in the HVDC network transient response during dc side faults when converters with dc fault

reverse blocking capabilities are employed, the test system in Fig. 2 is simulated first with converters

having inherent dc fault reverse blocking capability (mainly H-bridge M2C) and then with

conventional two-level converters without reverse blocking capability. To maintain reasonable

simulation speed, the H-bridge modular multilevel converters are modelled with two cells per arm and

controlled using sinusoidal pulse width modulation with 2.1kHz switching frequency. A capacitor

voltage balancing method is also incorporated. Both ac and dc transmission lines are represented by

simple lumped π models. Table 1 summarises system parameters.

Fig. 2: Test system

Table 1: System parameters

Two-level H-bridge Converter rating (MVA) 200 200

Dc link voltage (kV) 275 275

Interfacing transformer

200MVA

T1&T2: 230kV/132kV

Z=(0.008+j0.32)pu

T1&T2: 132kV/400kV

Z=(0.008+j0.32)pu

200MVA

T1&T2: 230kV/132kV

Z=(0.008+j0.32)pu

T1&T2: 132kV/400kV

Z=(0.008+j0.32)pu

Interfacing reactors j0.32pu no

Arm reactor - 20mH

Dc link capacitors 500µF 150µF

H-bride cell capacitors - 1000µF

dc lines (150km) Z=(0.0055+j0.0198)pu and C=34.6µF Z=(0.0055+j0.0198) pu and C=34.6µF

A. Case I: HVDC network employing converters with inherent dc fault reverse blocking capability

This section assesses the viability of HVDC converter topologies with inherent dc reverse blocking

capability than can be exploited to improve the resilience of the dc grid to dc side faults. This is tested

6

by subjecting the test system in Fig. 2 to a solid pole-to-pole dc fault at the middle of the line

connecting converters VSC2 and VSC4, with fault duration of 140ms (7 cycles for 50Hz systems).

During the dc fault period, the active power commands to the converters VSC1 and VSC2 are reduced

to zero and pulse width modulation signals to the switches of all converters are inhibited, including

those controlling dc voltages. To prevent the converter station dc link voltages from oscillating against

each other due to the absence of common dc link capacitors when the H-bridge modular converters are

employed in Fig. 2, a small capacitor of 150µF is connected across each converter station dc link to

decouple the oscillations due to capacitor voltage balancing dynamics from the dc network. As a

consequence, the magnitude of the lead-through currents that may flow in the dc side is expected to

increase due to discharge of the these capacitors.

Fig. 3 shows the results obtained when the system in Fig. 2 is subjected to a solid pole-to-pole dc fault

at the middle of the line connecting converters 2 and 4. Figs. 3a and 3b show active and reactive

power that the converter stations exchange with their points of common coupling B1 to B4. Figs. 3c

and 3d show current waveforms converters 1 and 4 inject into B1 and B4. It can be observed from Figs.

3a to 3d that there is no real power exchange between the ac sides and the HVDC network, noreactive

power exchange between the converters and ac systems, and no current flow in the converter switches

during the entire fault period as the converter gate signals are inhibited. Fig. 3e and 3f show the grid

contribution to the dc network during the solid pole-to-pole dc fault. It can be observed that the ac

side’s contribution to the dc fault currents through converter switches is completely eliminated. Also

converter switches experience only manageable current stresses during HVDC network recovery from

the dc fault when the dc side capacitors (reservoir and cable distributed stray capacitance) are

recharging from the ac side as the converters collapsed dc link voltages are building up. Fig. 3g shows

current waveforms at the links 1-3 and 2-4. It can be seen that the current magnitude in these links is

much larger than ac side’s contributions shown in Figs. 3e and 3f. This is because the link currents

include a large transient component due to the discharge of the dc side capacitors. Therefore any dc

circuit breakers must be able to tolerate such a large current for a short period of time, as it decays

quickly, but are not required to be capable of breaking such high current. Fig. 3h shows dc link voltage

of converters 2 and 4. The main issue with HVDC network recovery from dc faults is that the current

magnitude in the converter switches and dc side are limited only by the effective impedance between

points of common coupling and converter terminals (including arm inductors in H-bridge modular

converters), and not the current controller. The current controller becomes effective after dc link

voltage has partially or fully recovered.

(a) Converters 1 and 2 active and reactive power exchange with

B1 and B2

(b) Converters 1 and 2 active and reactive power exchange with

B3 and B4

(c) Current injected by VSC1 into B1

(d) Current injected by VSC4 into B4

7

(e) Converters 1 and 2 dc link currents (grid contribution),

excluding dc side capacitor discharge current

(f) Converter 3 and 4 dc link currents (grid contribution),

excluding dc side capacitor discharge current

(g) DC currents in links connecting converters 1 and 3, and 2 and

4

(h) DC link voltage of converters 2 and 4

Fig. 3: Waveforms demonstrating recovery of the HVDC network that employs converters with dc fault reverse blocking capability

B. Case II: HVDC network employing converters without dc fault reverse blocking capability

The results in Fig. 4 are obtained when converter stations are standard two-level converters without dc

fault reverse blocking capability. It can be seen that the converter stations consume large reactive

power from the ac sides during dc side fault when converter switches are blocked by inhibiting the

gate signals (in this case, converters behave as typical uncontrolled rectifiers with poor input power

factor feeding the low impedance dc side). This may cause voltage stability problems if some of the

converter stations are connected to weak ac networks (Figs. 4a and 4b). Also it can be observed that

the converter stations leak high current to the dc side from ac side through converter anti-parallel

diodes that are connected across each IGBT (Figs. 4c, 4d and 4e). This increases the risk of converter

switches failure and also complicates the design of dc circuit breakers in terms of current handling

capability as shown Fig. 4f. To limit the magnitude of potential leakage current from the ac sides to dc

side during dc faults, the effective impedance between the converter terminals and points of common

coupling is set to twice of that used with the H-bridge M2C approach.

a) Active and reactive power converters 1 and 2 exchange with

B1 and B2

b) Active and reactive power converters 3 and 4 exchange with

B3 and B4

c) Current waveforms converter 3 injects into B3

d) Converters 1 dc link current (grid contribution), excluding

discharge current of the dc side capacitors

8

e) Converter 3 dc link current (grid contribution), excluding

discharge current of the dc side capacitors

f) dc current in the link connecting converters 1 and 3,

including transient contribution of the dc side capacitors

Fig. 4: Sample waveforms demonstrating the recovery of the HVDC network that employs standard two-level converters without dc fault reverse

blocking capability

5. CONCLUSIONS This paper investigated the potential improvement that may be achieved in the transient behavior of

the HVDC network during dc side faults when converter stations with dc fault reverse blocking

capability are employed. The response of the HVDC network during dc side faults is obtained using

converter stations with dc fault reverse blocking capability and compared to that obtained with

standard two-level converters without blocking capability. This paper also highlights the potential

benefits of the dc fault blocking capability feature in the context of the HVDC network, which can be

summarized in the following points:

• Reduces the risk of converter stations damage during dc side faults and recovery period.

• Minimizes the magnitude of the lead-through current dc circuit breakers may experience.

However, this depends on the HVDC converter topology employed (see references [2],[3] and

[8] for more details).

• May permit the use of relatively slow dc circuit breakers with low current breaking capacity

(as ac networks contribution to the fault current are stopped, and the currents in the all

branches of the HVDC network will die out after discharge of the dc side capacitors).

• Recovery without interruption from temporary dc side faults may be possible.

• Improves voltage stability of the ac networks connected to the HVDC network during dc side

faults and system recovery as the amount of reactive powers flow toward the converter

stations are significantly reduced (only during recovery from dc side faults). This is because

during dc side faults ac networks will see the points of common coupling where the converter

stations of the HVDC network are connected as open circuit nodes.

6. REFERENCES [1] G.O. Kalcon et al., “HVDC Network: Wind Power Integration and Creation of Super Grid,” IEEE Electrical Engineering and Environment

International Conference (EEEIC), May 2011.

[2] G. P. Adam, et al., "Network Fault Tolerant Voltage-Source-Converters for High-Voltage Applications," in IET, the 9th International conference

on AC and DC Power Transmission, London, UK, 2010.

[3] G.P. Adam et al., “ H-bridge Modular Multilevel Converter (M2C) for High-Voltage Applications,” CIRED 2011, Frankfurt, Germany, June

2011.

[4] B. Jacobson;, et al., "VSC-HVDC Transmission with Cascaded Two-level Converters," presented at the CIGRE 2010, 2010.

[5] Dirk et al., “Prospects of HVDC&FACTS for Bulk Power Transmission and System Security,” paper available online at SIEMENS website

www.usa.siemens.com.

[6] W. Manfred, K. Arthur and S. Peter, “A Modular Direct Converter for Transformerless Rail Interties,” Proceedings of International Symposium

on Industrial Electronics (ISIE2010), Bari-Italy, 4-7 July 2007,pp.1-6.

[7] M. Hagiwara and H. Akagi, "PWM control and experiment of modular multilevel converters," in Power Electronics Specialists Conference,

2008. PESC 2008. IEEE, 2008, pp. 154-161.

[8] M. Merlin et al., “A new Hybrid Multi-level Voltage Source Converter with DC Fault Blocking Capability,” Paper available at www.supergen-

network.org.uk.

[9] G. P. Adam, et al., "Modular multilevel inverter: Pulse width modulation and capacitor balancing technique," Power Electronics, IET, vol. 3, pp.

702-715, 2010.

[10] Hagar and P. W. Lehn, "A scalable multi-input multi-level voltage sourced converter," in Electrical and Computer Engineering, 2009. CCECE

'09. Canadian Conference on, 2009, pp. 265-268.

[11] N. Flourentzou, et al., "VSC-Based HVDC Power Transmission Systems: An Overview," Power Electronics, IEEE Transactions on, vol. 24, pp.

592-602, 2009.