hvac introduction

5
Introduction The modern day definition of air-conditioning was created in the early 20th century based on the vision and works of Hermann Rietschel, Alfred Wolff, Stuart Cramer, and Willis Carrier. Cramer, a textile engineer in North Carolina, is credited with coining the phrase "air- conditioning" in 1906. In 1908, G.B. Wilson developed the first holistic definition of what air-conditioning encompasses. The Original Definition of Air-Conditioning To maintain a suitable degree of humidity in all seasons and in all parts of a building To free the air from excessive humidity during certain seasons To supply a constant and adequate supply of ventilation To efficiently wash and free the air from all micro-organisms, effluvias, dust, soot, and other foreign bodies To efficiently cool the air of the rooms during certain seasons To either heat the rooms in winter or to help heat them To combine all the above desiderata in an apparatus that will not be commercially prohibitive in first cost or cost of maintenance (Source: Nagengast, B., 1999, "Early Twentieth Century Air-Conditioning Engineering", ASHRAE Journal, March (p.55) Though he did not actually invent air-conditioning nor did he take the first documented scientific approach to applying it, Willis Carrier is credited with integrating the scientific method, engineering, and business of this developing technology and creating the industry we know today as air-conditioning. Back to top Description Today's HVAC&R engineer, or mechanical engineer of record (MER), continues to be a steward of the basic discipline issues identified by Mr. Wilson nearly 100 years ago. Roles have expanded, though, to address more modern quality of life issues. ASHRAE offers the current vision of the MER's stewardship responsibilities: to improve the quality of life by helping keep indoor environments comfortable and productive; by helping to deliver healthy food to consumers; and by helping to preserve the outdoor environment. As part of a holistic controlled environment design solution, the MER is responsible for addressing seven major processes. These are: 1. Heatingthe addition of thermal energy to maintain space or process conditions in response to thermal heat loss 2. Coolingthe removal of thermal energy to maintain space or process conditions in response to thermal heat gain 3. Humidifyingthe addition of water vapor to maintain space or process moisture content

Upload: ali-aimran

Post on 03-Sep-2015

212 views

Category:

Documents


0 download

DESCRIPTION

HVAC intro

TRANSCRIPT

  • Introduction

    The modern day definition of air-conditioning was created in the early 20th century based on

    the vision and works of Hermann Rietschel, Alfred Wolff, Stuart Cramer, and Willis Carrier.

    Cramer, a textile engineer in North Carolina, is credited with coining the phrase "air-

    conditioning" in 1906. In 1908, G.B. Wilson developed the first holistic definition of what

    air-conditioning encompasses.

    The Original Definition of Air-Conditioning

    To maintain a suitable degree of humidity in all seasons and in all parts of a building

    To free the air from excessive humidity during certain seasons

    To supply a constant and adequate supply of ventilation

    To efficiently wash and free the air from all micro-organisms, effluvias, dust, soot,

    and other foreign bodies

    To efficiently cool the air of the rooms during certain seasons

    To either heat the rooms in winter or to help heat them

    To combine all the above desiderata in an apparatus that will not be commercially

    prohibitive in first cost or cost of maintenance

    (Source: Nagengast, B., 1999, "Early Twentieth Century Air-Conditioning Engineering",

    ASHRAE Journal, March (p.55)

    Though he did not actually invent air-conditioning nor did he take the first documented

    scientific approach to applying it, Willis Carrier is credited with integrating the scientific

    method, engineering, and business of this developing technology and creating the industry we

    know today as air-conditioning.

    Back to top

    Description

    Today's HVAC&R engineer, or mechanical engineer of record (MER), continues to be a

    steward of the basic discipline issues identified by Mr. Wilson nearly 100 years ago. Roles

    have expanded, though, to address more modern quality of life issues. ASHRAE offers the

    current vision of the MER's stewardship responsibilities: to improve the quality of life by

    helping keep indoor environments comfortable and productive; by helping to deliver healthy

    food to consumers; and by helping to preserve the outdoor environment.

    As part of a holistic controlled environment design solution, the MER is responsible for

    addressing seven major processes. These are:

    1. Heatingthe addition of thermal energy to maintain space or process conditions in response to thermal heat loss

    2. Coolingthe removal of thermal energy to maintain space or process conditions in response to thermal heat gain

    3. Humidifyingthe addition of water vapor to maintain space or process moisture content

  • 4. Dehumidifyingthe removal of water vapor to maintain space or process moisture content

    5. Cleaningthe process of removing particulate and bio-contaminants from the conditioned space.

    6. Ventilatingthe process of providing suitable quantities of fresh outside air for maintaining air quality and building pressurization.

    7. Effectivenessthe process of achieving the desired thermal energy transfer, humidity control, filtration, and delivery of ventilation air to the breathing zone of the occupied

    space in accordance with required needs.

    It is important for the MER to be involved early in the project, even as early as the

    programming stage, so that mechanical system space issues and facility energy budgets can

    be evaluated and integrated into the design process before building construction elements,

    configurations, and orientations are finalized (see also WBDG High-Performance HVAC). A

    few critical issues that need to be considered early are:

    Financial Focus: Will the project be a code minimum type facility or will total

    ownership cost perspectives be considered that balance capital first costs against long-

    term ownership and operating costs?

    Owner Sophistication: The MER needs to understand the abilities of the owner and

    keep these in mind as mechanical system architecture issues are considered. The best

    of design solutions aren't much good if operators do not understand how to correctly

    operate or control the equipment.

    Operations and Maintenance: No matter what level of system complexity is applied, it

    is imperative that suitable space be made available for equipment without

    compromising performance or maintenance access. A good MER will understand the

    requirements published in equipment installation manuals and focus on providing

    prescribed minimum service and operating considerations in the planning of a facility

    layout.

    Before any equipment selections can be finalized, the MER will need to perform a thermal

    load calculation for the developing facility based on internal and external influencing factors.

    In many cases, this activity will be expanded to include analysis of comprehensive energy

    models. These models will foster dynamic integration opportunities whereby the design team

    and owner can evaluate the impacts of trade-offs between facility construction elements,

    mechanical system alternatives, and available operating efficiencies. Load calculations can be

    utilized for any or all of the following design activities:

    A. Defining the basic load dynamics B. Evaluating solution alternatives via life-cycle analysis C. Optimizing system performance D. Selecting final HVAC equipment E. Establishing energy budgets for owners F. Verification of proposed equipment performance G. Commissioning Design Intent for seasonal comparison

    The MER will be responsible for securing/developing the following fundamental information

    from the Owner and design team members:

    Basic Load Calculations:

  • o Establish summer/winter design weather conditions paying particularly close

    attention to regional weather issues and impact on

    humidification/dehumidification considerations.

    o All elements of the building envelope must be identified so that thermal

    energy loss/gain can be determined. Reference should be made to ASHRAE

    Standard 90.1 for regionally documented envelope construction minimum

    thermal quality considerations.

    Orientation of walls and roofs need to be defined so that sun angle

    impacts can be evaluated.

    The composite construction of all walls, roofs, and floors needs to be

    defined so that thermal transfer calculations can be performed. This

    information will also be useful when a dew point analysis is performed

    on the envelope.

    Thermal mass and color of walls and roofs need to be defined so that

    thermal time lags and radiation absorption can be evaluated.

    Fenestration U-values and solar heat gain coefficients need to be

    defined.

    External/internal shading provisions need to be defined that may

    impact fenestration heat gain.

    o Lighting:

    Lighting densities and ballast loss factors need to be mapped per

    individual space. Maximum densities are identified for individual

    space types in ASHRAE Standard 90.1.

    Opportunities to capture natural light (Daylighting) and apply

    occupancy sensing techniques to reduce light heat gain need to be

    explored.

    o Basic internal sensible heat gain allowances for receptacle loads need to be

    established.

    o Miscellaneous sensible and latent heat gain values need to be identified for

    special circumstances.

    o People contributions:

    The total number of people and the occupancy usage profiles need to

    be established.

    The activity levels of people need to be identified.

    o Ventilation:

    For a given space, the area factor and people factor ventilation rate

    components need to be calculated per ASHRAE Standard 62.1.

    Depending on HVAC system architecture employed, critical space

    calculations may need to be performed to adjust ventilation quantities

    to ensure adequate outside air is being provided to occupied spaces

    during all system fluctuations.

    Calculate all building exhaust requirements and compare to minimum

    required outside air ventilation rates. The overall impact of building

    pressurization dynamics must be evaluated for the facility, for seasonal

    conditions, and for regional locations. The MER must fully understand

    how moisture and thermal gradients work with the building envelope

    construction and what influence infiltration/exfiltration has on

    condensation potential.

    o Basic system zoning:

    Identify spaces and zones.

  • Establish summer/winter design temperature set-point conditions and

    dead-band ranges per thermal comfort recommendations of ASHRAE

    Standard 55.

    Energy Modeling:

    o Establish realistic average weather profiles for project location.

    o Define realistic 24-hour usage profiles for the entire calendar year taking into

    account workdays, weekends, holidays, etc.

    o Obtain current rate structures from utilities.

    o Define accurate equipment power consumption paying particular attention to

    part load efficiencies.

    Life-Cycle Analysis:

    o Define capital cost impacts of equipment and system alternatives.

    o Determine client applicable time value of money evaluation parameters.

    o Determine accurate maintenance costs for equipment and system alternatives.

    Integrated Design Process (See also WBDG High-Performance HVAC)

    Once the facility thermal issues are identified, the MER will be faced with application

    decisions to find appropriate, constructible, controllable, affordable, and maintainable

    HVAC&R solutions. These solutions must be integrated and coordinated with parallel design

    and planning activities of fellow design team members. While not totally encompassing, the

    following discipline considerations need fundamental attention:

    Architectural Interaction:

    Impacts By Impacts To

    Equipment room locations, accessibility, and size

    Location and appearance of air distribution devices

    Floor to floor height, depth of structure, ceiling height,

    and available utility space in ceiling cavity

    Component aggregation and location of building

    envelope elements

    Location of Life Safety features such as fire and smoke

    rated construction and the impacts on HVAC

    constructability

    Location and construction of noise sensitive areas

    Selection of interior finishes and VOC impacts.

    Location of

    equipment

    Orientation of the

    building

    Structural Engineering Interaction:

    Impacts By Impacts To

    Type of construction: steel,

    concrete, wood, etc.

    Foundation design

    Fireproofing techniques

    Seismic criteria

    Location, weights, and

    support/attachment of equipment

  • Civil Engineering Interaction:

    Impacts By Impacts To

    Location of site utilities

    Siting and landscaping impacts on thermal

    loads and noise trespass

    Size and location of utility

    connections

    Electrical Engineering Interaction:

    Impacts By Impacts To

    Size of available power service

    Layout of design

    Gen-set ventilation, heat removal, and

    fuel support requirements

    Location of electrical infrastructure:

    switchboards, panels, feeders, etc.

    Equipment power requirements

    Coordination of power hook-up

    and disconnecting means

    Coordination of Fire Alarm shut-

    down and smoke detectors

    Location of duct, pipe, and air

    distribution

    Plumbing Engineering Interaction:

    Impacts By Impacts To

    Type and capacity of heat generation

    plant for hot water heating

    Location of plumbing infrastructure:

    equipment, piping, etc.

    Make-up water requirements and

    backflow protection

    Condensate drainage disposal

    requirements

    Location of duct, pipe, and air

    distribution

    Fire Protection Engineering Interaction:

    Impacts By Impacts To

    Fire pump ventilation, heat removal, and fuel

    support requirements

    Location of sprinkler and standpipe

    infrastructure: equipment, piping, heads, etc.

    Location of duct, pipe, and

    air distribution

    Back to top