HVAC Economizers 101Section #3
Wh E i F il d Why Economizers Fail and Increase Energy Use
3-1
![Page 2: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/2.jpg)
Section #3-Why Economizers Fail and Increase Energy UseIncrease Energy Use• Jammed or frozen outside-air damper• Broken and/or disconnected linkage
N f i i di d i• Nonfunctioning actuator or disconnected wire• Malfunctioning outside air/return air temperature sensor• Malfunctioning controller
F lt t l tti
Wired poorly
• Faulty control settings• Installed wrong or wired incorrectly
3-2
Source: Financial Times EnergyJammed/Frozen Damper Disconnected Damper
![Page 3: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/3.jpg)
Packaged Rooftop Units with Economizers are Often Neglected, Hard to Access, or Installed Poorly
3-3
![Page 4: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/4.jpg)
Poorly Design-Packaged Rooftop Units with Economizer Installed Next to with Economizer Installed Next to Heat Source from Condenser
3-4
![Page 5: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/5.jpg)
AHU and Economizers Often Don’t Get Adequate MaintenanceDon t Get Adequate Maintenance
3-5
![Page 6: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/6.jpg)
Inefficient Designs on RTU Contribute to Poor Air Circulation at Intake Airto Poor Air Circulation at Intake Air
3-6
![Page 7: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/7.jpg)
Rooftop HVAC Units with EconomizersAre Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by Many Techs
3-7
![Page 8: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/8.jpg)
Potential Economizer Savings from Enthalpy ControlEnthalpy Control
Approximately 15% Savings
3-8
Source: Honeywell Controls
![Page 9: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/9.jpg)
Potential Economizer Savings fromDifferential Enthalpy ControlDifferential Enthalpy Control
3-9Source: Honeywell Controls
![Page 10: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/10.jpg)
The Potential of Energy Savings from Properly Operating Economizers in Various p y p gCities New York 16.3%
Washington, DC 13.0%
Atlanta 15.0%
Miami 5.5%
Pittsburgh 15.0%
Chicago 13.2%
Nashville 13.4%
Minneapolis 12.3%p
Fort Worth 12.5%
Denver 24.9%
Albuquerque 27 9%Albuquerque 27.9%
Seattle 17.4%
Sacramento 17.5%
3-10
Los Angeles 32.0%
Phoenix 9.5%
![Page 11: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/11.jpg)
Typical Problems with Rooftop Units
3-11
Source: New Buildings Institute - PIERProblems and Frequency in %Notice-Economizers are a problem on rooftop units over 70% of the time
![Page 12: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/12.jpg)
Ideal Economizer Performance Profile During the DayDuring the Day
Damper Signal
3-12Source: Pacific Energy Center
![Page 13: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/13.jpg)
Good vs. Evil of Malfunctioning EconomizersEconomizers
3-13Source: Pacific Energy Center
![Page 14: HVAC Economizers 101-Section 3 · Rooftop HVAC Units with Economizers Are Installed Quickly on Flat or Pitched Roofs Are Installed Quickly on Flat or Pitched Roofs, and Serviced by](https://reader033.vdocuments.us/reader033/viewer/2022042712/5fa0f51e97685a09c15cb546/html5/thumbnails/14.jpg)
Why Economizers Fail Exercise #3 Exercise #3 (Provide Answers below on notes page)
1 List three reasons economizers fail or do not work1. List three reasons economizers fail or do not work properly.
2. What are the top two reasons that rooftop HVAC equipment is energy inefficient?
3. Which has a greater impact on the energy of the HVAC unit refrigerant charge or low air flow?unit refrigerant charge or low air flow?
4. What hours of the day are best for utilizing free cooling via the economizer?
5. Which areas of the country have the greatest percent of energy savings regarding single enthalpy controlled economizers the west or the mid-west? Explain
3-14
economizers, the west or the mid west? Explain.