    7.12 HVAC Duct Construction Standards Metal and Flexible • Third Edition

    FIGURE 711 FLEXIBLE DUCT LINER INSTALLATION

    E

    E

     A

     A

    B

    B

    D

          D

          B

          C

    LAPPED AND BUTTED CORNER

     ALTERNATEFOLDEDCORNER

     ALL TRANSVERSEEDGES TO BECOATED WITH

     ADHESIVE EXCEPT

    MAXIMUM SPACING FOR FASTENERS. ACTUAL INTERVALS ARE APPROXIMATE.

    DUCTSECTION(TYPICALLY 4 FT. (1.2 m)

    THE VELOCITY RATEDSIDE OF LINER MUSTFACE THE AIR FLOW

     AIR FLOWSEE TYPICAL DUCT BRANCH ENTRY CONDITION IN FIG. 26.

    DETAIL  A

    UNLESS A LOWERLEVEL IS SET BYMANUFACTUREROR LISTING

     AGENCY

     *

    DimensionsVelocity  *

     A

    3”

    (76.2) (152)

    12”

    B

    (102)

    4”

    C

    (152)

    6”

    D

    0  2500 FPM

    (12.7  30.5 MPS)

    OR 5 FT. (1.52 m))

    3” 6” 4” 6”2501  6000 FPM

    (76.2) (305) (102) (152)(0  12.7 MPS)

    WHEN NOSING ISPRESENT

    ”A” PIN ROW MAY BE OMITTED WHEN METAL NOSING ISUSED. ”E” THEN STARTS FROM THE NOSING.

    METAL NOSING MUST BE USED WHEREVER LINER IS PRECEDEDBY UNLINED METAL; OTHERWISE WHEN VELOCITY EXCEEDS4000 FPM (20.3 MPS) USE METAL NOSING ON EVERY LEADING

    EDGE. NOSING MAY BE FORMED ON DUCT OR BE CHANNELOR ZEE ATTACHED BY SCREWS, RIVETS OR WELDS.

    INTERIOR WIDTH OF 8” (200 mm) AND LESS DOES NOT

    REQUIRE PINS.

    NOTE:

    METAL NOSING

    CHANNEL OR ZEE

    C

    PLACE PINS

    3” (76 mm) ALONG

    EACH SIDE OF ABUTTED LONGITUDINALLINER SEAM THATIS AWAY FROM ACORNER

    (457)

    16”

    18”

    (406)

    E

    LINER ADHERED TOTHE DUCT WITH 90%MIN. AREA COVERAGEOF ADHESIVE