hvac designs book
TRANSCRIPT
Wor
k:HVAC Designs, Inc. // Collection Vol. 1
North
HVAC SCHEDULES + DETAILS
x
SCALE 1/8"=1'-0"1 OF 1
DRAWINGHVAC
CLASSIFICATION : Commercial Add + RemodelCONDITIONED SQ. FT.: 6949PROJECT STATE, ZIP: Temple Terrace FloridaPROJECT ADDRESS: 5903 E 130th AvenuePROJECT NAME: American Youth Academy 6949 w
PERMIT SET8/26/2008
DRAWING DATE
T
H
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
REGISTERCEILING
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DUCTED T/A
CEILING GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORK
FLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
STANDHANDLER ONVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
D
R R
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
STRUCTUREFROM
MOUNTHANDLER
HORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/ADOOR
1" UNDERCUT
303 -- 312SECTIONS
FMCHANDLER
AIRDUCTLESS
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFM
Walk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
D
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC NOTES
Class
Corridor 1
Locker G
Restroom G Mech Locker B
Office
Reading
Computers
Media Electric Office 102 Office 101
Server
Break
Office 121 Office 123 Office 125
Office 122
Lobby
22x22,9",199 CFM22x22,9",199 CFM
22x22,9",199 CFM
22x22,9",199 CFM
22x22,8",171 CFM
22x22,8",171 CFM
22x22,6",97 CFM
8x4,4",51 CFM
22x22,9",263 CFM
22x22,8",171 CFM
22x22,8",161 CFM
22x22,8",161 CFM
22x22,8",161 CFM
22x22,9",263 CFM
22x22,9",300 CFM22x22,9",206 CFM
22x22,9",206 CFM
22x22,9",238 CFM
22x22,9",238 CFM
22x22,9",300 CFM
22x22,9",300 CFM
22x22,9",171 CFM
22x22,7",140 CFM
22x22,6",103 CFM
22x22,7", 157 CFM
22x22,5",85 CFM
22x22, 6",70 CFM
22x22,8", 174 CFM22x22,9",238 CFM 22x22,9",238 CFM
Corridor 2
22x22,9", 266 CFM
22x22,9", 266 CFM
Restroom
Restroom B
22x22,5",88 CFM
Corridor 3
22x22, 18", -794 22x22,18",-686
22x22,5",81 CFM
8x4,4",29 CFM
22x22, 14", -500
22x22, 14", -460
22x22, 14", -520
8x4,4",51 CFM 8x4,4",36 CFM
Corridor 4
22x22,5",67 CFM
22x22,16",-860 CFM
Science
22x22,14",-620 CFM
22x22,8",168 CFM
22x22,8",168 CFM
Office 12022x22,7",-103 CFM
22x22,9", -174 CFM
22x22,8", -157 CFM
22x22,16",-889 CFM
22x22,8", -157 CFM
22x22,7", 157 CFM
22x22,5",86 CFM
Pricipal Office
22x22,6",93 CFM
ON SLAB
CU-5
ABOVE CEILINGMECH ROOM
AHU-1 ABOVE CEILINGMECH ROOM
AHU-3ABOVE CEILINGMECH ROOM
AHU-2
ABOVE CEILINGMECH ROOM
AHU-4
WALL MOUNT
AHU-5NO OCCUPANCY
600 CFM R/A600 CFM S/A
AIR HANDLERDUCTLESS
EF-2VTE
EF-1VTE
ON SLAB
CU-4ON SLAB
CU-1ON SLAB
CU-2
ON SLAB
CU-3
12x16
14x16
24x12
24x12
24x12 24x12
24x12
24x12
24x12
24x18
24x18
24x18
24x18
24x12
14x12 14x12 10x12
14x1210x12 8x12
12x16
14x12
16x12
10x12
6x12
16x16,9",-300 CFM
16x16, 9",-300 CFM
12x12,7",-125 CFM16x16,9",-300 CFM
16x16,9",-200 CFM10x10 10x14 10x14 10x12
EF-3VTE
300 MAX CFMDOOR MOUNT
GRILLE - WALL /TRANSFER AIR
TYPICAL (x6) 16x16
14x12
VTE,FILTER,SET TO 368 CFMTYPICAL (x4) 9" FRESH AIR DUCT
FL BERS #884813-885-2258
HVAC DesignsNeil Fimbel
Designed By:
EXHAUST FAN SCHEDULE
FAN MARK: EF-1 EF-2 EF-3MANUFACTURER: NUTONE NUTONE GREENHECK
MODEL NUMBER: 690 QT-200 CSP-264
FAN TYPE: EXHAUST EXHAUST INLINE EXHAUST
FAN CFM: 50 200 1225
TOTAL PRESSURE: 0.25 .25 .5
FAN VOLTAGE: 120/1/60 120/1/60 120 / 1 / 60
FAN AMPERAGE: 0.5 1.0 7.8
FAN DIMEN LWH: 9X11X8 14X10X9 24X14X14
DUCT OUTLET SIZE: 3 3.25X10 TO 7 19X8
DUCT INLET SIZE: 12X11 15X11 23X13
FAN WEIGHT: 10 14 59
NOTES: 1,2 1,3 1,2
1 = VENT TO EXTERIOR 3 = WALL SWITH CONTROL
2 = INTERLOCK WITH LIGHTS
TRANE EQUIPMENTAIR HANDLER MARK: AHU-1,2,3,4UNIT MODEL NUMBER: TWE065E
UNIT DIMEN H/W/D: 63X26X21
UNIT WEIGHT: 218
SUPPLY PLENUM SIZE : 24X12
RETURN PLENUM SIZE : 24X18
SUPPLY FAN CFM / SP : 1800 / .40
SUPPLY FAN H/P : 1
OUTDOOR AIR CFM: 368
UNIT PHASE / HERTZ: 1 / 60
UNIT VOLTAGE: 208 / 240
HEATER KW: 7.2 / 9.6
HEATER BREAKER: 50 / 60
CONDENSER MARK: CU-1,2,3,4NOMINAL A/C TONS : 5
UNIT MODEL NUMBER: 2TTR4060A
UNIT VOLTAGE: 208/230/ 1 / 60
UNIT MCA / BREAKER: 34 / 50
UNIT DIMEN H/W/D: 46.4X35.1X38.7
UNIT WEIGHT: 279
TOTAL COOLING BTUH: 61,000
SENS. COOLING BTUH: 44,500
LAT. COOLING BTUH: 16,500
TOTAL HEATING BTUH: 34,120
SENSIBLE HEAT % 0.73
SEER: 14
THERMOSTAT MODEL: T8411R1002
NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
WALL
FLOOR
FMC 1101 - MAY ALSO ROUTE BELOW SLABREFRIGERANT PIPING + CONTROL WIRING
GRADEEQUIPMENT SLAB
FMC 301.13FASTENER
FMC 303CONDENSING UNIT
PIPE COVER - MAY MOUNT INTERIOR
CONDENSING UNIT DETAIL
1101CONTROL WIRING FMCREFRIGERANT PIPING +
HORIZONTAL AIR HANDLER DETAIL
FMC 401DUCT
AIR* FRESH
TOP CHORDSUSPEND FROM
1/2 THREADED ROD
FMC 303AIR HANDLER
SUPPLY AIR DUCT FMC 601FMC 601
RETURN DUCT
CONDENSATE DRAIN FMC 307
* ACCESS PANEL FMC 306.3
* CEILING
SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
BUILDING AIR BALANCE SCHEDULE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 Class 17 > 3 HRS 797 795 0 255
1 Science 17 > 3 HRS 686 685 0 255
1 Corridor 1 0 N/A 97 0 0 0
1 Locker G 0 N/A 51 0 300 0
1 Restroom G 0 N/A 88 0 300 0
1 Restroom B 0 N/A 81 0 300 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 Mech 0 > 3 HRS 51 0 0 0
2 Locker B 0 N/A 36 0 325 0
2 Restroom 0 N/A 29 0 50 0
2 Lobby 0 N/A 535 520 0 0
2 Office 2 > 3 HRS 527 500 0 40
2 Reading 17 > 3 HRS 485 460 0 255
2 Corridor 2 0 N/A 137 0 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 Media 17 > 3 HRS 900 860 0 255
3 Electric 0 N/A 67 67 T/A 0 0
3 Office 102 1 > 3 HRS 336 620 0 20
3 Office 101 1 > 3 HRS 412 0 0 20
3 Corridor 3 0 N/A 85 0 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
4 Computers 17 > 3 HRS 955 889 0 255
4 Break 0 N/A 86 86 T/A 0 0
4 Office 120 1 > 3 HRS 93 93 T/A 0 20
4 Office 121 1 > 3 HRS 157 157 0 20
4 Office 123 1 > 3 HRS 157 157 0 20
4 Office 125 1 > 3 HRS 174 174 0 20
4 Pricipal 1 > 3 HRS 103 103 0 20
4 Office 122 1 > 3 HRS 70 70 T/A 0 20
4 Corridor 4 0 N/A 5 0 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
5 SERVER 0 N/A 600 405 200 0
BUILDING TOTALS 95 > 3 HRS 7800 6325 1475 1475
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
BUILDING VENTILATION CALCULATION
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON OR SQ FOOT
PEAK Classrooms 85 1.00 15 15 1275 15
PEAK Office 10 1.00 20 20 200 20
BUILDING TOTALS 95 1475
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
GWB, PROVIDE ACCESSINSULATION + SEALEDROOM IN ATTIC, R-19
ENCLOSED MECHANICALHIGH WALL- CORRIDOR
FROM BREAKTRANSFER AIR
DUCT AND 22x22 GRILLEFOR OFFICE - USE 7" S/A
FOR COMPUTER SERVERSTHIS ROOM IS USEDOPTIONAL ONLY IF
NOTE: AHU-5, CU-5 ARE
ENVIRO AIR EQUIPMENT
AIR HANDLER MARK: AHU-5UNIT MODEL NUMBER: ACWH1800
NOMINAL A/C TONS : 1.5
SUPPLY PLENUM SIZE : DUCTLESS
RETURN PLENUM SIZE : DUCTLESS
SUPPLY FAN CFM / SP : 600 / .40
SUPPLY FAN H/P : .35
OUTDOOR AIR CFM: 0
UNIT VOLTAGE: 200/230/ 1 / 60
UNIT DIMEN LWH: 42X12X8
UNIT WEIGHT: 29
HEATSTRIP KW: 2.5
CONDENSER MARK: CU-5UNIT MODEL NUMBER: CCW18000
UNIT VOLTAGE: 200/230/ 1 / 60
UNIT MCA / BREAKER: 12.5 / 20
UNIT DIMEN LWH: 35X12X28
UNIT WEIGHT: 156
TOTAL COOLING BTUH: 18,400
SENS. COOLING BTUH: 11,200
LAT. COOLING BTUH: 7,200
TOTAL HEATING BTUH: 17,000
SEER: 13
THERMOSTAT MODEL:
North
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DUCTED T/A
CEILING GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
DD
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFM
Walk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
SCALE 1/8"=1'-0"1 OF 1
DRAWINGHVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
PERMIT SET9/19/2008
DRAWING DATE
New Commercial13352Tampa Florida14400 N Florida AveRose Lake Plaza Phase 2
FL BERS C#8508FL BERS R#884
813-885-2258HVAC Designs
Neil FimbelDesigned By:
Unit J1
Toilet 10
Toilet 9
Unit H
Toilet 8
Unit G Unit F
Toilet 6
Unit A2
Unit E
Toilet 5
Unit D Unit C Unit B
HVAC NOTES
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
Toilet 1
Toilet 3
Unit A1
22x22,10",300 CFM
22x22,10",300 CFM22x22,10",300 CFM
22x22,10",300 CFM
12" O/A DUCT
18x18 +480 CFM O/A
22x22,10",287 CFM
22x22,10",287 CFM
Toilet 2
22x22,10",287 CFM
22x22,10",287 CFM
16"
(2) 9" O/A @ 240 CFM
(2) 24x18 R/A -960 CFM
16"
240 CFMDUCT @(2) 9" O/A
B
2 STG
ON STAND
AHU-1B
ON STAND
AHU-1A
8x4,4",53 CFM
B
22x22,10",312 CFM
22x22,10",312 CFM
22x22,10",312 CFM
22x22,10",312 CFM22x22,10",312 CFM
30x20 R/A -1240 CFM
16"
18x18 + 360 CFM O/A
ON STAND
AHU-2
HVAC DUCT SYSTEMS ARE TYPICAL FOR UNITS B,C,D,E,F
ON STANDAHU-4
ON STANDAHU-3
8x4,4",42 CFM
22x22,10",310 CFM
22x22,10",310 CFM
22x22,10",310 CFM 22x22,10",310 CFM
22x22,10",310 CFM
8x4,4",48 CFM
B
16"
ON STANDAHU-5
ON STANDAHU-6
Toilet 7
18x18 +360 CFM O/A
EF-1VTE
EF-1VTE
EF-1VTE
ON STAND
AHU-7
10" O/A DUCT
18x18 + 420 CFM O/A
10" O/A DUCT
10" O/A DUCT
LOBBYUNCONDITIONED
22x22,10",326 CFM
22x22,10",326 CFM
22x22,10",326 CFM
22x22,10",326 CFM
22x22,10",326 CFM
8x4,4",42 CFM
18"
C
30x20 R/A -1600 CFM
ON STAND
AHU-8
30x20 R/A - 1240 CFM
22x22,10",311 CFM
22x22,10",311 CFM
22x22,10",311 CFM
22x22,10",311 CFM
8x4,4",47 CFM
EF-1VTE
30x20 R/A -1200 CFM
ON STAND
AHU-9
16"
18x18 + 400 CFM O/A
22x22,10",311 CFM
16"
22x22,10",284 CFM
22x22,10",284 CFM
22x22,10",284 CFM
22x22,10",284 CFM
8x4,5",63 CFM
(2) 24x18 R/A - 960 CFM
B
16"
2 STG
B
10" O/A DUCT
12" O/A DUCT
EF-1VTE
22x22,10",300 CFM22x22,10",300 CFM
22x22,10",300 CFM
22x22,10",300 CFM
18x18 +480 CFM O/A
Toilet 4
B
B
+ BACKDRAFT DAMPER16x16 480 CFM 10"RELIEF AIR VENT
+ BACKDRAFT DAMPER16x16 480 CFM 10"RELIEF AIR VENT
+ BACKDRAFT DAMPER16x16 360 CFM 10"RELIEF AIR VENT
+ BACKDRAFT DAMPER16x16 360 CFM 10"RELIEF AIR VENT
+ BACKDRAFT DAMPER16x16 420 CFM 10"RELIEF AIR VENT
+ BACKDRAFT DAMPER16x16 400 CFM 10"RELIEF AIR VENT
CU-1BCU-2
RAISED PLATFORM
CU-1ACU-3CU-4CU-5
PLATFORMRAISED
CU-10A
CU-9
CU-10B
CU-8
CU-7
CU-6
Unit J2
Unit I
FROM PARKING10' MINIMUM
22x22,10",326 CFM
FROM PARKING10' MINIMUM
ON STAND
AHU-10B
ON STAND
AHU-10A
AMERICAN STANDARD SPLIT SYSTEM EQUIPMENT SCHEDULE
AIR HANDLER MARK: AHU-1A,1B,10A,10B AHU-2,3,4,5,6,7 AHU-8 AHU-9UNIT MODEL NUMBER: 2TEC3F36A 2TEC3F48A 2TEC3F60A 2TEC3F48A
UNIT DIMEN H/W/D: 46.5X24X23.5 59.5X26X23.5 59.5X26X23.5 59.5X26X23.5
UNIT WEIGHT: 125 151 155 151
SUPPLY PLENUM SIZE : 12.02X19.22 12.02X21.22 12.02X21.22 12.02X21.22
RETURN PLENUM SIZE : 18.07X19.5 18.07X21.5 18.07X21.5 18.07X21.5
SUPPLY FAN CFM / SP : 1200 / .40 1600 / .40 2000 / .40 1600 / .40
SUPPLY FAN H/P : 1/3 1/2 1 1/2
OUTDOOR AIR CFM: 240 360 420 400
UNIT PHASE / HERTZ: 1 / 60 1 / 60 1 / 60 1 / 60
UNIT VOLTAGE: 208 / 240 208 / 240 208 / 240 208 / 240
HEATER KW: 5.76 / 7.68 7.2 / 9.6 7.2 / 9.6 7.2 / 9.6
HEATER BREAKER: 40 / 45 50 / 60 50 / 60 50 / 60
CONDENSER MARK: CU-1A,1B,10A,10B CU-2,3,4,5,6,7 CU-8 CU-9NOMINAL A/C TONS : 3 4 5 4
UNIT MODEL NUMBER: 2TTR3036A 2TTR3048A 2TTR3060A 2TTR3048A
UNIT VOLTAGE: 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60
UNIT MCA / BREAKER: 18 / 30 25 / 40 32 / 50 25 / 40
UNIT DIMEN H/W/D: 38X30.1X33 46.4X35.1X38.7 46.4X35.1X38.7 46.4X35.1X38.7
UNIT WEIGHT: 194 273 269 273
TOTAL COOLING BTUH: 34,200 47,000 58,000 47,000
SENS. COOLING BTUH: 25,400 33,800 40,000 33,800
LAT. COOLING BTUH: 8,800 13,200 18,000 13,200
TOTAL HEATING BTUH: 25,590 34,120 34,120 34,120
SENSIBLE HEAT % 0.74 0.72 0.69 0.72
SEER: 13 13 13.5 13
THERMOSTAT MODEL: T8411R1002 T8411R1002 T8411R1002 T8411R1002
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
CYCLE EQUIPMENT OFF DURING UNOCCUPIED HOURS.
EXHAUST FAN SCHEDULE
FAN MARK: EF-1MANUFACTURER: NUTONE
MODEL NUMBER: QT-80
FAN TYPE: EXHAUST
FAN CFM: 80
TOTAL PRESSURE: .25
FAN VOLTAGE: 120/1/60
FAN AMPERAGE: .7
FAN DIMEN LWH: 9X9X6
DUCT OUTLET SIZE: 4
DUCT INLET SIZE: 10X10
FAN WEIGHT: 12
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
BUILDING AIR BALANCE SCHEDULE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST / RELIEF AIR CFM FRESH AIR CFM
1 UNIT A1 6 > 3 HRS 1200 960 240 240X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 UNIT B 9 > 3 HRS 1558 1240 360 360
2 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 UNIT C 9 > 3 HRS 1558 1240 360 360
3 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
4 UNIT D 9 > 3 HRS 1558 1240 360 360
4 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
5 UNIT E 9 > 3 HRS 1558 1240 360 360
5 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
6 UNIT F 9 > 3 HRS 1558 1240 360 360
6 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
7 UNIT G 9 > 3 HRS 1552 1240 360 360
7 TOILET 0 N/A 48 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
8 UNIT H 12 > 3 HRS 1958 1600 400 400
8 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
9 UNIT I 10 > 3 HRS 1553 1200 400 400
9 TOILET 0 N/A 47 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
10 UNIT J1 5 > 3 HRS 1137 960 240 240
10 TOILET 0 N/A 63 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
11 UNIT A2 6 > 3 HRS 1147 960 240 240
11 TOILET 0 N/A 53 0 80 SWITCHED 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
12 UNIT J2 4 > 3 HRS 1200 960 240 240
BUILDING TOTALS 97 > 3 HRS 18000 14080 3920 3920
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
BUILDING VENTILATION CALCULATION
TIME CLASSIFICATION OCCS / SF DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SF
PEAK Mechant (usable sq ft) 97 / 13066 1.00 0.3 0.3 3919.8 0.3
BUILDING TOTALS 3920 PROVIDED
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
HANDLER DETAILVERTICAL AIR
FMC 401AIR DUCT* FRESH
FMC 1101WIRING
+ CONTROLPIPING
REFRIGERANT
FMC 303AIR HANDLER
FMC 601AIR DUCTSUPPLY
FMC 307DRAIN
CONDENSATE
* CEILING
FLOOR
STANDAIR HANDLER
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
WALL
FLOOR
FMC 1101REFRIGERANT PIPING + CONTROL WIRING
PLATFORMEQUIPMENT
FMC 301.13FASTENER
FMC 303CONDENSING UNIT
PIPE COVER
CONDENSING UNIT DETAIL
RAIL
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC NOTES
North
HVAC SCHEDULES + DETAILS
x
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DUCTED T/A
CEILING GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
D D
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFM
Walk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
1 OF 1DRAWING
HVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
SCALE 1/4"=1'-0"
Permit Set9/12/2008
DRAWING DATE
New Residence1991
HDS Model Residence 1964 s
FL BERS R#884813-885-2258
HVAC DesignsNeil Fimbel
Designed By:
Dining / Living
M Bed
M Wic
Bed 4
Lav
Bed 3Bed 2
Stair / OtbPowder
Laundry
Foyer
Family / Nook / KitchenM Bath
M Toilet
12x8,116 CFM
12x8,116 CFM
8x4,4",24 CFM
8x4,4",31 CFM
12x6,6",113 CFM
12x8,8",116 CFM
12x6,6",106 CFM
12x6,6",106 CFM
12x8,334 CFM
8x4,4",13 CFM
10x6,6",99 CFM
8x4,4",5 CFM
14"
10"
14"
14"
14"
A
ON SLABCU-1
4" DRYER VTE
7" RANGE VTE
ROOM R-19 ISULIN SEALED MECHABOVE CEILING
AHU-1
E
ZD ZD BP
WYE
8x4,4",43 CFM
ATTICACCESS TO
DUCTS DOWN
Bath 2
12x12,9",-215 CFM
12x12,7",-99 CFM 12x12,7",-91 CFM
12x12,7",-89 CFM
12"-500 CFM@ CHASE18x18 R/A
10x6,5",77 CFM
10x6,5",77 CFM
10x6,6",91 CFM
8x4,4",35 CFM
8x4,4",5 CFM
18x18, 12",-606 CFM
10"
10x6,6",89 CFM
A
A
FLOORFIRST
FLOORSECOND
12" BYPASS
TRANE HEAT PUMPAIR HANDLER MARK: AHU-1UNIT MODEL NUMBER: 2TEC3F48A
UNIT DIMEN H/W/D: 59.5X26X23.5
UNIT WEIGHT: 151
SUPPLY PLENUM SIZE : 12.02X21.22
RETURN PLENUM SIZE : 18.07X21.5
SUPPLY FAN CFM / SP : 1600 / .40
SUPPLY FAN H/P : 1/2
OUTDOOR AIR CFM: 0
UNIT PHASE / HERTZ: 1 / 60
UNIT VOLTAGE: 208 / 240
HEATER KW: 7.2 / 9.6
HEATER BREAKER: 50 / 60
CONDENSER MARK: CU-1NOMINAL A/C TONS : 4
UNIT MODEL NUMBER: 2TWR3048A
UNIT VOLTAGE: 208/230/ 1 / 60
UNIT MCA / BREAKER: 25 / 40
UNIT DIMEN H/W/D: 46.4X35.1X38.7
UNIT WEIGHT: 279
TOTAL COOLING BTUH: 46,000
SENS. COOLING BTUH: 33,200
LAT. COOLING BTUH: 12,800
TOTAL HEATING BTUH: 43,500
SENSIBLE HEAT % 0.72
SEER / HSPF : 13 / 8.4
THERMOSTAT MODEL: PROGRAM
NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE.
ZONING SHOWN PER MANUAL J
EXHAUST FAN SCHEDULE FAN MARK: EF-1MANUFACTURER: NUTONE
MODEL NUMBER: 690
FAN TYPE: EXHAUST
FAN CFM: 50
TOTAL PRESSURE: 0.25
FAN VOLTAGE: 120/1/60
FAN AMPERAGE: 0.5
FAN DIMEN LWH: 9X11X8
DUCT OUTLET SIZE: 3
DUCT INLET SIZE: 12X11
FAN WEIGHT: 10
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
FMC 1101+ CONTROL WIRING
REFRIGERANT PIPING
HORIZONTAL AIR HANDLER DETAIL
FMC 401DUCTAIR
* FRESH
TOP CHORDSUSPEND FROM
1/2 THREADED ROD
FMC 303AIR HANDLER
SUPPLY AIR DUCT FMC 601FMC 601
RETURN DUCT
CONDENSATE DRAIN FMC 307
* ACCESS PANEL FMC 306.3
* CEILING
SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
WALL
FLOOR
FMC 1101 - MAY ALSO ROUTE BELOW SLABREFRIGERANT PIPING + CONTROL WIRING
GRADEEQUIPMENT SLAB
FMC 301.13FASTENER
FMC 303CONDENSING UNIT
PIPE COVER - MAY MOUNT INTERIOR
CONDENSING UNIT DETAIL
MARKBOX
A
B
C
D
E
F
DIMENSIONS - INCHES
N/A
H L W2W
21
17
13
*
N/A
N/A
**
13
13
13
17
1717
2121
21
18
18
18
18
18
18
= CAP SIZE EQUALS OUTLET DUCT + 1"
TRI - BOX REDUCER - BOX
WW
W2
H
L
H
L
*
*
HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC NOTES
North
HVAC SCHEDULES + DETAILS
x
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DUCTED T/A
CEILING GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
D D
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFM
Walk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
1 OF 1DRAWING
HVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
SCALE 1/4"=1'-0"
Permit Set8/14/2008
DRAWING DATE
Restaurant Renovation1320Boynton Beach Florida, 33461
Marcos Pizza Renov Boynton Beach 1320 e
FL BERS #884813-885-2258
HVAC DesignsNeil Fimbel
Designed By:
Cooler
Kitchen
Restroom
Order - Cashier
22x22,10",320 CFM
22x22,10",320 CFM
22x22,10",320 CFM
22x22,10",320 CFM
22x22,10",320 CFM
22x22,10",320 CFM
8x4,4",18 CFM
22x22, 10",316 CFM
22x22, 10",316 CFM
22x22, 10",316 CFM22x22, 10",316 CFM
22x22, 10",316 CFM
ON ROOFEXISTING
RTU-2
EF-1VTE
A/C EQUIPMENTCFM MUA BY
BY OTHERS 380KITCHEN HOOD
(2) 22x22, 16", -920 CFM EA
ON ROOF
RTU-1
TYPICAL OF 2TO GUTTER / GRASSCONDENSATE DRAIN
-1380 CFM22x22, 16"
20x12
18x12
12x12 12x12
24x12
ROOFTOP EQUIPMENT SCHEDULE
PACKAGE UNIT MARK: RTU-1 RTU-2UNIT MANUFACTURER: TRANE EXISTING
UNIT MODEL NUMBER: THC063A3 THC043A3
NOMINAL A/C TONS : 5 4
UNIT CONFIGURATION: DOWNFLOW DOWNFLOW
UNIT DIMEN H/W/D: 37X45X70 37X45X70
UNIT WEIGHT: 682 669
SUPPLY PLENUM SIZE : 17X15 17X15
RETURN PLENUM SIZE : 23X14 23X14
SUPPLY FAN CFM / SP : 2000 / .4 1600 / .4
SUPPLY FAN H/P : 1 1
OUTDOOR AIR CFM: 160 220
UNIT PHASE / HERTZ: 3/60 3/60
UNIT VOLTAGE: 208/230 208/230
UNIT MCA: 28.8 22.6
UNIT MAX BREAKER: 40 35
HEATER KW: 9/12 9/12
HEATER MCA: 37.5/42.4 37.5/42.4
HEATER BREAKER: 45/45 40/45
TOTAL COOLING BTUH: 62,400 49,800
SENS. COOLING BTUH: 47,300 39,400
LAT. COOLING BTUH: 15,100 10,400
TOTAL HEATING BTUH: 40,944 40,944
SENS. HEAT % 0.76 0.79
COOLING EFFICIENCY: 13 13
THERMOSTAT MODEL: T8411R1002 T8411R1002
NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
EXHAUST FAN SCHEDULE
FAN MARK: EF-1MANUFACTURER: NUTONE
MODEL NUMBER: 690
FAN TYPE: EXHAUST
FAN CFM: 50
TOTAL PRESSURE: 0.25
FAN VOLTAGE: 120/1/60
FAN AMPERAGE: 0.5
FAN DIMEN LWH: 9X11X8
DUCT OUTLET SIZE: 3
DUCT INLET SIZE: 12X11
FAN WEIGHT: 10
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
ROOFTOP PACKAGE UNIT DETAIL
CONNECTIONCURB
CURB
601FMC
DUCTS/A
601FMC
DUCTR/A
CONNECTIONDUCT
CONNECTIONEQUIPMENT
FMC 303EQUIPMENTROOFTOP
SPAN 3 JOISTS1/4" THK
2" U CHANNEL X
ROOF
CURB
@ 18" O.C.3/8 BOLT
JOIST
EQUIPMENTROOFTOP
DUCT@ 8" O.C.SCREWS
1/2"
SEALMASTIC
CURB
EQUIPMENTROOFTOP
@ 18"" O.C.OR ANGLE1/4" PLATESCREWS
3/8"
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOADMECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
BUILDING AIR BALANCE SCHEDULE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 COOLER ROOM 0 N/A 78 0 0 0
1 KITCHEN 5 > 3 HRS 1922 1840 380 CFM @ HOOD 160X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 RESTROOM 0 N/A 18 0 50 INTERMITTENT 0
2 ORDER / CASHIER 9 VARIES 1582 1380 0 220X X X X X X X X
BUILDING TOTALS 14 VARIES 3600 3220 380 380
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
BUILDING VENTILATION CALCULATION
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON OR SQ FOOT
PEAK Dining / Order 9 1.00 20 20 180 20
PEAK HOOD MUA 0 1.00 125 125 125 0
PEAK Kitchen / Prep 5 1.00 15 15 75 15
BUILDING TOTALS 14 380
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
North
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DUCTED T/A
CEILING GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
DD
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFM
Walk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
HVAC NOTES
SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC SCHEDULES + DETAILS
x
SCALE 1/8"=1'-0"1 OF 1
DRAWINGHVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
PERMIT SET9/28/2008
DRAWING DATE
Commercial Office Renovation7563 Revised 9/28/08Spring Hill Florida (Hernando)14378 Spring Hill Drive14378 Spring Hill Dr Office Renovation
FL BERS C#959FL BERS R#884
813-885-2258HVAC Designs
Neil FimbelDesigned By:
Office ExamReception
Restroom
Restroom
Exam
Consult Exam Exam
Lab
Break
Work Stations
Waiting
Reception
Office
Exam Exam
Reception
Corridor
Exam Exam
Reception
Restroom
Restroom
Waiting
U Restroom
Storage
Exam
Office
Exam
Corridor
Exam
Exam
P Restroom E Restroom
Waiting
22x22,7",124 CFM
22x22,10",347 CFM
22x22,7",130 CFM
22x22,10",347 CFM
8x4,4",31 CFM
22x22,10",347 CFM
22x22,10",347 CFM
22x22,7",129 CFM
22x22,9",257
8x4,4",21 CFM
22x22,6",101 CFM
22x22,6",108 CFM
22x22,6",99 CFM
22x22,5",64 CFM22x22,4",37 CFM
22x22,9",243 CFM
22x22,6",118 CFM
22x22,6",100 CFM
8x4,4",12 CFM
22x22,9",257
22x22,10",307 CFM
22x22,10",307 CFM
22x22,5",82 CFM
22x22,6",105 CFM
22x22,10",332 CFM
22x22,6",93 CFM
22x22,6",120 CFM
22x22,5",64 CFM
22x22,9",253
22x22,10",307 CFM
22x22,10",307 CFM
ON STAND
AHU-1
EF-1VTE
22x22,10", -304
22x22,10",-26122x22,10", -256
22x22,8",-147
22x22,6",-6422x22,6",-64
8x4,4",39 CFM
22x22,10",332 CFM8x4,4",38 CFM
22x22,9",258 CFM 22x22,7",146 CFM 22x22,9",261 CFM 22x22,10",304 CFM
22x22,7",-94
22x22, 14",-680
10x10
14x12
20x1224x12
12x1420x14
DUCT VTE6" FRESH AIR(TYPICAL x7)
(TYPICAL x7)
ON SLAB
CU-1
BUILDING AIR BALANCE SCHEDULE
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 Office 1 > 3 HRS 256 256 0 20
1 Exam 1 VARIES 147 147 0 15
1 Exam 1 VARIES 261 261 0 15
1 Reception 1 > 3 HRS 304 304 0 20
1 Restroom 0 N/A 38 0 90 0
1 Restroom 0 N/A 31 0 90 0
1 Exam 1 VARIES 94 94 0 10
1 Consult 1 > 3 HRS 37 37 T/A 0 20
1 Exam 1 VARIES 64 64 0 15
1 Exam 1 VARIES 64 64 0 15
1 Lab 0 VARIES 39 39 T/A 0 0
1 Work Stations 0 VARIES 665 680 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 Break 2 VARIES 243 243 0 15
2 Waiting 20 VARIES 1389 1292 0 75
2 Reception 2 > 3 HRS 335 335 0 40
2 P Restroom 0 N/A 10 0 90 0
2 E Restroom 0 N/A 23 0 90 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 Office 1 > 3 HRS 118 118 0 20
3 Exam 1 VARIES 124 124 0 20
3 Exam 1 VARIES 100 100 0 20
3 Reception 1 > 3 HRS 108 119 0 20
3 Corridor 0 N/A 83 0 0 0
3 Exam 1 VARIES 120 120 0 20
3 Exam 1 VARIES 99 99 0 20
3 Restroom 0 N/A 24 0 90 0
3 Restroom 0 N/A 24 0 90 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
4 Reception 1 > 3 HRS 253 253 0 20
4 Waiting 4 VARIES 514 427 0 100
4 U Restroom 0 N/A 21 0 90 0
4 Storage 0 N/A 12 12 T/A 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
5 Exam 1 VARIES 89 89 0 15
5 Office 1 > 3 HRS 130 130 0 20
5 Corridor 0 N/A 257 127 0 0
5 Exam 1 VARIES 101 101 0 15
5 Exam 1 VARIES 89 89 0 15
5 Exam 1 VARIES 105 105 0 15
5 Waiting 20 VARIES 1229 1229 0 50
BUILDING TOTALS 68 VARIES 7600 6970 630 630
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
BUILDING VENTILATION CALCULATION
TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON
PEAK Office 8 1.00 20 20 160 20
PEAK Waiting 47 0.50 15 7.5 352.5 7.5
PEAK Exam Office 13 0.50 15 7.5 97.5 7.5
BUILDING TOTALS 68 610 (630 provided)
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
22"
22x22,10",-335
22x22,14",-646
8x4,4",10 CFM8x4,4",23 CFM
22x22,10",335 CFM
22x22,10",-243
22x22,14",-646
CEILINGABOVE
RELOCATED
AHU-2
Exam
12
x1
21
8x
12
24
x1
2
ON SLAB
CU-2
ON SLAB
CU-4
ON SLAB
CU-3
ON SLAB
CU-5
ABOVEMEZZANINE
RELOCATED TO
AHU-3
22x22,7",-120
22x22,8",-124
8x4,4",24 CFM
22x22,7",-118 8x4,4",24 CFM
22x22,8",-119
22x22,7"-100
22x22,7",-99
HORIZONTALVERTICAL OREXISTING AHU
MAY CONFIGURE
6x10
12x10
12
x8
8x10
10x12
ABOVEMEZZANINE
EXISTING ON
AHU-4
22x22,10",-253
22x22,12",-427
14x14
10
x1
21
4x
12
ABOVEMEZZANINE
EXISTING ON
AHU-5
HORIZONTALVERTICAL OREXISTING AHU
MAY CONFIGURE
22x22,14",-615
22x22,14",-61522x22,7",-89
22x22,7",-101
22x22,7",-105
22x22,8",-130
22x22,7",129 CFM
22x22,7",-89
22x22,6",89 CFM
22x22,8",-12722x22,6",89 CFM
24
x1
2
16x1220x12
12
x1
61
4x
16
18x16
SPLIT SYSTEM EQUIPMENT SCHEDULEAIR HANDLER MARK: AHU-1,2,5 AHU-3,4UNIT MODEL NUMBER: EXISTING EXISTING
UNIT DIMEN H/W/D: 59.5X26X23.5 44.5X24X23.5
UNIT WEIGHT: 155 111
SUPPLY PLENUM SIZE : 12.02X21.22 12.02X19.22
RETURN PLENUM SIZE : 18.07X21.5 19.5X18.07
SUPPLY FAN CFM / SP : 2000 / .70 800 / .60
SUPPLY FAN H/P : 1 1/4
OUTDOOR AIR CFM: 130 / 130 / 130 120 / 120
UNIT PHASE / HERTZ: * *
UNIT VOLTAGE: * *
HEATER KW: * *
HEATER BREAKER: * *
CONDENSER MARK: CU-1,2,5 CU-3,4NOMINAL A/C TONS : 5 2
UNIT MODEL NUMBER: EXISTING EXISTING
UNIT VOLTAGE: * *
UNIT MCA / BREAKER: * *
UNIT DIMEN H/W/D: 46.4X35.1X38.7 37.2X26.7X30
UNIT WEIGHT: 269 175
TOTAL COOLING BTUH: 58,000 22,800
SENS. COOLING BTUH: 40,000 16,600
LAT. COOLING BTUH: 18,000 6,200
TOTAL HEATING BTUH: 34,120 17,060
SENSIBLE HEAT % 0.69 0.73
SEER: 13 13
THERMOSTAT MODEL: T8411R1002 T8411R1002
NOTES: * EQUIPMENT IS EXISTING,SEE NAME PLATE
DATA FOR EXACT INFORMATION. CLEAN AND CHECK
EQUIPMENT TO INSURE PROPER OPERATION.
SIZE AND INSTALL STAND ALONE DEHUMIDIFICATION
AT THE INDOOR FOUNTAIN AREA.
EXHAUST FAN SCHEDULE
FAN MARK: EF-1MANUFACTURER: NUTONE
MODEL NUMBER: QT-80
FAN TYPE: EXHAUST
FAN CFM: 90
TOTAL PRESSURE: .2
FAN VOLTAGE: 120/1/60
FAN AMPERAGE: .7
FAN DIMEN LWH: 9X9X6
DUCT OUTLET SIZE: 4
DUCT INLET SIZE: 10X10
FAN WEIGHT: 12
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
HANDLER DETAILVERTICAL AIR
FMC 401AIR DUCT* FRESH
FMC 1101WIRING
+ CONTROLPIPING
REFRIGERANT
FMC 303AIR HANDLER
FMC 601AIR DUCTSUPPLY
FMC 601RISER DUCT
* RETURN AIR
FMC 307DRAIN
CONDENSATE
* CEILING
FLOOR
STANDAIR HANDLER
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
FMC 1101+ CONTROL WIRING
REFRIGERANT PIPING
HORIZONTAL AIR HANDLER DETAIL
FMC 401DUCTAIR
* FRESH
TOP CHORDSUSPEND FROM
1/2 THREADED ROD
FMC 303AIR HANDLER
SUPPLY AIR DUCT FMC 601FMC 601
RETURN DUCT
CONDENSATE DRAIN FMC 307
* ACCESS PANEL FMC 306.3
* CEILING
SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
WALL
FLOOR
FMC 1101 - MAY ALSO ROUTE BELOW SLABREFRIGERANT PIPING + CONTROL WIRING
GRADEEQUIPMENT SLAB
FMC 301.13FASTENER
FMC 303CONDENSING UNIT
PIPE COVER - MAY MOUNT INTERIOR
CONDENSING UNIT DETAIL
AHU TYPEVERIFY EXISTING
HORIZONTAL -VERTICAL OREXISTING AHU
MAY CONFIGURE
ALONE DEHUMIDIFICATIONAND PROVIDE STAND
FOUNTAIN - CALCULATETHIS AREA CONTAINS A
North
PERMIT SET1/31/2009
DRAWING DATE
New Office Building721 of 22,597Hillsborough County FloridaCorner of Lakewood & OakfieldPrieto Office Building 1st Floor
1 OF 3DRAWING
HVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
SCALE 1/8"=1'-0"R#884 C#959FLORIDA BERS
813-885-2258HVAC Designs
Neil FimbelDesigned By:
HVAC SCHEDULES + DETAILS
x
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD. SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC NOTES
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
D
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFMWalk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
D
FMC 603.15DUCTED T/ A
CEILING GRILLE
Lobby
COMPLIES WITH FBC 406.3.3.1NATURALLY VENTILATEDOPEN PARKING GARAGE
COMPLIES WITH FBC 406.3.3.1NATURALLY VENTILATEDOPEN PARKING GARAGE
TYPICAL OPENING x10' HEIGHT
22x22,9",250 CFM
22x22,9",250 CFM
22x22,9",250 CFM
22x22,9",250 CFM
22x22,16",-895 CFM
10x12
TO GUTTER / GRASS AREAPUMP CONDESATE DRAIN
FIRE CAULK PENETRATIONSPIPING UP TO ROOF
DUCT SET TO 105 CFM12x12 OAL,6" FRESH AIR
20x18 20x12
ABOVEON ROOF
CU-1
CEILINGABOVE
AHU-1
12x12,8",-105 CFM
RELIEVE 105 CFMRELIEF AIR DAMPER TODUCT SET BAROMETRIC12x12 OAL,8" RELIEF AIR
FIRST FLOOR
PARKING GARAGE NATURAL VENTILATION CALCULATION
FLOOR CLASSIFICATION OPEN WALL PERIMETER OPEN WALL HEIGHT GROSS OPEN AREA % OF OPENING GROSS PERIMETER RESULT
1 OPEN PARKING 328 10.00 3280 54 597 PASSES
BUILDING TOTALS 597
OPENINGS ARE UNIFORMLY DISTRIBUTED ON ALL 4 WALLS, THE OPENING AREA EXCEEDS THE MINIMUM OF 20% OPENING TO PERIMETER WALL AREA.
CALCULATIONS BASED ON THE 2004 + SUPPLEMENTS FLORIDA MECHANICAL CODE SECTION 403.1, 403.3 AND FLORIDA BUILDING CODE 406.3.3.1
FIRST FLOOR AIR BALANCE SCHEDULEZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM
1 LOBBY 14 0.5 1000 895 105 105X X X X X X X X
FIRST FLOOR TOTALS 14 0.5 1000 895 105 105
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
FIRST FLOOR VENTILATION CALCULATION TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT
PEAK Reception / Wait 14 0.50 15 7.5 105 7.5
FIRST FLOOR TOTALS 105
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
TRANE EQUIPMENT
AIR HANDLER MARK: AHU-1UNIT MODEL NUMBER: 2TEC3F30A
UNIT DIMEN H/W/D: 46.5X24X23.5
UNIT WEIGHT: 125
SUPPLY PLENUM SIZE : 12.02X19.22
RETURN PLENUM SIZE : 18.07X19.5
SUPPLY FAN CFM / SP : 1000 / .40
SUPPLY FAN H/P : 1/3
OUTDOOR AIR CFM: 105
UNIT PHASE / HERTZ: 1 / 60
UNIT VOLTAGE: 208 / 240
HEATER KW: 3.6 / 4.8
HEATER BREAKER: 25 / 30
CONDENSER MARK: CU-1NOMINAL A/C TONS : 2.5
UNIT MODEL NUMBER: 2TTR3030A
UNIT VOLTAGE: 208/230/ 1 / 60
UNIT MCA / BREAKER: 13 / 20
UNIT DIMEN H/W/D: 38X30.1X33
UNIT WEIGHT: 198
TOTAL COOLING BTUH: 27,600
SENS. COOLING BTUH: 20,400
LAT. COOLING BTUH: 7,200
TOTAL HEATING BTUH: 17,060
SENSIBLE HEAT % 0.74
SEER: 13
THERMOSTAT MODEL: T8411R1002
NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
FMC 1101+ CONTROL WIRING
REFRIGERANT PIPING
HORIZONTAL AIR HANDLER DETAIL
FMC 401DUCTAIR
* FRESH
TOP CHORDSUSPEND FROM
1/2 THREADED ROD
FMC 303AIR HANDLER
SUPPLY AIR DUCT FMC 601FMC 601
RETURN DUCT
CONDENSATE DRAIN FMC 307
* ACCESS PANEL FMC 306.3
* CEILING
SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
ROOFTOP CONDENSING UNIT DETAIL
CONNECTIONCURB
CURB
CONNECTIONEQUIPMENT
FMC 303EQUIPMENTROOFTOP
MEMBERTRUSS
CONNECT TO
ROOF
CURB
@ 18" O.C.3/8 BOLT
JOISTCURB
EQUIPMENTROOFTOP
O.C.@ 18""
OR ANGLE1/4" PLATESCREWS
3/8"
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOADMECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
North
PERMIT SET1/31/2009
DRAWING DATE
New Office Building10,938 of 22,597Hillsborough County FloridaCorner of Lakewood & OakfieldPrieto Office Building 2nd Floor
2 OF 3DRAWING
HVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
SCALE 1/8"=1'-0"R#884 C#959FLORIDA BERS
813-885-2258HVAC Designs
Neil FimbelDesigned By:
HVAC SCHEDULES + DETAILS
x
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD. SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC NOTES
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
D
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFMWalk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
D
FMC 603.15DUCTED T/ A
CEILING GRILLE
Unit 2 H
Restroom
Unit 2 G
Unit 2 F
Infusion
Pharmacy Cold
Restroom
Exam 2
Exam 1
Lab
Restroom
Exam 3
Exam 4
Exam 5
Server
CorridorFiles
Storage
Phone
Dr Off 4
Dr Off 2
Admin
Billing
Lunch
F Office
Conference
Storage
Unit 2 C Unit 2 B
Restroom
Unit 2 A
Restroom
22x22,8",164 CFM22x22,8",164 CFM
22x22,8",164 CFM 22x22,8",164 CFM
22x22,8",164 CFM22x22,8",164 CFM
SCHEDULE FOR CFMSEE AIR BALANCEFRESH AIR INTAKE12x12 LOUVER + 9"
TYPICAL
10' SEPERATION REQUIREDEXHAUST AIR EQUAL TO FRESH AIR
TYPICAL
10' SEPERATION
22x22,14",-880 CFM
8x4,4",14 CFM
DUCT12x12,9" T/A
TYPICAL
TO ROOFPIPE CHASE
TYPICAL
SECOND FLOOR
18x20 20x12
T/ACFM106
CEILINGABOVE
AHU-1
EF-1VTE
12
x8
12
x1
28
x1
2
NOTEDUNLESSTYPICAL
FLOORABOVE 3rd
CURBON ROOF
CU-1
TYPICAL
T/ACFM147
CEILINGABOVE
AHU-2
FLOORABOVE 3rd
CURBON ROOF
CU-2
22x22,16",-1040 CFM18x20
22x22,8",198 CFM22x22,8",198 CFM
22x22,8",198 CFM22x22,8",198 CFM
22x22,8",198 CFM22x22,8",198 CFM
8x4,4",13 CFM
20x12
12
x8
14
x1
28
x1
2
T/ACFM126
CEILINGABOVE
AHU-3
FLOORABOVE 3rd
CURBON ROOF
CU-3
Restroom
22x22,16",-860 CFM
22x22,8",164 CFM22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",164 CFM
8x4,4",14 CFM
22x22,8",164 CFM
20x12
12x8
12x12
8x12
18x20
Corridor
22x22,8",195 CFM22x22,10",278 CFM
22x22,6",90 CFM
22x22,5",75 CFM
22x22,6",103 CFM
10x6,6",100 CFM8x4,4",19 CFM
Restroom
22x22,5",75 CFM
22x22,9",-184 CFM
22x22,9",-195 CFM
Dr Off 122x22,12",-278 CFM22x22,8",184 CFM
10x6,5",63 CFM
HIGH WALL12x12 T/A
Restroom
22x22,9",-183 CFM
22x22,6",-75 CFM
Dr Off 3
22x22,7",-90 CFM
22x22,6",-75 CFM
8x4,4",19 CFM
18x2020x12
8x12
12x12
12x12
14
x1
2
CEILINGABOVE
AHU-4
FLOORABOVE 3rd
CURBON ROOF
CU-4
22x22,10",307 CFM
8x4,4",14 CFM
8x4,4",11 CFM
22x22,10",289 CFM
22x22,10",289 CFM
22x22,10",289 CFM
Restroom
EF-2VTE
EF-2VTE
EF-2VTE
EF-2VTE
EF-2VTE
EF-2VTE
22x22,9",-192 CFM
22x22,14",-868 CFM
CEILINGABOVE
AHU-5
20
x1
21
8x
20
16
x1
2
FLOORABOVE 3rd
CURBON ROOF
CU-5
22x22,5",65 CFM
22x22,4",28 CFM
22x22,4",28 CFM
22x22,8",165 CFM
SR-82,8",165 CFM
22x22,8",165 CFM
22x22,8",165 CFM
22x22,8",165 CFM
8x4,4",54 CFM
Restroom
22x22,14",-860 CFM
FLOORABOVE 3rd
CURBON ROOF
CU-6
CEILINGABOVE
AHU-6
Recep / Wait
18
x2
02
0x
12
10
x1
2
22x22,5",81 CFM
22x22,9",213 CFM
EF-2VTE
22x22,9",213 CFM
22x22,9",213 CFM
10x6,6",92 CFM
22x22,6",91 CFM
22x22,9",223 CFM 22x22,5",63 CFM
10x6,5",66 CFM
8x4,4",43 CFM
Restroom
22x22,14",-640 CFM
8x4,4",51 CFM
22x22,7",-78 CFM
22x22,9",249 CFMP Infusion
12x12,6",-66 CFM
8x4,4",20 CFM
22x22,10",-300 CFM
10
' S
EP
ER
AT
ION
22x22,10",-223 CFM
22x22,6",-63 CFM
22x22,10",-252 CFM
22x22,6",-63 CFM
22x22,6",-65 CFM
22x22,5",65 CFM
22x22,5",63 CFM
22x22,9",252 CFM
FLOORABOVE 3rd
CURBON ROOF
CU-7
CEILINGABOVE
AHU-7
21x12 18x21
8x
12
12
x1
4
16
x1
01
6x
12
18
x1
2
18
x1
4
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,16",-1060 CFM
Restroom8x4,4",13 CFM
T/ACFM127
EF-1VTE
NOTEDUNLESSTYPICAL
FLOORABOVE 3rd
CURBON ROOF
CU-8
CEILINGABOVE
AHU-8
20
x1
2
12x8 12x12 8x12
18
x2
0
CEILINGABOVE
AHU-9
FLOORABOVE 3rd
CURBON ROOF
CU-9
Restroom
22x22,9",231 CFM
22x22,9",231 CFM
22x22,9",231 CFM
22x22,9",231 CFM
22x22,9",231 CFM
22x22,9",231 CFM
T/ACFM148
22x22,16",-1240 CFM
8x4,4",12 CFM 18
x2
02
0x
12
10x1216x1210x12
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
T/ACFM107
22x22,16",-1080 CFM
8x4,4",13 CFM
FLOORABOVE 3rd
CURBON ROOF
CU-10
CEILINGABOVE
AHU-10
20x12
12x8 12x12 8x12
18x20
TRANE SPLIT SYSTEM EQUIPMENT SCHEDULE
AIR HANDLER MARK: AHU-1,3,6 AHU-2,4,5,8,10 AHU-7 AHU-9UNIT MODEL NUMBER: 2TEC3F30A 2TEC3F36A 2TEC3F60A 2TEC3F42A
UNIT DIMEN H/W/D: 46.5X24X23.5 46.5X24X23.5 59.5X26X23.5 53.25X26X23.5
UNIT WEIGHT: 125 125 155 150
SUPPLY PLENUM SIZE : 12.02X19.22 12.02X19.22 12.02X21.22 12.02X21.22
RETURN PLENUM SIZE : 18.07X19.5 18.07X19.5 18.07X21.5 18.07X21.5
SUPPLY FAN CFM / SP : 1000 / .40 1200 / .40 2000 / .40 1400 / .40
SUPPLY FAN H/P : 1/3 1/3 1 1/2
OUTDOOR AIR CFM: 120/140/140 160/120/140/140/120 250 160
UNIT PHASE / HERTZ: 1 / 60 1 / 60 1 / 60 1 / 60
UNIT VOLTAGE: 208 / 240 208 / 240 208 / 240 208 / 240
HEATER KW: 3.6 / 4.8 3.6 / 4.8 7.2 / 9.6 3.6 / 4.8
HEATER BREAKER: 25 / 30 25 / 30 50 / 60 25 / 30
CONDENSER MARK: CU-1,3,6 CU-2,4,5,8,10 CU-7 CU-9NOMINAL A/C TONS : 2.5 3 5 3.5
UNIT MODEL NUMBER: 2TTR3030A 2TTR3036A 2TTR3060A 2TTR3042A
UNIT VOLTAGE: 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60
UNIT MCA / BREAKER: 13 / 20 18 / 30 32 / 50 21 / 35
UNIT DIMEN H/W/D: 38X30.1X33 38X30.1X33 46.4X35.1X38.7 38.4X35.1X38.7
UNIT WEIGHT: 198 194 269 250
TOTAL COOLING BTUH: 27,600 34,200 58,000 41,000
SENS. COOLING BTUH: 20,400 25,400 40,000 29,800
LAT. COOLING BTUH: 7,200 8,800 18,000 11,200
TOTAL HEATING BTUH: 17,060 17,060 34,120 17,060
SENSIBLE HEAT % 0.74 0.74 0.69 0.73
SEER: 13 13 13.5 13.5
THERMOSTAT MODEL: T8411R1002 T8411R1002 T8411R1002 T8411R1002
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
EXHAUST FAN SCHEDULE
FAN MARK: EF-1 EF-2
MANUFACTURER: NUTONE NUTONE
MODEL NUMBER: QT-150 QT-110
FAN TYPE: EXHAUST EXHAUST
FAN CFM: 140 92.85
TOTAL PRESSURE: .25 .25
FAN VOLTAGE: 120/1/60 120/1/60
FAN AMPERAGE: 1.0 .7
FAN DIMEN LWH: 14X10X9 9X9X6
DUCT OUTLET SIZE: 3.25X10 TO 7 4
DUCT INLET SIZE: 15X11 10X10
FAN WEIGHT: 14 12
NOTES: 1,2 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
SECOND FLOOR VENTILATION CALCULATION TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT
PEAK Conference 10 VARIES 20 19.75 197.5 19.75
PEAK Office 56 1.00 20 20 1120 20
PEAK Reception / Wait 23 0.50 15 7.5 172.5 7.5
SECOND FLOOR TOTALS 89 1490
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
SECOND FLOOR AIR BALANCE SCHEDULEZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 Unit 2 A 6 > 3 HRS 986 880 0 120
1 Restroom 0 N/A 14 0 120 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 Unit 2 B 8 > 3 HRS 1187 1040 0 160
2 Restroom 0 N/A 13 0 160 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 Unit 2 C 7 > 3 HRS 986 860 0 120
3 Restroom 0 N/A 14 0 120 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
4 Server 0 N/A 100 100 T/A 0 0
4 Dr Off 4 1 > 3 HRS 75 75 0 20
4 Dr Off 3 1 > 3 HRS 75 75 0 20
4 Restroom 0 N/A 19 0 96 0
4 Dr Off 2 1 > 3 HRS 184 184 0 20
4 Restroom 0 N/A 63 0 96 0
4 Dr Off 1 1 > 3 HRS 195 195 0 20
4 Admin 1 > 3 HRS 90 90 0 20
4 Billing 1 > 3 HRS 278 278 0 20
4 F Office 0 N/A 18 0 0 0
4 Corridor 0 N/A 103 183 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
5 Lunch 4 < 3 HRS 307 192 0 40
5 Restroom 0 N/A 14 0 95 0
5 Conference 10 < 3 HRS 868 868 0 120
5 Storage 0 N/A 11 0 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
6 Files 0 N/A 28 0 0 0
6 Storage 0 N/A 28 0 0 0
6 Recep / Wait 10 VARIES 825 860 0 140
6 Restroom 0 N/A 54 0 95 0
6 Phone 0 N/A 65 0 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
7 Infusion 9 VARIES 640 640 0 90
7 Restroom 0 N/A 43 0 96 0
7 Pharmacy 1 > 3 HRS 249 300 0 20
7 Cold 0 N/A 51 0 0 0
7 P Infusion 1 > 3 HRS 66 66 0 20
7 Restroom 0 N/A 20 0 96 0
7 Exam 2 1 > 3 HRS 223 223 0 20
7 Exam 1 1 > 3 HRS 63 63 0 20
7 Lab 1 > 3 HRS 92 0 0 20
7 Restroom 0 N/A 92 0 96 0
7 Exam 3 1 > 3 HRS 252 252 0 20
7 Exam 4 1 > 3 HRS 63 63 0 20
7 Exam 5 1 > 3 HRS 65 65 0 20
7 Corridor 0 N/A 81 78 0 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
8 Unit 2 F 7 > 3 HRS 1187 1060 0 140
8 Restroom 0 N/A 13 0 140 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
9 Unit 2 F 8 > 3 HRS 1388 1240 0 160
9 Restroom 0 N/A 12 0 160 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
10 Unit 2 F 6 > 3 HRS 1187 1080 0 120
10 Restroom 0 N/A 13 0 120 0
SECOND FLOOR TOTALS 89 VARIES 12400 10910 1490 1490
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
ROOFTOP CONDENSING UNIT DETAIL
CONNECTIONCURB
CURB
CONNECTIONEQUIPMENT
FMC 303EQUIPMENTROOFTOP
MEMBERTRUSS
CONNECT TO
ROOF
CURB
@ 18" O.C.3/8 BOLT
JOISTCURB
EQUIPMENTROOFTOP
O.C.@ 18""ANGLE
ORPLATE
1/4"SCREWS
3/8"
LOADMECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WINDLOADMECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND
1101CONTROL WIRING FMCREFRIGERANT PIPING +
HORIZONTAL AIR HANDLER DETAIL
FMC 401DUCTAIR
* FRESH
TOP CHORDSUSPEND FROM
1/2 THREADED ROD
FMC 303AIR HANDLER
SUPPLY AIR DUCT FMC 601FMC 601
RETURN DUCT
CONDENSATE DRAIN FMC 307
* ACCESS PANEL FMC 306.3
* CEILING
SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT
DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN
LOBBY BELOWPIPING UP FROM
North
PERMIT SET1/31/2009
DRAWING DATE
New Office Building10,938 of 22,597Hillsborough County FloridaCorner of Lakewood & OakfieldPrieto Office Building 2nd Floor
3 OF 3DRAWING
HVAC
CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:
PROJECT NAME:
SCALE 1/8"=1'-0"R#884 C#959FLORIDA BERS
813-885-2258HVAC Designs
Neil FimbelDesigned By:
HVAC SCHEDULES + DETAILS
x
THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD. SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.
IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND
HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING
HVAC NOTES
BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR
E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE
O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN
S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT
ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN
HVAC SYMBOLS
FMC 603.151 WAY THROW
CEILING REGISTER
FMC 603.152 WAY THROW
CEILING REGISTER
FMC 603.153 WAY THROW
CEILING REGISTER
FMC 603.154 WAY THROW
CEILING REGISTER
FMC 603.15CORNER THROW
CEILING REGISTER
FMC 603.152 WAY THROW
WALL REGISTER
FMC 603.152 WAY THROW
FLOOR REGISTER
AIR FMC 603.15FILTER RETURNFLOOR GRILLE
AIR FMC 603.15FILTER RETURNCEILING GRILLE
AIR FMC 603.15FILTER RETURN
WALL GRILLE
FMC 603.15DIRECT T/ A
WALL GRILLE
FMC SECTION 603DUCTWORKFLEXIBLE
FMC SECTION 603DUCTWORK
RECTANGULAR
SECTION 603BOXES FMC
AIR DISTRIBUTION
FMC SECTION 602PLENUM TRUNK
RETURN AIR
FMC SECTION 602PLENUM TRUNK
SUPPLY AIR
CAP FMC 504ROOF / WALLDRYER VENT
FMC 505 - 506ROOF / WALL CAP
RANGE VENT
ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED
FMC SECTION 606SMOKE DETECTOR
DUCT MOUNTED
FEC 13-613ABOVE FLOOR
THERMOSTAT @ 60"
FMC SECTION 307DRAIN TO GRASS
CONDENSATE
PIPING FMC 1101REFRIGERANT
CONTROL /
FMC SECTION 403EF-1 or as NOTED
EXHAUST FAN
FMC SECTION 306ACCESS PANEL
EQUIPMENT
FMC SECTION 307TO DRYWELLCONDENSATE
FMC SECTION 607FIRE DAMPER
DUCT MOUNTED
FMC 603.15CONTROL DAMPER
AIR VOLUME
303 --- 312FMC SECTIONS
HANDLER ON STANDVERTICAL AIR
FMC 303 -- 312AIR DAMPER
ZONE CONTROL
D
R R
T
DS
FMC 303 -- 312DAMPER
BYPASS AIR
303 -- 312FMC SECTIONS
ON SLABCONDENSING UNIT
ZD
BP
303 --- 312FMC SECTIONS
FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR
303 -- 312FMC SECTIONS
ROOF MOUNTEDPACKAGE UNIT
303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT
30 CFM T/A1" UNDERCUT DOOR
H
303 -- 312FMC SECTIONS
HANDLERDUCTLESS AIR
= DEVICE NECK SIZE
= BRANCH DUCT SIZE
ADJUSTMENTS= AIRFLOW CFMWalk In Closet
Bedroom
4"
32
8x4
TYPICAL ROOM
DUCTBRANCHTYPICAL
DEVICETYPICAL AIR
D
FMC 603.15DUCTED T/ A
CEILING GRILLE
Restroom
Unit 3 G
Restroom
Unit 3 F
Unit 3 Esouth
Unit 3 DeastUnit 3 Dwest
Restroom
Restroom
Restroom
Unit 3 AUnit 3 BUnit 3 C
Unit 3 Enorth
THIRD FLOOR
22x22,8",198 CFM22x22,8",198 CFM
Restroom
T/A DUCT12x12,9"TYPICAL
T/ACFM106
EXHAUST AIR EQUAL TO FRESH AIRTYPICAL
22x22,16",-1080 CFM
T/ACFM148
T/ACFM125
T/ACFM107
T/ACFM147
T/ACFM127
22x22,198 CFM22x22,198 CFM
22x22,198 CFM 22x22,198 CFM
8x4,4",14 CFM
22x22,8",198 CFM22x22,8",198 CFM
22x22,8",198 CFM22x22,8",198 CFM
22x22,8",198 CFM22x22,8",198 CFM
8x4,4",12 CFM
22x22,16",-1040 CFM
EF-1VTE
NOTEDUNLESSTYPICAL
TO GUTTER / GRASSCONDENSATE DRAIN
TYPICAL
ON ROOF
RTU-1ON ROOF
RTU-2
22x22,8",197 CFM22x22,8",197 CFM
22x22,8",197 CFM
22x22,8",197 CFM
22x22,8",197 CFM
22x22,8",197 CFM
8x4,4",15 CFM
22x22,16",-1060 CFM
ON ROOF
RTU-3
18
x1
6
18
x1
6
18
x1
6
22x14 22x14 22x14
12
x1
21
2x
12
12
x1
21
2x
12
12
x1
21
2x
12
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM22x22,9",267 CFM
22x22,9",267 CFM 22x22,9",267 CFM
22x22,18",-1400 CFM
ON ROOF
RTU-4
22x14
18
x1
61
2x
14
12
x1
4
ON ROOF
RTU-5
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,18",-1400 CFM
22x22,9",267 CFM
22x14
18
x1
61
2x
14
8x14 16x14
RELIEF / TYPICAL OF 4 ZONESGRILLE -- FOR INTERIOR AIR PRESSURERELIEF AIR DAMPER + 12x12 RELIEF AIRTYPICAL 12x12 LOUVER + BAROMETRIC
ROOFTOP EQUIPMENTFRESH AIR INTAKE @
TYPICAL
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,18",-1400 CFM
22x22,9",267 CFM
ON ROOF
RTU-6
22x14
18x16 12x14
8x14
16x14
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,9",267 CFM
22x22,18",-1400 CFM
ON ROOF
RTU-7
22x14
18x16 12x1412x14
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM 22x22,8",198 CFM
22x22,198 CFM
22x22,16",-1060 CFM
8x4,4",13 CFM
22
x1
4
12x1218x1612x12
ON ROOF
RTU-8
22x22,9",265 CFM
22x22,9",265 CFM
22x22,9",265 CFM 22x22,9",265 CFM
22x22,18",-1440 CFM
22x22,9",265 CFM
22x22,9",265 CFM
8x4,4",13 CFM
22x14
12x1412x14 18x16
ON ROOF
RTU-9
8x4,4",13 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,16",-1080CFM
Unit 3 H
22
x1
4
12x1218x1612x12
ON ROOF
RTU-10
SECOND FLOORSSPLIT SYSTEMS SERVE FIRST AND
CONDENSING UNIT ON ROOF ABOVETYPICAL CURB MOUNTED
ROOFTOP EQUIPMENT SCHEDULE PACKAGE UNIT MARK: RTU-1,2,3,8,10 RTU-4,5,6,7,9UNIT MANUFACTURER: TRANE TRANE
UNIT MODEL NUMBER: THC033A3 THC043A3
NOMINAL A/C TONS : 3 4
UNIT CONFIGURATION: DOWNFLOW DOWNFLOW
UNIT DIMEN H/W/D: 37X45X70 37X45X70
UNIT WEIGHT: 627 669
SUPPLY PLENUM SIZE : 17X15 17X15
RETURN PLENUM SIZE : 23X14 23X14
SUPPLY FAN CFM / SP : 1200 / .4 1600 / .4
SUPPLY FAN H/P : 1 1
OUTDOOR AIR CFM: 120/160/140/140/120 200/200/200/200/160
UNIT PHASE / HERTZ: 3/60 3/60
UNIT VOLTAGE: 208/230 208/230
UNIT MCA: 19.9 22.6
UNIT MAX BREAKER: 30 35
HEATER KW: 4.5/6 9/12
HEATER MCA: 21.9/24.3 37.5/42.4
HEATER BREAKER: 25/25 40/45
TOTAL COOLING BTUH: 38,000 49,800
SENS. COOLING BTUH: 28,800 39,400
LAT. COOLING BTUH: 9,200 10,400
TOTAL HEATING BTUH: 20,472 40,944
SENS. HEAT % 0.76 0.79
COOLING EFFICIENCY: 13 13
THERMOSTAT MODEL: T8411R1002 T8411R1002
NOTES: ALTERNATE BRAND EQUIPMENT WITH
EQUAL PERFORMANCE ARE ACCEPTABLE.
SUBMIT PERFORMANCE DATA FOR APPROVAL.
EXHAUST FAN SCHEDULE FAN MARK: EF-1MANUFACTURER: NUTONE
MODEL NUMBER: QT-150
FAN TYPE: EXHAUST
FAN CFM: 140
TOTAL PRESSURE: .25
FAN VOLTAGE: 120/1/60
FAN AMPERAGE: 1.0
FAN DIMEN LWH: 14X10X9
DUCT OUTLET SIZE: 3.25X10 TO 7
DUCT INLET SIZE: 15X11
FAN WEIGHT: 14
NOTES: 1,2
1 = VENT TO EXTERIOR
2 = INTERLOCK WITH LIGHTS
THIRD FLOOR AIR BALANCE SCHEDULEZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
1 Unit 3 A 6 > 3 HRS 1186 1080 0 120
1 Restroom 0 N/A 14 0 120 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
2 Unit 3 B 8 > 3 HRS 1188 1040 0 160
2 Restroom 0 N/A 12 0 160 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
3 Unit 3 C 7 > 3 HRS 1185 1060 0 140
3 Restroom 0 N/A 15 0 140 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM
4 Unit 3 Deast 10 > 3 HRS 1600 1400 200 200X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM
5 Unit 3 Dwest 10 > 3 HRS 1600 1400 200 200X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM
6 Unit 3 Enorth 10 > 3 HRS 1600 1400 200 200X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM
7 Unit 3 Esouth 10 > 3 HRS 1600 1400 200 200X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
8 Unit 3 F 7 > 3 HRS 1187 1060 0 140
8 Restroom 0 N/A 13 0 140 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
9 Unit 3 G 8 > 3 HRS 1587 1440 0 160
9 Restroom 0 N/A 13 0 160 0X X X X X X X X
ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM
10 Unit 3 H 6 > 3 HRS 1187 1080 0 120
10 Restroom 0 N/A 13 0 120 0
THIRD FLOOR TOTALS 82 > 3 HRS 14000 12360 1640 1640
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
THIRD FLOOR VENTILATION CALCULATION TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT
PEAK Office 82 1.00 20 20 1640 20
THIRD FLOOR TOTALS 82 1640
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
CURB
ROOFTOP PACKAGE UNIT DETAIL
CONNECTIONCURB
CURB
601FMC
DUCTS/A
601FMC
DUCTR/A
CONNECTIONDUCT
CONNECTIONEQUIPMENT
FMC 303EQUIPMENTROOFTOP
SPAN 3 JOISTS1/4" THK
2" U CHANNEL X
ROOF
@ 18" O.C.3/8 BOLT
JOIST
EQUIPMENTROOFTOP
DUCT @ 8" O.C.SCREWS
1/2"
FMC 601SEALDUCT
CURB
EQUIPMENTROOFTOP
CORNEREACH
ANGLE(1) 1/4x2x2SCREWS(4) 3/8x2
MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOADMECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD
DOWN FOR A MAXIMUM OF 140 MPH WINDBOLT AND SCREW SIZES MAY VARY - TIEANGLE PLATE, OR STRAP FOR TIE DOWNA/C CONTRACTOR MAY USE FLAT PLATE,
NOTE: TIE DOWN METHOD MAY VARY