A LOOK AT SERVICE SAFETY Installation and Replacement Information 85 5 INSTALLATION AND REPLACEMENT INFORMATION I. Compressor Tube Connections . . . . . . . . 86 II. Refrigerant Line Sizes . . . . . . . . . . . . . . . 88 III. Refrigerant Line Pressure Drops . . . . . . . 93 IV. Refrigerant Line Velocities . . . . . . . . . . . . 98 V. Service Valves . . . . . . . . . . . . . . . . . . . . 103 VI. Processing the System . . . . . . . . . . . . . 103 VII. System Cleanup and Compressor Replacement After Compressor Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . 104 VIII. Replacing Compressors in Water- Utilizing Systems: Preventing Explosions. . . . . . . . . . . . . . . . . . . . . . . . 108

Upload: others

Post on 30-Jan-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 85

    5

    INSTALLATION AND REPLACEMENT INFORMATION

    I. Compressor Tube Connections . . . . . . . .86II. Refrigerant Line Sizes . . . . . . . . . . . . . . .88III. Refrigerant Line Pressure Drops . . . . . . .93IV. Refrigerant Line Velocities . . . . . . . . . . . .98V. Service Valves . . . . . . . . . . . . . . . . . . . .103VI. Processing the System . . . . . . . . . . . . .103VII. System Cleanup and Compressor

    Replacement After Compressor Failure. . . . . . . . . . . . . . . . . . . . . . . . . . .104

    VIII. Replacing Compressors in Water-Utilizing Systems: Preventing Explosions. . . . . . . . . . . . . . . . . . . . . . . .108

    PowellTypewritten TextFor more free Tecumseh literature please visit

    PowellTypewritten Text

    PowellTypewritten Text

    PowellTypewritten Text

    PowellTypewritten Text

    PowellTypewritten Textwww.HVACRinfo.com

    PowellTypewritten Text

    www.hvacrinfo.com

  • 86 Chapter 5

    I. Compressor Tube Connections

    Tecumseh Products Company supplies compressorsto hundreds of manufacturers requiring differenttubing sizes and arrangements. Because of this thesame compressor model may be found in the field inmany suction and discharge tube variations, eachdepending upon the specific application in which itis installed.

    Suction connections can usually be identified as thelargest diameter stub tube in the housing. If 2 stubshave the same outer diameter (OD), then the onewith the heavier wall will be the suction connection.If both of the largest stub tubes are the same ODand wall thickness, then either can be used as thesuction connection. Whenever possible, suctionconnections should be kept away from the hermeticterminal area so that condensation will not drip onhermetic terminals, causing corrosion.

    The stub tube, not chosen for the suction connec-tion, may be used for processing the system.

    Identification of compressor connections can usuallybe accomplished without difficulty; however, occa-sionally some question arises concerning oil coolertubes and process tubes.

    Oil cooler tubes are found only in low temperaturerefrigeration models. These tubes connect to a coilor hairpin bend within the compressor oil sump.This coil or hairpin bend is not open inside thecompressor and its only function is to cool the com-pressor sump oil. The oil cooler tubes are most gen-erally connected to a separated tubing circuit in theair cooled condenser.

    Process tubes are installed in compressor housingsduring manufacture as an aid in factory dehydrationand charging.

    Standard discharge tubing arrangements for Tecum-seh hermetic compressors are outlined below. Dis-charge tubes are generally in the same positionwithin any model family. Suction and process tubepositions may vary substantially.

    Figure 5-1. Standard discharge tubing arrangements.

    DischargeTube

    DischargeTube

    DischargeTube

    DischargeTube

    On some AE refrigerationmodels the terminal coverfaces the other way.

    OptionalOil Cooler Tubes

    AERefrigeration

    AW-E AW-F

    AEAir Conditioning

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 87

    Figure 5-1. Standard discharge tubing arrangements - continued.

    AKAir Conditioning

    DischargeTube

    DischargeTube

    DischargeTube

    DischargeTube

    DischargeTube

    DischargeTube

    AJ

    AH

    AVAZ

    AN

    AG

    AB

    RK

  • 88 Chapter 5

    II. Refrigerant Line Sizes

    A. R-12 and R-22 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    The recommended suction line sizes are based pri-marily on the velocities necessary for good oilreturn. In most instances, the resulting pressuredrop will be acceptable for suction lines up to 100’in length.

    Refer to these installation considerations for goodoil return on commercial systems:

    • Slope horizontal suction line downwards in thedirection of the compressor at least 1/2” fall per10 feet of line.

    • The setting of the refrigerant control device(expansion valve) should maintain a minimumof superheat. This is typical of the usual directexpansion evaporators where the oil is returnedby refrigerant vapor.

    • In the case of a flooded type evaporator (bot-tom feed, top suction header, large internal vol-ume, low refrigerant/oil velocities), it isnecessary to maintain a liquid spillover into thesuction line so as to return the oil with the liq-uid refrigerant and to minimize oil trapping inthe evaporator. If because of the spillover, the

    return gas is “wet” at the compressor, a suctionline accumulator should be installed adjacent tothe compressor.

    • On systems with evaporators below -10°F, theoil/refrigerant mixture reaches a maximum vis-cosity when the refrigerant superheat is about30°F on R-22 and R-502 and when about 45°Fto 60°F superheat on R-12 systems. Oil mayreturn sluggishly in such cases because of thehigh viscosity. Two solutions should be consid-ered:

    a. Reduce superheat.b. Add a liquid to suction gas heat

    exchanger close to the evaporator butoutside the refrigerated space.

    • On multiple evaporator systems, prevent the oil(and refrigerant) from collecting in an idle coil.If the evaporator coils are to operate indepen-dently of each other, each should have its ownsuction riser sized to the coil’s capacity.

    • Insulate suction lines.Tables 5-1 and 5-2 show recommended suction linesizes for installations where that line is horizontal ordown flow. In the event the suction line is up flow,use “one standard size” smaller. EXAMPLE: Where a7/8” diameter tube is recommended on that tablefor horizontal or down flow, the recommended sizefor up flow would be 3/4” diameter.

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 89

    Table 5-1: R-12 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. Unit CAPACITY (BTU/Hr.)

    SUCTION LINE SIZESAT SYSTEM EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40°F -20°F 0°F +20°F +40°F1200 5/8 1/2 3/8 3/8 3/8 1/42400 3/4 5/8 1/2 1/2 3/8 1/43600 7/8 3/4 5/8 1/2 1/2 1/44800 1 1/8 7/8 5/8 5/8 1/2 1/46000 1 1/8 7/8 3/4 5/8 1/2 1/47200 1 1/8 1 1/8 7/8 3/4 5/8 1/48400 1 3/8 1 1/8 7/8 3/4 5/8 3/89600 1 5/8 1 1/8 7/8 3/4 5/8 3/8

    10800 1 5/8 1 1/8 1 1/8 7/8 5/8 3/812000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/818000 2 1/8 1 5/8 1 1/8 1 1/8 7/8 3/824000 2 5/8 2 1/8 1 3/8 1 1/8 1 1/8 1/236000 3 1/8 2 1/8 1 5/8 1 3/8 1 1/8 1/248000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/260000 3 5/8 2 5/8 2 5/8 1 5/8 1 3/8 1/272000 4 1/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2

    Table 5-2: R-22 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. Unit CAPACITY (BTU/Hr.)

    SUCTION LINE SIZESAT SYSTEM EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40°F -20°F 0°F +20°F +40°F1200 3/8 3/8 3/8 3/8 1/4

    2400 1/2 1/2 3/8 3/8 1/4

    3600 5/8 1/2 1/2 3/8 1/4

    4800 3/4 5/8 1/2 3/8 1/4

    6000 3/4 5/8 1/2 1/2 1/4

    7200 7/8 3/4 5/8 1/2 1/4

    8400 7/8 3/4 5/8 1/2 1/4

    9600 1 1/8 3/4 5/8 5/8 1/4

    10800 1 1/8 7/8 3/4 5/8 3/8

    12000 1 1/8 7/8 3/4 5/8 3/8

    18000 1 3/8 1 1/8 7/8 3/4 3/8

    24000 1 3/8 1 1/8 1 1/8 7/8 3/8

    36000 1 5/8 1 3/8 1 3/8 1 1/8 1/2

    48000 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    60000 2 1/8 2 1/8 1 5/8 1 3/8 1/2

    72000 2 5/8 2 1/8 1 5/8 1 3/8 1/2

  • 90 Chapter 5

    B. R-22 Refrigerant Line Sizes for Remote Systems Air Conditioning and Heat Pumps

    Condensers and evaporators should be designed andcircuited to maintain adequate velocity to preventoil trapping.

    The tube sizes suggested below are for connectinglines of remote systems. The basis for selection is tomaintain adequate velocity which assures oil returnto the compressor, an acceptable pressure drop toassure compressor capacity and minimum tubingcost.

    To assure adequate oil return, suction line velocitiesshould be minimum of 750 fpm for horizontal ordown flow and 1500 fpm for up flow. Gas velocitiesof 3000 fpm or more will create noise problems andshould be avoided.

    Where a choice of line sizes is possible because of theoverlap in the compressor capacity table, the largersized lines are suggested to minimize the systempressure drop.

    Consider these installation notes:

    • Suction line sizes (up flow) provide adequategas velocities to assure oil return to the com-pressor and, therefore, remain constant in sizeregardless of the vertical lift. Suction line trapsare not required. Horizontal suction lines aresized larger to reduce pressure drop.

    • Suction line lengths in excess of 100’ are notrecommended.

    • On heat pump systems, the lines serving asboth a discharge line and suction line, shouldbe sized as a suction line.

    • Liquid line sizes are based on pressure dropsthat will not permit gas formation for horizon-tal lengths up to 100’.

    The recommendations shown in Table 5-3 are basedon the use of standard refrigeration grade tubingand do not include considerations for additionalpressure drop due to elbows, valves, or reduced jointsizes.

    Table 5-3: R-22 Refrigerant Line Sizes for Remote Systems Air Conditioning and Heat Pumps

    SUCTION LINE OUTER DIAMETER

    Nominal Compressor Cooling Capacity

    (BTU/Hr.) Vertical Up Flow

    Vertical Down Flow

    or Horizontal

    Liquid Line Outer

    Diameter

    Discharge Line Length &Outer Diameter

    25’ 50’ 100’1500 FPM 2500 FPM5700 9400 3/8 1/2 1/4 5/16 5/16 3/8

    8000 13000 1/2 1/2 1/4 5/16 3/8 3/8

    11200 18500 1/2 5/8 5/16 3/8 3/8 1/2

    17000 30000 5/8 3/4 5/16 3/8 1/2 1/2

    27000 44000 3/4 7/8 3/8 3/8 1/2 5/8

    38000 51000 7/8 1 1/8 3/8 1/2 5/8 5/8

    38000 67000 7/8 1 1/8 1/2 1/2 5/8 5/8

    60000 102000 1 1/8 1 3/8 1/2 5/8 3/4 3/4

    96000 156000 1 3/8 1 5/8 5/8 3/4 3/4 7/8

    144000 228000 1 5/8 2 1/8 5/8 3/4 7/8 1 1/8

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 91

    C. R-502 and R-134a Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    The selection of suction gas line sizes should beguided by the following criteria:

    • Assurance of adequate velocity thus insuringoil return capability. (The tube size must belimited to maintain velocities no less than 750fpm for horizontal and down flow and no lessthan 1500 fpm for up flow.)

    • Assurance of acceptable pressure drop. (Thetube size should be limited to maintain veloci-ties no greater than 1500 fpm for horizontaland down flow and no greater than 2500 fpm

    for up flow.

    • Assurance of satisfactory sound level. (Thetube size should be limited to maintain veloci-ties no greater than 3000 fpm.)

    • Assurance of minimum tubing cost. (Thetube size should be as small as possible whilesatisfying the three points mentioned above.)

    Tables 5-4 and 5-5 show recommended suction linesizes for installations where that line is horizontal ordown flow. In the event the suction line is up flow,use “one standard size” smaller. EXAMPLE: Where a7/8” diameter tube is recommended on that tablefor horizontal or down flow, the recommended sizefor up flow would be 3/4” diameter.

    Table 5-4: R-502 Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. Unit CAPACITY BTU/HR.

    SUCTION LINE SIZESAT SYSTEMS EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40°F -20°F 0°F +20°F +40°F1200 1/2 3/8 3/8 3/8 3/8 1/4

    2400 5/8 1/2 1/2 3/8 3/8 1/4

    3600 3/4 5/8 1/2 1/2 3/8 1/4

    4800 7/8 3/4 5/8 1/2 1/2 1/4

    6000 1 1/8 7/8 5/8 5/8 1/2 1/4

    7200 1 1/8 7/8 3/4 5/8 1/2 1/4

    8400 1 1/8 7/8 3/4 5/8 1/2 1/4

    9600 1 1/8 1 1/8 7/8 3/4 5/8 1/4

    10800 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    12000 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    18000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    24000 2 1/8 1 5/8 1 3/8 1 1/8 7/8 3/8

    36000 2 5/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    48000 2 5/8 2 1/8 1 5/8 1 3/8 1 1/8 1/2

    60000 3 1/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

    72000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

  • 92 Chapter 5

    Table 5-5: R-134a Refrigerant Line Sizes for Remote Systems Commercial Refrigeration

    Cond. Unit CAPACITY (BTU/Hr.)

    SUCTION LINE SIZESAT SYSTEMS EVAPORATOR DESIGN TEMPERATURE Liquid Line

    Size-40°F -20°F 0°F +20°F +40°F1200 5/8 1/2 3/8 3/8 3/8 1/4

    2400 3/4 5/8 1/2 1/2 3/8 1/4

    3600 7/8 3/4 5/8 1/2 1/2 1/4

    4800 1 1/8 7/8 3/4 5/8 1/2 1/4

    6000 1 1/8 7/8 3/4 5/8 1/2 1/4

    7200 1 3/8 1 1/8 7/8 3/4 5/8 1/4

    8400 1 3/8 1 1/8 7/8 3/4 5/8 3/8

    9600 1 5/8 1 1/8 7/8 3/4 5/8 3/8

    10800 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    12000 1 5/8 1 3/8 1 1/8 7/8 3/4 3/8

    18000 2 1/8 1 5/8 1 3/8 1 1/8 7/8 3/8

    24000 2 5/8 2 1/8 1 3/8 1 3/8 1 1/8 1/2

    36000 3 1/8 2 1/8 2 1/8 1 3/8 1 1/8 1/2

    48000 3 5/8 2 5/8 2 1/8 1 5/8 1 3/8 1/2

    60000 3 5/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2

    72000 4 1/8 3 1/8 2 5/8 2 1/8 1 5/8 1/2

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 93

    III. Refrigerant Line Pressure Drops

    Figure 5-2. Refrigerant line pressure drops for “Freon” 12 refrigerant (reprinted by permission of DuPont Fluorochemicals).

    .2 .3 .4 .6 .8 2 3 4 6 8 10 20 30 40 60 80 100

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    0.2

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 5 6 8 10 20 30 40 50

    0.3

    0.4

    0.6

    0.8 1 2 3 4 5 6 8 10 20 30 40 50

    EXAMPLE:

    5.5 Tons at -40°C Evap. 85°F Cond.3 1/8" Suction Line Pressure Drop = 0.155 p.s.i./100 ft.3/4" Liquid Line Pressure Drop = 1.0 p.s.i./100 ft.

    At 120°F Condenser

    At 100°F Condenser

    At 80°F Condenser

    6 1 /8

    "

    5 1 /8

    "

    4 1 /8

    "

    3 5 /8

    "

    3 1 /8

    "

    2 1 /8

    "

    1 5 /8

    "

    1 1 /8

    "

    7 /8"

    3 /4"

    5 /8"

    1 /2"

    3 /8"

    -60°

    F E

    vapo

    rato

    r Tem

    pera

    ture

    -40°

    F

    40°F

    Dis

    char

    ge L

    ines

    80°

    F C

    onde

    nser

    100°

    F C

    onde

    nser

    120°

    F C

    onde

    nser

    Liqu

    id L

    ine

    -20°

    F20

    °F0°F

    1 3 /8

    " O.D

    . Typ

    e L

    Copp

    er Tu

    bing

    2 5 /8

    "

    Tons of Refrigeration

    Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.

    NOTE: Pressure drops do not allow for pulsating flow. If flow is pulsating, use next larger pipe size. Liquid line determined at 0°F evap. & 80°F cond. Discharge lines at 0°F evap. Other conditions do not appreciably change result. Vapor evap. outlet assumed to be at 65°F.

  • 94 Chapter 5

    Figure 5-3. Refrigerant line pressure drops for “Freon” 22 refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.2

    0.3

    0.4

    0.6

    0.8

    1 2 3 4 6 8 10 20 30 40 60 80 100

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    0.2

    0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 8 10 20 30 40 506

    0.3

    0.4

    0.6

    0.8 1 2 3 4 5 6 8 10 20 30 40 50

    At 80°F Condenser

    At 100°F Condenser

    At 120°F Condenser

    6 1 /8

    "

    5 1 /8

    "

    4 1 /8

    "

    3 5 /8

    "

    2 5 /8

    "

    1 5 /8

    "

    1 1 /8

    "

    7 /8"

    3 /4"

    5 /8"

    1 /2"

    3 /8"

    -60º

    F Ev

    apor

    ator

    Tem

    pera

    ture

    -40º

    F

    1 3 /8

    " O.D

    . Typ

    e L

    Copp

    er Tu

    bing

    3 1 /8

    "

    2 1 /8

    "

    Tons of Refrigeration

    Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.

    EXAMPLE:

    5.5 Tons at -40°F Evap. 85°F Cond.2 5/8" Suction Line Pressure Drop = 0.18 p.s.i./100 ft.5/8" Liquid Line Pressure Drop = 1.7 p.s.i./100ft.

    -20º

    F20

    ºF40

    ºFD

    isch

    arge

    line

    s 80

    ºF C

    onde

    nser

    100º

    F C

    onde

    nser

    120º

    F C

    onde

    nser

    Liqu

    id L

    ine

    0ºF

    NOTE: Pressure drops do not allow for pulsating flow. If flow is pulsating, use next larger pipe size. Liquid line determined at 0°F evap. & 80°F cond. Discharge lines at 0°F evap. Other conditions do not appreciably change result.Vapor evap. outlet assumed to be at 65°F.

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 95

    Figure 5-4. Refrigerant line pressure drops for “Freon” 502 refrigerant (reprinted by permission of DuPont

    0.2

    0.3

    0.4

    0.6

    0.8

    1 2 3 4 6 8 10 20 30 40 60 80 100

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    0.2

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 8 10 20 30 40 50

    2 3 4 5 6 810 20 30 40500.3 0.4 0.6 0.8 1

    At 80°F CondenserAt 100°F Condenser

    At 120°F Condenser

    7 1 /8

    "6

    1 /8"

    5 1 /8

    "4

    1 /8"

    3 5 /8

    "3

    1 /8"

    2 5 /8

    "2

    1 /8"

    1 5 /8

    "1

    3 /8"

    1 1 /8

    "7 /8

    "3 /4

    "1 /2

    "3 /8

    "

    5 /8" O

    .D. T

    ype

    L Co

    pper

    Tubin

    g

    -60°

    F Ev

    apor

    ator

    Tem

    pera

    ture

    -40°

    F

    Tons of Refrigeration

    Pressure Drop In Lbs. Per Sq. In. Per 100 Ft.

    EXAMPLE:

    5.5 Tons at -40°F Evap. 85°F Cond.Choose 2 5/8" Suction Line Pressure Drop = 0.3

    Choose 3/4" Liquid Line Pressure Drop = 1.7

    -20°

    F

    20°F

    40°F

    Dis

    char

    ge L

    ine

    Liqu

    id L

    ine

    0°F

    NOTE: Pressure drops do not allow forpulsating flow. If flow is pulsating,use next larger pipe size.

  • 96 Chapter 5

    Figure 5-5. Refrigerant line pressure drops for HP62 (404A) refrigerant (reprinted by permission of DuPont Fluorochemeicals).

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8

    1 2 3 4 6 8 10 20 30 40 60 80 100

    200

    300

    400

    600

    800

    1000

    0.01 0.

    4

    0.6

    0.8 1 2 3 4 6 8 10

    0.08 0.

    1

    0.2

    0.3

    0.02

    0.02

    0.03

    0.04

    0.06

    0.08 0.

    1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 8 10

    0.03

    0.04

    0.06

    At 30°C Condenser

    At 40°C Condenser

    At 50°C Condenser

    6 1 /8

    " O.D

    . Typ

    e L

    Copp

    er Tu

    bing

    5 1 /8

    "4

    1 /8"

    3 5 /8

    "3

    1 /8"

    2 5 /8

    "2

    1 /8"

    1 5 /8

    "

    1 3 /8

    "

    1 1 /8

    "

    7 /8"

    3 /4"

    5 /8"

    1 /2"

    3 /8"

    -50°

    C E

    vapo

    rato

    r Tem

    pera

    ture

    s

    -40°

    C-2

    0°C

    0°C

    -30°

    C-1

    0°C

    10°C

    Dis

    char

    ge L

    ines

    Line

    s Li

    nes

    Pressure Drop In Kpai Per Meter

    Tons of Refrigeration

    EXAMPLE:15 kW at -40°C Evap., 40°C Cond.2 1/8" Suction Line Pressure Drop = 0.11kPa/m5/8" Liquid Line Pressure Drop = 0.47 kPa/m

    NOTE: Pressure drops do notallow for pulsating flow.If flow is pulsating, usenext larger pipe size.Liquid line and dischargelines determined at -20°Cevap. and 30°C cond.Other conditions do notappreciably changeresult. Vapor at evap.outlet assumed to be at 20°C.

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 97

    Figure 5-6. Refrigerant line pressure drops for HFC-134a refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.2

    0.3

    0.4

    0.5

    0.6

    0.8 1 2 3 4 6 8 10 20 30 40

    0.1

    0.2

    0.4

    0.6

    1 2 4 6 10 20 30 40 60 100

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 6 8 10 20 30 40 60 80 100

    At 80°F CondenserAt 100°F Condenser

    At 120°F Condenser

    6 1 /8

    " O.D

    . Typ

    e L

    Copp

    er Tu

    bing

    -60°

    F E

    vapo

    rato

    r Tem

    pera

    ture

    -40°

    F-2

    0°F

    20°F

    40°F

    Dis

    char

    ge L

    ines

    Liqu

    id L

    ines

    0°F

    5 1 /8

    "4

    1 /8"

    3 5 /8

    "3

    1 /8"

    2 5 /8

    "2

    1 /8"

    1 5 /8

    "1

    3 /8"

    1 1 /8

    "7 /8

    "3 /4

    "5 /8

    "

    1 /2"

    3 /8"

    Pressure Drop In Psi Per 100 Ft.

    Tons of Refrigeration

    EXAMPLE:25 Tons at -40°F Evap. and 100°F Cond.2 5/8" Suction LinePressure Drop = 5.5 p.s.i./100 ft.1 1/8" Liquid LinePressure Drop = 1.6 p.s.i./100 ft.

    NOTE: Pressure drops do notallow for pulsating flow.If flow is pulsating, usenext larger pipe size.Liquid line and dischargelines determined at 0°Fevap. and 80°F cond.Other conditions do notappreciably changeresult. Vapor at evap.outlet assumed to be at 65°F.

  • 98 Chapter 5

    IV. Refrigerant Line Velocities

    Figure 5-7. Refrigerant line velocities for “Freon” 12 refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.1

    0.2

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    0.4

    0.6

    1 2 4 6 10 20 40 60 100

    15 20 30 40 50 60 70 80 100

    150

    200

    300

    400

    500

    600

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    10,0

    00800

    700

    15 20 30 40 50 60 70 80 100

    150

    200

    300

    400

    500

    600

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    10,0

    00800

    700

    At 80°F Condenser

    EXAMPLE:5.5 Tons at -40°F Evap. 85°F Cond.3 1/8" Suction Line Velocity = 1916 ft./min.3/4" Liquid Line Velocity = 94 ft./min.

    At 100°F Condenser

    At 120°F Condenser

    6 1 /8

    "

    -60°

    F Ev

    apor

    ator

    Tem

    pera

    ture

    -40°

    F

    -20°

    F

    0°F

    20°F

    40°F

    80°F

    Con

    dens

    er

    5 1 /8

    "

    4 1 /8

    "

    3 5 /8

    "

    1 3 /8

    "

    3/4

    "

    5 /8"

    3 1 /8

    "

    2 5 /8

    "

    2 1 /8

    "

    1 5 /8

    "

    1 1 /8

    "

    7 /8" O

    .D. T

    ype

    L Co

    pper

    Tubin

    g

    1/2

    "

    3/8

    "

    Tons of Refrigeration

    Velocity In Feet/Minute

    100°

    F Co

    nden

    ser

    Liquid

    Line

    Disc

    harg

    e Lin

    es 1

    20°F

    Con

    dens

    er

    NOTE: Liquid line determined at 0°F evap. and 80°F cond. Discharge lines at 0°F evap. Net refrigeration for"Freon" 12 includes suction gas at 65°F.

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 99

    Figure 5-8. Refrigerant line velocities for “Freon” 22 refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.1

    0.2

    0.4

    0.6

    1 2 4 6 10 20 40 60 100

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    1515 20 30 40 60 80 10

    0

    150

    200

    300

    400

    600

    800

    1000

    1500

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    20 30 40 60 80 100

    150

    200

    300

    400

    600

    800

    1000

    1500

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    At 80°F CondenserAt 100°F Condenser

    At 120°F Condenser

    5 1 /8

    "

    4 1 /8

    "

    -60°

    F Ev

    apor

    ator

    Tem

    pera

    ture

    Disc

    harg

    e lin

    es 8

    0°F

    Cond

    ense

    r

    -40°

    F

    -20°

    F

    20°F

    40°F

    Liquid

    Line

    100°

    F Co

    nden

    ser

    120°

    F Co

    nden

    ser

    0°F

    3 5 /8

    "

    3 1 /8

    "

    2 5 /8

    "

    2 1 /8

    "

    1 5 /8

    "

    1 3 /8

    "

    1 1 /8

    "

    7 /8" O

    .D. T

    ype

    L Co

    pper

    Tubin

    g

    5 /8"

    1 /2"

    3 /8"

    3 /4"

    Tons of Refrigeration

    Velocity, Feet/Minute

    EXAMPLE:5.5 Tons at -40°F Evap. 85°F Cond.2 5/8" Suction Line Velocity = 1718 ft./min.5/8" Liquid Line Velocity = 114 ft./min.

    NOTE: Liquid line determinedat 0°F evap. and 80°Fcond. Discharge linesat 0°F evap. Netrefrigeration for "Freon"22 includes suction gasat 65°F.

  • 100 Chapter 5

    Figure 5-9. Refrigerant line velocities for “Freon” 502 refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.1

    0.2

    0.4

    0.6

    1 2 4 6 10 20 40 60 100

    2000

    3000

    4000

    6000

    8000

    10,0

    00

    BTU's Per HR

    15 20 30 40 50 60 80 100

    150

    200

    300

    400

    500

    600

    800

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    8000

    10,0

    00

    15 20 30 40 50 60 80 100

    150

    200

    300

    400

    500

    600

    800

    1000

    1500

    2000

    3000

    4000

    5000

    6000

    8000

    10,0

    00

    At 80°F CondenserAt 100°F Condenser

    At 120°F Condenser

    6 1 /8

    "

    1 5 /8

    "1

    3 /8"

    1 1 /8

    "7 /8

    "3 /4

    "5 /8

    "1 /2

    "3 /8

    "

    5 1 /8

    "

    4 1 /8

    "3

    5 /8"

    3 1 /8

    "2

    5 /8"

    2 1 /8

    "

    -60°

    F Ev

    apor

    ator

    Tem

    pera

    ture

    -40°

    F-2

    0°F

    0°F

    20°F

    40°F

    Disc

    harg

    e Lin

    es 8

    0°F

    Cond

    ense

    r

    100°

    F Co

    nden

    ser

    120°

    F Co

    nden

    ser

    Liquid

    Line

    Tons of Refrigeration

    Velocity, Feet/Minute

    EXAMPLE:5.5 Tons at -40°F Evap. 85°F Cond.2 5/8" Suction Line Velocity = 1555 ft./min.3/4" Liquid Line Velocity = 105 ft./min.

    NOTE: Liquid line determinedat 0°F evap. and 80°Fcond. Discharge linesat 0°F evap. Netrefrigeration for "Freon"502 includes suction gasat 65°F.

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 101

    Figure 5-10. Refrigerant line velocities for HP62 (404A) refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8

    1 2 3 4 6 8 10 20 30 40 60 80 100

    200

    300

    400

    600

    800

    100

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 8 10 20 30 40 60 80 100

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 8 10 20 30 40 60 80 100

    At 30°C Condenser

    At 40°C Condenser

    At 50°C Condenser

    6 1 /

    8" O

    .D. T

    ype

    L C

    oppe

    r Tub

    ing

    5 1 /

    8"4

    1 /8"

    3 5 /

    8"3

    1 /8"

    2 5 /

    8"

    7 /8"

    3 /4"

    5 /8"

    3 /8"

    1 /2"

    2 1 /

    8"1

    5 /8"

    1 1 /

    8"

    1 3 /

    8"

    -50°

    C E

    vapo

    rato

    r Tem

    pera

    ture

    s

    -40°

    C-3

    0°C

    -20°

    C

    0°C-10°

    C

    10°C

    Dis

    char

    ge L

    ines

    Liqu

    id L

    ines

    Velocity In M/S

    Kilowatts of Refrigeration

    EXAMPLE:55 kW at -40°C Evap., 40°C Cond.2 1/8" Suction Line Velocity = 38 m/s1 3/8" Liquid Line Velocity = 0.55 m/s

    NOTE: Liquid line and discharge lines determined at -20°C evap.and 30°C cond. Other conditions do not appreciably changeresult. Net refrigeration for HP-62 includes suction gas at 20°C.

  • 102 Chapter 5

    Figure 5-11. Refrigerant line velocities for HFC-134a refrigerant (reprinted by permission of DuPont Fluorochemicals).

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    1 2 3 4 6 8 10 20 30 40 60 80 100

    200

    300

    400

    600

    800

    1000

    0.2

    0.1

    0.2

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 8 10 20 30 40 60 80 100

    0.3

    0.4

    0.6

    0.8 1 2 3 4 6 8 10 20 30 40 60 80 100

    At 30°C CondenserEXAMPLE:45 kW at -30°C Evap., 40°C Cond.3 1/8" Suction Line Velocity = 18 m/s1 3/8" Liquid Line Velocity = 0.37 m/s

    NOTE: Liquid line determined at -20°C evap. and 30°C cond.Discharge lines at -20°C evap. Other conditions do notappreciably change result. Net refrigeration forHFC-134a includes suction gas at 20°C.

    At 40°C Condenser

    At 50°C Condenser

    6 1 /

    8" O

    .D. T

    ype

    L C

    oppe

    r Tub

    ing

    5 1 /

    8"

    4 1 /

    8"

    3 1 /

    8"

    2 1 /

    8" 3

    5 /8"

    2

    5 /8"

    1 5 /

    8"

    1 3 /

    8"

    1 1 /

    8"

    7 /8"

    3 /

    4"

    5 /8"

    1 /

    2"

    3 /8"

    -50°

    C E

    vapo

    rato

    r Tem

    pera

    ture

    s

    -40°

    C

    -30°

    C

    -20°

    C

    -10°

    C

    0°C

    10

    °C

    -40°

    C C

    onde

    nser

    -50°

    C C

    onde

    nser

    Liqu

    id L

    ines

    Dis

    char

    ge L

    ines

    -30°

    C C

    onde

    nser

    Kilowatts of Refrigeration

    Velocity In M/S

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 103

    V. Service ValvesAs shipped with the compressors, the rotolock ser-vice valves have a small plastic dust plug inside thethreaded end. Be sure to remove this plug beforeinstalling.

    Service valves on Tecumseh systems are “frontseated” by turning the valve stem clockwise. Thiscloses the valve and opens the gauge port.

    Turning the stem counter-clockwise “back seats” thevalve and thus opens the system and closes the gaugeport.

    If present, the valve port to the system control (highpressure cutout, low pressure control, fan controletc.) is always open regardless of the position of thevalve stem.

    If it is desired to operate the system with the servicegauge operating, it is necessary to “crack” the valvefrom its back seated position for the gauges to per-form. Before removing the gauges, close the gaugeport by returning the valves to their fully open posi-tion (back seated).

    Remember to check the packing gland nut (ifpresent) on the stem for snugness before leaving thejob. Install the cover nut over the valve stem as a sec-ondary safeguard against leaks at the stem.

    VI. Processing the SystemThe performance and longevity of a refrigerationsystem is strongly influenced by how the system was“processed,” that is, how the system was prepared foroperation at the time of installation. The procedureis:

    1. On split systems, install the liquid and suctionline. See “Refrigerant Line Sizes” on pages 88-92 for recommended line sizes. A properlysized suction line accumulator is recom-mended. See “Accumulator Selection Data” onpage 118 for accumulator sizing. Insulate thesuction line to reduce heat exchange andexcessive return gas temperatures to the com-pressor.

    2. To prevent oxidation and scale forming insidethe tubes, it is good practice to flow dry nitro-gen through the tubing during the soldering

    operations. A light flow of about 1/4 cubic feetper minute is sufficient.

    3. Install a filter in the liquid line immediatelyahead of the capillary tube or expansion valve.A liquid line drier should also be installed.

    4. A suction line filter/drier is recommended toprotect the compressor. A suction accumulatormust be installed on those systems havingdefrost cycles (heat pumps, low temperaturerefrigeration) or the likelihood of periodicfloodbacks (bulk milk coolers, ice machines).See “Accumulator Selection Data” on page 118for accumulator sizing.

    5. Pressure test the system for leaks using thesafety precautions outlined in “System Flush-ing, Purging, and Pressure Testing for Leaks”on pages 4-5. Do not pressurize the systembeyond 150 PSIG field leak test pressure.

    6. Use a vacuum pump (not a compressor) todraw a vacuum of 1000 microns or less fromboth sides of the system. It is a waste of time toattempt to draw a vacuum on a system withthe pump connected only to the low side.Entry must be made directly into the highpressure side to properly evacuate that portionof the system. Use a good electronic gauge tomeasure the vacuum. An accurate reading can-not be made with a refrigeration gauge.Remember 29” of mercury as read on a com-pound gauge equals 23,368 microns of vac-uum.WARNING! Never use a compressor toevacuate a system. Instead, use a high vac-uum pump specifically designed for that pur-pose.

    Never start the compressor while it is underdeep vacuum. Always break a vacuum withrefrigerant charge before energizing thecompressor.

    Failure to follow these instructions can dam-age the hermetic terminal and may result interminal venting. As always, to reduce therisk of serious injury or death from fire dueto terminal venting, never energize the com-pressor unless the protective terminal coveris securely fastened.

  • 104 Chapter 5

    7. If a suction line accumulator is present, chargeinto the accumulator to prevent liquid refrig-erant from reaching the compressor. If this isnot possible, then break the vacuum by allow-ing refrigerant vapor to enter the low side atthe suction service valve. When the systempressure reaches 60 psig for R-22 (70 psig forR-502, 35 psig for R-12), start the compressorand continue charging at rate not more than 5pounds per minutes for the larger systems andsomewhat less for smaller systems. Follow thesafety precautions outlined in “System Charg-ing” on pages 5-6.

    8. Check fans and blowers for correct directionof rotation, belt tension, and proper air flow(CFM).

    9. With the protective terminal cover securelyfastened, run the compressor and allow thesystem pressures and temperatures to stabilize.Systems vary in their operating characteristicsbut generally these approximations will apply:

    10. Before leaving the job run the system forawhile. Listen for abnormal noises. Feel thebottom crankcase housing and determine thatit is warm. Is the compressor upper housingsweating indicating that liquid refrigerant isreaching the compressor? Is the return gastemperature at the compressor 65°F or lessand not more than 80°F? Recheck pressures,amps, fan motors, belts, CFM, etc.

    VII. System Cleanup and Compressor Replacement After Compressor Failure

    Once you determine that a compressor needs to bereplaced you must then determine whether the sys-tem has been contaminated. Compressor motor fail-ure can lead to such contamination. (Whilecompressor motor failure is sometimes referred to asmotor “burnout,” it does not mean that a fire actu-ally occurs inside a hermetic compressor.) Evensmall amounts of contamination must be removedfrom the system to avoid damaging the replacementcompressor. Therefore, it is important to thoroughlyclean a refrigeration/air conditioning system if sys-tem contamination is present.

    If a compressor motor failure has occurred,refrigerant or mixtures of refrigerant and oil inthe system can be acidic and cause chemicalburns. As always, to avoid injury, wear appro-priate protective eyewear, gloves and clothingwhen servicing an air conditioning or refrigera-tion system. If refrigerant or mixtures of refrig-erant and oil come in contact with skin or eyes,flush the exposed area with water and get medi-cal attention immediately.

    The following outlines a process for compressorreplacement and system clean-up for a systemequipped with a Tecumseh compressor. You shouldrefer to the original equipment manufacturers(OEM) service information.

    A. Determine Extent of System Contamination

    Following the precautions in “Refrigerants andOther Chemicals” and “Compressor Removal” onpage 4, remove the compressor.

    Use the following guidelines to determine whethercontamination, if any, is limited to the compressoror extends to the system.

    If the discharge line shows no evidence of contami-nation and the suction stub is clean or has only lightcarbon deposits, then the contaminants are limitedto the compressor housing (Compressor Housing

    Table 5-6: Pressure and Temperature Stabilization

    Pressure Temperature

    Saturated Head Pressure

    Ambient temperature °F + 25°F for air cooled condenser.

    Water cooled Discharge water °F + 10°F

    Saturated evaporator pressure

    Air Conditioning Discharge air °F - 20°F

    Medium Temperature

    Product temperature -10°F to -12°F

    Low Temperature Product temperature -6° to -8°F

    ! WARNING

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 105

    Contamination). A single installation of liquid andsuction line filter-driers should cleanup the system.

    If, however, the discharge line or the suction lineshows evidence of contamination, the compressorwas running at the time of the motor failure andcontaminants were pumped throughout the system(System Contamination). If System Contaminationhas occurred, several changes of the liquid and suc-tion line filter-driers will be needed to cleanup thesystem. In addition, the expansion device will needto be replaced. If the system is a heat pump, the fourway valve should be replaced.

    B. Install Replacement Compressor and Components

    1. Install the replacement compressor with newexternal electrical components (capacitors,relay, overload, etc., where applicable). Checkthe contacts of the starting control or contac-tor.

    2. Install an oversized liquid line filter-drier.

    3. Install a generously sized suction line filter-drier immediately upstream of the compressor.The drier when permanently installed in aclean system, or as initially installed in a dirtysystem, must have a pressure drop not morethan that of Table 5-3. Pressure taps must besupplied immediately before and after the suc-tion filter-drier to permit the pressure drop tobe measured.

    If a suction line accumulator is present andSystem Contamination has occurred, it mustbe thoroughly flushed to remove any trappedsludge and thus prevent it from plugging theoil return hole. The filter-drier should beinstalled upstream of the accumulator and thecompressor.

    In the case of Compressor Housing Contami-nation, the filter-drier should be installedbetween the compressor and the suction lineaccumulator.

    Rubber refrigeration hoses are not satisfactoryfor temporarily hooking up the suction line fil-ter-drier to the system since the acid quicklybreaks down the rubber and plastic.

    4. Follow the precautions in “System Flushing,Purging, and Pressure Testing for Leaks” onpages 4-5, to purge the system and pressuretest for leaks.

    C. Evacuate the System

    Evacuate the system to less than 1000 microns,using a good vacuum pump (not a compressor) andan accurate high vacuum gauge. Operate the pumpat 1000 microns, or less, for several hours to be surethe vacuum is maintained.

    An alternate method of removing moisture and non-condensables from the system is:

    1. Evacuate the system to 29 inches vacuum.Break vacuum with refrigerant to be used forfinal charging of system and vapor charge to35-50 pounds gauge pressure. Leave vaporcharge in system for a minimum of five min-utes. Reduce pressure to 0 gauge pressure.

    2. Repeat step 1.

    3. Evacuate system to 29 inches vacuum. Chargesystem with the specified kind and quantity ofrefrigerant.

    WARNING! Never use a compressor to evacuatea system. Instead, use a high vacuum pump specif-ically designed for that purpose.

    Never start the compressor while it is under deepvacuum. Always break a vacuum with refrigerantcharge before energizing the compressor.

    Failure to follow these instructions can damagethe hermetic terminal and may result in terminalventing. As always, to reduce the risk of seriousinjury or death from fire due to terminal venting,never energize the compressor unless the protec-tive terminal cover is securely fastened.

  • 106 Chapter 5

    D. Charge the System and Check the Pressure Drop

    Charge the system and place in operation. Followthe safety precautions outlined in “System Charg-ing” on pages 5-6. Immediately after startup, checkthe pressure drop across the suction line filter-drier.This will serve two purposes:

    • Verify that the drier selection was correct; thatis, large enough.

    • Serve as a base point to which subsequent pres-sure checks can be compared.

    Because the permissible pressure drop across thedrier is relatively small, it is suggested that a differ-ential pressure gauge be used for the measurement.

    E. Measure the Pressure Drop

    After the system has been operating for an hour orso, measure the pressure drop across the suction linefilter-drier.

    In the case of Compressor Housing Contamination,little change should be noted. The pressure dropwill, in most instances, be below that tolerable for apermanent installation (see Table 5-3).

    On the other hand, where System Contaminationoccurred, an increased pressure drop will be mea-sured. Change the suction filter-drier and the liquidline filter-drier whenever the pressure dropapproaches or exceeds that allowed for temporaryoperation during cleanup (see Table 5-4).

    Keep changing both the suction and liquid line fil-ter-driers until the pressure drop stabilizes at a figureequal to or below that permitted for permanentoperation in a system (see Table 5-3). At this point,it is the service person’s option as to whether to leavethe suction drier in the system or remove it fromoperation.

    If the system is to be opened to permit the perma-nent removal of the suction filter-drier then the liq-uid line filter-drier should be changed once more.

    Table 5-3: Suggested Maximum Pressure Drop (PSI) for Permanent Suction Filter-Drier Installation

    Application Air Cond. High Medium Low Low

    Evaporator Range, °F +55 to +32 +55 to +20 +30 to -10 +10 to -20 -20 to -40

    R-12 2 2 1 1/2 1/2 1/2

    R-22 3 3 2 1 1/2

    R-502 3 3 2 1 1/2

    Table 5-4: Suggested Maximum Pressure Drop (PSI) for Temporary Suction Filter-Drier Installation During Cleanup

    Application Air Cond. High Medium Low Low

    Evaporator Range, °F +55 to +32 +55 to +20 +30 to -10 +10 to -20 -20 to -40

    R-12 9 9 6 2 3/4

    R-22 15 15 9 3 1 1/2

    R-502 15 15 9 3 1 1/2

  • A LOOK AT SERVICE SAFETY

    Installation and Replacement Information 107

    F. Test for Acidity If Multiple Motor Failures Have Occurred

    If the system has suffered multiple motor failures, itis advisable that the oil of the replacement be testedafter Section E and judged acid free before the sys-tem is considered satisfactorily cleaned. An oil sam-ple may be taken from a hermetic system if at thetime the replacement compressor was installed an oiltrap is installed in the suction line (see Figure 5-12).When the trapped oil level appears in the sight glass(less than an ounce is needed) the oil may be slowlytransferred to the beaker of the acid test kit as avail-able from several manufacturers. A reading of lessthan 0.05 acid number is an indication that the sys-

    tem is free of acid. A reading of higher than 0.05means continued cleaning is required. Return to B2on page 105.

    G. Monitor the System

    The above procedure for the cleanup of hermeticsystems after motor failure through the use of suc-tion line filter-drier will prove satisfactory in mostinstances provided the system is monitored and keptclean by repeated drier changes, if such are needed.The failure to follow these minimum cleanup recom-mendations will result in an excessive risk of repeatmotor failure.

    Figure 5-12. Method of obtaining oil sample on hermetic system. After satisfactory oil test, Schrader valve may be capped and the oil sampler taken to next job.

    Schrader Valve Vertically Downward

    Female Schrader Valve Connection

    1/2" Liquid Sight Glass

    1/2" Shut Off Valve

    2" M

    inim

    um

    At Least 6 Diameters

    Suction Line

  • 108 Chapter 5

    VIII. Replacing Compressors in Water-Utilizing Systems: Preventing Explosions

    In certain water-utilizing refrigeration systems,water can leak into the refrigerant side of the system.This can lead to an explosion of system compo-nents, including but not limited to, the compressor.If such an explosion occurs, the resulting blast cankill or seriously injure anyone in the vicinity.

    Water-utilizing systems that have single-wall heatexchangers may present a risk of explosion. Suchsystems may include:

    • water source heat pump/air conditioning sys-tems, and

    • water cooling systems, such as icemakers, watercoolers, and juice dispensers.

    Water-utilizing systems that have single-wall heatexchangers present a risk of explosion unless theyhave either:

    • a high pressure cut-out which interrupts powerto ALL leads to the compressor or

    • an external pressure relief valve. Before replacing a compressor in a water-utilizingsystem, read and follow “Prevention of Water-Utiliz-ing System Explosions” on pages 6-7.