HV Field Testing and CCVT Re-verification

December 2013

© 2013 Quanta Technology LLC Page 2

CVT Calibration and Re-Verification Circuit

IED

Comparator

Fiber cable

Voltage measurement accuracy of 0.05% of amplitude and 0.05 degrees of phase.

4 V or 115V rated

69 V/ 115 V

CVT OVT

CVT Calibration

Control Room

Reference OVT

0.05% Class

OVT Electronics

Copper Cable

69 V/ 115 V

© 2013 Quanta Technology LLC Page 3

CCVT or PT Calibration

CCVTs or PT under test

Ref. VTs connecting to HV line (live)

Electronic comparator (bridge)

© 2013 Quanta Technology LLC Page 4

CCVT or PT Accuracy Re-verification Report

Test report provides:

1. Ratio Error and RCF

(Ratio Correction

Factor)

2. Phase Error, and

3. TCF (Transformer

Correction Factor)

for the CCVT under test at

the real operating voltage,

per IEEE Std. C57.13 and

C57.13.6.

Electronic Comparator (bridge) with < 0.05%

uncertainty traceable to NIST

Extract from Current/Voltage Sensors for Precise Measurements of Power Quality in

Distribution Systems for the Smart Grid

Eddy So and Farnoosh RahmatianNational Research Council Canada and Quanta Technology

IEEE PES General Meeting, Vancouver, BCJuly 23, 2013

© 2013 - Quanta Technology Canada ULC

Ease of Installation and Use• Safety• Light weight• Easy to connect to HV line

– High-impedance– Isolation

• Integrated data processing• Rugged design (environmental elements)

© 2013 - Quanta Technology Canada ULC

Traceability• Unbroken chain of measurements• Compliance with regulations and standards• On site calibration / verification of sensors

– The accuracy requirements of the reference system– Uncertainty < 1/4 devices being verified in the field

• Documentation

© 2013 - Quanta Technology Canada ULC

Calibration and Traceability• Traceability

– Unbroken Chain of Measurements Tracing Back to National and/or International Standards (e.g., NIST)

– Uncertainty analysis and certification

International Standard

National Standard – National Labs, e.g., NIST, NRC

Regional or Portable References

Device Under Test

DUT 1 DUT 2 DUT n

Ref. A Ref. B

NIST Reference Std

DUT 3

Ref. C

NRC Reference Std

International Reference Std

Example:

0.2 – 1.0%

200-1000 ppm

20-50 ppm

DUT 4

© 2013 - Quanta Technology Canada ULC

Calibration Circuit for OVT (OPT)

© 2013 - Quanta Technology Canada ULC

Calibration Results for OVT (OPT)Ratio Error

© 2013 - Quanta Technology Canada ULC

Calibration Results for OVT (or OPT)Phase Error

© 2013 - Quanta Technology Canada ULC

Live-line Connections of OVT• Advantage OVT

– Excitation Current about 1 mA regardless of rated voltage, as compared to conventional PT excitation current of about 100 mA to 1 A (depending on rated voltage).

• Can be connected live

© 2013 - Quanta Technology Canada ULC

OVT Qualification Conclusion• NRC (NIST) Test Results indicate the suitability

of OVT to be used as reference Instrument Transformers for live-line on-site calibrations of HV Revenue Metering Systems of accuracy class 0.2 – 0.3, including HV PMU Systems which usually are of accuracy class 0.5 – 1.0.

• Because of its linearity, certain accuracy and performance parameters can be extended over harmonics and frequency