hpac primary secondary loop vs. primary loop only systems
DESCRIPTION
Primary Secondary Loop vs. Primary Loop Only SystemsTRANSCRIPT
-
SBy ALEXANDER L. BURD, PHD, PE, and GALINA S. BURD, MS
Advanced Research Technology LLC
Sufeld, Conn.
Subdividing various systems into a primary/secondary
(P/S) loop via a hydraulically dependant interconnection
long has been a standard solution for central chilled-water
plants in the United States and Europe. This achieves, at
a relatively low cost, reasonably good hydraulic separa-
tion of central-water-plant cooling-generation systems
(primary loop) from distribution piping
and terminal units (secondary loop).
Primary-loop flow is relatively con-
stant, while secondary-loop flow varies
based on load demand. Primary- and
secondary-loop water flows are inter-
changeable.
In a primary loop, control is achieved
by maintaining a relatively constant flow
rate; water temperature may be changed
via a reset control. This commonly is
referred to as a qualitative control strat-
egy. In a secondary loop, control typi-
cally is achieved by varying water-flow
rate. This commonly is referred to as a
quantitative control strategy.
Figure 1 depicts a system with a con-
stant- or variable-flow primary loop
and a variable-flow secondary loop.
The dedicated constant-speed Pump 1
maintains practically constant flow in
the primary loop (the pump does not
have variable-frequency-drive [VFD]
control), even if flow in the secondary loop (which has its
own pump, variable-speed Pump 2) varies significantly.1,2
Pump 1 is sized to maintain water flow between the chiller
evaporators minimum and maximum allowable values.
Typical Control StrategyIn the system in Figure 1, the direction of water flow
in the decoupling pipe is not controllable and may vary,
depending on the ratio of flow in the secondary and
primary loops.
Various modes of operation of the system were investi-
gated.3,4 The major parameters in the evaluation of energy
efficiency were supply- and return-water temperature and
flow rate before and after the decoupling pipe separating
the primary and secondary loops.
36 HPAC ENGINEERING DECEMBER 2010
Primary/Secondary-Loop vs.
Primary-Loop-Only Systems
Alexander L. Burd, PhD, PE, is president of and Galina S. Burd, MS, is a project manager for Advanced Research Technology, an
engineering and research consulting firm with offices in Suffield, Conn., and Green Bay, Wis. Alexander ([email protected])
has 35 years of experience in the design, research, and optimization of HVAC and district energy systems, which includes
publication of more than 35 research and technical papers in American and European journals, while Galina (gburd@energyart
.net) has more than 25 years of design and research experience in the HVAC and architectural-engineering fields. She has
co-authored many technical and research papers published in American journals.
Comparison of operational modes
and performance of two schemes for
optimizing chilled-water plants
Load
P2
1
2
B
A
3F2
F1t2
t1
t4
t3
P1
VFD
Chiller
1 = Optional constant or variable speed with variable-frequency-drive (VFD) primary-loop pump 2 = Variable-speed secondary-loop pump with VFD 3 = Non-controllable bidirectional decoupling pipe (AB or BA direction) between primary and secondary loop F1 = Flow-meter primary-loop flow rate F2 = Flow-meter secondary-loop flow rate t1 = Temperature of water leaving chiller t2 = Temperature of water returning to chiller t3 = Secondary-loop supply-water temperature t4 = Secondary-loop return-water temperatureP1 = Pressure differential for controlling F1 in Pump 1P2 = Pressure differential for controlling F2 in Pump 2
VFD
Secondary loop (distribution-system piping)Primary loop
(generation-system piping)
FIGURE 1. Optimized control strategy for chilled-water plant with primary (constant- or
variable-flow)/secondary (variable-flow) loop.
-
New Filtration Technology Keeps Cooling Tower Water Clean
ORIVALCoolingTower
CoolingTower
ORIVAL
CoolingTower
ORIVA
L
CoolingTower
ORIVA
LTypicalFull Flow filtrationusingexistingpump.
TypicalSideStream filtrationusing aboosterpump.
Typical SideStream filtration of basinusing a
recirculatingpump.
TypicalSide
Stream filtration
usingexisting
pump.
Every cooling tower has its unique dirtconditions, space constraints and
other special characteristics. Filtrationsystems must take these into account inorder to maintain particle free water.
Orival filters are versatile enough tomeet these criteria. They remove a widerange of dirt down to micron size, of any
specific gravity, even lighter than water.Typical examples include: airborne par-ticles, microbiological growth, bugs,sand, scale, algae, rust, etc.
Line pressure powered, they permit useof the existing cooling tower pump, lowering initial system cost. The fullyautomatic self cleaning cycle takes
seconds and does not interrupt flow.Reclaim units recirculate rinse water
making filtration a zero discharge opera-tion. For more information and system designassistance, contact: Orival, Automatic Self-Cleaning Filters, 213 S. Van Brunt St.,Englewood, NJ 07631. (201) 568-3311,(800) 567-9767, Fax: (201) 568-1916.
FILTRATION TRENDS
www.orival.com
Mode 1. When water flow in the secondary loop (F2)
exceeds water flow in the primary loop (F1) because of a
load increase, a portion of the water returning from the
secondary loop recirculates into the supply-distribution
system (A-to-B direction) and mixes with the flow in the
primary loop. This mode of operation is represented
by the following equations: F2 > F1, t3 > t1, t2 = t4, and
(t4 t3) < (t2 t1).
Mode 2. When water flow in the secondary loop (F2)
is less than water flow in the primary loop (F1) because
of a load reduction, flow in the decoupling pipe reverses
(B-to-A direction). Thus, the excessive flow exiting the
cooling-generation system returns to the primary-loop
system and the chiller. This mode of operation is repre-
sented by the following equations: F1 > F2, t1 = t3, t2 < t4,
and (t4 t3) > (t2 t1).
Mode 3: When the flow in the primary loop (F1) equals
the flow in the secondary loop (F2), there is no flow in the
decoupling line. All water from the secondary loop returns
to the primary loop and chiller, while all water exiting the
chiller flows through the secondary loop. This mode of op-
eration is represented by the following equations: F1 = F2,
t1 = t3, t2 = t4, and (t2 t1) = (t4 t3). Obviously, this mode of
operation is the most beneficial from an energy perspective.
Optimized Control StrategyFigure 1 depicts the optimized control strategy (Mode
3). Unlike a system with an optional constant-speed
primary-loop pump, the system has an additional VFD
controlling the speed of the primary-loop pump. The
rate of water flow in the secondary loop via Pump 2 is
dependent on system load. Water-flow rate in the primary
loop is a function of water-flow rate in the secondary loop
and adjusted to maintain equalized flow.
Following are simplified thermal-balance equations ap-
plicable for both primary and secondary loops, assuming
the specific heat of water does not change appreciably:
QPR = QSEC (1)
QPR = F1 (t2 t1) = F1 (tPR) (2)
QSEC = F2 (t4 t3) = F2 (tSEC) (3)
F1 tPR = F2 tSEC (4)
F1 = F2 (5)
tPR = tSEC (6)
where:
QPR = Primary-loop cooling load, British thermal units
per hour
QSEC = Secondary-loop cooling load, British thermal
DECEMBER 2010 HPAC ENGINEERING 37
Circle 166
-
units per hour
tPR = Primary-loop temperature
differential, degrees Fahrenheit
tSEC = Secondary-loop tempera-
ture differential, degrees Fahrenheit
Equations 5 and 6 essentially rep-
resent the algorithm for the control
of chilled-water plants. For the sys-
tem in Figure 1, control is accom-
plished by varying the speed of
Pump 1. The pumps speed should
not be reduced to the extent water-
flow rate falls below the allowable
low limit or increased to the extent
water-flow rate exceeds the allow-
able high limit.
The building-automation system
would have to limit VFD-turndown
and turn-up ratios to stay within
the range of allowable current fre-
quencies correlated to the range of
allowable primary-loop water-flow
rates. To better match primary- and
secondary-loop water-flow rates,
two-phase control is suggested. The
first phase could consist of quanti-
tative control in both the primary
and secondary loops (Equation
5) while the chilled-water-supply
temperature remained at a given
constant value. The second phase
could consist of qualitative control
in the primary loop and quantita-
tive control in the secondary loop.
(The order in which the control ac-
tions are implemented may vary.)
Reset water-temperature control
(Equation 6) could be realized by
varying water temperature (t1) at
a given fixed (limited) magnitude
of water-flow rate in the primary
loop. The change in water tempera-
ture would impact flow rate in the
secondary loop indirectly; flow via
the primary-loop pump could not
be changed further because of the
aforementioned evaporator-flow
limitations. The P/S-loop system
with variable flow and temperature
control in both loops in Figure 1 is
very versatile, allowing the estab-
lishment of flow-limiting parame-
ters and temperature set points (t1)
over a given time period.
Primary-Loop-Only-Variable-Flow Control System
A primary-loop-only-variable-flow
(PLOVF) control system employs
a single pump to circulate water
through generation- and distribu-
tion-system piping loops (Figure 2).
This arrangement allows uniformly
distributed variable flow throughout
entire systems. The generation- and
distribution-piping systems have a
dependant flow-control arrange-
ment, unlike the generation- and
distribution-piping systems in the
P/S-loop system in Figure 1, which
have an independent flow-control
arrangement with two dedicated
pumps. When flow in a PLOVF dis-
tribution system varies because of
a load change, a VFD control varies
the speed of the pump. If flow in the
distribution system falls below the
chillers low limit, an automatic con-
trol valve modulates to divert flow
from the supply line of the distribu-
tion system back to the chiller (A-to-B
direction). This system, unlike the
P/S-loop system in Figure 1, does not
have the ability to bypass the chiller
if flow in the distribution system
exceeds the chillers high-limit flow.
For this capability to be provided in a
PLOVF system, a second controllable
decoupling pipeline with automatic
control valve and reversed flow di-
rection would have to be added on
the other side of the pump. Other-
wise, another chiller, as well as an-
cillary equipment (i.e., chilled-water
pump, cooling tower, condenser
pump), would have to be placed on-
line, which would result in increased
chiller-plant power demand as soon
as flow in the distribution system
exceeded the high-level limit.
A PLOVF system essentially is
capable of maintaining limited total
flow rate. Typically, control of systems
with flow-rate-limiting devices5 is
achieved by assigning priority status
to one of the two loads. For instance,
in a district-heating-system customer
substation with space-heating and
domestic-hot-water loads, priority is
given to the domestic-hot-water load.
The space-heating load has substan-
tial thermal inertia and the ability to
temporarily accept a lower water-
flow rate without noticeable impact
on air temperature. In a PLOVF sys-
tem, two systems that typically have
low thermal inertia (space cooling) or
no inertia at all (chiller-evaporator-
water flow) share the same level of
priority control.
Control of a PLOVF system is
somewhat more challenging than
control of a P/S-loop system. This
38 HPAC ENGINEERING DECEMBER 2010
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
1 = Primary-loop-only variable-speed pump with variable-frequency drive (VFD) 2 = Automatic control valve for converting primary-loop-only system to constant primary-loop and variable secondary-loop flow operation (single AB-direction controllable flow decoupling pipe) F1 = Flow-meter generation-system-piping-loop flow rate F2 = Flow-meter distribution-system-piping-loop flow rate t1 = Temperature of water leaving chiller t2 = Temperature of water returning to chiller t3 = Distribution-system-piping-loop supply-water temperature t4 = Distribution-system-piping-loop return-water temperatureP1 = Pressure differential for controlling F1P2 = Pressure differential for controlling F2
Distribution-system piping loop
Generation-system piping loopLoad
P2
1
2
F2
F1t2
t1
t4
t3
P1
VFD
Chiller
B
A
FIGURE 2. Primary-loop-only-variable-flow control system.
-
is because a PLOVF system has to
maintain two variables that are con-
tinually fighting: a given set point
of pressure differential (P2) in the
distribution-system loop and a given
set point of pressure differential (P1)
in the generation-system-piping
loop. Thus, overall control-strategy
execution and system operation may
be less accurate and stable, and an
allowance for the possible deviation
from the control-parameter set point
may have to be made. Typically, to
avoid a chiller shutting down because
of insufficient flow, the set point for
low-limit flow via the evaporator is
increased. Because any problems
with the modulating control valve
could impair system performance or
even shut down the entire chilled-
water system, the application of reset
chilled-water-temperature control
during off-design conditions (when
the chilled-water-flow limitation is in
place) is difficult. In comparison with
a P/S-loop system, design chilled-
water temperature may be constant
and elevated in a PLOVF system,
which may lead to increased costs
for distribution piping, pumping,
cooling coils, etc.
Chilled-Water-System Temperature Differential
Chilled-water temperature differ-
ential is critical to P/S and PLOVF
operations in that it determines
chilled-water flow per cooling ton.
Impacting chilled-water temperature
differential most significantly are the
end-users connected to chiller plants.
Take, for instance, an air-handling
unit (AHU) with the following param-
eters:
Air is cooled in a counterflow
chilled-water coil.
The design cooling load is 28.5
tons.
The design sensible and latent
loads are 76 percent and 24 percent
of the design cooling load, respec-
tively.
The cooling load varies in direct
proportion to outdoor dry-bulb air
temperature.
The cooling coil has a two-way
chilled-water control valve to vary
water flow through the coil to satisfy
loads.
The cooling coil is selected for
15F design chilled-water tempera-
ture differential.
The design chilled-water flow via
the cooling coil at 40F inlet water
temperature is 45.7 gpm.
End-user load control. The authors
considered two types of AHU cool-
ing-load-control systems: constant
airflow control (CAFC) and variable
airflow control (VAFC). Maximum
airflow turndown ratio was assumed
to be 3.4 at a relative cooling load
of 0.29 and lower. The top graph
in Figure 3 shows the CAFC sys-
tem requires a substantially greater
change in relative chilled-water flow
to achieve the same level of variation
in cooling-coil load. For instance, for
cooling-coil capacity to be reduced
to 40 percent of the design load, rela-
tive chilled-water flow would have
to be reduced to about 21 percent of
its design magnitude. For the same
reduction in cooling-coil capacity to
be achieved with the VAFC system,
relative chilled-water flow rate would
have to be reduced to about 35 per-
cent of its design magnitude. The bot-
tom graph in Figure 3 indicates the
CAFC system will increase the rela-
tive chilled-water temperature differ-
ential by a factor of about 1.9 when
the relative cooling load is reduced
to 40 percent of its design magnitude.
For the same conditions, the VAFC
system will increase relative chilled-
water temperature differential by a
factor of only about 1.2. Thus, the
same relative reduction in chilled-
water flow via the cooling coil would
result in about 1.6-times-higher rela-
tive chilled-water temperature differ-
ential with the CAFC system than it
would with the VAFC system.
Chiller-evaporator low-limit flow
control. Various control strategies
can be utilized to ensure the sustain-
DECEMBER 2010 HPAC ENGINEERING 39
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
Chill
ed-w
ater
-coil
rela
tive
ch
illed
-wat
er t
emper
ature
diffe
rential
Cooling-coil relative chilled-water flow rate
Chill
ed-w
ater
-coil
rela
tive
coolin
g lo
ad
1.0
0.8
0.6
0.4
0.2
0.2 0.4 0.6 0.8 1.0
Cooling-coil relative chilled-water flow rate
0.2 0.4 0.6 0.8 1.0
2.0
1.8
1.6
1.4
1.2
1.0
CAFC
CAFC
VAFC
VAFC
FIGURE 3. Air-handling-unit-cooling-coil operational parameters with variable (VAFC) and
constant (CAFC) airflow control.
-
ability of a systems low-limit chilled-
water flow. Figure 4 shows the reset
water-temperature control required
to maintain a given low-limit water-
flow level when relative cooling load
changes from 0.64 to 0.17 of design.
The temperature of water entering
the cooling coil increases as load
decreases. Limited chilled-water
flow is maintained by increasing the
temperature of water entering the
cooling coil.
The variation in relative cooling
load from 0.67 to 0.17 requires the
temperature of water entering the
coil to be increased from 40F to
about 52F. The bottom graph in
Figure 4 indicates chilled-water tem-
perature differential will be reduced
from 15F at the relative cooling load
of 0.67 to 3.7F at the relative cooling
load of 0.17.
Other factors impacting chilled-
water-system temperature differ-
ential. Chilled-water temperature
differential also can be impacted by
deposits on the inside and outside
surfaces of cooling coils. Proper and
timely cleaning of heat-exchanger
heat-transfer surfaces, thus, is
important,6 as is cleaning of chilled-
water cooling coils and chiller evapo-
rators and condensers.
Because of the complexity of
real-life conditions, it is unrealistic
to expect an increase in cooling-coil
chilled-water temperature differen-
tial coinciding with a reduction in
cooling load. If a system is balanced
and well-maintained, temperature
differential will remain relatively
close to its design value during off-
design conditions.
Distribution-piping-system design
temperature differential. Distribution-
piping-system design temperature
differential impacts the installed and
operating costs of central chilled-
water systems. For retrofit projects,
such as conversion from direct-
expansion cooling coils to central
chilled-water cooling coils, the cost of
distribution piping could run as high
as 30 percent of the entire system.3,4
Design temperature differential for
the example chilled-water primary
piping system was assumed to vary
from about 2.1F to 22.4F (Table
1). The magnitude of the tempera-
ture differential at the chillers
design cooling load was limited by
t h e a l l o w a b l e m i n i m u m a n d
maximum flow at a given number of
evaporator passes. Low-level flow
rate was specified to ensure evapo-
rator operation with sufficient heat-
exchanger-tube water velocity. High-
level flow rate was specified to ensure
evaporator operation with allowable
heat-exchanger-tube velocity and
avoid unstable heat transfer and tube
40 HPAC ENGINEERING DECEMBER 2010
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
Chill
ed-w
ater
-coil
rela
tive
coolin
g lo
adCooling-coil inlet chilled-water temperature, degrees Fahrenheit
Coolin
g-c
oil
chill
ed-w
ater
tem
per
ature
diffe
rential
, deg
rees
Fah
renhei
t
0.0
16
40 41 42 43 44 45 46 47 48 49 50 51 52 53
Cooling-coil inlet chilled-water temperature, degrees Fahrenheit
40 41 42 43 44 45 46 47 48 49 50 51 52 53
14
12
10
8
6
4
2
0
0.2
0.4
0.6
0.8
FIGURE 4. Cooling-coil inlet chilled-water temperature, relative cooling load, and
temperature differential with low-limit chilled-water-flow control.
Number of evaporator passes 1 2 3
Low-limit evaporator-water flow rate, gallons per minute 964 482 321
Maximum evaporator chilled-water temperature differential, degrees Fahrenheit
7.5 14.9 22.4
Minimum evaporator specific chilled-water flow rate per cooling ton, gallons per minute per ton
3.2 1.6 1.1
High-limit evaporator flow rate, gallons per minute 3,473 1,737 1,158
Minimum evaporator chilled-water temperature differential, degrees Fahrenheit
2.1 4.1 6.2
Maximum evaporator specific chilled-water flow rate per cooling ton, gallons per minute per ton
11.6 5.8 3.9
Relative evaporator-water-flow-rate variation 3.6 3.6 3.6
Notes:1. Relative evaporator-water flow rate shows the ratio of maximum to minimum specific
chilled-water flow rate at the given fixed number of evaporator passes.2. Minimum allowable water-flow rate (gallons per minute) via evaporator at a water velocity of
3.3 fps at a given number of passes could be calculated as minimum specific flow rate (gallons per minute per ton) multiplied by design cooling load (tons).
3. Maximum allowable water-flow rate (gallons per minute) via evaporator at water velocity of 12 fps at a given number of passes could be calculated as maximum specific flow rate (gallons per minute per ton) multiplied by design cooling load (tons).
4. Parameters based on the performance of a 300-ton centrifugal chiller.
TABLE 1. Chiller-evaporator design operational parameters.
-
erosion. Lower water-flow rates
relate to higher chilled-water tem-
perature differentials and vice versa.
Table 1 indicates temperature
differential is dependent on num-
ber of evaporator passes. It shows
evaporator relative water-flow rate
remains the same (i.e., 3.6the ratio
of maximum to minimum tube water
velocities) for all considered number
of evaporator passes.
Allowable minimum chiller rela-
tive cooling load (MCRCL) in Table
2 was calculated using the following
equation:
MCRCL = [1 (TDEMAX TDEMIN)]
SOSF 100, %
where:
TDEMAX = maximum chiller-evapo-
rator design temperature differential
TDEMIN = minimum chiller-evapo-
rator design temperature differential
SOSF = system operational safety
factor, which increases minimum
chilled-water flow via a chillers
evaporator (for PLOVF) to prevent
chiller shutdown on low flow
The higher water-flow turndown
ratios (WFTDRs) in Table 2 are
advantageous because they allow
optimal operation of a system to
satisfy cooling loads.
Chilled-Water Turndown Ratio and Energy Savings
Figure 5 shows WFTDR patterns
for various control strategies. The
system was assumed to use mechani-
cal free cooling at outdoor dry-bulb
air temperatures of 55F and below.
Also, system cooling load was as-
sumed to change linearly in direct
proportion to outdoor dry-bulb air
temperature.
The following options, shown in
Table 2, were considered:
Option 1
TDEMIN = 15F, TDEMAX = 22.4F,
WFTDR = 1.5
This means re la t ive chi l ler-
evaporator chilled-water flow could
be reduced to 67 percent of its
design value.
Relative chilled-water flow via the
pump serving the PLOVF system
in Figure 2 will follow two straight
lines outlined by the triangle ACB in
Figure 5 and remain constant at the
level designated by straight line CB.
Although relative water flow via the
distribution-piping system will fol-
low the load change, the bypass valve
will be open to ensure the required
low-limit chiller-evaporator flow is
maintained. This means the pump
will run at the constant flow rate
indicated by the straight line CB.
P/S-loop systems with variable-
primary and secondary-loop pump-
ing could provide energy savings
(compared with the PLOVF-system
operation indicated by straight line
CB in Figure 5) while dry-bulb out-
door-air temperature ranged from
DECEMBER 2010 HPAC ENGINEERING 41
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
primary/secondary and primary-loop-only systems.
Maximum chiller-evapora-tor design temperature differential, TDEMAX, degrees Fahrenheit
Minimum chiller-evaporator design temperature differential, TDEMIN, degrees Fahrenheit
Allowable reduction in water-flow turn-down ratio (TDEMAXto TDEMIN), times
Allowable MCRCL, percent
22.4 15.0 1.5 73.6
22.4 10.0 2.2 49.0
22.4 6.2 3.6 30.5
Notes:1. Allowable reduction in chilled-water flow rate in distribution piping system the ratio of TDEMAX
to TDEMIN.2. Data adapted from Table 1 (chiller with three-pass evaporator).3. Minimum allowable flow rate via chiller evaporator increased by 10 percent to ensure chiller
in PLOVF system will not be turned down on low-level evaporator flow rate.4. MCRCL = Minimum chiller relative cooling load, at which Bypass Control Valve 2 in Figure 2
will remain closed.
F
C
D
B
H
E
G
A
AC = Secondary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T
DEMIN = 15F, T
DEMAX = 22.4F)
CB = Minimum primary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T
DEMIN = 15F, T
DEMAX = 22.4F)
ACB = PLOVF-system relative flow-rate variation (TDEMIN
= 15F, TDEMAX
= 22.4F)AD = Secondary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T
DEMIN = 10F, T
DEMAX = 22.4F)
DH = Minimum primary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pump (T
DEMIN = 10F, T
DEMAX = 22.4F)
ADH = PLOVF-system relative flow-rate variation (TDEMIN
= 10F, TDEMAX
= 22.4F)AF = Secondary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T
DEMIN = 6.2F, T
DEMAX = 22.4F)
FG = Minimum primary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T
DEMIN = 6.2F, T
DEMAX = 22.4F)
AFG = PLOVF-system relative flow-rate variation (TDEMIN
= 6.2F, TDEMAX
= 22.4F)AE = Relative flow-rate variations for secondary-loop pumps for all considered P/S-loop systems and T
DEMIN and T
DEMAX values
Pri
mar
y/se
condar
y an
d p
rim
ary-
loop-o
nly
re
lative
flow
rat
e 0.75
1.00
0.50
0.25
0.0055 65 10575 85 95
Outdoor dry-bulb air temperature, degrees Fahrenheit
FIGURE 5. Primary/secondary and primary-loop-only relative chilled-water-flow variation.
TABLE 2. Considered design temperature differentials for chiller evaporators serving
-
55F to 83F because of the variable
secondary-loop pumping (Pump 2 in
Figure 1) depicted by straight line CE
in Figure 5.
Option 2
TDEMIN = 10F, TDEMAX = 22.4F,
WFTDR = 2.2
This means relative chiller-evap-
orator chilled-water flow could be
reduced to 44.6 percent of its design
value.
Relative chilled-water flow via the
pump serving the PLOVF system
in Figure 2 will follow two straight
lines outlined by the triangle ADH in
Figure 5 and remain constant at the
level designated by straight line DH.
Although water flow via the distri-
bution-piping system will follow the
load change, the bypass valve (2) will
be open to ensure the required low-
limit chiller-evaporator flow is main-
tained. This means the pump will run
at the constant flow rate indicated by
straight line DH.
P/S-loop systems with variable-
primary and secondary-loop pump-
ing could provide energy savings
(compared with the PLOVF-system
operation indicated by straight line
DH in Figure 5) while dry-bulb out-
door-air temperature ranged from
55F to 74F because of the variable
secondary-loop pumping (Pump 2 in
Figure 1) depicted by straight line DE
in Figure 5.
Option 3
TDEMIN = 6.2F, TDEMAX = 22.4F,
WFTDR = 3.6
This means relative chiller-evap-
orator chilled-water flow could be
reduced to 27.7 percent of its design
value.
Relative chilled-water flow via the
pump serving the PLOVF system
in Figure 2 will follow two straight
lines outlined by the triangle AFG in
Figure 5 and remain constant at the
level designated by straight line FG.
Although water flow via the distri-
bution-piping system will follow the
load change, the bypass valve (2) will
be open to ensure the required low-
limit chiller-evaporator flow is main-
tained. This means the pump will run
at the constant flow rate indicated by
straight line FG.
P/S-loop systems with variable-
primary and secondary-loop pump-
ing could provide energy savings
(compared with the PLOVF-system
operation indicated by straight line
DH in Figure 5) while dry-bulb out-
door-air temperature ranged from
55F to 67F because of the variable
secondary-loop pumping (Pump 2 in
Figure 1) depicted by straight line FE
in Figure 5.
Cooling-Load ProfileCooling-load profile depends on
the ratio of constant load (e.g., inter-
nal heat gain from lights, equipment,
people, etc.) to variable load (e.g.,
ventilation, heat gain from building
envelope, etc.).
Cumulative relative cooling load
and time-duration factor for eight
constant- and variable-load compo-
nents in New England are given in
Figure 6. The design cooling load for
the process area of a manufacturing
facility is close to 57 tons. The actual
constant-cooling-load component
was near 35 tons, or 62 percent of the
design load. The actual variable-load
component was close to 22 tons, or
38 percent of the design load.
Applied in energy analysis, Figure
6 is illustrative of relative cooling-
load variations when the percentage
of constant-cooling-load component
(PCCLC) changes from 0 percent to
100 percent of total cooling load.
P/S- and PLOVF-System Electrical-Energy Usage
Chilled-water-pumping electrical-
energy savings. The top graph in
Figure 7 shows potential annual
chilled-water-pumping electrical-
energy savings for a P/S-loop sys-
tem with variable-flow-rate control
in both loops. The electrical energy
consumed by pump motors was
assumed to vary in direct propor-
tion to changes in motor speed by a
power of 2.5. This is lower than the
theoretical value of 3 recommended
for centrifugal pumps. These savings
will be realized when distribution-
system water flow is equal to or lower
than the allowable chiller-evaporator
low limit (Figure 5). In calculations
of annual electrical-energy use, the
pump serving the PLOVF system was
assumed to have a design flow rate
42 HPAC ENGINEERING DECEMBER 2010
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
Systems with 62-percent PCCLC
Systems with 50-percent PCCLC
Systems with 38-percent PCCLC
Systems with 15-percent PCCLC
Systems with 80-percent PCCLC
Systems with 0-percent PCCLC
Systems with 26-percent PCCLC
Systems with 100-percent PCCLC
Notes:1. Constant load percentage based on ratio of constant-cooling-load component that does not change during mechanical cooling season to design cooling load.2. Relative cooling load shows ratio of current load to design cooling load.3. PCCLC = Percentage of constant-cooling-load component.
Cum
ula
tive
load
tim
e-dura
tion f
acto
r, p
erce
nt
(at
load
equal
to o
r lo
wer
than
show
n)
Relative cooling load, percent
100
90
80
70
60
50
40
30
20
10
10 20 30 40 50 60 70 80 90 1000
0
FIGURE 6. System relative cooling load and cumulative time-duration factor.
-
equal to the design flow rate of the
P/S-loop pumps. The pump serving
the PLOVF system also was assumed
to have a design pressure head equal
to the cumulative design pressure
head of the P/S-loop pumps.
With a MCRCL of 73.6 percent
(Table 2), P/S-loop-system annual
electrical-energy savings vary from
5.8 percent (calculated PCCLC of 62
percent) to 60 percent (calculated PC-
CLC of 0 percent). Annual pumping
electrical-energy usage for the con-
sidered P/S and PLOVF systems will
be equalized at a PCCLC greater than
or equal to 75 percent (Figure 7).
With a MCRCL of 49 percent
(Table 2), P/S-loop-system annual
electrical-energy savings vary from
10.4 percent (PCCLC of 26 percent)
to 41 percent (PCCLC of 0 percent).
Annual pumping electrical-energy
usage for the considered P/S and
PLOVF systems will be equalized
at a PCCLC greater than or equal to
35 percent (Figure 7).
With a MCRCL of 30.5 percent
(Table 2), P/S-loop system annual
electrical-energy savings vary from
2.8 percent (PCCLC of 15 percent)
to 9.5 percent (PCCLC of 0 percent).
Annual electrical-energy usage for
the considered P/S and PLOVF sys-
tems will be equalized at a PCCLC
greater than or equal to 21.5 percent
(Figure 7).
With an MCRCL of 73.6 percent
and a PCCLC varying from 0 percent
to 40 percent, the P/S-loop system
with constant-primary-loop and
variable-secondary-loop pumping
control consumes less electrical
energy annually than the PLOVF
system. These savings are identified
in Figure 7 as the difference in Y-axis
values to the left of the intersection of
the dashed lines. The savings could
be as high as 22 percent at a PCCLC
of 0 percent.
In calculations of electrical-energy
savings, primary- and secondary-
pump usage was assumed to be
about 6 percent of chiller-plant an-
nual electrical-energy consumption.
The data in the top graph of Figure
7 are related to single-chiller plants.
The use of multiple chillers will in-
crease WFTDR and reduce MCRCL.
This will reduce annual pumping
electrical-energy savings. Correc-
tion factors for two- and three-chiller
plants are given in Table 3.
Reset-chilled-water-temperature
electrical-energy savings. The P/S-
loop system with variable-flow
DECEMBER 2010 HPAC ENGINEERING 43
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
.
Linear (approximated MCRCL = 73.6 percent)Linear (approximated MCRCL = 49 percent)Linear (approximated MCRCL = 30.5 percent)Linear (approximated MCRCL = 73.6 percent)
Calculated MCRCL = 73.6 percentCalculated MCRCL = 49 percentCalculated MCRCL = 30.5 percentCalculated MCRCL = 73.6 percent
Two-chillers MCRCL = 36.7 percentSingle-chiller MCRCL = 30.5 percentTwo-chillers MCRCL = 22.9 percent
Single-chiller MCRCL = 73.6 percentTwo-chillers MCRCL = 55.2 percentSingle-chiller MCRCL = 49 percent
Notes:1. Savings calculated for chiller plant operating 24 hr a day, seven days a week in Hartford, Conn.2. MCRCL = minimum chiller relative cooling load (Table 2), at which Bypass Control Valve 2 in the primary-loop-only-variable-flow system (Figure 2) remains closed.3. Single-chiller operation considered in top graph only.4. Dashed red line in top graph indicates pumping savings over primary (constant-flow)/secondary (variable-flow) system.5. Dashed lines indicate savings over the primary-loop-only system.6. Annual pumping savings in top graph compared with chiller-plant annual pumping electrical energy only.7. In bottom graph, pumping and reset-chilled-water-temperature-control annual electrical-energy savings compared with annual electrical energy of entire chiller plant.
Percentage of constant-cooling-load component in relation to overall design cooling load, percent706050403020100
0
1
2
3
4
5
6
Percentage of constant-cooling-load component in relation to overall design cooling load, percent70605040302010
10
20
30
40
50
60
70
00
P/S
-loop-s
yste
m p
um
pin
g a
nd r
eset
ch
illed
-wat
er-t
emper
ature
-contr
ol a
nnual
el
ectr
ical
-ener
gy
savi
ngs,
per
cent
Pri
mar
y/se
condar
y-lo
op-s
yste
m p
um
pin
g
annual
ele
ctri
cal-
ener
gy
savi
ngs,
per
cent
FIGURE 7. Potential annual electrical-energy savings for primary/secondary-loop system with
variable flow.
multiple-chiller operations.
Single-chiller plant Two-chiller plant Three-chiller plant
1.00 0.75 0.50
Notes:1. Single-chiller-plant loading factor assumed to be 100 percent.2. Multiple-chiller-plant loading factor assumed to be 75 percent.3. Minimum allowable chiller relative cooling load increased by 10 percent.
TABLE 3. Correction factors for adjusting pumping annual energy savings to account for
-
control also has savings associated
with reset chilled-water-temperature
control. While considering these
savings, the authors assumed, based
on manufacturer data, that approxi-
mately 2 percent of the chillers input
energy would be saved per degree-
Fahrenheit increase in chilled-water
temperature. The increase in chilled-
water temperature also would in-
crease secondary-loop water flow,
which, in turn, would reduce the
electrical-energy savings associated
with the secondary-loop pump em-
ploying variable-flow control. The
authors incorporated that reduction
in their calculations. The chillers
power demand was assumed to be
about 78 percent of the total plant
power demand.
Cumulative annual electrical-
energy savings. Cumulative annual
electrical-energy savings for pump-
ing and reset chilled-water-temper-
ature control expressed as a per-
centage of total chiller-plant annual
energy consumption are shown in the
bottom graph of Figure 7. The annual
savings of a single-chiller plant with
an MCRCL of 30.5 percent and a
PCCLC of 62 percent and a single-
chiller plant with an MCRCL of 73.6
percent and a PCCLC of 0 percent
vary from 0.5 percent to 5.2 percent.
The annual savings of a two-chiller
plant with an MCRCL of 22.9 percent
and a PCCLC of 62 percent and a two-
chiller plant with an MCRCL of 55.2
percent and a PCCLC of 0 percent
vary from 0.4 percent to 4.1 percent.
Converting From PLOVF to P/S-Loop-With-VFD-Control System
A central chilled-water system
with 2,500-ton chillers serving mul-
tiple AHUs at a New England manu-
facturing facility was converted from
PLOVF (similar to that shown in Fig-
ure 2) to P/S-loop operation (nearly
identical to that shown in Figure 1).
The system had a design cooling load
of approximately 930 tons and a de-
sign secondary-loop chilled-water
flow of about 1,600 gpm. About 50
percent of the cooling load was con-
stant (PCCLC of 50 percent). The
P/S-loop system had two dedicated
water-flow meters to separately
measure the flows in the primary and
secondary loops, as well as in the
distribution- and generation-piping
loops of the PLOVF system. To com-
pare the hourly operational modes of
the systems, the authors selected a
two-day sample with approximately
the same dry-bulb outdoor-air tem-
perature for both systems. The reset
chilled-water-temperature control
for the P/S system was not activated
during the two days. The outdoor
dry-bulb air temperature ranged
from 57F to 83F. The average daily
dry-bulb air temperature was close to
69F, while the cooling load ranged
from 250 tons to 450 tons. Only one
chiller was running. The high-limit
chiller-evaporator flow was 1,200
gpm (i.e., TDEMIN was 10F). The low-
level chiller-evaporator flow was 670
gpm (i.e., TDEMAX was 17.9F). Thus,
WFTDR was 1.79.
44 HPAC ENGINEERING DECEMBER 2010
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS
Hourl
y el
ectr
ical
-ener
gy
usa
ge
by
pum
ps
in p
rim
ary/
seco
ndar
y an
d p
rim
ary-
loop-o
nly
sys
tem
s, k
ilow
att-
hours
Outdoor dry-bulb air temperature, degrees Fahrenheit55 60 65 7570 8580
Outdoor dry-bulb air temperature, degrees Fahrenheit55 60 65 7570 8580
Outdoor dry-bulb air temperature, degrees Fahrenheit55 60 65 7570 8580
Outdoor dry-bulb air temperature, degrees Fahrenheit55
50
40
30
20
10
0
900
800
700
600
500
40060 65 7570 8580
900
800
700
600
500
400
3
4
5
6
7
Pri
mar
y-lo
op-o
nly
-flow
-rat
e ch
illed
-w
ater
sys
tem
, gal
lons
per
min
ute
Primary-loop-only-system total water-flow rate (F1 in Figure 2)Primary-loop-only-system distribution-piping flow (F2 in Figure 2)
Pri
mar
y-lo
op-o
nly
-chill
ed-
wat
er-s
yste
m r
elat
ive
flow
ra
te v
ia b
ypas
s va
lve,
per
cent
Pri
mar
y/se
condar
y-ch
illed
-wat
er-s
yste
m-
loop fl
ow
rat
e, g
allo
ns
per
min
ute
Secondary-loop water-flow rate (F2 in Figure 1)Primary-loop water-flow rate (F1 in Figure 1)
Primary-loop-only-system pump hourly electrical-energy usagePrimary/secondary-pump cumulative hourly electrical-energy usage
FIGURE 8. Primary/secondary- and primary-loop-only-system hourly trend data.
-
Low-limit chiller-evaporator flow
was set at 700 gpm during P/S-loop
operation; during PLOVF-loop op-
eration, it was set at 770 gpm. An
attempt to lower low-limit flow
during PLOVF-loop operation was
unsuccessful because of evapora-
tor-induced chiller shutdown on
low flow.
Total chilled-water flow via the
pump in the PLOVF system (Point
F1 in Figure 2) was relatively sta-
ble, varying from about 720 to 860
gpm (Figure 8). Meanwhile, chilled-
water flow via the distribution-
piping system varied from 439 to
847 gpm. Chilled-water flow via the
chillers evaporator was maintained
at its allowable low-limit magnitude
through bypass-control-valve mod-
ulation. Chilled-water flow via the
bypass control valve, which repre-
sents the difference between flow
via the pump and flow via the distri-
bution-piping system, varied from
about 10 to 285 gpm. Flow via the
bypass valve, expressed as a per-
centage of total flow via the pump,
varied from about 2 percent (at
higher cooling loads) to 39 percent
(at lower cooling loads). Any time
and to any extentthe bypass valve
(2) was open, VFD speed and pump
flow remained constant, wasting
electrical energy.
Chilled-water flow in the P/S-loop
system varied from 700 to 816 gpm
(Figure 8). Flow in the secondary
loop varied from 420 to 820 gpm.
Chilled-water flow via the distribu-
tion-piping system varied indepen-
dently of water flow via the chiller
evaporator pump. Chilled-water
flow via the distribution system was
reduced following the load reduction
in the cooling system. This led to
reduced electrical-energy use by
Pump 2. Chilled-water flow via the
primary-loop pump and chil ler
evaporator remained relatively con-
stant, satisfying low-limit water-flow
requirements via the evaporator.
The same 100-hp pump (design
water flow 2,400 gpm) was used for
the PLOVF system and the secondary
loop of the P/S-loop system. The pri-
mary loop of the P/S-loop system had
its own 15-hp pump (design water
flow 1,200 gpm). The long operational
hours of the PLOVF system, with
nearly constant flow via the pump
necessary to maintain low-limit flow
via the chiller evaporator, resulted
in wasted electrical-energy power
demand (kilowatts) and usage (kilo-
watt-hours). Secondary-loop pump
electrical-energy usage decreased
and increased following cooling-load
variations. Electrical-energy savings
for the P/S-loop system varied from
about 3 percent to 50 percent, aver-
aging around 20 percent per day.
The authors have observed similar
electrical-energy savings following
other chiller plants conversion from
PLOVF to P/S-loop operation.
SummaryThis article compared the opera-
tional modes and performance of
P/S-loop and PLOVF systems.
The operating efficiency of chilled-
water systems with a primary (con-
stant-flow)/secondary (variable-
flow)-loop arrangement can be
improved by applying a two-phase
optimized control strategy consist-
ing of variable flow and temperature
control for primary-loop pumps and
variable-flow control for secondary-
loop pumps.
PLOVF-with-VFD control wastes
energy when primary-loop flow is
constrained by the chiller-evaporator
low limit and chilled water is diverted
via decoupling line from the supply
pipe to the return pipe of the gen-
eration system. The magnitude of
annual energy savings (pumping
and reset chilled-water temperature)
of P/S-loop control depends on
multiple variables, such as chiller-
evaporator-flow turndown ratio,
minimum chiller relative cooling load,
load composition, number of chill-
ers, etc. For New England weather
conditions, annual electrical-energy
savings could be 0.5 to 5.2 percent
for a single-chiller plant and 0.4 to 4.1
percent for a two-chiller plant.
P/S-loop-with-variable-flow con-
trol reduces chiller-plant power
demand by resetting chilled-water
temperature when flow in the dis-
tribution piping exceeds a high-limit
value for the chiller evaporator and
the system diverts water via decou-
pling line from the return pipe to the
supply pipe of the distribution sys-
tem. This prevents or delays the addi-
tion of a chiller and associated ancil-
lary equipment and saves energy.
Compared with PLOVF systems,
P/S-loop systems with variable flow
also have the advantage of more-
accurate, flexible, and stable control
and operational conditions.
References1) Burd, A.L. (1994). Optimizing
customers heating systems to reduce
capital and operating cost in district
heating with cogeneration. Proceed-
ings of International District Heat-
ing and Cooling Association Annual
Conference, pp. 237-252.
2) Burd, A.L. (1993). Computer
design of terminal heating substa-
tions for district heating. ASHRAE
Transactions, 99 (2), 245-265.
3) Burd, A.L., Burd, G.S., & De
Maio, M. (2005, March). Smith &
Wesson: The story of a chilled-water
retrofit (part 1). HPAC Engineering,
pp. 38-47.
4) Burd, A.L., Burd, G.S., & De
Maio, M. (2005, July) . Smith &
Wesson: The story of a chilled-water
retrofit (part 2). HPAC Engineering,
pp. 24-37.
5) Burd, A.L. (1997). Deferred
heat supply for space heating using
a capacity-limiting device A ben-
eficial approach for district heating.
ASHRAE Transactions, 103 (2), 23-31.
6) Burd, A.L., & Burd, G.S. (1996).
Optimal cycle for plate heat exchanger
cleaning in customer substation.
Proceedings of International District
Energy Association Annual Confer-
ence, pp. 177-192.
Did you find this article useful? Send
comments and suggestions to Scott
Arnold at [email protected].
DECEMBER 2010 HPAC ENGINEERING 45
PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS