hpac primary secondary loop vs. primary loop only systems

10
 S By ALEXANDER L. BURD, PHD, PE, and GALINA S. BURD, MS Advanced Research Technology LLC Sufeld, Conn. Subdividing various systems into a primary/secondary (P/S) loop via a hydraulically dependant interconnectio n long has been a standard solution for central chilled-water plants in the United States and Europe. This achieves, at a relatively low cost, reasonably good hydraulic separa- tion of central-water-plant cooling-generation systems (primary loop) from distribution piping and terminal units (secondary loop). Primary-loop flow is relatively con- stant, while secondary-loop flow varies based on load demand. Primary- and secondary-loop water flows are inter- changeable. In a primary loop, control is achieved by maintaining a relatively constant flow rate; water temperature may be changed  via a res et con tro l. Thi s c ommo nly is referred to as a qualitative control strat- egy. In a secondary loop, control typi- cally is achieved by varying water-flow rate. This commonly is referred to as a quantitative control strategy. Figure 1 depicts a system with a con- stant- or variable-flow primary loop and a variable-flow secondary loop. The dedicated constant-speed Pump 1 maintains practically constant flow in the primary loop (the pump does not have variable-frequency-drive [VFD] control), even if flow in the secondary loop (which has its own pump, variable-speed Pump 2) varies significantly. 1,2  Pump 1 is sized to maintain water flow between the chiller evaporator’s minimum and maximum allowable values. Typical Control Strategy In the system in Figure 1, the direction of water flow in the decoupling pipe is not controllable and may vary, depending on the ratio of flow in the secondary and primary loops. Various modes of operation of the system were investi- gated. 3,4  The major parameters in the evaluation of energy efficiency were supply- and return-water temperature and flow rate before and after the decoupling pipe separating the primary and secondary loops. 36 HPAC ENGINEERING DECEMBER 2010 Primary/Secondary-Loop  v s. Primary-Loop-Only Systems  Alexande r L. Burd, PhD, PE, is pre sident of an d Galina S . Burd, MS, is a projec t manager for Advanced R esearch Tec hnology, an engineering and research consulting firm with offices in Suffield, Conn., and Green Bay, Wis. Alexander ( [email protected]  )  has 35 y ears of e xper ience in t he de sign, rese arch, and optimizat ion o f HVAC and distr ict ener gy s yste ms, which includes  publication of more than 35 research and technical papers in American and European journals, while Galin a ( gburd@energyart  .net  ) has more than 25 years of design and research experience in the HVAC and architectural-engineering fields. She has co-authored many technical and research papers published in American journals. Comparison of operational modes and performance of two schemes for  optimizing chilled-water plants Load P2 1 2 B A 3 F2 F1 t2 t1 t4 t3 P1 VFD Chiller  1 = Optional constant or variable speed with variable-frequency-drive ( VFD) primary-loop pump  2 = Variable-speed secondary-loop pump with VFD  3 = Non-controllable bidirectional decoupling pipe (AB  or BA direction) between primary and secondary loop  F1 = Flow-meter primary-loop ow rate  F2 = Flow-meter secondary-loop ow r ate  t1 = Temperature of water leaving chiller  t2 = Temperature of water returning to chil ler  t3 = Secondary-loop supply-water temperature  t4 = Secondary-loop return-water temperature P1 = Pressure differential for controlling F1 in Pump 1 P2 = Pressure differential for controlling F2 in Pump 2 VFD Secondary loop (distribution-system piping) Primary loop (generation-system piping) FIGURE 1. Optimized control strategy for chilled-water plant with primary (constant- or  variable-flow)/s econdary ( variable-flow) loop.

Upload: antonio-lebrun

Post on 02-Nov-2015

218 views

Category:

Documents


0 download

DESCRIPTION

Primary Secondary Loop vs. Primary Loop Only Systems

TRANSCRIPT

  • SBy ALEXANDER L. BURD, PHD, PE, and GALINA S. BURD, MS

    Advanced Research Technology LLC

    Sufeld, Conn.

    Subdividing various systems into a primary/secondary

    (P/S) loop via a hydraulically dependant interconnection

    long has been a standard solution for central chilled-water

    plants in the United States and Europe. This achieves, at

    a relatively low cost, reasonably good hydraulic separa-

    tion of central-water-plant cooling-generation systems

    (primary loop) from distribution piping

    and terminal units (secondary loop).

    Primary-loop flow is relatively con-

    stant, while secondary-loop flow varies

    based on load demand. Primary- and

    secondary-loop water flows are inter-

    changeable.

    In a primary loop, control is achieved

    by maintaining a relatively constant flow

    rate; water temperature may be changed

    via a reset control. This commonly is

    referred to as a qualitative control strat-

    egy. In a secondary loop, control typi-

    cally is achieved by varying water-flow

    rate. This commonly is referred to as a

    quantitative control strategy.

    Figure 1 depicts a system with a con-

    stant- or variable-flow primary loop

    and a variable-flow secondary loop.

    The dedicated constant-speed Pump 1

    maintains practically constant flow in

    the primary loop (the pump does not

    have variable-frequency-drive [VFD]

    control), even if flow in the secondary loop (which has its

    own pump, variable-speed Pump 2) varies significantly.1,2

    Pump 1 is sized to maintain water flow between the chiller

    evaporators minimum and maximum allowable values.

    Typical Control StrategyIn the system in Figure 1, the direction of water flow

    in the decoupling pipe is not controllable and may vary,

    depending on the ratio of flow in the secondary and

    primary loops.

    Various modes of operation of the system were investi-

    gated.3,4 The major parameters in the evaluation of energy

    efficiency were supply- and return-water temperature and

    flow rate before and after the decoupling pipe separating

    the primary and secondary loops.

    36 HPAC ENGINEERING DECEMBER 2010

    Primary/Secondary-Loop vs.

    Primary-Loop-Only Systems

    Alexander L. Burd, PhD, PE, is president of and Galina S. Burd, MS, is a project manager for Advanced Research Technology, an

    engineering and research consulting firm with offices in Suffield, Conn., and Green Bay, Wis. Alexander ([email protected])

    has 35 years of experience in the design, research, and optimization of HVAC and district energy systems, which includes

    publication of more than 35 research and technical papers in American and European journals, while Galina (gburd@energyart

    .net) has more than 25 years of design and research experience in the HVAC and architectural-engineering fields. She has

    co-authored many technical and research papers published in American journals.

    Comparison of operational modes

    and performance of two schemes for

    optimizing chilled-water plants

    Load

    P2

    1

    2

    B

    A

    3F2

    F1t2

    t1

    t4

    t3

    P1

    VFD

    Chiller

    1 = Optional constant or variable speed with variable-frequency-drive (VFD) primary-loop pump 2 = Variable-speed secondary-loop pump with VFD 3 = Non-controllable bidirectional decoupling pipe (AB or BA direction) between primary and secondary loop F1 = Flow-meter primary-loop flow rate F2 = Flow-meter secondary-loop flow rate t1 = Temperature of water leaving chiller t2 = Temperature of water returning to chiller t3 = Secondary-loop supply-water temperature t4 = Secondary-loop return-water temperatureP1 = Pressure differential for controlling F1 in Pump 1P2 = Pressure differential for controlling F2 in Pump 2

    VFD

    Secondary loop (distribution-system piping)Primary loop

    (generation-system piping)

    FIGURE 1. Optimized control strategy for chilled-water plant with primary (constant- or

    variable-flow)/secondary (variable-flow) loop.

  • New Filtration Technology Keeps Cooling Tower Water Clean

    ORIVALCoolingTower

    CoolingTower

    ORIVAL

    CoolingTower

    ORIVA

    L

    CoolingTower

    ORIVA

    LTypicalFull Flow filtrationusingexistingpump.

    TypicalSideStream filtrationusing aboosterpump.

    Typical SideStream filtration of basinusing a

    recirculatingpump.

    TypicalSide

    Stream filtration

    usingexisting

    pump.

    Every cooling tower has its unique dirtconditions, space constraints and

    other special characteristics. Filtrationsystems must take these into account inorder to maintain particle free water.

    Orival filters are versatile enough tomeet these criteria. They remove a widerange of dirt down to micron size, of any

    specific gravity, even lighter than water.Typical examples include: airborne par-ticles, microbiological growth, bugs,sand, scale, algae, rust, etc.

    Line pressure powered, they permit useof the existing cooling tower pump, lowering initial system cost. The fullyautomatic self cleaning cycle takes

    seconds and does not interrupt flow.Reclaim units recirculate rinse water

    making filtration a zero discharge opera-tion. For more information and system designassistance, contact: Orival, Automatic Self-Cleaning Filters, 213 S. Van Brunt St.,Englewood, NJ 07631. (201) 568-3311,(800) 567-9767, Fax: (201) 568-1916.

    FILTRATION TRENDS

    www.orival.com

    Mode 1. When water flow in the secondary loop (F2)

    exceeds water flow in the primary loop (F1) because of a

    load increase, a portion of the water returning from the

    secondary loop recirculates into the supply-distribution

    system (A-to-B direction) and mixes with the flow in the

    primary loop. This mode of operation is represented

    by the following equations: F2 > F1, t3 > t1, t2 = t4, and

    (t4 t3) < (t2 t1).

    Mode 2. When water flow in the secondary loop (F2)

    is less than water flow in the primary loop (F1) because

    of a load reduction, flow in the decoupling pipe reverses

    (B-to-A direction). Thus, the excessive flow exiting the

    cooling-generation system returns to the primary-loop

    system and the chiller. This mode of operation is repre-

    sented by the following equations: F1 > F2, t1 = t3, t2 < t4,

    and (t4 t3) > (t2 t1).

    Mode 3: When the flow in the primary loop (F1) equals

    the flow in the secondary loop (F2), there is no flow in the

    decoupling line. All water from the secondary loop returns

    to the primary loop and chiller, while all water exiting the

    chiller flows through the secondary loop. This mode of op-

    eration is represented by the following equations: F1 = F2,

    t1 = t3, t2 = t4, and (t2 t1) = (t4 t3). Obviously, this mode of

    operation is the most beneficial from an energy perspective.

    Optimized Control StrategyFigure 1 depicts the optimized control strategy (Mode

    3). Unlike a system with an optional constant-speed

    primary-loop pump, the system has an additional VFD

    controlling the speed of the primary-loop pump. The

    rate of water flow in the secondary loop via Pump 2 is

    dependent on system load. Water-flow rate in the primary

    loop is a function of water-flow rate in the secondary loop

    and adjusted to maintain equalized flow.

    Following are simplified thermal-balance equations ap-

    plicable for both primary and secondary loops, assuming

    the specific heat of water does not change appreciably:

    QPR = QSEC (1)

    QPR = F1 (t2 t1) = F1 (tPR) (2)

    QSEC = F2 (t4 t3) = F2 (tSEC) (3)

    F1 tPR = F2 tSEC (4)

    F1 = F2 (5)

    tPR = tSEC (6)

    where:

    QPR = Primary-loop cooling load, British thermal units

    per hour

    QSEC = Secondary-loop cooling load, British thermal

    DECEMBER 2010 HPAC ENGINEERING 37

    Circle 166

  • units per hour

    tPR = Primary-loop temperature

    differential, degrees Fahrenheit

    tSEC = Secondary-loop tempera-

    ture differential, degrees Fahrenheit

    Equations 5 and 6 essentially rep-

    resent the algorithm for the control

    of chilled-water plants. For the sys-

    tem in Figure 1, control is accom-

    plished by varying the speed of

    Pump 1. The pumps speed should

    not be reduced to the extent water-

    flow rate falls below the allowable

    low limit or increased to the extent

    water-flow rate exceeds the allow-

    able high limit.

    The building-automation system

    would have to limit VFD-turndown

    and turn-up ratios to stay within

    the range of allowable current fre-

    quencies correlated to the range of

    allowable primary-loop water-flow

    rates. To better match primary- and

    secondary-loop water-flow rates,

    two-phase control is suggested. The

    first phase could consist of quanti-

    tative control in both the primary

    and secondary loops (Equation

    5) while the chilled-water-supply

    temperature remained at a given

    constant value. The second phase

    could consist of qualitative control

    in the primary loop and quantita-

    tive control in the secondary loop.

    (The order in which the control ac-

    tions are implemented may vary.)

    Reset water-temperature control

    (Equation 6) could be realized by

    varying water temperature (t1) at

    a given fixed (limited) magnitude

    of water-flow rate in the primary

    loop. The change in water tempera-

    ture would impact flow rate in the

    secondary loop indirectly; flow via

    the primary-loop pump could not

    be changed further because of the

    aforementioned evaporator-flow

    limitations. The P/S-loop system

    with variable flow and temperature

    control in both loops in Figure 1 is

    very versatile, allowing the estab-

    lishment of flow-limiting parame-

    ters and temperature set points (t1)

    over a given time period.

    Primary-Loop-Only-Variable-Flow Control System

    A primary-loop-only-variable-flow

    (PLOVF) control system employs

    a single pump to circulate water

    through generation- and distribu-

    tion-system piping loops (Figure 2).

    This arrangement allows uniformly

    distributed variable flow throughout

    entire systems. The generation- and

    distribution-piping systems have a

    dependant flow-control arrange-

    ment, unlike the generation- and

    distribution-piping systems in the

    P/S-loop system in Figure 1, which

    have an independent flow-control

    arrangement with two dedicated

    pumps. When flow in a PLOVF dis-

    tribution system varies because of

    a load change, a VFD control varies

    the speed of the pump. If flow in the

    distribution system falls below the

    chillers low limit, an automatic con-

    trol valve modulates to divert flow

    from the supply line of the distribu-

    tion system back to the chiller (A-to-B

    direction). This system, unlike the

    P/S-loop system in Figure 1, does not

    have the ability to bypass the chiller

    if flow in the distribution system

    exceeds the chillers high-limit flow.

    For this capability to be provided in a

    PLOVF system, a second controllable

    decoupling pipeline with automatic

    control valve and reversed flow di-

    rection would have to be added on

    the other side of the pump. Other-

    wise, another chiller, as well as an-

    cillary equipment (i.e., chilled-water

    pump, cooling tower, condenser

    pump), would have to be placed on-

    line, which would result in increased

    chiller-plant power demand as soon

    as flow in the distribution system

    exceeded the high-level limit.

    A PLOVF system essentially is

    capable of maintaining limited total

    flow rate. Typically, control of systems

    with flow-rate-limiting devices5 is

    achieved by assigning priority status

    to one of the two loads. For instance,

    in a district-heating-system customer

    substation with space-heating and

    domestic-hot-water loads, priority is

    given to the domestic-hot-water load.

    The space-heating load has substan-

    tial thermal inertia and the ability to

    temporarily accept a lower water-

    flow rate without noticeable impact

    on air temperature. In a PLOVF sys-

    tem, two systems that typically have

    low thermal inertia (space cooling) or

    no inertia at all (chiller-evaporator-

    water flow) share the same level of

    priority control.

    Control of a PLOVF system is

    somewhat more challenging than

    control of a P/S-loop system. This

    38 HPAC ENGINEERING DECEMBER 2010

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    1 = Primary-loop-only variable-speed pump with variable-frequency drive (VFD) 2 = Automatic control valve for converting primary-loop-only system to constant primary-loop and variable secondary-loop flow operation (single AB-direction controllable flow decoupling pipe) F1 = Flow-meter generation-system-piping-loop flow rate F2 = Flow-meter distribution-system-piping-loop flow rate t1 = Temperature of water leaving chiller t2 = Temperature of water returning to chiller t3 = Distribution-system-piping-loop supply-water temperature t4 = Distribution-system-piping-loop return-water temperatureP1 = Pressure differential for controlling F1P2 = Pressure differential for controlling F2

    Distribution-system piping loop

    Generation-system piping loopLoad

    P2

    1

    2

    F2

    F1t2

    t1

    t4

    t3

    P1

    VFD

    Chiller

    B

    A

    FIGURE 2. Primary-loop-only-variable-flow control system.

  • is because a PLOVF system has to

    maintain two variables that are con-

    tinually fighting: a given set point

    of pressure differential (P2) in the

    distribution-system loop and a given

    set point of pressure differential (P1)

    in the generation-system-piping

    loop. Thus, overall control-strategy

    execution and system operation may

    be less accurate and stable, and an

    allowance for the possible deviation

    from the control-parameter set point

    may have to be made. Typically, to

    avoid a chiller shutting down because

    of insufficient flow, the set point for

    low-limit flow via the evaporator is

    increased. Because any problems

    with the modulating control valve

    could impair system performance or

    even shut down the entire chilled-

    water system, the application of reset

    chilled-water-temperature control

    during off-design conditions (when

    the chilled-water-flow limitation is in

    place) is difficult. In comparison with

    a P/S-loop system, design chilled-

    water temperature may be constant

    and elevated in a PLOVF system,

    which may lead to increased costs

    for distribution piping, pumping,

    cooling coils, etc.

    Chilled-Water-System Temperature Differential

    Chilled-water temperature differ-

    ential is critical to P/S and PLOVF

    operations in that it determines

    chilled-water flow per cooling ton.

    Impacting chilled-water temperature

    differential most significantly are the

    end-users connected to chiller plants.

    Take, for instance, an air-handling

    unit (AHU) with the following param-

    eters:

    Air is cooled in a counterflow

    chilled-water coil.

    The design cooling load is 28.5

    tons.

    The design sensible and latent

    loads are 76 percent and 24 percent

    of the design cooling load, respec-

    tively.

    The cooling load varies in direct

    proportion to outdoor dry-bulb air

    temperature.

    The cooling coil has a two-way

    chilled-water control valve to vary

    water flow through the coil to satisfy

    loads.

    The cooling coil is selected for

    15F design chilled-water tempera-

    ture differential.

    The design chilled-water flow via

    the cooling coil at 40F inlet water

    temperature is 45.7 gpm.

    End-user load control. The authors

    considered two types of AHU cool-

    ing-load-control systems: constant

    airflow control (CAFC) and variable

    airflow control (VAFC). Maximum

    airflow turndown ratio was assumed

    to be 3.4 at a relative cooling load

    of 0.29 and lower. The top graph

    in Figure 3 shows the CAFC sys-

    tem requires a substantially greater

    change in relative chilled-water flow

    to achieve the same level of variation

    in cooling-coil load. For instance, for

    cooling-coil capacity to be reduced

    to 40 percent of the design load, rela-

    tive chilled-water flow would have

    to be reduced to about 21 percent of

    its design magnitude. For the same

    reduction in cooling-coil capacity to

    be achieved with the VAFC system,

    relative chilled-water flow rate would

    have to be reduced to about 35 per-

    cent of its design magnitude. The bot-

    tom graph in Figure 3 indicates the

    CAFC system will increase the rela-

    tive chilled-water temperature differ-

    ential by a factor of about 1.9 when

    the relative cooling load is reduced

    to 40 percent of its design magnitude.

    For the same conditions, the VAFC

    system will increase relative chilled-

    water temperature differential by a

    factor of only about 1.2. Thus, the

    same relative reduction in chilled-

    water flow via the cooling coil would

    result in about 1.6-times-higher rela-

    tive chilled-water temperature differ-

    ential with the CAFC system than it

    would with the VAFC system.

    Chiller-evaporator low-limit flow

    control. Various control strategies

    can be utilized to ensure the sustain-

    DECEMBER 2010 HPAC ENGINEERING 39

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    Chill

    ed-w

    ater

    -coil

    rela

    tive

    ch

    illed

    -wat

    er t

    emper

    ature

    diffe

    rential

    Cooling-coil relative chilled-water flow rate

    Chill

    ed-w

    ater

    -coil

    rela

    tive

    coolin

    g lo

    ad

    1.0

    0.8

    0.6

    0.4

    0.2

    0.2 0.4 0.6 0.8 1.0

    Cooling-coil relative chilled-water flow rate

    0.2 0.4 0.6 0.8 1.0

    2.0

    1.8

    1.6

    1.4

    1.2

    1.0

    CAFC

    CAFC

    VAFC

    VAFC

    FIGURE 3. Air-handling-unit-cooling-coil operational parameters with variable (VAFC) and

    constant (CAFC) airflow control.

  • ability of a systems low-limit chilled-

    water flow. Figure 4 shows the reset

    water-temperature control required

    to maintain a given low-limit water-

    flow level when relative cooling load

    changes from 0.64 to 0.17 of design.

    The temperature of water entering

    the cooling coil increases as load

    decreases. Limited chilled-water

    flow is maintained by increasing the

    temperature of water entering the

    cooling coil.

    The variation in relative cooling

    load from 0.67 to 0.17 requires the

    temperature of water entering the

    coil to be increased from 40F to

    about 52F. The bottom graph in

    Figure 4 indicates chilled-water tem-

    perature differential will be reduced

    from 15F at the relative cooling load

    of 0.67 to 3.7F at the relative cooling

    load of 0.17.

    Other factors impacting chilled-

    water-system temperature differ-

    ential. Chilled-water temperature

    differential also can be impacted by

    deposits on the inside and outside

    surfaces of cooling coils. Proper and

    timely cleaning of heat-exchanger

    heat-transfer surfaces, thus, is

    important,6 as is cleaning of chilled-

    water cooling coils and chiller evapo-

    rators and condensers.

    Because of the complexity of

    real-life conditions, it is unrealistic

    to expect an increase in cooling-coil

    chilled-water temperature differen-

    tial coinciding with a reduction in

    cooling load. If a system is balanced

    and well-maintained, temperature

    differential will remain relatively

    close to its design value during off-

    design conditions.

    Distribution-piping-system design

    temperature differential. Distribution-

    piping-system design temperature

    differential impacts the installed and

    operating costs of central chilled-

    water systems. For retrofit projects,

    such as conversion from direct-

    expansion cooling coils to central

    chilled-water cooling coils, the cost of

    distribution piping could run as high

    as 30 percent of the entire system.3,4

    Design temperature differential for

    the example chilled-water primary

    piping system was assumed to vary

    from about 2.1F to 22.4F (Table

    1). The magnitude of the tempera-

    ture differential at the chillers

    design cooling load was limited by

    t h e a l l o w a b l e m i n i m u m a n d

    maximum flow at a given number of

    evaporator passes. Low-level flow

    rate was specified to ensure evapo-

    rator operation with sufficient heat-

    exchanger-tube water velocity. High-

    level flow rate was specified to ensure

    evaporator operation with allowable

    heat-exchanger-tube velocity and

    avoid unstable heat transfer and tube

    40 HPAC ENGINEERING DECEMBER 2010

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    Chill

    ed-w

    ater

    -coil

    rela

    tive

    coolin

    g lo

    adCooling-coil inlet chilled-water temperature, degrees Fahrenheit

    Coolin

    g-c

    oil

    chill

    ed-w

    ater

    tem

    per

    ature

    diffe

    rential

    , deg

    rees

    Fah

    renhei

    t

    0.0

    16

    40 41 42 43 44 45 46 47 48 49 50 51 52 53

    Cooling-coil inlet chilled-water temperature, degrees Fahrenheit

    40 41 42 43 44 45 46 47 48 49 50 51 52 53

    14

    12

    10

    8

    6

    4

    2

    0

    0.2

    0.4

    0.6

    0.8

    FIGURE 4. Cooling-coil inlet chilled-water temperature, relative cooling load, and

    temperature differential with low-limit chilled-water-flow control.

    Number of evaporator passes 1 2 3

    Low-limit evaporator-water flow rate, gallons per minute 964 482 321

    Maximum evaporator chilled-water temperature differential, degrees Fahrenheit

    7.5 14.9 22.4

    Minimum evaporator specific chilled-water flow rate per cooling ton, gallons per minute per ton

    3.2 1.6 1.1

    High-limit evaporator flow rate, gallons per minute 3,473 1,737 1,158

    Minimum evaporator chilled-water temperature differential, degrees Fahrenheit

    2.1 4.1 6.2

    Maximum evaporator specific chilled-water flow rate per cooling ton, gallons per minute per ton

    11.6 5.8 3.9

    Relative evaporator-water-flow-rate variation 3.6 3.6 3.6

    Notes:1. Relative evaporator-water flow rate shows the ratio of maximum to minimum specific

    chilled-water flow rate at the given fixed number of evaporator passes.2. Minimum allowable water-flow rate (gallons per minute) via evaporator at a water velocity of

    3.3 fps at a given number of passes could be calculated as minimum specific flow rate (gallons per minute per ton) multiplied by design cooling load (tons).

    3. Maximum allowable water-flow rate (gallons per minute) via evaporator at water velocity of 12 fps at a given number of passes could be calculated as maximum specific flow rate (gallons per minute per ton) multiplied by design cooling load (tons).

    4. Parameters based on the performance of a 300-ton centrifugal chiller.

    TABLE 1. Chiller-evaporator design operational parameters.

  • erosion. Lower water-flow rates

    relate to higher chilled-water tem-

    perature differentials and vice versa.

    Table 1 indicates temperature

    differential is dependent on num-

    ber of evaporator passes. It shows

    evaporator relative water-flow rate

    remains the same (i.e., 3.6the ratio

    of maximum to minimum tube water

    velocities) for all considered number

    of evaporator passes.

    Allowable minimum chiller rela-

    tive cooling load (MCRCL) in Table

    2 was calculated using the following

    equation:

    MCRCL = [1 (TDEMAX TDEMIN)]

    SOSF 100, %

    where:

    TDEMAX = maximum chiller-evapo-

    rator design temperature differential

    TDEMIN = minimum chiller-evapo-

    rator design temperature differential

    SOSF = system operational safety

    factor, which increases minimum

    chilled-water flow via a chillers

    evaporator (for PLOVF) to prevent

    chiller shutdown on low flow

    The higher water-flow turndown

    ratios (WFTDRs) in Table 2 are

    advantageous because they allow

    optimal operation of a system to

    satisfy cooling loads.

    Chilled-Water Turndown Ratio and Energy Savings

    Figure 5 shows WFTDR patterns

    for various control strategies. The

    system was assumed to use mechani-

    cal free cooling at outdoor dry-bulb

    air temperatures of 55F and below.

    Also, system cooling load was as-

    sumed to change linearly in direct

    proportion to outdoor dry-bulb air

    temperature.

    The following options, shown in

    Table 2, were considered:

    Option 1

    TDEMIN = 15F, TDEMAX = 22.4F,

    WFTDR = 1.5

    This means re la t ive chi l ler-

    evaporator chilled-water flow could

    be reduced to 67 percent of its

    design value.

    Relative chilled-water flow via the

    pump serving the PLOVF system

    in Figure 2 will follow two straight

    lines outlined by the triangle ACB in

    Figure 5 and remain constant at the

    level designated by straight line CB.

    Although relative water flow via the

    distribution-piping system will fol-

    low the load change, the bypass valve

    will be open to ensure the required

    low-limit chiller-evaporator flow is

    maintained. This means the pump

    will run at the constant flow rate

    indicated by the straight line CB.

    P/S-loop systems with variable-

    primary and secondary-loop pump-

    ing could provide energy savings

    (compared with the PLOVF-system

    operation indicated by straight line

    CB in Figure 5) while dry-bulb out-

    door-air temperature ranged from

    DECEMBER 2010 HPAC ENGINEERING 41

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    primary/secondary and primary-loop-only systems.

    Maximum chiller-evapora-tor design temperature differential, TDEMAX, degrees Fahrenheit

    Minimum chiller-evaporator design temperature differential, TDEMIN, degrees Fahrenheit

    Allowable reduction in water-flow turn-down ratio (TDEMAXto TDEMIN), times

    Allowable MCRCL, percent

    22.4 15.0 1.5 73.6

    22.4 10.0 2.2 49.0

    22.4 6.2 3.6 30.5

    Notes:1. Allowable reduction in chilled-water flow rate in distribution piping system the ratio of TDEMAX

    to TDEMIN.2. Data adapted from Table 1 (chiller with three-pass evaporator).3. Minimum allowable flow rate via chiller evaporator increased by 10 percent to ensure chiller

    in PLOVF system will not be turned down on low-level evaporator flow rate.4. MCRCL = Minimum chiller relative cooling load, at which Bypass Control Valve 2 in Figure 2

    will remain closed.

    F

    C

    D

    B

    H

    E

    G

    A

    AC = Secondary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T

    DEMIN = 15F, T

    DEMAX = 22.4F)

    CB = Minimum primary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T

    DEMIN = 15F, T

    DEMAX = 22.4F)

    ACB = PLOVF-system relative flow-rate variation (TDEMIN

    = 15F, TDEMAX

    = 22.4F)AD = Secondary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T

    DEMIN = 10F, T

    DEMAX = 22.4F)

    DH = Minimum primary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pump (T

    DEMIN = 10F, T

    DEMAX = 22.4F)

    ADH = PLOVF-system relative flow-rate variation (TDEMIN

    = 10F, TDEMAX

    = 22.4F)AF = Secondary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T

    DEMIN = 6.2F, T

    DEMAX = 22.4F)

    FG = Minimum primary-loop relative flow-rate value in systems with constant- and variable-flow primary-loop pumps (T

    DEMIN = 6.2F, T

    DEMAX = 22.4F)

    AFG = PLOVF-system relative flow-rate variation (TDEMIN

    = 6.2F, TDEMAX

    = 22.4F)AE = Relative flow-rate variations for secondary-loop pumps for all considered P/S-loop systems and T

    DEMIN and T

    DEMAX values

    Pri

    mar

    y/se

    condar

    y an

    d p

    rim

    ary-

    loop-o

    nly

    re

    lative

    flow

    rat

    e 0.75

    1.00

    0.50

    0.25

    0.0055 65 10575 85 95

    Outdoor dry-bulb air temperature, degrees Fahrenheit

    FIGURE 5. Primary/secondary and primary-loop-only relative chilled-water-flow variation.

    TABLE 2. Considered design temperature differentials for chiller evaporators serving

  • 55F to 83F because of the variable

    secondary-loop pumping (Pump 2 in

    Figure 1) depicted by straight line CE

    in Figure 5.

    Option 2

    TDEMIN = 10F, TDEMAX = 22.4F,

    WFTDR = 2.2

    This means relative chiller-evap-

    orator chilled-water flow could be

    reduced to 44.6 percent of its design

    value.

    Relative chilled-water flow via the

    pump serving the PLOVF system

    in Figure 2 will follow two straight

    lines outlined by the triangle ADH in

    Figure 5 and remain constant at the

    level designated by straight line DH.

    Although water flow via the distri-

    bution-piping system will follow the

    load change, the bypass valve (2) will

    be open to ensure the required low-

    limit chiller-evaporator flow is main-

    tained. This means the pump will run

    at the constant flow rate indicated by

    straight line DH.

    P/S-loop systems with variable-

    primary and secondary-loop pump-

    ing could provide energy savings

    (compared with the PLOVF-system

    operation indicated by straight line

    DH in Figure 5) while dry-bulb out-

    door-air temperature ranged from

    55F to 74F because of the variable

    secondary-loop pumping (Pump 2 in

    Figure 1) depicted by straight line DE

    in Figure 5.

    Option 3

    TDEMIN = 6.2F, TDEMAX = 22.4F,

    WFTDR = 3.6

    This means relative chiller-evap-

    orator chilled-water flow could be

    reduced to 27.7 percent of its design

    value.

    Relative chilled-water flow via the

    pump serving the PLOVF system

    in Figure 2 will follow two straight

    lines outlined by the triangle AFG in

    Figure 5 and remain constant at the

    level designated by straight line FG.

    Although water flow via the distri-

    bution-piping system will follow the

    load change, the bypass valve (2) will

    be open to ensure the required low-

    limit chiller-evaporator flow is main-

    tained. This means the pump will run

    at the constant flow rate indicated by

    straight line FG.

    P/S-loop systems with variable-

    primary and secondary-loop pump-

    ing could provide energy savings

    (compared with the PLOVF-system

    operation indicated by straight line

    DH in Figure 5) while dry-bulb out-

    door-air temperature ranged from

    55F to 67F because of the variable

    secondary-loop pumping (Pump 2 in

    Figure 1) depicted by straight line FE

    in Figure 5.

    Cooling-Load ProfileCooling-load profile depends on

    the ratio of constant load (e.g., inter-

    nal heat gain from lights, equipment,

    people, etc.) to variable load (e.g.,

    ventilation, heat gain from building

    envelope, etc.).

    Cumulative relative cooling load

    and time-duration factor for eight

    constant- and variable-load compo-

    nents in New England are given in

    Figure 6. The design cooling load for

    the process area of a manufacturing

    facility is close to 57 tons. The actual

    constant-cooling-load component

    was near 35 tons, or 62 percent of the

    design load. The actual variable-load

    component was close to 22 tons, or

    38 percent of the design load.

    Applied in energy analysis, Figure

    6 is illustrative of relative cooling-

    load variations when the percentage

    of constant-cooling-load component

    (PCCLC) changes from 0 percent to

    100 percent of total cooling load.

    P/S- and PLOVF-System Electrical-Energy Usage

    Chilled-water-pumping electrical-

    energy savings. The top graph in

    Figure 7 shows potential annual

    chilled-water-pumping electrical-

    energy savings for a P/S-loop sys-

    tem with variable-flow-rate control

    in both loops. The electrical energy

    consumed by pump motors was

    assumed to vary in direct propor-

    tion to changes in motor speed by a

    power of 2.5. This is lower than the

    theoretical value of 3 recommended

    for centrifugal pumps. These savings

    will be realized when distribution-

    system water flow is equal to or lower

    than the allowable chiller-evaporator

    low limit (Figure 5). In calculations

    of annual electrical-energy use, the

    pump serving the PLOVF system was

    assumed to have a design flow rate

    42 HPAC ENGINEERING DECEMBER 2010

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    Systems with 62-percent PCCLC

    Systems with 50-percent PCCLC

    Systems with 38-percent PCCLC

    Systems with 15-percent PCCLC

    Systems with 80-percent PCCLC

    Systems with 0-percent PCCLC

    Systems with 26-percent PCCLC

    Systems with 100-percent PCCLC

    Notes:1. Constant load percentage based on ratio of constant-cooling-load component that does not change during mechanical cooling season to design cooling load.2. Relative cooling load shows ratio of current load to design cooling load.3. PCCLC = Percentage of constant-cooling-load component.

    Cum

    ula

    tive

    load

    tim

    e-dura

    tion f

    acto

    r, p

    erce

    nt

    (at

    load

    equal

    to o

    r lo

    wer

    than

    show

    n)

    Relative cooling load, percent

    100

    90

    80

    70

    60

    50

    40

    30

    20

    10

    10 20 30 40 50 60 70 80 90 1000

    0

    FIGURE 6. System relative cooling load and cumulative time-duration factor.

  • equal to the design flow rate of the

    P/S-loop pumps. The pump serving

    the PLOVF system also was assumed

    to have a design pressure head equal

    to the cumulative design pressure

    head of the P/S-loop pumps.

    With a MCRCL of 73.6 percent

    (Table 2), P/S-loop-system annual

    electrical-energy savings vary from

    5.8 percent (calculated PCCLC of 62

    percent) to 60 percent (calculated PC-

    CLC of 0 percent). Annual pumping

    electrical-energy usage for the con-

    sidered P/S and PLOVF systems will

    be equalized at a PCCLC greater than

    or equal to 75 percent (Figure 7).

    With a MCRCL of 49 percent

    (Table 2), P/S-loop-system annual

    electrical-energy savings vary from

    10.4 percent (PCCLC of 26 percent)

    to 41 percent (PCCLC of 0 percent).

    Annual pumping electrical-energy

    usage for the considered P/S and

    PLOVF systems will be equalized

    at a PCCLC greater than or equal to

    35 percent (Figure 7).

    With a MCRCL of 30.5 percent

    (Table 2), P/S-loop system annual

    electrical-energy savings vary from

    2.8 percent (PCCLC of 15 percent)

    to 9.5 percent (PCCLC of 0 percent).

    Annual electrical-energy usage for

    the considered P/S and PLOVF sys-

    tems will be equalized at a PCCLC

    greater than or equal to 21.5 percent

    (Figure 7).

    With an MCRCL of 73.6 percent

    and a PCCLC varying from 0 percent

    to 40 percent, the P/S-loop system

    with constant-primary-loop and

    variable-secondary-loop pumping

    control consumes less electrical

    energy annually than the PLOVF

    system. These savings are identified

    in Figure 7 as the difference in Y-axis

    values to the left of the intersection of

    the dashed lines. The savings could

    be as high as 22 percent at a PCCLC

    of 0 percent.

    In calculations of electrical-energy

    savings, primary- and secondary-

    pump usage was assumed to be

    about 6 percent of chiller-plant an-

    nual electrical-energy consumption.

    The data in the top graph of Figure

    7 are related to single-chiller plants.

    The use of multiple chillers will in-

    crease WFTDR and reduce MCRCL.

    This will reduce annual pumping

    electrical-energy savings. Correc-

    tion factors for two- and three-chiller

    plants are given in Table 3.

    Reset-chilled-water-temperature

    electrical-energy savings. The P/S-

    loop system with variable-flow

    DECEMBER 2010 HPAC ENGINEERING 43

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    .

    Linear (approximated MCRCL = 73.6 percent)Linear (approximated MCRCL = 49 percent)Linear (approximated MCRCL = 30.5 percent)Linear (approximated MCRCL = 73.6 percent)

    Calculated MCRCL = 73.6 percentCalculated MCRCL = 49 percentCalculated MCRCL = 30.5 percentCalculated MCRCL = 73.6 percent

    Two-chillers MCRCL = 36.7 percentSingle-chiller MCRCL = 30.5 percentTwo-chillers MCRCL = 22.9 percent

    Single-chiller MCRCL = 73.6 percentTwo-chillers MCRCL = 55.2 percentSingle-chiller MCRCL = 49 percent

    Notes:1. Savings calculated for chiller plant operating 24 hr a day, seven days a week in Hartford, Conn.2. MCRCL = minimum chiller relative cooling load (Table 2), at which Bypass Control Valve 2 in the primary-loop-only-variable-flow system (Figure 2) remains closed.3. Single-chiller operation considered in top graph only.4. Dashed red line in top graph indicates pumping savings over primary (constant-flow)/secondary (variable-flow) system.5. Dashed lines indicate savings over the primary-loop-only system.6. Annual pumping savings in top graph compared with chiller-plant annual pumping electrical energy only.7. In bottom graph, pumping and reset-chilled-water-temperature-control annual electrical-energy savings compared with annual electrical energy of entire chiller plant.

    Percentage of constant-cooling-load component in relation to overall design cooling load, percent706050403020100

    0

    1

    2

    3

    4

    5

    6

    Percentage of constant-cooling-load component in relation to overall design cooling load, percent70605040302010

    10

    20

    30

    40

    50

    60

    70

    00

    P/S

    -loop-s

    yste

    m p

    um

    pin

    g a

    nd r

    eset

    ch

    illed

    -wat

    er-t

    emper

    ature

    -contr

    ol a

    nnual

    el

    ectr

    ical

    -ener

    gy

    savi

    ngs,

    per

    cent

    Pri

    mar

    y/se

    condar

    y-lo

    op-s

    yste

    m p

    um

    pin

    g

    annual

    ele

    ctri

    cal-

    ener

    gy

    savi

    ngs,

    per

    cent

    FIGURE 7. Potential annual electrical-energy savings for primary/secondary-loop system with

    variable flow.

    multiple-chiller operations.

    Single-chiller plant Two-chiller plant Three-chiller plant

    1.00 0.75 0.50

    Notes:1. Single-chiller-plant loading factor assumed to be 100 percent.2. Multiple-chiller-plant loading factor assumed to be 75 percent.3. Minimum allowable chiller relative cooling load increased by 10 percent.

    TABLE 3. Correction factors for adjusting pumping annual energy savings to account for

  • control also has savings associated

    with reset chilled-water-temperature

    control. While considering these

    savings, the authors assumed, based

    on manufacturer data, that approxi-

    mately 2 percent of the chillers input

    energy would be saved per degree-

    Fahrenheit increase in chilled-water

    temperature. The increase in chilled-

    water temperature also would in-

    crease secondary-loop water flow,

    which, in turn, would reduce the

    electrical-energy savings associated

    with the secondary-loop pump em-

    ploying variable-flow control. The

    authors incorporated that reduction

    in their calculations. The chillers

    power demand was assumed to be

    about 78 percent of the total plant

    power demand.

    Cumulative annual electrical-

    energy savings. Cumulative annual

    electrical-energy savings for pump-

    ing and reset chilled-water-temper-

    ature control expressed as a per-

    centage of total chiller-plant annual

    energy consumption are shown in the

    bottom graph of Figure 7. The annual

    savings of a single-chiller plant with

    an MCRCL of 30.5 percent and a

    PCCLC of 62 percent and a single-

    chiller plant with an MCRCL of 73.6

    percent and a PCCLC of 0 percent

    vary from 0.5 percent to 5.2 percent.

    The annual savings of a two-chiller

    plant with an MCRCL of 22.9 percent

    and a PCCLC of 62 percent and a two-

    chiller plant with an MCRCL of 55.2

    percent and a PCCLC of 0 percent

    vary from 0.4 percent to 4.1 percent.

    Converting From PLOVF to P/S-Loop-With-VFD-Control System

    A central chilled-water system

    with 2,500-ton chillers serving mul-

    tiple AHUs at a New England manu-

    facturing facility was converted from

    PLOVF (similar to that shown in Fig-

    ure 2) to P/S-loop operation (nearly

    identical to that shown in Figure 1).

    The system had a design cooling load

    of approximately 930 tons and a de-

    sign secondary-loop chilled-water

    flow of about 1,600 gpm. About 50

    percent of the cooling load was con-

    stant (PCCLC of 50 percent). The

    P/S-loop system had two dedicated

    water-flow meters to separately

    measure the flows in the primary and

    secondary loops, as well as in the

    distribution- and generation-piping

    loops of the PLOVF system. To com-

    pare the hourly operational modes of

    the systems, the authors selected a

    two-day sample with approximately

    the same dry-bulb outdoor-air tem-

    perature for both systems. The reset

    chilled-water-temperature control

    for the P/S system was not activated

    during the two days. The outdoor

    dry-bulb air temperature ranged

    from 57F to 83F. The average daily

    dry-bulb air temperature was close to

    69F, while the cooling load ranged

    from 250 tons to 450 tons. Only one

    chiller was running. The high-limit

    chiller-evaporator flow was 1,200

    gpm (i.e., TDEMIN was 10F). The low-

    level chiller-evaporator flow was 670

    gpm (i.e., TDEMAX was 17.9F). Thus,

    WFTDR was 1.79.

    44 HPAC ENGINEERING DECEMBER 2010

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS

    Hourl

    y el

    ectr

    ical

    -ener

    gy

    usa

    ge

    by

    pum

    ps

    in p

    rim

    ary/

    seco

    ndar

    y an

    d p

    rim

    ary-

    loop-o

    nly

    sys

    tem

    s, k

    ilow

    att-

    hours

    Outdoor dry-bulb air temperature, degrees Fahrenheit55 60 65 7570 8580

    Outdoor dry-bulb air temperature, degrees Fahrenheit55 60 65 7570 8580

    Outdoor dry-bulb air temperature, degrees Fahrenheit55 60 65 7570 8580

    Outdoor dry-bulb air temperature, degrees Fahrenheit55

    50

    40

    30

    20

    10

    0

    900

    800

    700

    600

    500

    40060 65 7570 8580

    900

    800

    700

    600

    500

    400

    3

    4

    5

    6

    7

    Pri

    mar

    y-lo

    op-o

    nly

    -flow

    -rat

    e ch

    illed

    -w

    ater

    sys

    tem

    , gal

    lons

    per

    min

    ute

    Primary-loop-only-system total water-flow rate (F1 in Figure 2)Primary-loop-only-system distribution-piping flow (F2 in Figure 2)

    Pri

    mar

    y-lo

    op-o

    nly

    -chill

    ed-

    wat

    er-s

    yste

    m r

    elat

    ive

    flow

    ra

    te v

    ia b

    ypas

    s va

    lve,

    per

    cent

    Pri

    mar

    y/se

    condar

    y-ch

    illed

    -wat

    er-s

    yste

    m-

    loop fl

    ow

    rat

    e, g

    allo

    ns

    per

    min

    ute

    Secondary-loop water-flow rate (F2 in Figure 1)Primary-loop water-flow rate (F1 in Figure 1)

    Primary-loop-only-system pump hourly electrical-energy usagePrimary/secondary-pump cumulative hourly electrical-energy usage

    FIGURE 8. Primary/secondary- and primary-loop-only-system hourly trend data.

  • Low-limit chiller-evaporator flow

    was set at 700 gpm during P/S-loop

    operation; during PLOVF-loop op-

    eration, it was set at 770 gpm. An

    attempt to lower low-limit flow

    during PLOVF-loop operation was

    unsuccessful because of evapora-

    tor-induced chiller shutdown on

    low flow.

    Total chilled-water flow via the

    pump in the PLOVF system (Point

    F1 in Figure 2) was relatively sta-

    ble, varying from about 720 to 860

    gpm (Figure 8). Meanwhile, chilled-

    water flow via the distribution-

    piping system varied from 439 to

    847 gpm. Chilled-water flow via the

    chillers evaporator was maintained

    at its allowable low-limit magnitude

    through bypass-control-valve mod-

    ulation. Chilled-water flow via the

    bypass control valve, which repre-

    sents the difference between flow

    via the pump and flow via the distri-

    bution-piping system, varied from

    about 10 to 285 gpm. Flow via the

    bypass valve, expressed as a per-

    centage of total flow via the pump,

    varied from about 2 percent (at

    higher cooling loads) to 39 percent

    (at lower cooling loads). Any time

    and to any extentthe bypass valve

    (2) was open, VFD speed and pump

    flow remained constant, wasting

    electrical energy.

    Chilled-water flow in the P/S-loop

    system varied from 700 to 816 gpm

    (Figure 8). Flow in the secondary

    loop varied from 420 to 820 gpm.

    Chilled-water flow via the distribu-

    tion-piping system varied indepen-

    dently of water flow via the chiller

    evaporator pump. Chilled-water

    flow via the distribution system was

    reduced following the load reduction

    in the cooling system. This led to

    reduced electrical-energy use by

    Pump 2. Chilled-water flow via the

    primary-loop pump and chil ler

    evaporator remained relatively con-

    stant, satisfying low-limit water-flow

    requirements via the evaporator.

    The same 100-hp pump (design

    water flow 2,400 gpm) was used for

    the PLOVF system and the secondary

    loop of the P/S-loop system. The pri-

    mary loop of the P/S-loop system had

    its own 15-hp pump (design water

    flow 1,200 gpm). The long operational

    hours of the PLOVF system, with

    nearly constant flow via the pump

    necessary to maintain low-limit flow

    via the chiller evaporator, resulted

    in wasted electrical-energy power

    demand (kilowatts) and usage (kilo-

    watt-hours). Secondary-loop pump

    electrical-energy usage decreased

    and increased following cooling-load

    variations. Electrical-energy savings

    for the P/S-loop system varied from

    about 3 percent to 50 percent, aver-

    aging around 20 percent per day.

    The authors have observed similar

    electrical-energy savings following

    other chiller plants conversion from

    PLOVF to P/S-loop operation.

    SummaryThis article compared the opera-

    tional modes and performance of

    P/S-loop and PLOVF systems.

    The operating efficiency of chilled-

    water systems with a primary (con-

    stant-flow)/secondary (variable-

    flow)-loop arrangement can be

    improved by applying a two-phase

    optimized control strategy consist-

    ing of variable flow and temperature

    control for primary-loop pumps and

    variable-flow control for secondary-

    loop pumps.

    PLOVF-with-VFD control wastes

    energy when primary-loop flow is

    constrained by the chiller-evaporator

    low limit and chilled water is diverted

    via decoupling line from the supply

    pipe to the return pipe of the gen-

    eration system. The magnitude of

    annual energy savings (pumping

    and reset chilled-water temperature)

    of P/S-loop control depends on

    multiple variables, such as chiller-

    evaporator-flow turndown ratio,

    minimum chiller relative cooling load,

    load composition, number of chill-

    ers, etc. For New England weather

    conditions, annual electrical-energy

    savings could be 0.5 to 5.2 percent

    for a single-chiller plant and 0.4 to 4.1

    percent for a two-chiller plant.

    P/S-loop-with-variable-flow con-

    trol reduces chiller-plant power

    demand by resetting chilled-water

    temperature when flow in the dis-

    tribution piping exceeds a high-limit

    value for the chiller evaporator and

    the system diverts water via decou-

    pling line from the return pipe to the

    supply pipe of the distribution sys-

    tem. This prevents or delays the addi-

    tion of a chiller and associated ancil-

    lary equipment and saves energy.

    Compared with PLOVF systems,

    P/S-loop systems with variable flow

    also have the advantage of more-

    accurate, flexible, and stable control

    and operational conditions.

    References1) Burd, A.L. (1994). Optimizing

    customers heating systems to reduce

    capital and operating cost in district

    heating with cogeneration. Proceed-

    ings of International District Heat-

    ing and Cooling Association Annual

    Conference, pp. 237-252.

    2) Burd, A.L. (1993). Computer

    design of terminal heating substa-

    tions for district heating. ASHRAE

    Transactions, 99 (2), 245-265.

    3) Burd, A.L., Burd, G.S., & De

    Maio, M. (2005, March). Smith &

    Wesson: The story of a chilled-water

    retrofit (part 1). HPAC Engineering,

    pp. 38-47.

    4) Burd, A.L., Burd, G.S., & De

    Maio, M. (2005, July) . Smith &

    Wesson: The story of a chilled-water

    retrofit (part 2). HPAC Engineering,

    pp. 24-37.

    5) Burd, A.L. (1997). Deferred

    heat supply for space heating using

    a capacity-limiting device A ben-

    eficial approach for district heating.

    ASHRAE Transactions, 103 (2), 23-31.

    6) Burd, A.L., & Burd, G.S. (1996).

    Optimal cycle for plate heat exchanger

    cleaning in customer substation.

    Proceedings of International District

    Energy Association Annual Confer-

    ence, pp. 177-192.

    Did you find this article useful? Send

    comments and suggestions to Scott

    Arnold at [email protected].

    DECEMBER 2010 HPAC ENGINEERING 45

    PRIMARY/SECONDARY-LOOP VS. PRIMARY-LOOP-ONLY SYSTEMS