L EXISTING NEW DESCRIPTION EXISTING NEW DESCRIPTION LIST OF DRAWINGS SHEET NO. DWG. NO. DISCIPLINE TITLE REINFORCED CONCRETE PIPE REQUIRED RIGHT RIGHT OF WAY SANITARY SODIUM HYPOCHLORITE SQUARE STAINLESS STEEL STATION STANDARD STEEL TO BE ABANDONED TO BE REMOVED TOP THRUST COLLAR TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED WITH WATERSTOP, WATER SURFACE YARD RCP REQ’D RT R/W SAN SH SQ SST STA STD STL TBA TBR T/ T/C TYP UG UON W/ WS YD EXIST FF FLG GALV HK HYD INV IPS IPF JB LT LF MIN MH MJ No NTS O.C. PROP PVC ABBREVIATIONS NOT TO SCALE NOTES: 1. THE SIZE OF THE SYMBOLS MAY VARY FROM THOSE SHOWN. 2. ALL ABBREVIATIONS AND SYMBOLS SHOWN MAY NOT BE USED. BENCHMARK BUSH TREE GAS VALVE SANITARY OR STORM MANHOLE DROP INLET LIGHT POLE POWER POLE IRON PIN TELEPHONE POLE, WITH GUY AND ANCHOR RIPRAP BORING LOCATION NORMAL WATER LEVEL SILT FENCE CONSTRUCTION ENTRANCE LIMITS OF CLEARING AND GRADING VDOT EC-2 LINER OUTLET PROTECTION RIGHT-OF-WAY SPOT ELEVATION TREE LINE TOP OF BANK/ TOE OF SLOPE CENTER/EDGE OF STREAM FENCE AND GATE PROPERTY LINE TAX MAP LINE OVERHEAD POWER AND/OR TELEPHONE STRUCTURE FUTURE STRUCTURE WATER METER FIRE HYDRANT WATER VALVE DEMOLISH OR ABANDON STRUCTURE CONTOUR (INTERVAL AS INDICATED ON SITE PLAN) YARD HYDRANT SANITARY SEWER STORM SEWER AND END WALL, TYPE AS INDICATED POTABLE WATER LINE TRAFFIC WIRE UNDERGROUND ELECTRICAL LINE UNDERGROUND TELEPHONE LINE ABANDONED OR REMOVED UTILITY EDGE OF ASPHALT PAVEMENT EDGE OF GRAVEL PAVEMENT +56.1 SAN ST W 435 R/W P TOB TOS L SAN ST W TW UGE UGT CIP CE SF OP +56.1 LEGEND GENERAL NOTES LOCATION MAP CS-1 1 NONE TOWN OF AMHERST, VIRGINIA CULVERT INLET PROTECTION DD ST DIVERSION DIKE TEMPORARY SEDIMENT TRAP EXISTING FINISHED FLOOR FLANGED GALVANIZED HOOK HYDRANT INVERT IRON PIN SET IRON PIN FOUND JUNCTION BOX LEFT LINEAR FEET MINIMUM MANHOLE MECHANICAL JOINT NUMBER NOT TO SCALE ON CENTER PROPOSED POLYVINYL CHLORIDE AIR AIR RELEASE VALVE AHEAD BLIND FLANGE BENCH MARK BACK CENTER TO CENTER CURB & GUTTER CAST IRON PIPE CENTER LINE CHAIN LINK CLOCKWISE CORRUGATED METAL PIPE CLEAN OUT CONCRETE CUBIC YARDS DIAMETER DROP INLET, DUCTILE IRON DUCTILE IRON PIPE DRAWING ELEVATION A ARV AHD BF BM BK C/C C&G CIP C CL CW CMP CO CONC CY DIA DI DIP DWG EL 435 COVER SHEET 4232CS1.DGN FILE: W:\Cadd\204232.12\4232cs1.dgn DATE: 24-Jan-08 11:28 PROJECT SITE 3 PHASE 2 FLUORIDE IMPROVEMENTS PROJECT WATER TREATMENT PLANT 1 0F 4 2 0F 4 3 0F 4 4 0F 4 CS-1 C-1 C-2 C-3 GENERAL CIVIL CIVIL CIVIL COVER SHEET IMPROVEMENTS PLAN DETAILS FLUORIDE ANALYZER SAMPLE PUMP ISOMETRIC & DETAILS 1. THE LOCATION AND ELEVATION OF EXISTING STRUCTURES, PIPING, AND UTILITIES SHOWN ARE BASED ON THE WATER TREATMENT PLANT 1997 RECORD DRAWINGS. THE CONTRACTOR SHALL VERIFY ALL DATA IN THE FIELD PRIOR TO CONSTRUCTION. THE DIAMETERS OF EXISTING PIPING ARE APPROXIMATE AND SHALL BE VERIFIED PRIOR TO PERFORMING FINAL CONNECTIONS. 2. CHANGES IN NEW PIPING FROM THAT SHOWN ON THE DRAWINGS, IN ORDER TO AVOID CONFLICTS WITH EXISTING ELECTRICAL SYSTEMS, MECHANICAL SYSTEMS, EQUIPMENT, STRUCTURES, OR EXISTING PIPING, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR WHETHER THE CONFLICTS ARE SHOWN OR ARE DISCOVERED IN THE FIELD. LIKEWISE, ALTERATIONS TO EXISTING ELECTRICAL SYSTEMS, MECHANICAL SYSTEMS, EQUIPMENT, OR EXISTING PIPING IN ORDER TO ACCOMMODATE NEW PIPING AND EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. THE OWNER AND THE ENGINEER MUST APPROVE ALL SUCH CHANGES. 3. PROVIDE A MINIMUM OF 6 INCHES CLEARANCE BETWEEN PIPING AND FOOTINGS, STRUCTURES, AND OTHER PIPING UNLESS OTHERWISE INDICATED. 4. VERTICAL PIPE FITTINGS ARE NOT SHOWN ON THE DRAWINGS FOR CLARITY. THE CONTRACTOR SHALL PROVIDE VERTICAL PIPE FITTINGS AS REQUIRED FOR COMPLETE AND OPERABLE PIPE INSTALLATIONS. PROVIDE ALL CONNECTING PIECES AND TRANSITION PIECES REQUIRED TO MAKE FINAL PIPING CONNECTIONS. 5. THE CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CONFINED SPACE ENTRY REGULATIONS. 6. MAINTAIN ALL OVERHEAD AND UNDERGROUND ELECTRICAL, TELEPHONE, WATER, AND GAS SERVICES AND ALL OTHER PERIOD. PHASES OF CONSTRUCTION INVOLVING TEMPORARY INTERRUPTION UTILITIES DURING ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL MAINTAIN WATER SERVICES TO THE MAXIMUM EXTENT POSSIBLE DURING THE CONSTRUCTION OF ESSENTIAL SERVICES AND DEMOLITION OF EXISTING EQUIPMENT SHALL BE SCHEDULED IN CONSULTATION WITH THE OWNER, SHALL NOT BE LONGER DURANTION THAN ESSENTIAL TO ACCOMPLISH THE PURPOSE FOR SUCH INTERRUPTIONS, AND SHALL BE COORDINATED TO GIVE THE OWNER THE ABILITY TO MAINTAIN WATER PRODUCTION. 7. THE CONTRACTOR SHALL COORDINATE ELECTRICAL POWER SUPPLY WITH THE OWNER PRIOR TO CONSTRUCTION. ALL ELECTRICAL POWER AND CONTROL WIRING, CONDUIT, AND ELECTRICAL APPURTENANCES REQUIRED SHALL BE SIZED, PROVIDED, AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND POWER COMPANY STANDARDS. POWER AND CONTROL WIRING SHALL BE INSTALLED IN SEPARATE CONDUITS. 8. ALL TUBING, PIPING, PUMPS, EQUIPMENT, AND OTHER APPURTENANCES ASSOCIATED WITH THIS PROJECT MUST COMPLY WITH NSF STARD 61 TO ENSURE IT IS SATISFACTORY FOR USE WITH POTABLE WATER APPLICATIONS. 9. THE TOWN OF AMHERST WATER TREATMENT PLANT OPERATORS SHALL MAINTAIN AND UTILIZE THE SPECIFIC ION ELECTRODE METER CURRENTLY USED IN THE LAB FOR REPORTING THE FINISHED WATER FLUORIDE CONCENTRATION IN THE MONTHLY REPORTS AS WELL AS FOR COLLECTION OF SPLIT FLUORIDE SAMPLES. NO. DATE BY REVISION NO. REVISION BY DATE REVISION NUMBER: PROJECT: TITLE: DISCIPLINE: DATE: DRAWN BY: DESIGNED BY: REVIEWED BY: DRAWING NUMBER: SHEET NUMBER: WWA NUMBER: FILE NAME: SCALE: 204232.12 OF 4 CIVIL GLM JLW JPC 11-09-06 TOWN OF AMHERST, VIRGINIA WATER TREATMENT PLANT PHASE 2 FLUORIDE IMPROVEMENTS 1 VDH COMMENT REVISIONS JPC 11-9-06 A SSOCI TES A 1402 Greenbrier Place Charlottesville, VA 22901 Phone: 434.984.2700 www.wwassociates.net S A P L NE N R S E ORS NGINEERS UR VEY P.O.Box 4119 Lynchburg, Va 24502 Phone: 434.316.6080 K H K L LL LL ALF 2 GLM 11-30-06 REVISED ELECTRICAL NOTES 3 JAC 1-21-08 RECORD DRAWINGS PER CONTRACTOR AS-BUILTS FOR INFORMATIONAL PURPOSES ONLY RECORD DRAWINGS JANUARY 21, 2008

Upload: dangkhue

Post on 25-Mar-2018

214 views

Category:

Documents


1 download

TRANSCRIPT

L

BM

GVSANST

WVWATERFH

WVWATER

EXISTING NEW DESCRIPTION EXISTING NEW DESCRIPTION

FH

PIN

LIST OF DRAWINGS

SHEET NO. DWG. NO. DISCIPLINE TITLE

REINFORCED CONCRETE PIPE REQUIRED RIGHT RIGHT OF WAY SANITARY SODIUM HYPOCHLORITE SQUARE STAINLESS STEEL STATION STANDARD STEEL TO BE ABANDONED TO BE REMOVED TOP THRUST COLLAR TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED WITH WATERSTOP, WATER SURFACE YARD

RCP REQ’D RT R/W SAN SH SQ SST STA STD STL TBA TBR T/ T/C TYP UG UON W/ WS YD

EXIST FF FLG GALV HK HYD INV IPS IPF JB LT LF MIN MH MJ No NTS O.C. PROP PVC

ABBREVIATIONS

NOT TO SCALE

NOTES: 1. THE SIZE OF THE SYMBOLS MAY VARY FROM THOSE SHOWN. 2. ALL ABBREVIATIONS AND SYMBOLS SHOWN MAY NOT BE USED.

BENCHMARK

BUSH

TREE

GAS VALVE

SANITARY OR STORM MANHOLE

DROP INLET

LIGHT POLE

POWER POLE

IRON PIN

TELEPHONE POLE, WITH GUY

AND ANCHOR

RIPRAP

BORING LOCATION

NORMAL WATER LEVEL

SILT FENCE

CONSTRUCTION ENTRANCE

LIMITS OF CLEARING

AND GRADING

VDOT EC-2 LINER

OUTLET PROTECTION

RIGHT-OF-WAY

SPOT ELEVATION

TREE LINE

TOP OF BANK/ TOE OF SLOPE

CENTER/EDGE OF STREAM

FENCE AND GATE

PROPERTY LINE

TAX MAP LINE

OVERHEAD POWERAND/OR TELEPHONE

STRUCTURE

FUTURE STRUCTURE

WATER METER

FIRE HYDRANT

WATER VALVE

DEMOLISH OR ABANDON

STRUCTURE

CONTOUR (INTERVAL AS

INDICATED ON SITE PLAN)

YARD HYDRANT

SANITARY SEWER

STORM SEWER AND END

WALL, TYPE AS INDICATED

POTABLE WATER LINE

TRAFFIC WIRE

UNDERGROUND ELECTRICAL LINE

UNDERGROUND TELEPHONE LINE

ABANDONED OR REMOVED

UTILITY

EDGE OF ASPHALT PAVEMENT

EDGE OF GRAVEL PAVEMENT

+56.1

SAN

ST

W

435

R/W

P

TOB TOS

L

SAN

ST

W

TW

UGE

UGT

CIP

CE

SF

OP

+56.1

LEGEND

GENERAL NOTES

LOCATION MAP

CS-1

1NONE

TOWN OF AMHERST, VIRGINIA

CULVERT INLET PROTECTION

DD

ST

DIVERSION DIKE

TEMPORARY SEDIMENT TRAP

EXISTING FINISHED FLOOR FLANGED GALVANIZED HOOK HYDRANT INVERT IRON PIN SET IRON PIN FOUND JUNCTION BOX LEFT LINEAR FEET MINIMUM MANHOLE MECHANICAL JOINT NUMBER NOT TO SCALE ON CENTER PROPOSED POLYVINYL CHLORIDE

AIR AIR RELEASE VALVE AHEAD BLIND FLANGE BENCH MARK BACK CENTER TO CENTER CURB & GUTTER CAST IRON PIPE CENTER LINE CHAIN LINK CLOCKWISE CORRUGATED METAL PIPE CLEAN OUT CONCRETE CUBIC YARDS DIAMETER DROP INLET, DUCTILE IRON DUCTILE IRON PIPE DRAWING ELEVATION

A ARV AHD BF BM BK C/C C&G CIP C CL CW CMP CO CONC CY DIA DI DIP DWG EL

435

COVER SHEET

4232CS1.DGN

FILE: W:\Cadd\204232.12\4232cs1.dgn

DATE: 24-Jan-08 11:28

PROJECTSITE

3

PHASE 2 FLUORIDE IMPROVEMENTS PROJECTWATER TREATMENT PLANT

1 0F 4

2 0F 4

3 0F 4

4 0F 4

CS-1

C-1

C-2

C-3

GENERAL

CIVIL

CIVIL

CIVIL

COVER SHEET

IMPROVEMENTS PLAN

DETAILS

FLUORIDE ANALYZER SAMPLE

PUMP ISOMETRIC & DETAILS

1. THE LOCATION AND ELEVATION OF EXISTING STRUCTURES, PIPING, AND UTILITIES SHOWN ARE BASED ON THE WATER TREATMENT PLANT 1997 RECORD DRAWINGS. THE CONTRACTOR SHALL VERIFY ALL DATA IN THE FIELD PRIOR TO CONSTRUCTION. THE DIAMETERS OF EXISTING PIPING ARE APPROXIMATE AND SHALL BE VERIFIED PRIOR TO PERFORMING FINAL CONNECTIONS.

2. CHANGES IN NEW PIPING FROM THAT SHOWN ON THE DRAWINGS, IN ORDER TO AVOID CONFLICTS WITH EXISTING ELECTRICAL SYSTEMS, MECHANICAL SYSTEMS, EQUIPMENT, STRUCTURES, OR EXISTING PIPING, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR WHETHER THE CONFLICTS ARE SHOWN OR ARE DISCOVERED IN THE FIELD. LIKEWISE, ALTERATIONS TO EXISTING ELECTRICAL SYSTEMS, MECHANICAL SYSTEMS, EQUIPMENT, OR EXISTING PIPING IN ORDER TO ACCOMMODATE NEW PIPING AND EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. THE OWNER AND THE ENGINEER MUST APPROVE ALL SUCH CHANGES.

3. PROVIDE A MINIMUM OF 6 INCHES CLEARANCE BETWEEN PIPING AND FOOTINGS, STRUCTURES, AND OTHER PIPING UNLESS OTHERWISE INDICATED.

4. VERTICAL PIPE FITTINGS ARE NOT SHOWN ON THE DRAWINGS FOR CLARITY. THE CONTRACTOR SHALL PROVIDE VERTICAL PIPE FITTINGS AS REQUIRED FOR COMPLETE AND OPERABLE PIPE INSTALLATIONS. PROVIDE ALL CONNECTING PIECES AND TRANSITION PIECES REQUIRED TO MAKE FINAL PIPING CONNECTIONS.

5. THE CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CONFINED SPACE ENTRY REGULATIONS.

6. MAINTAIN ALL OVERHEAD AND UNDERGROUND ELECTRICAL, TELEPHONE, WATER, AND GAS SERVICES AND ALL OTHER PERIOD. PHASES OF CONSTRUCTION INVOLVING TEMPORARY INTERRUPTION UTILITIES DURING ENTIRE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL MAINTAIN WATER SERVICES TO THE MAXIMUM EXTENT POSSIBLE DURING THE CONSTRUCTION OF ESSENTIAL SERVICES AND DEMOLITION OF EXISTING EQUIPMENT SHALL BE SCHEDULED IN CONSULTATION WITH THE OWNER, SHALL NOT BE LONGER DURANTION THAN ESSENTIAL TO ACCOMPLISH THE PURPOSE FOR SUCH INTERRUPTIONS, AND SHALL BE COORDINATED TO GIVE THE OWNER THE ABILITY TO MAINTAIN WATER PRODUCTION.

7. THE CONTRACTOR SHALL COORDINATE ELECTRICAL POWER SUPPLY WITH THE OWNER PRIOR TO CONSTRUCTION. ALL ELECTRICAL POWER AND CONTROL WIRING, CONDUIT, AND ELECTRICAL APPURTENANCES REQUIRED SHALL BE SIZED, PROVIDED, AND INSTALLED BY THE CONTRACTOR IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND POWER COMPANY STANDARDS. POWER AND CONTROL WIRING SHALL BE INSTALLED IN SEPARATE CONDUITS.

8. ALL TUBING, PIPING, PUMPS, EQUIPMENT, AND OTHER APPURTENANCES ASSOCIATED WITH THIS PROJECT MUST COMPLY WITH NSF STARD 61 TO ENSURE IT IS SATISFACTORY FOR USE WITH POTABLE WATER APPLICATIONS.

9. THE TOWN OF AMHERST WATER TREATMENT PLANT OPERATORS SHALL MAINTAIN AND UTILIZE THE SPECIFIC ION ELECTRODE METER CURRENTLY USED IN THE LAB FOR REPORTING THE FINISHED WATER FLUORIDE CONCENTRATION IN THE MONTHLY REPORTS AS WELL AS FOR COLLECTION OF SPLIT FLUORIDE SAMPLES.

NO. DATEBYREVISION NO. REVISION BY DATE

REVISION NUMBER:PROJECT:

TITLE:

DISCIPLINE: DATE:

DRAWN BY:

DESIGNED BY:

REVIEWED BY:

DRAWING NUMBER:

SHEET NUMBER:WWA NUMBER: FILE NAME: SCALE:

204232.12 OF 4CIVIL

GLM

JLW

JPC

11-09-06

TOWN OF AMHERST, VIRGINIA

WATER TREATMENT PLANT

PHASE 2 FLUORIDE IMPROVEMENTS

1 VDH COMMENT REVISIONS JPC 11-9-06

ASSOCI TESA1402 Greenbrier Place

Charlottesville, VA 22901

Phone: 434.984.2700

www.wwassociates.net

SAPL NEN R

S

E

ORS

NGINEERS

URVEY

P.O.Box 4119

Lynchburg, Va 24502

Phone: 434.316.6080

K

Y

O

C

E

R

A

H

A

L

F

HP5500 FULLK

Y

O

C

E

R

A

F

U

L

L

L

A

S

E

R

H

A

L

F

K

Y

O

C

E

R

A

F

U

L

L

HP5500 FULL

K

Y

O

C

E

R

A

H

A

L

F

2 GLM 11-30-06REVISED ELECTRICAL NOTES

3 JAC 1-21-08RECORD DRAWINGS PER CONTRACTOR AS-BUILTS FOR

INFORMATIONAL

PURPOSES

ONLY

RECORD DRAWINGS

JANUARY 21, 2008

C-1

4232C01.DGN 1/4 " = 1’

FILE: W:\Cadd\204232.12\4232C01.dgn

DATE: 24-Jan-08 11:26

3

2

5’ 0 5’

1/4 " = 1’-0"

SCALE: 1/4 " = 1’-0"

FIRST FLOOR PLAN

SCALE: 1/4 " = 1’-0"

SECOND FLOOR PLAN

IMPROVEMENTS PLAN

REMOVE AND SALVAGE EXISTINGFLUORIDE FEED PUMP. INSTALL NEW OWNER PROVIDED GRUNDFOSPUMP. SEE DWG. C-2 FOR ISOMETRIC.

REMOVE AND SALVAGE EXISTINGSCALE. INSTALL OWNER PROVIDED ELECTRONIC CARBOY SCALE-FOREFLOW 400 LB CAPACITY.

REMOVE AND SALVAGE EXISTINGRECORDER. INSTALL OWNER PROVIDED DIGITAL INDICATOR/RECORDER-WIZARD 4000.

INSTALL NEW PLC NEAR EXISTINGOPERATOR INTERFACE COMPUTER.SEE NOTES FOR MORE INFORMATION.

FLUORIDE FEED/STORAGE ROOM. SEE NOTES FOR MORE INFORMATION.

ELECTRICAL NOTES

E1.

E2.

E3.

E4.

E5.

E6.

E7.

1.

2.

3.

4.

5.

6.

9.

10.

11.

12.

7.

8.

FLUORIDE FEED STORAGE ROOM: MAINTAIN CONTINUOUS FLUORIDE FEED DURING

CONSTRUCTION. REMOVE EXISTING CHEMICAL FEED PUMP AND SCALES. COORDINATE STORAGE

LOCATION WITH OWNER. PROVIDE TEMPORARY FLUORIDE FEED POINT ON FIRST FLOOR NEAR

THE CURRENT INJECTION POINT WITH EXISTING FEED PUMP. USE FIRST FLOOR FOR TEMPORARY

STORAGE OF HYDROFLUOROSILIC ACID.

CLEAN FLUORIDE FEED ROOM AND REMOVE EXISTING SHELF. PROVIDE NEW PAINT FOR FEED

ROOM. PROVIDE A NEW WALL BRACKET FOR GRUNDFOS CHEMICAL FEED PUMP. ALSO PROVIDE

GRUNDFOS PRIMING AID, CALLIBRATION CHAMBER, AND OTHER APPURTENANCES AS LISTED BY

THE CONTRACT DOCUMENTS. CONTACT GRUNDFOS REPRESENTATIVE - JOHNSTON, INC. FOR OEM

BRACKET AND PRIMING AID. POINT OF CONTACT IS MR. RYLAND BROWN 434-525-7929.

INSTALL OWNER PROVIDED EQUIPMENT AND OTHER EQUIPMENT REQUIRED BY THE CONTRACT

DOCUMENTS TO FORM A COMPLETE AND OPERABLE FLUORIDE FEED SYSTEM. SEE SPECIFICATION

SECTION 01400 FOR A LIST OF OWNER PROVIDED EQUIPMENT, AND EQUIPMENT TO BE PROVIDED

BY THE CONTRACTOR.

PROVIDE A NEW ELECTRICAL EQUIPMENT RACK AS SHOWN IN THE FLOOR PLAN AND AS

DETAILED ON DRAWING C-3. THE CONTRACTOR SHALL FABRICATE A RACK USING A UNISTRUT

TYPE MATERIAL. RACK SHALL BE LOCATED ADJACENT TO THE FLUORIDE FEED ROOM IN FRONT

OF FILTER #4. RACK SHALL NOT INTERFERE WITH FILTER CONTROLS AND SHALL NOT LIMIT

ACCESS TO FEED ROOM, OR HINDER PEDESTRIAN TRAFFIC AROUND THE DESIGNATED AREA.

REMOVE ALL DIRT, SCALE AND CHEMICAL BUILD-UP FROM RAW WATER PIPING INSIDE THE

FILTER GALLERY. PAINT NEW AND EXISTING PIPE TO MATCH OWNER’S PIPE COLOR CODE (BARN

RED).

PROVIDE A NEW PLC IN ACCORDANCE WITH THE SPECIFICATIONS. INSTALL PLC IN DESIGNATED

AREA IN OFFICE ON SECOND FLOOR. PROVIDE ALL REQUIRED WIRING, CONDUIT AND DEVICES TO

CONNECT OWNER PROVIDED EQUIPMENT AND NEW CONTRACTOR PROVIDED EQUIPMENT WITH THE

PLC. WIRING SHALL BE OF THE TYPE, SIZE AND NUMBER TO ENSURE PROPER

COMMUNICATION AS INTENDED BY THE CONTRACT DOCUMENTS.

THE EXISTING OPERATOR INTERFACE COMPUTER LOCATED IN THE OFFICE SHALL BE

PROGRAMMED TO INCORPORATE NEW EQUIPMENT. EXISTING SOFTWARE CONSISTS OF

WONDERWARE AND SCADALARM. PROVIDE NEW CONTROL SCREENS FOR RAW WATER METER AND

FLUORIDE SCALES. SCREENS SHALL SHOW TRENDING AND REAL-TIME INFORMATION.

ALL CONTROL EQUIPMENT, PLC AND INSTALLATION SHALL BE COORDINATED THROUGH THE

SCADA FLUORIDE EQUIPMENT (PHASE 1) PROVIDER - E-MERGE SYSTEMS, INC., 314 N. 25TH

STREET, RICHMOND, VA 23223. POINT OF CONTACT IS MR. INDERDEEP S. HUJA:

1-804-608-6039.

INSTALL OWNER PROVIDED FLUORIDE ANALYZER WITH THE INSTALLATION KIT PROVIDED BY THE

OWNER. REMOVE ALL ELECTRICAL EQUIPMENT FROM FLUORIDE FEED ROOM. EXISTING EQUIPMENT

TO BE RELOCATED CONSISTS OF RAW WATER PUMP CONTACTORS, CARBON FEEDER ELECTRICAL

EQUIPMENT AND HVAC CONTROL EQUIPMENT. PROVIDE NEW ELECTRICAL EQUIPMENT TO MATCH

EXISTING ON NEW ELECTRICAL EQUIPMENT RACK WITH NEW NEMA 4X ENCLOSURES. PROVIDE

NEW WIRING AND CONDUIT TO CONNECT NEW ELECTRICAL EQUIPMENT TO EXISTING DEVICES.

ELECTRICAL OUTAGE SHALL BE COORDINATED WITH THE OWNER

INSTALL NEW SAMPLE PUMP ON FIRST FLOOR AS SHOWN ON THE PLAN VIEW, AND AS

DETAILED ON DRAWING NO. C-3. ROUTE ANALYZER SUPPLY LINE ALONG FIRST FLOOR CEILING

TO DELIVER SAMPLE TO FLUORIDE ANALYZER LOCATED ON EQUIPMENT RACK. PROVIDE SAMPLE

WASTE LINES THROUGH FLOOR TO WASTE SAMPLE TRENCH LOCATED ON FIRST FLOOR. PROVIDE

SAMPLE PUMP WITH ELECTRICAL POWER IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE.

NOTES

INSTALL NEW SAMPLEPUMP AND SUPPLY LINE.SEE NOTES AND NOTE E2.

EXISTING PANEL "L"

NOTE E3

NOTE E4

NEW ELECTRICAL EQUIPMENT RACK.SEE DWG C-3 FOR DETAIL. INSTALL NEW FLUORIDE ANALYZER &RELOCATED ELECTRICAL EQUIPMENT.SEE NOTES AND NOTE E5 FOR MORE INFO.

NOTEE6

EXISTING PANEL "L1"

TURBO FLOW METERINDICATOR/TRANSMITTERSEE NOTE E1.

REMOVE AND SALVAGE EXISTINGTURBINE FLOW METER. PROVIDE NEW 6" TURBO FLOW METER. SEE NOTES AND DETAIL ONDRAWING C-2.

REMOVE EXISTING TURBINE FLOW METER AND COORDINATE STORAGE LOCATION WITH OWNER.

RAW WATER PIPE WORK SHALL BE SCHEDULED WITH OWNER TO LIMIT DOWNTIME AND ENSURE

UNINTERUPTED WATER SUPPLY TO THE DISTRIBUTION SYSTEM. OWNER WILL FILL SYSTEM TO

MAXIMUM EXTENT POSSIBLE PRIOR TO CONSTRUCTION.

INSTALL NEW TURBO FLOW METER AND THE NEW REQUIRED PIPING AS SHOWN ON DRAWING

C-2. PROVIDE ALL NECESSARY PIPING, FITTINGS, GASKETS, ETC. FOR A COMPLETE, OPERABLE

AND WATERTIGHT SYSTEM. TAKE NECESSARY MEASUREMENTS PRIOR TO CONSTRUCTION TO

VERIFY REQUIRED SPOOL LENGTHS.

PROVIDE 120 VOLT POWER FOR THE NEW TURBO METER FROM EXISTING PANEL "L" WITH 3 #12,

3/4" CONDUIT. PROVIDE 20 AMP, SINGLE POLE CIRCUIT BREAKER.

PROVIDE 120 VOLT POWER FOR THE NEW SAMPLE PUMP FROM EXISTING PANEL "L" WITH 3

#12, 3/4" CONDUIT. PROVIDE 20 AMP, SINGLE POLE CIRCUIT BREAKER.

RELOCATE EXISTING WALLACE & TIERNAN CONTROLLER OUT OF THE FLUORIDE FEED ROOM TO

THE NEW ELECTRICAL EQUIPMENT RACK. SEE DRAWING C-3 FOR DETAILS.

RELOCATE EXISTING 12" X 12" X 6" DEEP "CHEMICAL FEED ROOM CONTACTORS" ENCLOSURE

OUT OF THE FLUORIDE FEED ROOM TO THE NEW ELECTRICAL EQUIPMENT RACK. SEE DRAWING

C-3 FOR DETAILS. PROVIDE A 12" X 12" X 6" DEEP NON-CORROSIVE NEMA 4 GASKETED,

NON-METALLIC JUNCTION BOX WITH A NEMA RATED TERMINAL STRIP IN THE SAME LOCATION AS

THE CONTACTOR ENCLOSURE. TERMINATE THE EXISTING CONDUCTORS ON THE TERMINAL STRIP

AND EXTEND NEW CONDUCTORS TO THE NEW LOCATION OF THE CONTACTOR ENCLOSURE.

REPLACE THE EXISTING CONTACTORS (2) WITH NEW CONTACTORS PROVIDED BY THE OWNER.

PROVIDE 1" PVC SCH 80 CONDUIT BETWEEN THE JUNCTION BOX AND THE RELOCATED

CONTACTOR ENCLOSURE. PROVIDE CONDUIT SEAL TO KEEP GASES FROM PASSING THRU

CONDUIT.

PROVIDE 120 VOLT POWER FOR THE NEW ELECTRICAL RACK EQUIPMENT FROM EXISTING PANEL

"L1" WITH 3 #12, 3/4" CONDUIT. PROVIDE 20 AMP, SINGLE POLE CIRCUIT BREAKER. PROVIDE

20 AMP HEAVY DUTY QUADRUPLEX (2) DUPLEX RECEPTACLES IN THE CENTER OF ELECTRICAL

RACK. SEE DRAWING C-3 FOR DETAIL.

THE ELECTRICAL RACK SHALL BE CONSTRUCTED WITH NON-CORROSIVE FIBERGLASS UNISTRUT.

PROVIDE "L" BRACKETS AS REQUIRED ON RACK TO SUPPORT THE WALLACE & TIERNAN

EQUIPMENT. BRACE THE ELECTRICAL RACK BACK TO THE ADJACENT WALL. BOLT THE RACK TO

THE CONCRETE FLOOR WITH 304 STAINLESS STEEL BOLTS AND LEAD ANCHORS.

PROVIDE NEW LAMINATED PHENOLIC NAME PLATES ON ALL RELOCATED AND NEW ELECTRICALLY

POWER EQUIPMENT. NAME PLATES SHALL INCLUDE THE EQUIPMENT NAME AND POWER CIRCUIT.

LETTERING SHALL BE 3/8" HIGH MINIMUM.

NO. DATEBYREVISION NO. REVISION BY DATE

REVISION NUMBER:PROJECT:

TITLE:

DISCIPLINE: DATE:

DRAWN BY:

DESIGNED BY:

REVIEWED BY:

DRAWING NUMBER:

SHEET NUMBER:WWA NUMBER: FILE NAME: SCALE:

204232.12 OF 4CIVIL

GLM

JLW

JPC

11-09-06

TOWN OF AMHERST, VIRGINIA

WATER TREATMENT PLANT

PHASE 2 FLUORIDE IMPROVEMENTS

1 VDH COMMENT REVISIONS JPC 11-9-06

ASSOCI TESA1402 Greenbrier Place

Charlottesville, VA 22901

Phone: 434.984.2700

www.wwassociates.net

SAPL NEN R

S

E

ORS

NGINEERS

URVEY

P.O.Box 4119

Lynchburg, Va 24502

Phone: 434.316.6080

K

Y

O

C

E

R

A

H

A

L

F

HP5500 FULLK

Y

O

C

E

R

A

F

U

L

L

L

A

S

E

R

H

A

L

F

K

Y

O

C

E

R

A

F

U

L

L

HP5500 FULL

K

Y

O

C

E

R

A

H

A

L

F

2 GLM 11-30-06REVISED ELECTRICAL NOTES

3 JAC 1-21-08RECORD DRAWINGS PER CONTRACTOR AS-BUILTS FOR

INFORMATIONAL

PURPOSES

ONLY

RECORD DRAWINGS

JANUARY 21, 2008

C-2

4232C02.DGN

DATE: 24-Jan-08 11:28

3

3

DETAILS

NTS

NOT TO SCALE

NEW SCH. 80 PVC PIPE

CONNECT DISCHARGETUBING TO PVC PIPE

165 LBS. HYDROFLUOROSILICACID DRUM

TO INJECTION POINT

NOT TO SCALE

NOT TO SCALE

P & I DIAGRAM

RAW WATER SUPPLY LINE DETAIL

CONNECT TO EXISTING PVC PIPE AT FLOOR.

XX PLC I/O POINT - XX INDICATES I/O TYPE

XXX

YYY

FRONT-OF-PANEL MOUNTED INSTRUMENT -

NORMALLY ACCESIBLE TO OPERATOR

LEGEND - P & I DIAGRAM

ABBREVIATIONS - P & I DIAGRAM

XXX

YYY

FIELD MOUNTED INSTRUMENT

XXX INDICATES TYPE OF INSTRUMENT

PIPING OR EQUIPMENT -

PART OF PROCESS FLOW

AUDIBLE ALARM DEVICE ON CONTROL PANEL

NEW ELECTRICAL SIGNAL

FE

FLUORIDEANALYZER

SAMPLE PUMP

RAW WATER

FLUORIDEFLUORIDEPUMP

FLUORIDESCALE

SCALE INDICATOR/TRANSMITTER

CENTRALCONTROLUNIT

PRINTER

mgL

EXISTING 12"RAW WATER

APPROX. LOCATIONOF EXISTINGCEILING BEAM

WALL MOUNTFLOW INDICATOR/TRANSMITTER

EXISTING 10"RAW WATER

14"

9"

FLUORIDE FEED ISOMETRIC

AI

AO

DI

DO

FE

FIT

FM

FQIR

YI

ANALOG INPUT

ANALOG OUTPUT

DISCRETE INPUT

DISCRETE OUTPUT

FLOW ELEMENT

FLOW INDICATING TRANSMITTER

FLOW METER

FLOW TOTALIZING INDICATOR/RECORDER

STATUS INDICATION

60" TO 90%%d

BEND

9’-6"

TO FLOOR

NOTE:

CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO ANY WORK.

WASTE SAMPLE

FM

FIT

AI

AO

AI

AI

PR

OG

RA

MM

AB

LE

LO

GIC

CO

NT

RO

LL

ER

RECORD FLOW (ANALOG IN)-INSTANTANEOUS FLOW-TOTALIZER- DAILY FLOWS

FLUORIDE SCALES (ANALOG IN)-CHEMICAL FEED RATE (MG/L)-USEAGE - LBS. (BASED ON TANK WEIGHT)

ANALYZER (ANALOG IN)-FLUORIDE RESIDUAL CONC. -HISTORIC CONCENTRATIONS

CCU - REQUIRED OUTPUTS

SEDIMENTATIONBASIN

FQIR

CONNECT NEWFLOW ELEMENTTO EXISTINGCHART RECORDERIN LAB ROOM

NOTES

1. ONLY INPUTS & OUTPUTS RELEVANT TO FLUORIDE FEED

ARE SHOWN, OTHERS OMITTED FOR CLARITY.

2. P & I DRAWING DOES NOT INDICATE ALL PIPING AND VALVE

ARRANGEMENTS. SEE DETAILED CIVIL DRAWINGS FOR ACTUAL

ARRANGEMENTS.

3. CONTRACTOR SHALL PROVIDE ALL CONTROL, POWER, AND

STATUS WIRING AS INDICATED FROM FIELD DEVICES TO

PANEL MOUNTED DEVICES AND PLC. ALL WIRING SHALL BE

INSTALLED IN CONDUIT.

4. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE

WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE

AND THE TOWN OF AMHERST REQUIREMENTS. ALL ELECTRICAL

EQUIPMENT SHALL BE MANUFACTURED BY SQUARE D WHEN

APPLICABLE TO MATCH EXISTING ELECTRICAL SYSTEMS.

5. WHEN SETTING UP THE INSTRUMENTATION & MONITORING

SYSTEM, CONFIGURE THE FLUORIDE OVERFEED ALARM FUNCTION

TO TRIGER WHEN THE RESIDUAL FLUORIDE CONCENTRATION

REACHES 1.8 MG/L.

SCALE INDICATOR/TRANSMITTER(OWNER FURNISHED)

400 LBS. ELECTRONICCARBOY SCALE(OWNER FURNISHED)

PVC SUCTION TUBING WITHFOOT VALVE & STRAINER(OWNER FURNISHED)

PE DICHARGE TUBING(OWNER FURNISHED)

MULTI-FUNCTION VALVE(OWNER FURNISHED)

PVC VENT TUBING(OWNER FURNISHED)

FLUORIDE FEED PUMPSEE NOTE 2(OWNER FURNISHED)

WALL BRACKET

1/2 " BALL VALVE

PRIMING AID

NOTES:

1. THE ISOMETRIC INDICATES GENERAL PIPING ARRANGEMENTS

& DOES NOT INDICATE ALL PIPE & FITTINGS REQUIRED. THE

GENERAL CONTRACTOR SHALL PROVIDE ALL PIPE & FITTINGS

REQUIRED FOR A COMPLETE & USEABLE SYSTEM.

2. WHEN SETTING THE FEED PUMP TO WORK IN CONJUNCTION

WITH THE 4-20 mA SIGNAL FROM THE FLOW METER, USE THE

MAXIMUM CAPACITY LIMITATION FUNCTION TO ENSURE

PROPER FLUORIDE FEED AND TO PROTECT AGAINST OVERFEED.

3. PROVIDE A 100-mL CALIBRATION CHAMBER AS SHOWN.

CHAMBER SHALL BE GRIFFCO VALVE, INC. OR APPROVED

EQUAL.

4. CONTRACTOR SHALL INSTALL OWNER FURNISHED EQUIPMENT.

ALL EQUIPMENT NOT LISTED AS "OWNER FURNISHED" SHALL BE

FURNISHED AND INSTALLED BY THE CONTRACTOR.

FLOW PACING

500CC CALIBRATION CHAMBER. SEE NOTES

4-20 MA

FILE: W:\Cadd\204232.12\4232C02.dgn

EXIST. 12"x6"REDUCER

NEW 6"TURBOMETER

EXIST. 10"90° ELBOW

EXIST. 10"x6"REDUCER

NEW FLG X PESPOOL W/UNIFLANGE

NO. DATEBYREVISION NO. REVISION BY DATE

REVISION NUMBER:PROJECT:

TITLE:

DISCIPLINE: DATE:

DRAWN BY:

DESIGNED BY:

REVIEWED BY:

DRAWING NUMBER:

SHEET NUMBER:WWA NUMBER: FILE NAME: SCALE:

204232.12 OF 4CIVIL

GLM

JLW

JPC

11-09-06

TOWN OF AMHERST, VIRGINIA

WATER TREATMENT PLANT

PHASE 2 FLUORIDE IMPROVEMENTS

1 VDH COMMENT REVISIONS JPC 11-9-06

ASSOCI TESA1402 Greenbrier Place

Charlottesville, VA 22901

Phone: 434.984.2700

www.wwassociates.net

SAPL NEN R

S

E

ORS

NGINEERS

URVEY

P.O.Box 4119

Lynchburg, Va 24502

Phone: 434.316.6080

K

Y

O

C

E

R

A

H

A

L

F

HP5500 FULLK

Y

O

C

E

R

A

F

U

L

L

L

A

S

E

R

H

A

L

F

K

Y

O

C

E

R

A

F

U

L

L

HP5500 FULL

K

Y

O

C

E

R

A

H

A

L

F

2 GLM 11-30-06REVISED ELECTRICAL NOTES

3 JAC 1-21-08RECORD DRAWINGS PER CONTRACTOR AS-BUILTS FOR

INFORMATIONAL

PURPOSES

ONLY

RECORD DRAWINGS

JANUARY 21, 2008