HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide B: Two Node System with M6720 Enclosures Abstract This guide provides information about connecting data cables for authorized technicians performing installation and maintenance services on HP 3PAR StoreServ 7000 Series Storage systems. HP Part Number: QR482-96796 Published: August 2014

Upload: vanphuc

Post on 11-May-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

HP 3PAR StoreServ 7000 Series StorageCabling Configuration Guide B:Two Node System with M6720 Enclosures

AbstractThis guide provides information about connecting data cables for authorized technicians performing installation and maintenanceservices on HP 3PAR StoreServ 7000 Series Storage systems.

HP Part Number: QR482-96796Published: August 2014

Page 2: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

© Copyright 2014 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the expresswarranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shallnot be liable for technical or editorial errors or omissions contained herein.

Acknowledgments

Microsoft®, Windows®, are U.S. registered trademarks of Microsoft Corporation.

Warranty

WARRANTY STATEMENT: To obtain a copy of the warranty for this product, see the warranty information website:

http://www.hp.com/go/storagewarranty

Printed in the US.

Page 3: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Contents1 Introduction...............................................................................................5

Audience.................................................................................................................................5Advisories................................................................................................................................5

2 Getting Started..........................................................................................6Following Precautions................................................................................................................6Identifying the Components, Enclosure Ports, and Labels................................................................6

3 Cabling Configurations...............................................................................92 Controller Nodes 1 Drive Enclosure..........................................................................................9

Labeling the Storage Drive Enclosures...................................................................................10Labeling the Cables for Controller Node 0............................................................................11Labeling the Cables for Controller Node 1............................................................................11Connecting the Cables to Controller Node 0 and 1................................................................12

2 Controller Nodes 2 Drive Enclosures......................................................................................14Labeling the Storage Drive Enclosures...................................................................................14Labeling the Cables for Controller Node 0............................................................................16Labeling the Cables for Controller Node 1............................................................................16Connecting the Cables to Controller Node 0 and 1................................................................18

2 Controller Nodes 3 Drive Enclosures......................................................................................19Labeling the Storage Drive Enclosures...................................................................................19Labeling the Cables for Controller Node 0............................................................................21Connecting Red-Labeled Cables to Controller Node 0............................................................22Labeling the Cables for Controller Node 1............................................................................22Connecting the Cables to Controller Node 1.........................................................................24

2 Controller Nodes 4 Drive Enclosures......................................................................................25Labeling the Storage Drive Enclosures...................................................................................25Labeling the Cables for Controller Node 0............................................................................27Connecting Red-Labeled Cables to Controller Node 0............................................................28Labeling the Cables for Controller Node 1............................................................................28Connecting the Cables to Controller Node 1.........................................................................30

2 Controller Nodes 5 Drive Enclosures......................................................................................31Labeling the Storage Drive Enclosures...................................................................................31Labeling the Cables for Controller Node 0............................................................................33Connecting Red-Labeled Cables to Controller Node 0............................................................34Labeling the Cables for Controller Node 1............................................................................34Connecting the Cables to Controller Node 1.........................................................................36

2 Controller Nodes 6 Drive Enclosures......................................................................................37Labeling the Storage Drive Enclosures...................................................................................37Labeling the Cables for Controller Node 0............................................................................39Connecting Red-Labeled Cables to Controller Node 0............................................................40Labeling the Cables for Controller Node 1............................................................................41Connecting the Cables to Controller Node 1.........................................................................43

2 Controller Nodes 7 Drive Enclosures......................................................................................44Labeling the Storage Drive Enclosures...................................................................................44Labeling the Cables for Controller Node 0............................................................................46Connecting Red-Labeled Cables to Controller Node 0............................................................47Labeling the Cables for Controller Node 1............................................................................48Connecting the Cables to Controller Node 1.........................................................................50

2 Controller Nodes 8 Drive Enclosures......................................................................................51Labeling the Storage Drive Enclosures...................................................................................51Labeling the Cables for Controller Node 0............................................................................53

Contents 3

Page 4: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting Red-Labeled Cables to Controller Node 0............................................................54Labeling the Cables for Controller Node 1............................................................................55Connecting the Cables to Controller Node 1.........................................................................57

2 Controller Nodes 9 Drive Enclosures......................................................................................58Labeling the Storage Drive Enclosures...................................................................................58Labeling the Cables for Controller Node 0............................................................................60Connecting Red-Labeled Cables to Controller Node 0............................................................61Labeling the Cables for Controller Node 1............................................................................62Connecting the Cables to Controller Node 1.........................................................................64

4 Additional Resources and Related Documentation.........................................65Contacting HP........................................................................................................................65HP 3PAR Documentation..........................................................................................................65

4 Contents

Page 5: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1 IntroductionAudience

This guide is intended for HP field engineers and authorized personnel installing or servicing HP3PAR StoreServ systems.

AdvisoriesTo avoid injury or damage to data and equipment, always observe the notes, cautions, andwarnings within this guide. Always be aware of the operating environment and handle electricalequipment carefully.

WARNING! Warnings alert you of actions that can cause injury to people or irreversible damageto the equipment, software, or data.

CAUTION: Cautions alerts you of actions that can cause damage to the equipment, software, ordata.

NOTE: Notes are reminders, tips, or suggestions that supplement the procedures included in thisguide.

Audience 5

Page 6: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Getting StartedRead the following sections as it list important instructions, precautions, and information aboutinstallation and cable connection options for the HP 3PAR StoreServ Storage system.

NOTE: The following diagrams do not present a storage-centric solution with the controller nodesmounted in the center of the rack or other non-HP supported component configurations. If the currentcomponents situated on the rack do not reflect the layout of the diagrams, continue to follow thecable instructions and carefully validate the port cable connections between all the controller nodesand storage drive enclosures to ensure proper operation and redundancy.

Following PrecautionsFollow these general precautions to avoid injury, data loss, and damage before and duringinstallation or while servicing the HP 3PAR StoreServ Storage system:• Avoid using improper tools

• Prepare an Electrostatic Discharge-safe (ESD) work surface by placing an antistatic mat onthe floor, or table, near the storage system. Attach the ground lead of the mat to an unpaintedsurface of the rack

• Always use a wrist-grounding strap, provided with the storage system. Attach the groundingstrap clip directly to an unpainted surface of the rack

• Avoid contact between electronic components and clothing which can carry an electrostaticcharge

• Ensure all cables are properly labeled and easily identifiable prior to removing a component

• Observe local occupational safety requirements and guidelines for handling heavy equipment

• Always load the heaviest item first, and start from the bottom when loading the rack. Loadingfrom the bottom makes the rack bottom-heavy and helps prevent the rack from becomingunstable

• Do not attempt to move a fully-loaded equipment rack. Remove all equipment from the rackbefore moving the rack

• Use at least two people to safely move the rack from the pallet

Identifying the Components, Enclosure Ports, and LabelsThe content in this section applies to all configurations and provides instructional guidance forcabling the HP 3PAR StoreServ 7000/7450 according to a specific configuration.

NOTE: The following diagrams do not present a storage-centric solution with the controller nodesmounted in the center of the rack or other non-HP supported component configurations. If the currentcomponents situated on the rack do not reflect the layout of the diagrams, continue to follow thecable instructions and carefully validate the port cable connections between all the controller nodesand storage drive enclosures to ensure proper operation and redundancy.

Controller Node and Storage Drive EnclosuresDepending on the system configuration, the HP 3PAR StoreServ 7200 enclosure is equipped withtwo controller nodes and the HP 3PAR StoreServ 7400/7450 supports either two or four controllernodes.

6 Getting Started

Page 7: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Figure 1 HP 3PAR StoreServ 7200 and 7400/7450 Controller Node Enclosure and SAS Ports

DP-1

DP-2M

fg

PULL

FC-2

FC-1

PCI-H

BA

MG

MT

RC-1M

fg

Mfg

1 2

2110G

be HP

3PAR

7200

CAUTION:

CAUTION:

PCM

PCM

1

0

1

0

DP-

1

DP-

2 Mfg

PULL

FC-2

FC-1

PCI-

HBA

MG

MT

RC-1 M

fg

Mfg

12

2 1 10Gbe

HP

3PA

R72

00

CAUTION:

CAUTION:

PCM

PCM

DP-1DP-2

DP-2

1

0

DP-

1

DP-

2

DP-1

DP-2

DP-

1

DP-

2

1

0

DP-1

DP-2

Node 1

DP-1

Node 0

CAUTION:

CAUTION:

PCM

PCM

CAUTION:

CAUTION:

PCM

PCM

DP-1

DP-2M

fg

PULL

FC-2

FC-1

PCI-H

BA 41 2 3

MG

MT

RC-1

Intr 0

Intr 1

HP

3PAR

7400

1

0

1

0

DP-

1

DP-

2 Mfg

PULL

FC-2

FC-1

PCI-

HBA4 123

MG

MT

RC-1

Intr

0

Intr

1

HP

3PA

R74

00

CAUTION:

CAUTION:

PCM

PCM

CAUTION:

CAUTION:

PCM

PCM

DP-1

DP-2M

fg

PULL

FC-2

FC-1

PCI-H

BA 41 2 3

MG

MT

RC-1

Intr 0

Intr 1

HP

3PAR

7400

3

2

3

2

DP-

1

DP-

2 Mfg

PULL

FC-2

FC-1

PCI-

HBA4 123

MG

MT

RC-1

Intr

0

Intr

1

HP

3PA

R74

00

DP-2DP-1

DP-2DP-1

DP-1DP-2

DP-1DP-2

3

2

1

0

DP-

1

DP-

2

DP-1

DP-2

DP-1

DP-2

DP-

1

DP-

2

DP-

1

DP-

2

1

0

3

2

DP-1

DP-2

DP-1

DP-2

DP-

1

DP-

2

Node 1

Node 2

Node 3

Node 0

The HP 3PAR StoreServ systems support a combination of small form-factor (SFF) M6710 and largeform-factor (LFF) M6720 storage drive enclosures. The M6710 (SFF) storage drive enclosure uses2.5-inch storage drives and the M6720 (LFF) enclosure supports 3.5-inch storage drives.

Figure 2 HP 3PAR M6710 and M6720 Storage Drive Enclosures and SAS Ports

CAUTION:

CAUTION:

PCM

PCM

CAUTION:

CAUTION:

PCM

PCM

1

0

1

0

DP-1

DP-2

Mfg

Mfg

DP-

1

DP-

2

Mfg

Mfg

DP-1DP-2

DP-2DP-1

1

0

DP-

1

DP-

2

DP-1

DP-2

1

0

DP-

1

DP-

2

DP-1

DP-2

IOM 1

IOM 0

CAUTION:

CAUTION:

PCM

PCM

CAUTION:

CAUTION:

PCM

PCM

DP-

1

DP-

2

Mfg

Mfg

DP-

1

DP-

2

Mfg

Mfg

1

0

1

0

DP-2DP-1

DP-2DP-1

1

0

DP-

1

DP-

2

DP-

1

DP-

2

1

0

DP-

1

DP-

2

DP-

1

DP-

2

IOM 1

IOM 0

Identifying the Components, Enclosure Ports, and Labels 7

Page 8: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Controller Node, Storage Drive Enclosure, and Cable Label KitsAll HP 3PAR StoreServ Storage systems contain special label kits for controller nodes, storage driveenclosures and cables. The labels are essential for identification purposes and part of the cablingprocess.The cabling configurations are identifiable by the specific number of nodes connecting to acombination of SFF and LFF storage drive enclosures. Each label specifies a direct connect froma controller node to a storage drive enclosure. All system cabling configurations use both red andgreen labels to assist with identifying and connecting the cables. Only connect a cable tocomponents sharing the same color.

Figure 3 Enclosure Labels

Figure 4 Cable Labels

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port 11 1E4

:1:D

P2 -

E2:

1:D

P1

E2:1:DP1 - E4:1:D

P2

Enclosure

IOM

Port

Enclosure

IOMPort

NodeNode

Red Data Loop Green Data Loop

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

8 Getting Started

Page 9: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

3 Cabling ConfigurationsThe following illustrative sections provide a rear view of the rack with recommended rackingconfiguration of the system.

NOTE: The following diagrams do not present a storage-centric solution with the controller nodesmounted in the center of the rack or other non-HP supported component configurations. If the currentcomponents situated on the rack do not reflect the layout of the diagrams, continue to follow thecable instructions and carefully validate the port cable connections between all the controller nodesand storage drive enclosures to ensure proper operation and redundancy.

2 Controller Nodes 1 Drive EnclosureBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 1 medium (2m) SAS cable

• 1 short (1m) SAS cable

Figure 5 2 Controller Nodes with 1 Large Form-Factor Drive Enclosure

Nodes 0/1

E1

2 Controller Nodes 1 Drive Enclosure 9

Page 10: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 6 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 7 Applying the Labels

Nodes 0/1

E1

10 Cabling Configurations

Page 11: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 8 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -1 1m A

1. Locate the labels for controller node 0 in the label kit.

Figure 9 Controller Node 0 Cable Labels

2. Select a short (1m) cable. Remove the two labels from row A and apply the labels four inchesaway from the connectors.

Figure 10 Labeling the Cable

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

2 Controller Nodes 1 Drive Enclosure 11

Page 12: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Figure 11 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -1 2m A- 1m -

1. Locate the labels for controller node 1 in the label kit.

Figure 12 Controller Node 1 Cable Labels

2. Select a medium (2m) cable. Remove the two labels from row A and apply the labels fourinches away from the connectors.

Figure 13 Labeling the Cable

Connecting the Cables to Controller Node 0 and 11. Connect the short (1m) cable to the identified ports of controller node 0.

Figure 14 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

12 Cabling Configurations

Page 13: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Connect a medium (2m) cable to the identified ports of controller node 1.

Figure 15 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

3. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 16 Reviewing Controller Nodes 0 and 1 Cable Connections

Nodes 0/1

E1

DP-1 DP-2

DP-2 DP-1

DP-1 DP-2

DP-1 DP-2

2 Controller Nodes 1 Drive Enclosure 13

Page 14: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 2 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 2 short (1m) SAS cables

Figure 17 2 Controller Nodes with 2 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

14 Cabling Configurations

Page 15: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 18 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 19 Applying the Labels

Nodes 0/1

E1

E2

2 Controller Nodes 2 Drive Enclosures 15

Page 16: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 20 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -2 1m A, B

1. Locate the labels for controller node 0 in the label kit.

Figure 21 Controller Node 0 Cable Labels

2. Select two short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors

Figure 22 Labeling the Cable

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

16 Cabling Configurations

Page 17: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Figure 23 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m A, B- 1m -

1. Locate the labels for controller node 1 in the label kit.

Figure 24 Controller Node 1 Cable Labels

2. Select two medium (2m) cables and do the following:a. Remove the two labels from row A and apply the labels four inches away from the

connectorsb. Remove the two labels from row B and apply the labels four inches away from the

connectors

Figure 25 Labeling the Cable

2 Controller Nodes 2 Drive Enclosures 17

Page 18: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 0 and 11. Connect the two short (1m) cables to the identified ports of controller node 0.

Figure 26 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

2. Connect the two medium (2m) cables to the identified ports of controller node 1.

Figure 27 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

3. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 28 Reviewing Controller Nodes 0 and 1 Cable Connections

Nodes 0/1

E1

E2

DP-1 DP-2

DP-2 DP-1

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

18 Cabling Configurations

Page 19: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 3 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 4 short (1m) SAS cables

Figure 29 2 Controller Nodes with 3 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

2 Controller Nodes 3 Drive Enclosures 19

Page 20: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 30 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 31 Applying the Labels

Nodes 0/1

E1

E2

E3

20 Cabling Configurations

Page 21: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 32 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -3 1m A-C

1. Locate the labels for controller node 0 in the label kit.

Figure 33 Controller Node 0 Cable Labels

2. Select three short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors

Figure 34 Labeling the Cable

2 Controller Nodes 3 Drive Enclosures 21

Page 22: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting Red-Labeled Cables to Controller Node 01. Connect the three short (1m) cables to the identified ports of controller node 0.

Figure 35 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 36 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

22 Cabling Configurations

Page 23: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Figure 37 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m B, C1 1m J

1. Locate the labels for controller node 1 in the label kit.

Figure 38 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row B and apply the labels four inches away from theconnectors

• Remove the two labels from row C and apply the labels four inches away from theconnectors

b. Select a short (1m) cable. Remove the two labels from row J and apply the labels fourinches away from the connectors.

Figure 39 Labeling the Cable

2 Controller Nodes 3 Drive Enclosures 23

Page 24: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the short (1m) cables to the identified ports of controller node 1.

Figure 40 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 41 Reviewing Controller Node 1 Cable Connections

Nodes 0/1DP-2 DP-1

E1

E2

E3

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-2 DP-1

24 Cabling Configurations

Page 25: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 4 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 6 short (1m) SAS cables

Figure 42 2 Controller Nodes with 4 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

E4

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

2 Controller Nodes 4 Drive Enclosures 25

Page 26: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 43 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 44 Applying the Labels

Nodes 0/1

E1

E2

E3

E4

26 Cabling Configurations

Page 27: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 45 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -4 1m A-D

1. Locate the labels for controller node 0 in the label kit.

Figure 46 Controller Node 0 Cable Labels

2. Select four short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors• Remove the two labels from row D and apply the labels four inches away from the

connectors

Figure 47 Labeling the Cable

2 Controller Nodes 4 Drive Enclosures 27

Page 28: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting Red-Labeled Cables to Controller Node 01. Connect the four short (1m) cables to the identified ports of controller node 0.

Figure 48 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 49 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

E4

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

28 Cabling Configurations

Page 29: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Figure 50 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m C, D2 1m J, K

1. Locate the labels for controller node 1 in the label kit.

Figure 51 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row C and apply the labels four inches away from theconnectors

• Remove the two labels from row D and apply the labels four inches away from theconnectors

b. Select two short (1m) cables:• Remove the two labels from row J and apply the labels four inches away from the

connectors• Remove the two labels from row K and apply the labels four inches away from the

connectors

Figure 52 Labeling the Cable

2 Controller Nodes 4 Drive Enclosures 29

Page 30: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the two short (1m) cables to the identified ports of controller node 1.

Figure 53 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 54 Reviewing Controller Node 1 Cable Connections

Nodes 0/1DP-2 DP-1

E1

E2

E3

E4

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-2 DP-1

30 Cabling Configurations

Page 31: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 5 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 8 short (1m) SAS cables

Figure 55 2 Controller Nodes with 5 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

E4

E5

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

2 Controller Nodes 5 Drive Enclosures 31

Page 32: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 56 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 57 Applying the Labels

Nodes 0/1

E1

E2

E3

E4

E5

32 Cabling Configurations

Page 33: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 58 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -5 1m A-E

1. Locate the labels for controller node 0 in the label kit.

Figure 59 Controller Node 0 Cable Labels

2. Select five short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors• Remove the two labels from row D and apply the labels four inches away from the

connectors• Remove the two labels from row E and apply the labels four inches away from the

connectors

Figure 60 Labeling the Cable

2 Controller Nodes 5 Drive Enclosures 33

Page 34: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting Red-Labeled Cables to Controller Node 01. Connect the five short (1m) cables to the identified ports of controller node 0.

Figure 61 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 62 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

34 Cabling Configurations

Page 35: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Figure 63 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m D, E3 1m J-L

1. Locate the labels for controller node 1 in the label kit.

Figure 64 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row D and apply the labels four inches away from theconnectors

• Remove the two labels from row E and apply the labels four inches away from theconnectors

b. Select three short (1m) cables:• Remove the two labels from row J and apply the labels four inches away from the

connectors• Remove the two labels from row K and apply the labels four inches away from the

connectors• Remove the two labels from row L and apply the labels four inches away from the

connectors

Figure 65 Labeling the Cable

2 Controller Nodes 5 Drive Enclosures 35

Page 36: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the three short (1m) cables to the identified ports of controller node 1.

Figure 66 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 67 Reviewing Controller Nodes 1 Cable Connections

Nodes 0/1DP-2 DP-1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-2 DP-1

36 Cabling Configurations

Page 37: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 6 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 10 short (1m) SAS cables

Figure 68 2 Controller Nodes with 6 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

E4

E5

E6

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

2 Controller Nodes 6 Drive Enclosures 37

Page 38: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 69 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 70 Applying the Labels

Nodes 0/1

E1

E2

E3

E4

E5

E6

38 Cabling Configurations

Page 39: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 71 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -6 1m A-F

1. Locate the labels for controller node 0 in the label kit.

Figure 72 Controller Node 0 Cable Labels

2 Controller Nodes 6 Drive Enclosures 39

Page 40: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Select six short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors• Remove the two labels from row D and apply the labels four inches away from the

connectors• Remove the two labels from row E and apply the labels four inches away from the

connectors• Remove the two labels from row F and apply the labels four inches away from the

connectors

Figure 73 Labeling the Cable

Connecting Red-Labeled Cables to Controller Node 01. Connect the six short (1m) cables to the identified ports of controller node 0.

Figure 74 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

40 Cabling Configurations

Page 41: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 75 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

E6DP-1 DP-2

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

Figure 76 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m E, F4 1m J-M

2 Controller Nodes 6 Drive Enclosures 41

Page 42: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the labels for controller node 1 in the label kit.

Figure 77 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row E and apply the labels four inches away from theconnectors

• Remove the two labels from row F and apply the labels four inches away from theconnectors

b. Select four short (1m) cables:• Remove the two labels from row J and apply the labels four inches away from the

connectors• Remove the two labels from row K and apply the labels four inches away from the

connectors• Remove the two labels from row L and apply the labels four inches away from the

connectors• Remove the two labels from row M and apply the labels four inches away from the

connectors

Figure 78 Labeling the Cable

42 Cabling Configurations

Page 43: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the four short (1m) cables to the identified ports of controller node 1.

Figure 79 Identifying Port Numbers on Green Label

11 1N

1:D

P2 -

E1:

1:D

P1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 80 Reviewing Controller Node 1 Cable Connections

Nodes 0/1DP-2 DP-1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-2 DP-1

E6DP-1 DP-2

2 Controller Nodes 6 Drive Enclosures 43

Page 44: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 7 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 12 short (1m) SAS cables

Figure 81 2 Controller Nodes with 7 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

E4

E5

E6

E7

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

44 Cabling Configurations

Page 45: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 82 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 83 Applying the Labels

Nodes 0/1

E1

E2

E3

E4

E5

E6

E7

2 Controller Nodes 7 Drive Enclosures 45

Page 46: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 84 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -7 1m A-G

1. Locate the labels for controller node 0 in the label kit.

Figure 85 Controller Node 0 Cable Labels

46 Cabling Configurations

Page 47: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Select seven short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors• Remove the two labels from row D and apply the labels four inches away from the

connectors• Remove the two labels from row E and apply the labels four inches away from the

connectors• Remove the two labels from row F and apply the labels four inches away from the

connectors• Remove the two labels from row G and apply the labels four inches away from the

connectors

Figure 86 Labeling the Cable

Connecting Red-Labeled Cables to Controller Node 01. Connect the seven short (1m) cables to the identified ports of controller node 0.

Figure 87 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

2 Controller Nodes 7 Drive Enclosures 47

Page 48: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 88 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2E6

DP-1 DP-2

DP-1 DP-2

E7

DP-1 DP-2

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

Figure 89 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m F, G5 1m J-N

48 Cabling Configurations

Page 49: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the labels for controller node 1 in the label kit.

Figure 90 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row F and apply the labels four inches away from theconnectors

• Remove the two labels from row G and apply the labels four inches away from theconnectors

b. Select five short (1m) cables:• Remove the two labels from row J and apply the labels four inches away from the

connectors• Remove the two labels from row K and apply the labels four inches away from the

connectors• Remove the two labels from row L and apply the labels four inches away from the

connectors• Remove the two labels from row M and apply the labels four inches away from the

connectors• Remove the two labels from row N and apply the labels four inches away from the

connectors

Figure 91 Labeling the Cable

2 Controller Nodes 7 Drive Enclosures 49

Page 50: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the five short (1m) cables to the identified ports of controller node 1.

Figure 92 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 93 Reviewing Controller Node 1 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2E6

DP-1 DP-2

DP-1 DP-2

E7

DP-1 DP-2

DP-2 DP-1

50 Cabling Configurations

Page 51: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 8 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 14 short (1m) SAS cables

Figure 94 2 Controller Nodes with 8 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

E4

E5

E6

E7

E8

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

2 Controller Nodes 8 Drive Enclosures 51

Page 52: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 95 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 96 Applying the Labels

Nodes 0/1

E1

E2

E3

E4

E5

E6

E7

E8

52 Cabling Configurations

Page 53: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 97 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -8 1m A-H

1. Locate the labels for controller node 0 in the label kit.

Figure 98 Controller Node 0 Cable Labels

2 Controller Nodes 8 Drive Enclosures 53

Page 54: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Select eight short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors• Remove the two labels from row D and apply the labels four inches away from the

connectors• Remove the two labels from row E and apply the labels four inches away from the

connectors• Remove the two labels from row F and apply the labels four inches away from the

connectors• Remove the two labels from row G and apply the labels four inches away from the

connectors• Remove the two labels from row H and apply the labels four inches away from the

connectors

Figure 99 Labeling the Cable

Connecting Red-Labeled Cables to Controller Node 01. Connect the eight short (1m) cables to the identified ports of controller node 0.

Figure 100 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

54 Cabling Configurations

Page 55: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 101 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2E6

DP-1 DP-2

DP-1 DP-2

E7

DP-1 DP-2

DP-1 DP-2

E8

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

Figure 102 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m G, H6 1m J-O

2 Controller Nodes 8 Drive Enclosures 55

Page 56: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the labels for controller node 1 in the label kit.

Figure 103 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row F and apply the labels four inches away from theconnectors

• Remove the two labels from row G and apply the labels four inches away from theconnectors

b. Select six short (1m) cables:• Remove the two labels from row J and apply the labels four inches away from the

connectors• Remove the two labels from row K and apply the labels four inches away from the

connectors• Remove the two labels from row L and apply the labels four inches away from the

connectors• Remove the two labels from row M and apply the labels four inches away from the

connectors• Remove the two labels from row N and apply the labels four inches away from the

connectors• Remove the two labels from row O and apply the labels four inches away from the

connectors

Figure 104 Labeling the Cable

56 Cabling Configurations

Page 57: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the six short (1m) cables to the identified ports of controller node 1.

Figure 105 Identifying Port Numbers on Green Label

11 1N

1:D

P2 -

E1:

1:D

P1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 106 Reviewing Controller Node 1 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2E6

DP-1 DP-2

DP-1 DP-2

E7

DP-1 DP-2

DP-2 DP-1

DP-1 DP-2

E8

2 Controller Nodes 8 Drive Enclosures 57

Page 58: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2 Controller Nodes 9 Drive EnclosuresBefore you begin cabling the storage system, carefully read or print the section, “Identifying theComponents, Enclosure Ports, and Labels” (page 6).

NOTE: Apply all the labels on to the appropriate system components and cables before connectingthe cables.

This cabling configuration consists of the following:• 2 medium (2m) SAS cables

• 16 short (1m) SAS cables

Figure 107 2 Controller Nodes with 9 Large Form-Factor Drive Enclosures

Nodes 0/1

E1

E2

E3

E4

E5

E6

E7

E8

E9

Labeling the Storage Drive EnclosuresThis section describes the procedures for labeling the storage drive enclosures connecting tocontroller nodes 0 and 1.

58 Cabling Configurations

Page 59: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the enclosure labels for controller nodes 0 and 1.

Figure 108 Controller Node Enclosure Labels

2. Apply the labels to the left rail of each storage drive enclosure.

NOTE: Do not label the controller node enclosures.

Figure 109 Applying the Labels

Nodes 0/1

E1

E2

E3

E4

E5

E6

E7

E8

E9

2 Controller Nodes 9 Drive Enclosures 59

Page 60: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Labeling the Cables for Controller Node 0Review the contents intended for controller node 0 in the red table before you proceed with labelingthe cables.

Figure 110 Controller Node 0 Cable Configuration

Node 0Number of cables Length Labels

- 6m -- 2m -9 1m A-I

1. Locate the labels for controller node 0 in the label kit.

Figure 111 Controller Node 0 Cable Labels

60 Cabling Configurations

Page 61: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Select nine short (1m) cables and do the following:• Remove the two labels from row A and apply the labels four inches away from the

connectors• Remove the two labels from row B and apply the labels four inches away from the

connectors• Remove the two labels from row C and apply the labels four inches away from the

connectors• Remove the two labels from row D and apply the labels four inches away from the

connectors• Remove the two labels from row E and apply the labels four inches away from the

connectors• Remove the two labels from row F and apply the labels four inches away from the

connectors• Remove the two labels from row G and apply the labels four inches away from the

connectors• Remove the two labels from row H and apply the labels four inches away from the

connectors• Remove the two labels from row I and apply the labels four inches away from the

connectors

Figure 112 Labeling the Cable

Connecting Red-Labeled Cables to Controller Node 01. Connect the nine short (1m) cables to the identified ports of controller node 0.

Figure 113 Identifying Port Numbers on Red Label

N0:

DP2

- E

1:0:

DP1

E1:0:DP1 - N

0:DP2

00 0Port

Node

Enclosure

IOM

Port

Node

Red Data Loop

2 Controller Nodes 9 Drive Enclosures 61

Page 62: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 114 Reviewing Controller Node 0 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2E6

DP-1 DP-2

DP-1 DP-2E7

DP-1 DP-2

DP-1 DP-2E8

DP-1 DP-2

DP-1 DP-2E9

DP-1 DP-2

Labeling the Cables for Controller Node 1Review the contents intended for controller node 1 in the green table before you proceed withlabeling the cables.

Figure 115 Controller Node 1 Cable Configuration

Node 1Number of cables Length Labels

- 6m -2 2m H, I7 1m J-P

62 Cabling Configurations

Page 63: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

1. Locate the labels for controller node 1 in the label kit.

Figure 116 Controller Node 1 Cable Labels

2. Do the following:a. Select two medium (2m) cables:

• Remove the two labels from row H and apply the labels four inches away from theconnectors

• Remove the two labels from row I and apply the labels four inches away from theconnectors

b. Select seven short (1m) cables:• Remove the two labels from row J and apply the labels four inches away from the

connectors• Remove the two labels from row K and apply the labels four inches away from the

connectors• Remove the two labels from row L and apply the labels four inches away from the

connectors• Remove the two labels from row M and apply the labels four inches away from the

connectors• Remove the two labels from row N aand apply the labels four inches away from the

connectors• Remove the two labels from row O and apply the labels four inches away from the

connectors• Remove the two labels from row P and apply the labels four inches away from the

connectors

Figure 117 Labeling the Cable

2 Controller Nodes 9 Drive Enclosures 63

Page 64: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

Connecting the Cables to Controller Node 11. Do the following:

a. Connect the two medium (2m) cables to the identified ports of controller node 1.b. Connect the seven short (1m) cables to the identified ports of controller node 1.

Figure 118 Identifying Port Numbers on Green Label

11 1

N1:

DP2

- E

1:1:

DP1

E1:1:DP1 - N

1:DP2

Port

Node

Enclosure

IOM

Port

Node

Green Data Loop

2. Use the diagram to verify all cabling is correct after connecting the cables to the controllernodes.

Figure 119 Reviewing Controller Node 1 Cable Connections

Nodes 0/1

E1

E2

E3

E4

E5

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

DP-1 DP-2

E6

DP-1 DP-2

E7

DP-1 DP-2

DP-1 DP-2

E8

DP-1 DP-2

E9

DP-1 DP-2

DP-2 DP-1

64 Cabling Configurations

Page 65: HP 3PAR StoreServ 7000 Series Storage Cabling ...h20628. · 2GettingStarted Readthefollowingsectionsasitlistimportantinstructions,precautions,andinformationabout installationandcableconnectionoptionsfortheHP3PARStoreServStoragesystem

4 Additional Resources and Related DocumentationContacting HP

For worldwide technical support information, see the HP support website:http://www.hp.com/support

Before contacting HP, collect the following information:

• Product model names and numbers

• Technical support registration number (if applicable)

• Product serial numbers

• Error messages

• Operating system type and revision level

• Detailed questionsSpecify the type of support you are requesting:

Support RequestHP 3PAR Storage System

StoreServ 7000 Series StorageHP 3PAR StoreServ 7200, 7400, and 7450 Storagesystems

HP 3PAR DocumentationFor additional information about other related system cable configurations, refer to the followingdocuments:

• HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide A: Two Node Systemwith M6710 Enclosures

• HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide B: Two Node Systemwith M6720 Enclosures

• HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide C: Two Node Systemwith M6710/M6720 Enclosures

• HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide D: Four Node Systemwith M6710 Enclosures

• HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide E: Four Node Systemwith M6720 Enclosures

• HP 3PAR StoreServ 7000 Series Storage Cabling Configuration Guide F: Four Node Systemwith M6710/M6720 Enclosures

Contacting HP 65