Achieving High Chilled-Water Delta Ts

Page 2: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Chillers Plant-Main Components

LoadAHUFCU

FAHU

CoolingTower

Chilled Water Pump

Page 3: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Quizzes as introduction

Page 4: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

4.5’C40’F

13’C56’F

What is High Delta Temp.?

Page 5: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Delta T: 3’F (1.5’C)

CH. Inefficient Operation

If Chiller Maximum Cap. is 600 TR: It can COOL 1000 gpm of CH.W.

Delta T: 16’F (9’C)

CH. Optimum Operation

13.5’C

56’F

4.5’C

40’F

6’C

43’F

4.5’C

40’F

Page 6: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

The Challenges-

Page 7: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

What will happen to CH. W. Sys. Components when Delta Temp. Differ (Keep Changing)?

Chillers

Pumps

Cooling

Energy Meters

Occupants Satisfaction

Towers

Enviro. Effect

Page 8: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Can same-GPM transfer more Cooling if Delta Temp. Increases?

gpm Delta-T TR

1000 1 42

1000 2 83

1000 3 125

1000 4 167

1000 5 208

1000 6 250

1000 7 292

1000 8 333

1000 9 375

1000 10 417

1000 11 458

1000 12 500

1000 13 542

1000 14 583

1000 15 625

1000 16 667

Page 9: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

1000gpm/Pump

-1-Chiller & 1-Pump is Working to Deliver 600 TR @ Delta Temp.: 15’F

600- TR/Chiller

5.5’C

42’F

4.5’C

40’F

14.5’C

58’F

13.5’C

56’F

Page 10: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

When Delta Temp. is fixed, how many TR can be transfer when flow change?

gpm Delta-T TR

500 4 83.3600 4 100700 4 117800 4 133900 4 150

1000 4 1671400 4 2331100 4 1831200 4 2001500 4 2501800 4 3002000 4 3332500 4 4173000 4 500

4000 4 667

Page 11: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

-5-Chillers & 5-Pumps are Working to Deliver 600 TR @ Delta Temp.: 4’F

4000-gpm

Pump

600- TR/Chiller

12.2 ’C54’F

4.5 ’C40’F

14.5 ’C

58’F

6.7 ’C

44’F

Page 12: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

3’F

6’F

9’F

12’F

16’F

If we have a Building Load 600 TR: How many Chiller we will Work?

5000gpm

4000gpm

3000gpm

2000gpm

1000gpm

Page 13: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Inefficient Operation

If we have a Building Load 600 TR: How many Chiller we will Work?

Optimum Operation

13’C

56’F

4.5’C

40’F

6.7’C

44’F

4.5’C

40’F

Page 14: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

What will happen to Power Consumption Ratio when Delta T decreases? (Low T. Syndrome)

Chillers

Pumps

Cooling

Energy Meters

Occupants Satisfaction

Towers

Enviro. Effect (-)

Page 15: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

What will happen to Power Consumption Ratio when Delta T increases? (High T. Syndrome)

Chillers

Pumps

Cooling

Energy Meters

Occupants Satisfaction

Towers

Enviro. Effect

Page 16: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

What will happen to Power Consumption Ratio when the need for CH. W. Flow decrease?

Chillers

Pumps

Cooling

Energy Meters

Occupants Satisfaction

Towers

Page 17: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-Once high

chilled-water Delta Ts is achieved, more Btu’s (J/s) of cooling will be accomplished per gallon (liter) of chilled-water distributed.

J/S)

gpm Delta-T TR

1000 1 41.71000 2 83.31000 3 125.01000 4 166.71000 5 208.31000 6 250.01000 7 291.71000 8 333.31000 9 375.01000 10 416.71000 11 458.31000 12 500.01000 13 541.71000 14 583.3

1000 15 625.0

Page 18: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-

hydronic

hydronic

Pressure losses and pumping energy will declineconsiderably in existing hydronic cooling systems and smaller pumps and piping may be installed in new hydroniccooling systems.

One Working Pump Compare to 5-Pumps

Page 19: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-Also, water chiller

capacities will no longer be limited by maximum cooler flow rates chilled-water storage tanks will store many more ton/hours (MJ) of cooling.

MJ

Page 20: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-This

fundamental approach provides significant, enduring improvements in the performance of variable-flow hydroniccooling systems.

hydronic

Page 21: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-Maximize the

cooling efficiency of Cooling Coil and prevent over flooding of CH. Water & increase Delta-T

Page 22: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-Anther

important benefit is the cooling transferred from Primary Circuit to Secondary Circuit 1’C+/-1’C

Page 23: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Results-The efficient

cooling & pumping means less Working:

• Chillers.

• C. Towers.

• Pumps.

• Dhs Per TR.

Page 24: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

The Challenge: How to achieve & maintain High Delta-T?

Page 25: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Estimate of Situation: The Need for Balancing and/or re-balancing of CH. W. Flow System.

Page 26: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

ASHRAE

Basic: Since “ASHRAE” approved 5 Methods of Chilled Water Piping

1- No Balancing Method

2- Manual Balance

Using DRV Method

3- Automatic Flow Limiting

Valves

4- Reverse Return

Method

5- Oversized Main Piping

Method

Page 27: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

ASHRAE-

Basic of “ASHRAE”: No Balancing required except Manual Balance Method using DRV.

Page 29: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

Agenda:• Identify Possible Reasons for

Low Delta-T and quantify effect of peak heating load?

• Design an automatic control system that will higher Delta-T

• Fix the control system and commission, also keep monitoring the performance.

• Ensure system capacity to treat dehumidification preciously while trying to control high DT .

• Balance the comfort with efficiency and energy saving.

• Suggest New Specifications with connected Load.

:•

•----

Page 30: How to achieve high chilled water delta temp. for 5th dc summit-2013 in qatar-by getco

How DC-Provider Can Achieve High Delta?

When CH.W. Pumps are located below loads, How can u transfer Cooling?