OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 127
4
______________________________HON EYWELL
AT87A, AT88A NEMA STANDARD TRANSFORMERS
Order No. Voltage (50/60 Hz) Conn.
Voltage (Open circuit) Conn. Mounting Overload Protection
AT87A1106 120/208/240 Vac 13" leads 28 2 screw terminals 50 VA Foot-mounted Built-in protectionor 4" x 4" plate
SecondaryPrimary
Used primarily for powering 24V air conditioning circuits. Can also be used in other applications that do not exceed the listed ratings.
Output (100% power factor)
AT SERIES TRANSFORMERSFOR ANY 24V CIRCUITS IN HEATING/COOLING CONTROL SYSTEMS
Order No.
Voltage (50/60 Hz) Conn.
Voltage (Open circuit) Conn. Mounting
Output VA
Rating
AT72D1683 120V 9" leadwires 26.5 2 screw terminals Can be foot-mounted; plate mounted on 4"x4" , octogan, or 2"x4" electrical boxes (transformer all above plate or 3/4" above plate); or clamp-mounted via a junction box knockout.
40 VA
SecondaryPrimary
Reset Type
Capillary Range
Capillary Length Switching Action
Manual 15-55oF. 20' 2 spst, one N.C., one N.O.
L482A1004 For temperature or limit control of air conditioning systems and refrigeration
L482 REFRIGERATION CONTROLLER
Order No. Application
Used to limit or control temperatures in air conditioning systems or refrigerated enclosures.
L4006, L6006 AQUASTAT CONTROLLERS
Order No. Application Switch ActionTemp. Range
Midscale Differential Includes 120 Vac 240 Vac
L4006A1678 High or Low Limit spst,contacts break on temp.rise
100-240oF. 5-30oF. Adj. 3" insulation, stop
factory set at 240oF.
8.0A 5.1A
L4006A1959 High or Low Limit spst,contacts break on temp.rise
40-180oF. 2oF. Fixed 1 1/2" insulation 2.6A 1.3A
L4006E1067 High Limit spst,contacts break on temp.rise
110-290oF. Manual Reset 3" insulation, stop
factory set at 240oF.
8.0A 5.1A
L6006A1145 Circulator, high or low limit
spdt 100-240oF. 5-30oF, Adj. 3" insulation, stop
factory set at 240oF.
8.0A 5.1A
STRAP ON AQUASTATL6006C1018 Circulator, high or
low limitspdt 65-200oF. 5-30oF. Adj. Bracket for strap-on
mounting, stop factory o
8.0A 5.1A
IMMERSION TYPE CONTROLLERS FOR LIMITING OR REGULATING TEMPERATURES OF LIQUIDS IN BOILERS OR TANKSTotally enclosed Micro Switch snap-acting switches operates on temperature rise to setpoint. Visible control point scale and extrenal adjustment screw permit easy setting. Horizontal or vertical insertion of the sensing element. Direct or well immersion of the sensing element. Models available for strap-on mounting. Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications. TRADELINE models include well adapter and tube of heat-conductive compound. Select models have wells.
Electrical Ratings: Full Load
-
128 www.federalcorp.com
4
HO NEYWELL______________________________
IMMERSION WELLS
Order No. ConnectionInsulation
DepthBulb
Diameter
Insertion/ Max. Bulb
Length Includes
COPPER112622AA 1/2" NPT 1 1/2" 1/2" 4" Spring clip112630AA 3/4" NPT 1" 1/2" 4 1/4" Spring clip121371A 1/2" NPT 1 1/2" 3/8" 3" Mounting clamp121371B 3/4" NPT 1 1/2" 3/8" 3" Mounting clamp121371L 1/2" NPT 3" 3/8" 3" Mounting clampSTAINLESS STEEL121371E 1/2" NPT 1 1/2" 3/8" 3" Mounting clamp
L4008, L6008 REMOTE BULB AQUASTAT
Order No. Description Switch Action Temp. RangeMidscale
Differential
Max. Ambient Temp. at Element
L4008E1156 High Limit Contacts break on temp.rise
110-290oF. Manual Reset
345oF.
L6008A1192 Circulator and low limit spdt 100-240oF. 5-30oF. Adj. 265oF.Electrical Ratings: Full Load: 120 Vac/8.0A, 240 Vac/5.1A
Bulb size: 3/8" X 2 7/8"
Remote temperature sensing element detects and responds rapidly to temperature changes. Totally enclosed Micro Switch™ snap-acting switch. Visible control point scale and external adjustment screw permit easy setting. Horizontal or vertical mounting of the remote element into boiler, tank, or other container. Case mounts to a vertical surface.
FOR LIMITING OR REGULATING TEMPERATURES OF LIQUIDS IN BOILERS OR TANKS
L4081 MULTIPLE AQUASTAT CONTROLLERS
Order No. Description Switching ActionAdjustable Differential
L4081A1023 130-240oF.High Limit/110-220o F. Low Limit Spst, high limit Spst, low limit
Yes, on low limit
Immersion type, liquid-filled sensing element actuates two snap switches. Controller may be mounted in any position and does not require leveling. Adjustments made inside front cover for accessibility
HIGH LIMIT, LOW LIMIT AND/OR CIRCULATOR CONTROLLER USED TO REGULATE BOILER WATER TEMPERATURE IN GAS- OR OIL-FIRED HYDRONIC HEATING SYSTEMS
M436, M836 DAMPER MOTORS
Order No.
Voltage (50/60 Hz)
Nominal Opening Current
Nominal Opening
TimeMax. Load
Torque
Breakaway
Torque1Damper
Blade Area
M436A1116 120 Vac 0.37A 30 sec. 20 in-lb. 30 in-lb 13 sq.ft.
SPRING-RETURN MOTORS FOR TWO-POSITION ZONE OR DAMPER Use with two-wire thermostats or other spst controllers. With thermal breaker for overload protection during the lifting stroke or if motor stalls.
1 Maximum torque available to overcome large loads such as a seized damper or valve. Not to be used continuously at this rating.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 129
4
______________________________ HO NEY WELLM6184D MODUTROL MOTORS
Order No. W VA Torque2 Timing3 Stroke
M6184D1035 24 15 17 150 lb/in. 30-60 sec. 90-160o
3 Shorter timing applies to 90o stroke.
Available with fixed or adjustable stroke, Double-ended Crankshaft 3/8" square. UL listed. CSA certified.
1 Internal actuator motor and circuitry operates from 24 Vac. Line voltage models shipped with internal transformers.
REVERSING, THREE-WIRE SPDT OF FLOATING CONTROL MOTORS USED TO OPERATE DAMPERS AND VALVES. REPLACES M644A-E MOTORS
Voltage1
(50/60 Hz)
Power
2 Normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
M6284D MODUTROL MOTORS
Order No.
Voltage1
(50/60 Hz) W VA Torque2 Timing3 Stroke
M6284D1000S 24 15 17 150 lb/in. 30-60 sec. 90-160o
3 Shorter timing applies to 90o stroke.
REVERSING, THREE-WIRE FLOATING-CONTROL MOTORS WITH FEEDBACK POTENTIOMETER. USED WITH CONTROLLERS THAT PROVIDE A SPDT OUTPUT TO OPERATE DAMPERS AND VALVES. REPLACES M944B,E,G,S MOTORS
Power
2 Normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
Available with fixed or adjustable stroke, Double-ended Crankshaft 3/8" square untapped. UL listed. CSA certified.
1 Internal actuator motor and circuitry operates from 24 Vac. Line voltage models shipped with internal transformers.
M8185D MODUTROL MOTORS
Order No.
Voltage1
(50/60 Hz) W VA Torque2 Timing3 Stroke
M8185D1006 24 20 21 50 lb/in. 30-60 sec. 90-160o
3 Shorter timing applies to 90o stroke.
Power
TWO-POSITION, SPRING-RETURN MOTORS USED TO OPERATE DAMPERS AND VALVES. REPLACES M445A,D; M845A,C,E; AND M865B MOTORS
2 Normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
Integral helical spring returns motor shaft to normal position (Full closed) on power interruption. Double-ended Crankshaft, 3/8" square. US listed. CSA certified.
1 Internal actuator motor and circuitry operates from 24 Vac. Line voltage models shipped with internal transformers.
M7284C MODUTROL MOTORS
Order No.
Voltage (50/60 Hz) W VA
1 Torque2 Timing Stroke Includes
M7284C1000 120 23 29 150 lb/in. 30 sec. 902 aux.
Switches1 VA figures listed are for 60 Hz. Values will be higher by 5VA at 50 Hz.
Power
2 Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
Replaces M744S,T,Y nd M745S,T,Y motors. Use with a modulating 4-20 m-A current.
PROPORTIONAL MOTORS USED TO OPERATE DAMPERS AND VALVES
-
130 www.federalcorp.com
4
HONE YWE LL ______________________________
M9164A,C,D; M9174B,C,D MODUTROL MOTORS
Order No. W VA Torque2 Timing3 Stroke
M9164D1009 24 14 15 35 lb/in. 30-60 sec 90-160o
M9174D1007 24 21 27 75 lb/in 30-60 sec 90-160o
Power
3 Shorter timing applies to 90o stroke.
Voltage1
(50/60 Hz)
REVERSING, PROPORTIONAL MOTORS USED TO OPERATE DAMPERS AND VALVES. REPLACES M934 MOTORSAvailable with fixed or adjustable stroke; refer to order table. All M9164 motors have an electronic drive circuit. One series 90 controller can drive up to six Modutrol motors using 4074BYK Resistor Bag Assembly or 221508A Resistor Board Kit. Interface modules available for series 70 (electronic) control. Double-ended Crankshaft 3/8" square. UL listed. CSA certified.
2 Normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
1 Internal actuator motor and circuitry operates from 24 Vac. Line voltage models shipped with internal transformers. Separate transformer may be required for 24V models for proper system operation.
M9184A,C,D,F; M9194D,E MODUTROL MOTORS
Order No.
Voltage1
(50/60 Hz) W VA Torque3 Timing2 Stroke Includes
M9184D1021 24 18 19 150 lb/in. 30-60 sec. 90-160Tapped shaft
M9194D1003 24 18 19 300 lb/in. 120-240 sec. 90-160 -1 Internal actuator motor and circuitry operates from 24 Vac. Line voltage models shipped with internal transformers.2 Shorter timing applies to 90o stroke.
Power
3 Torque given is normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE RATING.
Available with fixed or adjustable stroke. All M9184 motors have an electronic drive circuit. One series 90 controller can drive up to six Modutrol motors using 4074BYK Resistor Bag Assembly or 221508A Resistor Board Kit. Interface modules available for series 70 (electronic) control. Double-ended Crankshaft 3/8" square. Models available with tapped (8/32) shafts for Flame Safeguard applications. UL listed. CSA certified.
REVERSING, PROPORTIONAL MOTORS USED TO OPERATE DAMPERS AND VALVES. REPLACES M944A,C,D AND M954 MOTORS.
M9185A,C,D,E MODUTROL MOTORS
Order No.
Voltage1
(50/60 Hz) W VA Torque2 Timing3 Stroke
M9185D1004 24 23 24 60 IB/IN. 30-60 SEC. 90-160o
1 Internal actuator motor and circuitry operates from 24 Vac. Line voltage models shipped with internal transformers.
3 Shorter timing applies to 90o stroke.
REVERSING, PROPORTIONAL SPRING-RETURN MOTORS USED TO OPERATE DAMPERS AND VALVES. M9184, M9186 REPLACES M945A,D,F AND M955 MOTORS. M9175 REPLACES M965 AND M975 MOTORS
Power
2Normal running torque. Breakaway torque rating is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve.MOTOR NOT TO BE USED CONTINUOUSLY AT BREAKAWAY TORQUE.
Integral helical spring returns motor shaft to normal position (Full closed for M9175 and M9185, full open for M9186) on power interruption. Available with fixed or adjustable stroke. All M9175, M9185 and M9186 motors have an electronic drive circuit. One series 90 controller can drive up to six Modutrol motors using 4074BYK Resistor Bag Assembly or 221508A Resistor Board Kit. Interface modules available for series 70 (electronic) control. Double-ended Crankshaft 3/8" square. UL listed. CSA certified.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 131
4
______________________________ HON EYWELL
PARTS AND ACCESSORIES FOR HONEYWELL MOTORSOrder No. Application/Description Use With
HARDWARE220736A 1 spdt switch for internal mounting Auxiliary equipment for Mod IV motors220736B 2 spdt switches for internal mounting Auxiliary equipment for Mod IV motors220738A Mounting adapter for Mod IV motors Auxiliary equipment for Mod IV motors221455A Motor crank arm Auxiliary equipment for Mod IV motors221508A Resistor board. Any M91XX Mod IV motor, multiple configuration4074EDC Resistor kit Converts Series 90 Mod motor to 4-20mA inputTRANSFORMERS198162AA Internal transformer,120V/208V/240V Mod IV motors198162EA Internal transformer,120V Mod IV motors5001746001 Internal transformer, 24V/120V/230V Mod IV motors5001746003 Internal transformer, 120V Mod IV motors
M9484D, E, F MODUTROL MOTORS
Order No. 90o Stroke 160o Stroke Running Torque2 Additional Features
STANDARD MODEL
M9484D1010 30 sec. 60 sec. 150 lb/in. Shipped in 90o position
STANDARD MODEL WITH 1 SPDT AUXILIARY SWITCH3
M9484E1033 30 sec. 60 sec. 150 lb/in. Shipped in 90o position, switch set at 4o, with tapped shaft
STANDARD MODEL WITH 2 SPDT AUXILIARY SWITCHES3
M9484F1031 30 sec. 60 sec. 150 lb/in.
Shipped in 90o position, 1 switch set at 5o and 1 set
at 54o of 90o stroke. With tapped shaft.1 Shorter timing applies when 90o stroke is selected.2 Normal running torque. Breakaway torque is 2X normal running torque and is the maximum torque available to overcome occasional large loads such as a seized damper or valve. Motor not to be used continuously at breakaway torque rating.
Timing
REVERSING, PROPORTIONAL MOTORS USED TO DRIVE BURNER FIRING RATE VALVES, DAMPERS OR AUXILIARY EQUIPMENT. REPLACES M941A, C, D MOTORSDesigned for flame safeguard applications in commercial/industrial oil or gas burner systems. With vibration-resistant electronic
balancing circuit. Regulated by 3-wire proportional controller. Stroke is field selectable to 90 or 160 o. Double-ended Crankshaft, 3/8" square. Dead Weight Load on shaft: Power end-200 lbs.; auxiliary end-100 lbs. Dimensions: 7 3/16"(H) x 5 5/8"(W) x 7 5/16"(D). Electrical rating: 24V @ 50/60 Hz.
3 Cam-adjusted Micro Switch auxilary switch. Auxilary switch differential factory set at 1o (selectable for 10o). One contact switchratings: Full load: 7.2A@120V, 3.6A@240V; Locked rotor: 43.2A@120V,21.6A@24V.
DAMPER/VALVE ACTUATOR ACCESSORIESOrder No. Model No. Description
BALLJOINT-5 27518 SWIVEL BALL JOINT FOR 5/16 ROD for dampers.26026G 26026G 1/2 X 4-15/16 CRANK ARM for dampers.27174B 27174B 7/16" X 4-15/16" Damper Crank Arm AssemblyPUSHROD-5X360 27520K PUSH ROD LINKAGE 5/16 X 36 for dampers.7616BR 7616BR Crank Arm for Modutrol Motors
ML7984 VALVE ACTUATORS
Order No. Control Signal Comments
ML7984A40092-10V or 10-2Vdc,4-20 mA or 20-4 mA,
135 ohm, or electronic Series 90Use with V5011/V5013 valves. Field
selectable for either direct or reverse acting.
Mount directly, without a linkage, on V5011A,C,F,G, V5013F and V5045 1/2- to 3-inch water and steam, threaded valve bodies only. Compact size is ideal for unit heaters, fan coil units, narrow ceiling plenums and computer room motorized valve applications. 160-pound minimum valve closing force, either direction. Stem travel is 3/4". Non-spring return. Timing is 63 seconds for 3/4" travel.
-
132 www.federalcorp.com
4
HONEY WELL ______________________________
PA404 PRESSURETROL® CONTROLLERS
Order No. Application Oper. Range Switch Action
PA404A1025 Safety control for steam heating boilers; breaks an electrical circuit to shut down burner if steam pressure rises above a safe level.
3-15psi adj. Breaks at set point on pressure rise; makes at set point minus differential on pressure fall.
PA404A1033 Safety control for steam heating boilers; breaks an electrical circuit to shut down burner if steam pressure rises above a safe level.
0.5-9.0psi adj. Makes at setpoint on pressure fall; breaks at setpoint plus differential on pressure rise.
Electrical Ratings: Full load: 8.0A @ 120 Vac., 5.1A @ 240 Vac.
STEAM PRESSURE CONTROLLERSDifferential (adjustable) 1-5 psi
Q298B DAMPER LINKAGE
Order No. Damper Arms Ball Joints Pushrod
Q298B1065 2 2 1 (24")
CONNECTS M833 OR M835 MOTOR TO 1 OR 2 ZONE DAMPERS
Q313 REPLACEMENT THERMOPILE GENERATORS
Order No. Open Circuit Output Includes
Q313A1139 600 mV to 750 mV 35" leads
Q313A1170 600 mV to 750 mV 35" leads, PG9 adaptor
For use with Q314, Q324, Q327, Q377, Q379, Q382 Pilot Burners
PROVIDES POWER FOR A MILLIVOLTAGE, SELF-POWERED CONTROL
Q340A UNIVERSAL 30 MILLIVOLT THERMOCOUPLES
Order No. Lead Length
Q340A1074 24"Q340A1082 30"Q340A1090 36"Q340A1108 48"
REPLACES MOST 30 mV THERMOCOUPLES
NXL AND NXS VARIABLE FREQUENCY DRIVES
FEATURES
NOTE: Special Order only.
Highly flexible I/O configurationMulti-application software package pre-installedContinuous self-supervising runtime and alarm system enhances reliability and safetyControl logic can be powered from an external auxiliary supply, maintaining power to the control panel, internal drive functions and fieldbuses.
Integrated AC choke for maximum protection and minimum harmonicsIntegral RFI filter for industrial applicationsFlexibility in communication with multiple fields options: LonWorks,ModBus, deficient and prefabs
From simple HVAC applications to closed-loop process control applications, you can depend on the Honeywell NX series to control anything from simple fans, pumps and compressors to elevators, cranes or winders. NXS models offer the greatest application versatility for multiple control applications. Together these versatile performers feature modular, easily adaptable hardware, precise semiconductor technology, and a flexible, pre-installed application package that supports a fields systems. Our comprehensive offering of NXL and NXS variable frequency drives uses the latest frequency converter technology for more efficient motor operation. These compact, lightweight, reliable drives enable easy commissioning and start-up, convenient installation.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 133
4
______________________________HONE YWELL
R4222, R8222 SWITCHING RELAYS
Order No. SwitchingCoil Voltage (50/60
Hz.) Pole 1-2-3 Pole 4-5-6
GENERAL PURPOSE RELAYSR4222B1082 spdt 120V Power NoneR4222D1013 spdt 120V Power PowerR8222D1014 dpdt 24V Power Power
For use in refrigeration and air conditioning equipment, appliances, vending machines and similar applications. UL listed.
Q607 AUXILIARY SWITCHES
Order No. Switches Applicable Motors
Special Order 1 or 2 Modutrol motors
Electrical Ratings: Full load: 9.8A @ 120V, 4.9A @ 240V, 2.45A @ 480V
FOR CONTROL OF AUXILIARY EQUIPMENT AS A FUNCTION OF MOTOR SHAFT POSITION
Models available with adaptor for cover and spring-return motor and mounting bracket.
Q5001 VALVE LINKAGE
Order No. Bonnet Size Stem Force Lift Adjustment
Q5001D1000 1-3/8" 80 or 160 lbs./in. 3/4" fixedQ5001D1018 1-3/8" 160 or 320 lbs./in. 3/4" fixedSpecial Order 1-3/8" 160 or 320 lbs./in. 1-1/2" fixed
Connects Modutrol III or Modutrol IV motors to V5011, V5013, V5047 and V5051 valves. Replaces nine of the older Q601 and Q618 linkages. Overtravel permits tight close-off with less stress on the motor. Linkage mounts directly on the valve bonnet; motor mounts on linkage bracket. An easy-to-see position indicator tells at a glance if the valve is open or closed.
Q7000 SERIES INTERFACE MODULES
Order No. Application/Description Replaces Replaces Use With
Q7230A1005 Provides adjustable zero and span, voltage or current control (includes 4-20mA and 2-10VDC). Adapts M91XX Modutrol IV motors to function as M72XX model for M744S,T,Y; M745S,T,Y replacements.
M744S1005, M744S1013, M744T1004, M744T1012, M744Y1009, M744Y1017, M745S1002, M745S1010, M745T1001, M745T1019, M745Y1006, M745Y1014
M7284A1004,M7284A1012, M7284C1000, M7284C1018, M7284Q1009, M7284Q1017, M7285A1003, M7285A1011, M7285C1009, M7285C1017, M7285Q1008, M7285Q1016
M9184D1013, M9185D1004
FOR CONVERTING SERIES 90 MODUTROL IV MOTORS TO SERIES 70 (ELECTRONIC) CONTROLMount in wiring box of any series 90 Modutrol IV motor (M91XX model numbers). Allows for easy, cost-effective system upgrades. Module mates to quick-connect terminals and provides screw terminals for field-wiring connections. Solid state circuitry with surface-mount components. Plastic enclosure provides easy handling and protection for circuitry. Reversing switch for replacing models that rotate counter-clockwise with an increase in control signal (electrically NC models).
-
134 www.federalcorp.com
4
HON EYWELL ______________________________
T87F THERMOSTATS-THE ROUND®
Order No. Range
T87K1007 40-90oF.
T87N1000 40-90º F.
PROVIDES ELECTRONIC TEMPERATURE CONTROL FOR 24Vac RESIDENTIAL HEATING, COOLING OR HEATING/COOLING SYSTEMS. MERCURY FREE. PREMIER WHITE® COLOR.
Heat only gas or oil systems. Has OFF-HEAT system switching. For one stage heat only.
Features
Heating and Cooling Systems. Has COOL-OFF-HEAT system switching and AUTO-ON Fan switching. For one stage heat and one stage cooling.
Accessory129044A
Gold adapter kit includes 6 in. cover ring, adapter ring, screws to cover marks of old thermostat.
129044 adapter plate, 127293 6" decorator cover plate
Order No. Replaces Maximum Lockout Time Features
S8610U30091, 2 See Footnote 90 seconds 100% pilot shutoff on loss of flame. Includes remote reset, and automatic vent damper plug. For use in systems with combination igniter-sensor (single rod or local sense) or separate igniter and sensor (dual-rod or remote sense).
S8910U1000 See Footnote 3 Hot surface igniton module
3. Replaces wide range of hot surface modules made by Honeywell, Robertshaw, and White Rogers.2. Recommended Combination Gas Control: VR8204, VR8304, VR8345M.
CONTROL MODULES FOR INTERMITTENT PILOT GAS BURNER IGNITION AND HOT SURFACE SYSTEMS USED ON CENTRAL HEATING SYSTEMS AND HEATING APPLIANCES
1. Replaces most of the following intermittent pilot modules; Honeywell S86, S90, S8600 and S8610; Robertshaw SP715, SP715A, SP735, SP735L; Johnson GSA, G60, G65, G600, G770.
S8610/S8910 SERIES INTERMITTENT PILOT AND HOT SURFACE MODULES
INTERMITTENT IGNITION
HOT SURFACE IGNITION
S87 SERIES IGNITION CONTROL MODULES
Order No. ApplicationLockout Timing Use With Description
S87D1012 Uses separate electrodes for spark ignition and flame sensing. Includes optional alarm output. For direct replacement of S825C,D
11 seconds Q347A Spark Igniter and Q354A Flame Sensor
For use with any gas control for direct spark ignition application that is rated at 2.0A or less. Includes optional alarm circuit.
DIRECT SPARKSolid state, low voltage DSI control modules for use on gas-fired furnaces, boilers and heating appliances. Use with Q347A Spark Igniter and Q354A Flame Sensor
S443A MANUAL POTENTIOMETERS
Order No. Application/Description Resistance Use With
S443A1007 Manual or automatic potentiometer 135 ohm
30112A potentiometer for S443 135 ohmAccessories
RELAYSCompatable with Modutrol IV motors. Suitable for series 90, M745 and M765 motors controlled by 135 ohms slidewire inputs. Dpst toggle switch allow selection of automatic or manual control. Surface mounted. Conduit outlet on each side of case. Screw terminals. Scale marked OPEN-CLOSED.
Mod III and Mod IV motors controlled by 135 ohm slidewire inputs
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 135
4
______________________________ HON EYWELL
T675, T678 CONTROLLERS
Order No.Control Range
Capillary Length and Material
Max. Temperature Differential Switching
T675A1136 0-100oF. 20' copper 125oF. 1oF. fixed See note 1
T675A1425 55-175oF. 20' copper 200oF. 3.6-12oF. Adj. See note 1
T675A1508 0-100oF. 5' copper 125oF. 3-10oF. Adj. See note 1
T675A1532 160-260oF. 5' copper 280oF. 3-10oF. Adj. See note 1
T675A1540 55-175oF. 5' copper 200oF. 3.6-12oF. Adj. See note 1
T675A1565 0-100oF. 20' copper 125oF. 3-10oF. Adj. See note 1
T678A1437 0-100oF. 5' copper 125oF. Each switch fixed at
3oF. Adj. differential between switches 3-
10oF.
See note 2
Electrical Ratings: Full load 8A @ 120 Vac; 5.1A @ 240 Vac; 4.2A @ 277 Vac1 Switching spdt switch breakes R-B and makes R-W at set point on temperature rise.
REMOTE BULB THERMOSTATS REGULATE TEMPERATURE OF AIR OR LIQUIDS IN DUCTS, PIPES, TANKS AND BOILERS
2 Switching: Two spdt switches operating in sequence. Right switch breaks R-B and makes R-W at set point on a temperature rise. Left switch breaks R-B and makes R-W if temperature continues to rise through interstage differential.
Order No. Model No.
Switching Action
Control Range
SPECIAL ORDER T451A3005 Spst 44-86oF.
T651A3018 T651A3018 Spdt 44-86oF.
50/60 Hz 120V 208V 240V 277VFull Load 9.8A 5.6A 4.9A 4.2ALocked Rotor 58.8A 33.6A 29.4A 25.2APilot Duty
Resistive 19ANI
Heating Only 2.5kW 4.5kW
T451, T651 3000 SERIES LINE VOLTAGE THERMOSTATS
5kW
The T451 provides precision line voltage control of motor-rated electric, gas or oil heating equipment. The T651 provides direct, accurate line voltage control of inductively-rated heating, ventilating, or cooling equipment used in commercial or industrial environments. Both models feature a vapor-filled dual diaphragm.
Description
Makes on temperature fall. Heating only.
Heating/cooling thermostat.
ELECTRICAL RATINGS:
125VA
22A Non Inductive
Order No. Model No.
System Switches
Fan Switches
Special order T6069A4010 Heat-Off-Cool Hi-Med-Lo
Special order T6069B4018 Heat-Off-Cool Hi-Med-Lo
Special order T6069C4016 Heat-Off-Cool Hi-Med-LoSpecial order T6069D4014 On-Auto-Off Hi-Med-Lo
A B C D
X X X 8X X X 8
X8+13
X X X 8+8X X X 8+8
X8+13
T6069
Cycled fan for 4-pipe system.
Constant or cycled fan for 2- pipe system.
T6069 FAN COIL THERMOSTATS
Circuit Load (FLA)
120V 50/60
Hz
ELECTRICAL RATINGS: Thermostat and manual switch
Fan Mode
The T6069 thermostats control line voltage valves and/or blower motors on fan coil units in manual or automatic changeover cooling/heating systems. They feature separate fan and system manual switches.
Description
Constant or cycled fan for 2-pipe system.
Now available by special order - Digital Line Voltage and Low Voltage Fan Coil Thermostats
Constant fan for 4-pipe system.
Auto
On
Fan+CoolFan+Heat
Fan+Res.Heat (N.I.)
Fan+CoolFan+Heat
Fan+Res.Heat (N.I.)
-
136 www.federalcorp.com
4
HONEYW ELL______________________________
For 24 volt heating or cooling applications.
Order No. Application Scale Range Heat Anticipator Positive Off
T822D1032 For low voltage control 55-95oF. Yes1 Yesof heating systems
1 Adjustable. 0.18-0.8A @ 30 Vac
T822 THERMOSTATS
T921 PROPORTIONAL THERMOSTATS
Order No. Application Range
Accessory Faceplate Adapter
for Mounting Horizontally
Throttle Range (Fixed)
Auxilliary Switch Remarks
T921A1191 THERMOSTAT 1 POT 56-84oF. 135135A 2.5oF. None Includes slotted sides and an add-on faceplate to allow thermostat to be mounted horizontally.
LOW VOLTAGE, 3-WIRE CONTROLLER FOR VALVE MOTORS, DAMPER MOTORS, AND BALANCING RELAYS IN HEATING OR COOLING SYSTEM APPLICATIONS
T775 ELECTRONIC REMOTE TEMPERATURE CONTROLLERS
SPECIFICATIONS
Setpoint Range: -40-248oF
Sensor: Platinum sensor accurate up to 1000 feet from the controller
Order No. Description ReplacesRelay
Outputs
Analog Outputs 4/20 mA, 0-10 Vdc, 2-10 Vdc,
& Series 90
Floating
Output1
Sensor Inputs
Available
# Sensors
Included2
T775A2009 Standard T775A1001 1 SPDT 1 1
T775B2016Standard-NEMA
4X 2 SPDT 1 2 1
T775B2032 StandardT775A1009, T775B1000 2 SPDT 1 2 1
T775B2040 Standard
T775A1027, T775A1035, T775B1018, 4 SPDT 2 2 1
T775M2048 Modulating
T775E1015, T775E1023, T775E1056, 2 SPDT 2 2 1
T775R2027 Reset Option
T775J1043, T775J1050, T775J1068 2SPDT 2 2 2
T775U2006
Universal-humidity,
pressure, etc.
H775A1006, H775A1022, H775A1048, H775A1063, H775B1005, H775C1004, H775D1003, H775E1002 2 SPDT 1 or 2
2 (4 or 8 more relays
possible with T775S2008
relay expansion module(s).
Electrical Rating: Voltage input: 24/120/240 Vac, 50/60 Hz
Order No.
50021579-001
T775SENSSTRAP
T775SENSWT
FOR HEATING, COOLING OR HEATING/COOLING APPLICATIONSThe T775 electronic stand-alone controllers provide remote sensing of temperature with switched and/or proportional outputs to various types of loads. They feature an easy-to-use LCD graphical interface, configurable integral and derivative times, and an internal time clock. A Universal Model can control pressure, humidity, or any medium with an analog input. Reset models feature a simplified setup. Models with NEMA 4X enclosure are also available.
1 One floating output eliminates two relay outputs.2 50021579-001 included with non-NEMA 4x models and T775SENSWR included with NEMA 4x models.
Strap on sensor with wiring enclosure, -40 to 250 Fo
Water tight sensor with 6' leads, -40 to 270 Fo
ACCESSORIES
Description
Standard platinum indoor sensor, -40 to 350 Fo
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 137
4
______________________________ HO NEYWELL
T6054A SERIES INDUSTRIAL LINE VOLTAGE THERMOSTATS
Order No. Switching Temperature Range Differential System Controlled Dimensions
T6054A1005 Spdt, can be used in heating/cooling systems with external changeover switch.
30-100 F. 3.5oF., fixed Heating-cooling 7 1/4" x 2 5/8" x 2"
120Vac 240Vac7.4 3.7
44.4 22.210 5Resistive
PROVIDE SPDT HEAVY-DUTY, LINE VOLTAGE TEMPERATURE CONTROL IN VENTILATION, HEATING OR COOLING SYSTEMS
Electrical Ratings (Amps)Full LoadLocked Rotor
T991 PROPORTIONAL TEMPERATURE CONTROLLERS
Order No.Set Point
Range
Adjustable Throttle Range
Capillary Length & Material Bulb
Potential Resistance Includes
T991A1012 0-100oF. 3-30oF. 20' copper 1/2"x4 3/16" 135 ohm _
T991A1061 160-260oF. 3-30oF. 5' copper 1/2" x4 3/16" 135 ohm _
T991A1194 55-175oF. 3.5-36oF. 20' copper 1/2" x3 9/16" 135 ohm _T991A1244 55-175oF. 3.5-36oF. 5' copper 1/2" x3 9/16" 135 ohm 107324A Duct
Bulb Holder
FOR MODULATING CONTROL OF WATER OR AIR TEMPERATURE IN DUCTS, TANKS AND SIMILAR APPLICATIONS
Order No. Model No. Application/Description Use With
H107408 107408 4 oz. Heat-conductive compound for coating bulb to improve thermal response of bulb in immersion well.
Temperature controllers with immersion style bulbs
PARTS AND ACCESSORIES FOR REMOTE BULB TEMPERATURE CONTROLS
T6031 SERIES REMOTE BULB TEMPERATURE CONTROLS
Order No. Application Thermostat TypeTemp. Range Differential
Capilliary Length
T6031A1029 AQUASTAT - 30+90oF Refrigeration1 -30-90oF 3.5-16oF adj. 8'
T6031C1009 AQUASTAT 40-180 oF Aquastat controller/ambistat2 40-180oF 2oF mid-scale 5 1/2'1 SUPER TRADELINE model. Includes bulb holder and mounting plate. Ambient compensated for duct, tank, freezer or cooler.2 TRADELINE model. Includes 107324A bulb holder. Ambient compensated. High limit. For agricultural and industrial applications.
SPDT SWITCH ACTION
T6051 SERIES HEAVY DUTY LINE THERMOSTATS
Order No. Application Switching Mounting Differential Range RemarksT6051A1016 Heating/cooling; with
resistive rating for electric heat applications.
spdt Vertical or horizontal mounting on standard outlet box, or on Q651 Subbase.
1.0oF. 50-80oF. Standard cover-135535B
T6051B1006 Heating/cooling spdt Vertical mounting on explosion-proof housing.
1.0oF. 46-84oF. With explosion-proof housing.
Heavy duty line voltage thermostats are used to control fan coils, fans, motor starters, valves, contactors and circulator motors in heating and/or cooling systems.
Electrical Ratings--Full load: Heating T6501: 16A @ 120 Vac, 8A @ 240 Vac; Cooling T6051: 8A @ 120 Vac, 4A @ 240 Vac
-
138 www.federalcorp.com
4
H ONEYWELL ______________________________
V5011A,C,F &G,V5013 REPACK KITS1
Order No. Model No. Use With Valve Size Stem Size
14003294002 14003294-002 V5011C & G; V5011A & V5013 valves with six-sided bonnets; not to exceed 150 psi
1 1/4" or less 1/4"
14003294004 14003294-004 V5011A & F, V5013A & F 1 1/4" or less 1/4"14003295002 14003295-002 V5011C & G, 1 1/2" to 3" 3/8"14003295004 14003295-004 V5011A & F, V5013A & F 1 1/2 to 3" 3/8'1Not for use with V5011N and V5013N valves
Order No. Model No. Use With Valve Size Stem sizeSpecial Order 0901786A V5011N & V5013N 1 1/4" or less 1/4"Special Order 0901787A V5011N & V5013N 1 1/2" & 2" 3/8"
V5011N & V5013N REPACK KITSPacking kit contains packing wafers, washer, spring, and o-ring.
Packing kit contains packing, packing follower, follower spring, and packing lubricant.
V5013 3-WAY VALVES
Order No. Body Size (NPT) Cv Pipe Connection Lift Seat Plug
V5013N1055 3/4" 7.3 Screw 3/4" Brass; integral BrassV5013N1063 1" 11.7 Screw 3/4" Brass; integral BrassV5013N1071 1 1/4" 18.7 Screw 3/4" Brass; integral BrassV5013N1089 1 1/2" 29.3 Screw 3/4" Brass; integral BrassV5013N1097 2" 46.8 Screw 3/4" Brass; integral Brass
For use with Honeywell Actuators and valve linkages. 2 inlets; 1 outlet. Must not be used to divert flow from a common inlet to 2 outlets.
V5011 SINGLE-SEATED VALVES
Order No. Old Model No. Body Size (NPT) Cv Pipe Connection Lift Use With
V5011N1040 V5011F1139 1/2" 4.7 Screw 3/4" WaterV5011N1057 V5011F1147 3/4" 7.3 Screw 3/4" WaterV5011N1065 V5011F1154 1" 11.7 Screw 3/4" WaterV5011N1073 V5011F1162 1 1/4" 18.7 Screw 3/4" WaterV5011N1081 V5011F1170 1 1/2" 29.3 Screw 3/4" WaterV5011N1099 V5011F1188 2" 46.8 Screw 3/4" WaterV5011N2055 V5011G1194 3/4" 7.3 Screw 3/4" SteamV5011N2063 V5011G1202 1" 11.7 Screw 3/4" SteamV5011N2071 V5011G1210 1 1/4" 18.7 Screw 3/4" SteamV5011N2089 V5011G1228 1 1/2" 29.3 Screw 3/4" SteamV5011N2097 V5011G1103 2" 46.8 Screw 3/4" Steam
For use with Honeywell Actuators and valve linkages. Two-way straight through valve body. Equal percentage flow characteristic for water and linear flow characteristic for steam. Suitable for two-position and modulating service. Brass body. Stainless steel seat. Direct acting operation--push down to close
V4043 ZONE VALVE
Order No. Size CV Maximum Close-off Pressure
V4043A1010 1/2" sweat 3.5 20 psi
MOTORIZED VALVE, 120/60, CLOSED WHEN DE-ENERGIZED
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 139
4
______________________________ HO NEYWELL
SPECIFICATIONSBody pattern: Straight-through with 1/2" inlets and outlets.Pilot gas outlet: Compression fitting for 1/4" OD tubing.
Pressure tapping: 1/8" NPT with plug.
Order No.Inlet/Outlet
Size
AGA Certified
Capacity1Pressure Regulator
Setting Type of Gas Includes
VR8200A2132 1/2" x 1/2" 130cfh 3.5" WC Natural 1/2" x 3/8" reducer bushing; 393690-14 bag assembly-3/4" straight flange with O-ring, screws and wrench.
1 Capacity based on 1000 BTU/ cu. Ft., 0.64 sp. gr. natural gas at 1" WC pressure drop
VR8200A CONTINUOUS PILOT, DUAL AUTOMATIC VALVE, COMBINATION GAS VALVES
Pressure rating: 1/2 psi inlet pressureThermostat heat anticipator setting: 0.5A
Controls include manual valve, two automatic operators, servo pressure regulator and pilot adjustment. Meet codes requiring dual safety shutoff. Compatible with ECO connector.
COMBINATION GAS CONTROLS FOR USE IN 24 VAC, GAS-FIRED, STANDING PILOT APPLIANCES
SPECIFICATIONSBody pattern: Straight-throughPilot gas outlet: Compression fitting for 1/4" OD tubing.
Pressure tapping: 1/8" NPT with plug.
Order No. Openings Opening Characteristics Capacity1 Temperature Range
VR8300A3518 1/2" x 3/4" Standard opening 190 cu.ft/hr 0-175oF.
VR8300A CONTINUOUS PILOT, DUAL AUTOMATIC VALVE, COMBINATION GAS VALVES
1 Includes one 3/4" x 1/2" reducer bushing; 393690-14 bag assembly--3/4" straight flange with O ring, screws and wrench; 393200 ECO adapter; Q340 (36") thermocouple with adapters; and 393691 Natural LP gas conversion kit.
Thermostat heat anticipator setting: .05APressure rating: 1/2 psi inlet pressure
Controls include safety shutoff, manual valve, two automatic operators, pressure regulator and pilot adjustment.
FOR USE IN 24 VAC GAS-FIRED HEATING APPLIANCES
SPECIFICATIONS
Supply voltage: 24 Vac @ 60 Hz Ambient temperature range: 0-175oF.Wiring connection: 1/4" male quick-connects Pressure rating: 1/2 psi inlet pressurePilot gas outlet: Compression fitting for 1/4" OD tubing.
Order No. Inlet-Outlet cfh m3/hrPress. Regulator
SetingPress.
Regulator Includes
VR8304M4507 3/4" X 3/4" 300 cfh 8.5 3.5" WC Standard Two 3/4" X 1/2" reducer bushings2, 393691 Natural to LP gas conversion kit.
2 Use of 3/4" x 1/2" reducer bushing reduces capacity to 270 cfh.
Note: Mounting 0-90o in any direction from upright position of gas control knob, including vertically.
VR8304A INTERMITTENT PILOT, DUAL AUTOMATIC VALVE, COMBINATION GAS CONTROLS
1 Capacity based on 1000 BTU/ cu. Ft., 0.64 sp. gr. natural gas at 1" WC pressure drop
Capacity1
Pressure tapping: 1/8" NPT with plug
Combination gas control for use in 24 Vac, gas-fired, intermittent pilot appliances with capacities from 30 to 415 cfh. Controls include safety shutoff, manual valve, two automatic operators, pressure regulator and pilot adjustment. Use with S86F,H; S860D; S8600F,H; S8610 and S90A,B Control Modules. Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends. Diaphragm-operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted.
-
140 www.federalcorp.com
4
HO NEYWELL_______________________________
Y8610U UNIVERSAL RETROFIT INTERMITTENT PILOT GASBURNER IGNITION SYSTEMS
Current rating: 0.7A
Order No. Control ModuleCombination Gas Control
Capacity
(BTU/hr1) Inlet-OutletReducer Bushings
Temperature Range Type of Gas
Y8610U6006 S8610U30092,3 VR8304M3558 270,000 1/2" x 3/4" Two 3/4" x 1/2" -40 - 175o F Nat. Or LP1 0.64 sp. Gr. Nat. Gas at 1" WC pressure drop.2 With 100% pilot gas shutoff and lockout; 90 sec. Max. Timed trial for ignition3 Includes automatic vent damper plug.
FOR CONVERTING CONVENTIONAL STANDING PILOT SYSTEMS TO INTERMITTENT
Contains
For use with 24 Vac gas-fired atmospheric furnaces, boiler and heating appliances. Includes: 393691 LP gas conversion kit; 392431 igniter-sensor assembly. Includes ceramic-insulated kanthal rod that attaches to the existing pilot burner in place of the thermocouple; 394800-30 ignition cable; 393690-14 flange assembly. Includes 3/4" straight flange with O ring, 9/64" hex screws and wrench; wiring harness; and reducer bushings for gas control.SPECIFICATIONSVoltage and fequency: 24 Vac (nominal) @ 60 Hz Thermostat anticipator setting: 0.7A
W136A TEST METERS
Order No. 0-300 Vac 0-150 Vdc Used With
W136A10451 20,000 40,000 Flame Safeguard Controls
COMBINATION AC/DC VOLTMETER AND DC MICROAMMETER USED TO TEST BURNER EQUIPMENT
Sensitivity (ohms/volt)
1 Includes Cable Connector and Two push-on alligator clips.
Order No.
Inlet-Outlet Size(in.)
Capacity, A.G.A.
Certified
Pressure Regulator
Setting Type of Gas
Type of Pressure Regulator Includes
VR8345M4302 3/4 x 3/4 300 cfh 3.5" wc Natural or LP w/adapter
Standard Two 3/4" x 1/2" NPT bushings and one 1/2" x 3/8" NPT
Universal electronic iginition combination gas control for use with direct spark ignition, hot surface ignition or intermittent pilot ignition in 24 Vac, gas-fired appliances, with capacities from 30-415 cfh. VR8345 control replaces the following Honeywell and competitive combination gas controls for applications requiring a minimum capacity of 30 cfh and a maximum capacity of 415 cfh. Honeywell VR8204A,M; VR8205A,M; VR8304M, VR8305M; White Rodgers 36E01, 36E36 series(standard opening); Robertshaw 7100DER, 7200DER, 72001DER series.
VR8345M4302 UNIVERSAL ELECTRONIC IGNITION COMBINATION GAS CONTROL
VS820 FAMILY COMBINATION GAS CONTROLS
Mounting: 0 to 90 degrees in any direction from the upright position of the gas control knob.
Body Pattern: Straight-through. Pressure Rating: 1/2 psi inlet pressure
Pressure Tapping: 1/8 in. NPT with plug Pilot gas outlet: Compression fitting for1/4 in. tubing
Order No. Application DescriptionInlet-Outlet
Size Capacity1
Pressure Regulator
Setting1Type of
Gas
Includes Reducer
Bushings2
VS820A1047 Self-powered automatic control. Use with 750 mV pilot generator.
Color-coded red to identify Powerpile operation. Red pigtail power unit lead.
1/2" X 3/4" 250 cfh 3 1/2" WC Natural One 3/4" X 1/2" One 1/2" X 3/8"
Provide complete control of continuous pilot gas-fired central furnaces and boilers. Easy to install, adjust and service; all adjustments and connections are accessible from top of control. Complete safety shutoff on pilot flame failure. LITE-RITE (OFF-PILOT-ON) lightning sequence.
1. 1,000 BTU/cu.ft., 0.64 specific gravity. Natural gas @ 1" WC pressure differential.
SPECIFICATIONS
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 141
4
____________ HO NEYWELL FLAME SAFEGUARD
C7005 FLAME RECTIFIER PILOTS
Order No. Application Ignition Electrode
C7005B1035 For automatic electrically ignited gas applications Yes
Order No. Description101738B Flame rod assembly
Combination rectification flame rod and pilot burner for use with suitable relay on industrial or commercial gas or gas pilot-ignited oil burners.
REPLACEMENT PARTS
C437 GAS/AIR PRESSURE SWITCHES
Order No. Pressure Range1 Differential2
Max. Surge Pressure
Micro- Switch
Switch Action (Breaks)
Manual Reset (Lockout on Switch Break) Replaces
C437D2003 1-26" wc 1 3/4" 5.0 psi spst Rise Yes C437D1005C437D2029 1-10 psi 1 psi 30.0 psi spst Rise Yes C437D1021C437E2002 1-26" wc 1 1/4" 5.0 psi spst Fall Yes C437E1004
1 Equivalent SI metric units are listed for each pressure range in Honeywell catalog2 Differential at midscale. Subtractive for C437D,J,G. Additive for C437E,F,H,K. Equivalent SI metric units are listed for each pressure range in Honeywell catalog.
PRESSURE OR DIFFERENTIAL--PRESSURE LIMIT CONTROLS FOR INDUSTRIAL GAS SYSTEMSUse C437 for spst switching. Compensate for momentary surges in gas pressure with a restrictive orifice in inlet pressure channel on the models with pressure range of 1 to 26 in. wc (0.25 to 6.5 kPa). Resume operation by manually resetting when using lockout application models. Impede tampering and provide dust-resistant operation with enclosed setting. Increase strength of control diaphragm with Buna-N fiber-reinforced material. Clear glass cover allows observation of interior mechanism to aid in setting and checkout.
Order No. Model No. Description
H106729 106729 GLASS LENS
REPLACEMENT PARTS
C6097A, B PRESSURE SWITCHES
Order No. Superscedes Connection
Operating Presssure
RangeMax. At Min.
Stpt.Max. At Max.
StptDifferential
Type
Max. Rated Pressure
(continuous psi)
Manual Reset
C6097A1004¹ 1/4" NPT .04-5" wc 0.16" wc 0.24" wc Additive 2.9 No
C6097A10121 C645A1030 1/4" NPT 3-21" wc 2.4" wc 4.2" wc Additive 4.3 Yes
C6097A10201 Flange 3-21" wc 2.4" wc 4.2" wc Additive 4.3 Yes
C6097A1053¹ 1/4" NPT 3-21" wc 0.24" wc 0.48" wc Additive 5 No
C6097A1103¹ Flange 1.5-7psi 1.1 psi 1.4 psi Additive 9.3 Yes
C6097A1111¹ 1/4" NPT 1.5-7 psi 1.1 psi 1.4 psi Additive 9.3 Yes
C6097B10282 C645B1013 1/4" NPT 3-21" wc 2.4" wc 4.2" wc Subtractive 4.3 Yes
C6097B10362 Flange 3-21" wc 2.4" wc 4.2" wc Subtractive 4.3 Yes
C6097B1051² 1/4" NPT 1.5-7 psi 1.1 psi 1.4 psi Subtractive 9.3 Yes
C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure. For use with natural gas, liquid propane(LP) gas, or air. Diaphragm-actuated safety-limit switch. C6097A models break control circuit at setpoint on pressure fall. C6097B models break control circuit on pressure rise. Removable transparent cover protects scaleplate and adjusting knob.
1 C6097A breaks a circuit on a pressure fall.2 C6097B breaks a circuit on a pressure rise.
Reset Differential
-
142 www.federalcorp.com
4
HO NEYWELL FLAME SAFEGUARD___________
Order No. Model No. Description
H136733 136733 Heat Block 1/2" male by female thread
ACCESSORIES
C7027A MINIPEEPER ULTRAVIOLET FLAME DETECTORS
Order No. Ambient Temp. Range Lead Length
C7027A1023 0-215oF. 8'C7027A1031 -40-215oF. 8'
C7027A10491 0-215oF. 8'
C7027A10721 40-215oF. 8'
C7027A10802 0-215oF. 8'1 1/2" NPT threaded spud connector
COMPACT FLAME DETECTOR FOR USE WITH FLAME SAFEGUARD CONTROLS WITH ULTRAVIOLET AMPLIFIERS.Use on Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection.
2 Includes 136733 Heat Block and 390427B Bushing , 1/2" x 3/8" to replace Fireye UV2 sensor when replacing acomplete Fireye to Honeywell system.
Order No. Description
H113228 Ultraviolet sensing tube for solid state models.
ACCESSORIES
C7012 PURPLE PEEPERTM ULTRAVIOLET FLAME DETECTORS
Order No. Application/Description
Voltage (50/60 Hz)
Pipe Mounting Size Housing
C7012A1145 Use with Honeywell rectification-type flame safeguard controls
EXCEPT Dynamic Self Check models 1. Field-replacable viewing window and ultraviolet sensing tube.
120 VAC 3/4" NPT Violet, cast-
aluminum cover2
C7012E1104 Use with only Dynamic Self Check flame safeguard
controls1.Field-replaceable viewing window and ultraviolet sensing tube, self-checking coil and shutter.
120 VAC 3/4" NPT Violet, cast-
aluminum cover2
C7012E1112 Use with only Dynamic Self Check flame safeguard
controls1.Field-replaceable viewing window and ultraviolet sensing tube, self-checking coil and shutter.
120 VAC 1" NPT Violet, cast-
aluminum cover2
1Dynamic Self Check models are R4138A/B,R4181A, R4126/R4127 with R7256B, R4150 with R7253B, and R4057C/D/E,R4138C/D, or R4140 with R7247C amplifier.2 Mounting flange (with heat block) and faceplate are separate to provide heat insulation and seal-off. Meets NEMA 4 standards.
Solid state electronic flame detectors for use with appropriate Honeywell relays and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels.
Order No. Description
C7008A1174 12" Flame Rod
C7008 FLAME ROD AND HOLDERMiniature "spark plug" type flame rod holder with threaded base, snap-on cover and Kanthal A-1 Flame Rod. Use only with gas. Installs with or without cover. Use with Honeywell Flame Safeguard controls requiring rectification-type flame detection.
C7007 FLAME ROD HOLDERS
Order No. Description Mounting
C7007A1001 FLAME ROD HOLDER 1/2" male NPT
Used to apply flame rod in gas-fired system controlled by recitification type flame safeguard control. Use with pressurized fire boxes. Hold flame rods firmly over the pilot or burner with a chuck and setscrew arrangement.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 143
4
C7927A SOLID STATE ULTRAVIOLET FLAME DETECTORS
Order No. Ambient Temp. Range Lead Length
C7927A1016¹ 40-200oF. 96"¹ Use with R7851B Amplifier
The Solid State Ultraviolet Flame Detector detect the ultraviolet radiation emmited by combustion flames.The flame detectors are used with 7800 SERIES flame safeguard controls with R7851B amplifiers. Mounts on a 1/2 in. sighting pipe by using an integral collar. Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed.
Order No. Use WithC7915A1028 R7852
C7915A INFRARED(LEAD SULFIDE PHOTOCELL) FLAME DETECTORUsed for combination or dual-fuel applications. Mounts easily on a standard 3/4" sight pipe. Works where flame rod or rectifying photocell mounts are difficult to apply. Includes lead sulfide cell 32007255-001, bushing with magnifying lens,
orifice plate 1051342 heat block 1050613 and reducer bushing 390427A4.
Lead Length1
48"
2With 0.125" diameter hexagonal orifice to reduce the detector field of view.3To insulate the detector from sight pipe temperatures higher than -40ºF - 125ºF and up to 250ºF.4To mount the detector on a 1/2" sight pipe, specifically to replace Fireye™ lead sulfide infrared flame detectors.
1Models with 30" and 96" Lead Lengths available by Special Order.
C7035A MINIPEEPER ULTRAVIOLET FLAME DETECTORS
Order No. Ambient Temp. Range Lead Length
C7035A1023 0-250oF. 6'
C7035A1031 40-250oF. 6'
Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers. Mounts on a 1 in. sighting pipe by using an integral collar. Protects the sensing tube with a shield.Meets outdoor raintight requirements of Underwriters Laboratories Inc., NEMA 3 and NEMA 4. Wires in parallel for difficult sighting applications.Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed. Field-replaceable ultraviolet sensing tube.
Order No. Temp. Range Description
129464M 0-250oF Ultraviolet sensing tube.
129464N -40-250°F Ultraviolet sensing tube.
REPLACEMENT PARTS
Order No. Description
C7061A1012 Housing meets NEMA 4 enclosure standards. Oscillating shutter interrupts ultraviolet radiation reaching UV sensor 12 times per minute to provide the UV sensor tube checking function.
C7061 DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTORDynamic self-checking flame detector used with R7861 Dynamic Self-check Amplifiers for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels.
___________ HO NEYWELL FLAME SAFEGUARD
-
144 www.federalcorp.com
4
HO NEYWELL FLAME SAFEGUARD___________
L404A-D,F; L604 PRESSURETROL® CONTROLLERS
Order No.Operating Range
in psi
Subtractive
Differential in psi 1
Maximum diaphragm
pressure in psiIncludes
Siphon LoopSwitch Type Switch Action 3
L404F1060 2-15 2 to 6 25 Yes spdt R-W makes R-B breaks
L404F1078 5-50 6 to 14 85 Yes spdt R-W makes R-B breaks
L404F1102 10-150 10 to 22 225 - spdt R-W makes R-B breaks
L604A1169 2-15 2 to 6 Yes spdtR-W makes R-B breaks
3 On pressure rise
Provide operating control, automatic or manual reset limit protection for pressure systems up to 300 psi. Use with steam, air, noncombustible gases, or other fluids noncorrosive to pressure sensing element. Adjustments are made by screws on top of the case. Mount using 1/4" NPT female threads or surface mount through base of case. Models are mercury free, automatic reset and have stainless steel diaphragms.
1 Differential at midscale
L91 PROPORTIONAL PRESSURETROL CONTROLLERSMODULATING PRESSURE-OPERATED HIGH LIMIT CONTROL FOR STEAM SYSTEMS
Differential at Midscale
Order No. psi kPa psi kPa psi kPa adj.
L91B10351 0-15 0-103 20 138 1-12 7-83 Yes 1
L91B10502 5-150 34-1034 225 1151 5-23 34-159 Yes 11 Pipe connection: 1/4 NPT, male fitting (requires standard pipe coupling to mount on siphon loop).2 Pipe connection: 1/4 NPT female fitting (can be mounted directly on siphon loop).
Screw adj. top of case
Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases. Use with steam, air, noncombustible gases, or other fluids non-corrosive to the brass or phos-bronze (300 psi models) bellows. Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (10-300 psi models)
Control Range Max. Surge Pressure Number Potentio-meters
Main Setting Means
CR7890B INTEGRATED BURNER CONTROL
Item No. Description
CR7890B1019 Integrated Burner ControlSpecial Order
Power LED blinks a fault code when device is in ALARM. Optional keyboard display module (KDM) provides additional troubleshooting and diagnostic information.
The Honeywell CR7890B integrated burner control is a micro-processor-based control for automatically fired gas, oil, or combination fuel single burner applications. The CR7890B control consists of a self contained relay module, amplifier and a shutter type solid state ultraviolet detector for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels. Options include the S7800 keyboard display module (KDM), for use during burner setup or troubleshooting. Functions the CR7890B provides include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.Features
CR7890B1019 uses Brad Harrison® 3R9006A20A120 connector.
-40ºF (-40ºC) rated ultraviolet sensing tube. High pressure 50 psi (345 kPa) quartz viewing window, magnifying lens and anti-vibration mount are available as accessories. Housing meets NEMA 4 enclosure standards (NEMA 1 when access cover s used). Protective heat block built into mounting flange.
Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the UV sensor checking function. Amplifier circuitry components are checked from the microprocessor in the CR7890B Device can be mounted horizontally, vertically or at any other angle. The device has faceplate alignment and integral locating reference points to assure proper shutter mechanism operation. Quartz viewing window is field replaceable.
A swivel mount is available to facilitate flame sighting.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 145
4
Order Number Switching Action
L4079B1033 2 - 15 psi14-103
kPa 25 psi 172 kPaSPDT break on pressure rise
L4079B1041 10 -150 psi70-1035
kPa 225 psi 1550 kPaSPDT break on pressure rise
HIGH PRESSURE LIMIT SWITCHES High pressure limit switches which break electrical circuits when pressure rises to a preset value.Used with steam, air, noncombustible gases, and fluids noncorrosive to the sensing element.
L4079 PRESSURETROL® LIMIT CONTROL - MANUAL RESET
Operating Pressure Range
Maximum Sustained
Operating Pressure
Sensor Element: Stainless Steel diaphragm
Siphon Loop Included
Switch Contact Ratings:
120 Vac: 9.8 AFL, 58.8 ALR
240 Vac: 4.9 AFL, 29.4 ALR
Q179A FLAME RECTIFIER GAS PILOTS
Order No. Application Electrode Tip Style
Q179A1050 For intermittent or interrupted ignition. Has both flame electrode and ignition electrode.
Flame and ignition T
Q179A1126For intermittent or interrupted ignition. Has both flame electrode and ignition electrode. Flame and ignition I
Combination rectifying flame rod and pilot burner for use with suitable electronic relay on industrial or commercial gas burners or gas pilot-ignited oil burners.
PARTS AND ACCESSORIES FOR Q179AOrder No. Application/Description Tip Style
133451A Flame rod and insulator assembly T
Order No. Application Mounting Target Mount
Q179C1009 Combination pilot burner and rectifying flame rod flame detector. With ignition electrode; suitable for use on interrupted or intermittent electrically ignited gas pilot applications. Use with Q624 or other suitable ignition transformer.
End Dual wing-rear
Gas pilot burner assemblies prove pilot flame on industrial or commerical gas burners or gas pilot-ignited oil burners.
Q179C MINIATURE RECTIFICATION PILOTS
Q314 PILOT BURNERS
Order No. Type of Gas
Mounting
Bracket1 Includes
Q314A4586 Natural, LP B Natural gas orifice; LP gas orifice; 1/4" cc inlet fitting; special mounting bracket with screws for converting 'B' bracket to 'A'.
1 See diagrams in Honeywell catalog.
NONPRIMARY-AERATED, INSERT ORIFICE-TYPE PILOT BURNERS
Q345A IGNITER-SENSORS
Order No. Tip Style Type of GasMounting Bracket Includes
Q345A1305 Sprays Straight Natural B 1/4" cc inlet fitting
Used with the S86 in intermittent pilot systems
NONPRIMARY-AERATED COMBINATION PILOT BURNER AND IGNITER
___________ HO NEYWELL FLAME SAFEGUARD
-
146 www.federalcorp.com
4
RA890 SERIES PROTECTORELAY PRIMARY CONTROLS
Order No. Voltage Safety Switch Timing Flame Failure Response Time1
RA890F SERIES2, ALARM
RA890F1288 120V @ 50/60 Hz 15 seconds 3.0 secondsRA890F1346 120V @ 50/60 Hz 30 seconds 3.0 seconds
RA890G SERIES3
RA890G1260 120V @ 50/60 Hz 15 seconds 3.0 seconds1 3 second response is recommended for nonrecycling ignition cutoff service2 For use with flame rods, rectifying photocells and C7012A,C Purple Peeper Ultraviolet Flame Detectors
Note: For new installations, also specify Q270A1024 base
Nonprogramming primary control provides solid state, electronic, flame safe-guard protection for industrial and commercial single or dual fuel burners. With isolated spdt alarm terminals. NOTE: Honeywell recommends upgrade to RM7890 Series.
3 Used for interrupted ignition with intermittent pilot on gas burners; interrupted or intermittent ignition on oil burners. Uses C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector for flame sensing.
HO NEYWELL FLAME SAFEGUARD___________
Order No.
Number (see ordering table) Type
Flame Failure Response Time Use With
R7289A1004 1 Rectification(green) 3.0 seconds Rectifying photocell, flame rod or C7012A,C Purple Peeper Ultraviolet Flame Dectector.
R7290A1001 2 Ultraviolet(purple) 3.0 seconds Use with C7027A, C7035A or C7044A Minipeeper Ultraviolet Flame Detector
ACCESSORIES FOR R4795
R4795 PRIMARY CONTROLS
Order No.
Voltage (50/60 Hz)
Alarm Contacts
(spdt) Mounting Base Plug-in Amplifier1 Plug-in Purge Timer
R4795A1016 120Vac Yes Q270A1024 permits recessed or surface
mounting.
1 or 2 ST71A1000, 7 seconds ST71A1042, 10 seconds ST71A1018, 30 seconds ST71A1026, 60 seconds ST71A1034, 90 seconds
1 A number is listed for each amplifier in table below. These numbers correspond to those listed under "Plug-in Amplifier" in ordering.
PROVIDE SOLID STATE, ELECTRONIC, FLAME SAFEGUARD PROTECTION FOR COMMERCIAL AND INDUSTRIAL SINGLE OR DUAL FUEL BURNERS WITH PRE-IGNITION PURGE OF COMBUSTION CHAMBER.
Requried Components (Ordered Separately)
Q624 SOLID STATE IGNITION TRANSFORMERS
Order No. Application Voltage (60 Hz)Maximum
Output VoltagePrimary rating (@
120 Vac)
Q624A10141 Can be used to replace single electrode ignition transformers in interrupted gas or pilot applications. Prevents detection of ignition spark when properly applied in flame detection system with C7027 or C7035 Ultraviolet Flame Detector. Mounting plate designed to replace standard ignition transformers.
120 Vac 15,000V Peak 66 VA
IGNITE PILOTS ON COMMERCIAL OR INDUSTRIAL GAS BURNERS
1 With threaded terminal nut high voltage electrode.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 147
4
V48, V88 DIAPHRAGM GAS VALVES
Order No. Size cfh m3/hr Voltage Pressure
V48A2151 3/4" 668 18.9 120V @ 50/60 Hz 1/2 psiV48A2169 1" 1,021 28.9 120V @ 50/60 Hz 1/2 psiV48A2177 1 1/4" 2,100 59.5 120V @ 50/60 Hz 1/2 psiV48A2185 1 1/2" 2,400 67.9 120V @ 50/60 Hz 1/2 psiV48A2243 2" 4,178 118.3 120V @ 50/60 Hz 1 psiV88A1618 1" 1,021 28.9 24V @ 60 Hz 1/2 psiV88A1626 1 1/4" 2,100 59.5 24V @ 60 Hz 1/2 psiV88A1634 1 1/2" 2,400 67.9 24V @ 60 Hz 1/2 psiV88A1709 2" 4,178 118.3 24V @ 60 Hz 1 psi
Valve Capacities1
1 cfh Natural gas 1,000 BTU/cu.ft., 0.64 specific gravity, p.d. 1" WC (m3/hr Natural gas 37.3 MJ/m3, 0.64 specific gravity, p.d. 0.25 kPa).
SOLENOID-OPERATED DIAPHRAGM VALVES FOR CONTROLLING FUEL GASES
REPLACEMENT PARTSOrder No. Model No. Description Voltage
H116930 116930 Replacement coil for V88A 24V @ 60 HzH116931 116931 Replacement coil for V48A 120V @ 60 HzACCESSORIESH126590 126590 Adjustable bleed valve assembly
for opening speed control-
ACCESSORIES
Order No. Application/Description
H133569 Proof of closure switch7616BR Crank arm assembly for motor w/o tap
____________ HO NEYWELL FLAME SAFEGUARD
V4055 FLUID POWER GAS VALVE ACTUATORS
Order No. Description
Voltage (60
Hz)1 Opening Time1 Includes
ON-OFF FLUID POWER GAS VALVE ACTUATORS 2
V4055A1064 ON-OFF actuator.Normally used with V5055A,B valve bodies. Low Pressure.
120Vac 26 seconds Damper shaft.
V4055A1098 ON-OFF actuator.Normally used with V5055A,B valve bodies. Low Pressure.
120Vac 13 seconds Damper shaft.
V4055A1304 ON-OFF actuator.Normally used with V5055A,B valve bodies. Low Pressure.
120Vac 26 seconds Damper shaft and return spring intstalled.
V4055D1019 ON-OFF actuator.Normally used with V5055C
valve bodies. Low Pressure.3120Vac 13 seconds Damper shaft.
V4055G1004 Manually reset safety shutoff valve 120Vac 13 seconds Damper shaft.1 Can also be used at 50 Hz; however, opening time will increase by 20%.
3 Includes Factory Mutual "Proof of Closure" and UL "Valve Seal Overtravel Interlock" switch. Meets Factory Mutual and UL requirements when used with V5055C valve bodies.4 Provides manual reset, safety shut-off function as required on FM, IHEA-IRI and NFPA 86A,B,C industrial furnaces, ovens, and kilns. Mounts on V5055 valve. Indicator on valve and actuator provides visual indication of valve position.
Control gas supply for commercial and industrial burners. Valve opens when power is applied. Use with V5055 valve. Valve and actuator can be mounted in any direction.
2 Rated for final safety shutoff service when used with V5055 valve. Indicators on valve and actuator provide constant visual indication of valve position.
MANUAL RESET SAFETY SHUT-OFF GAS VALVE ACTUATORS (MANUAL OPENING, ELECTRIC HOLDING): 4
-
148 www.federalcorp.com
4
V5055 INDUSTRIAL GAS VALVES
Order No. Application Size cfh m3/hr
Special Order Low pressure characterized guide (provides slowly increasing gas flow on opening).
1" 960 27.2
V5055B1010 Low pressure characterized guide (provides slowly increasing gas flow on opening).
1 1/4" 1406 39.8
V5055B1028 Low pressure characterized guide (provides slowly increasing gas flow on opening).
1 1/2" 1717 48.6
V5055B1069 Low pressure characterized guide (provides slowly increasing gas flow on opening).
2" 3620 102.5
V5055B1077 Low pressure characterized guide (provides slowly increasing gas flow on opening).
2 1/2" 4250 120.3
V5055B1085 Low pressure characterized guide (provides slowly increasing gas flow on opening).
3" 5230 148
V5055C1000 Low pressure. Double seat (use with actuators having valve seal overtravel interlock).
2" 3620 102.3
V5055C1018 Low pressure. Double seat (use with actuators having valve seal overtravel interlock).
2 1/2" 4250 120.3
V5055C1026 Low pressure. Double seat (use with actuators having valve seal overtravel interlock).
3" 5230 148.3
SAFETY SHUTOFF VALVES USED WITH V4055, V4062 AND V9055 FLUID POWER ACTUATORS TO CONTROL GAS FLOW TO COMMERCIAL AND INDUSTRIAL BURNERS
Valve Capacities
VALVE-ACTUATOR PRESSURE RATINGS
Valve Sizes Diff.2 Close-Off3 Diff.2 Close-Off3 Diff.2 Close-Off3
V5055A,C 3/4" - 3" 5 psi 15 psi 15 psi 15 psi 5 psi 15 psiV5055A,C 4" 3 psi 15 psi 5 psi 15 psi 3 psi 15 psiV5055B 3/4" - 3" 5 psi 15 psi 15 psi 15 psi 5 psi 15 psiV5055B 4" 3 psi 15 psi 5 psi 15 psi 3 psi 15 psiV5055D,E 3/4",1", 1 1/4", 1 1/2" 5 psi 75 psi 25 psi 75 psi 5 psi 75 psiV5055D,E 2", 2 1/2", 3" 5 psi 45 psi 15 psi 45 psi 5 psi 45 psi
3 Maximum close-off pressure without leakage. This is the maximum allowable pressure drop to which a valve may be subjected while fully closed and is independent of the valve body ratings.
2 Maximum operating pressure differential.
Actuator
V4055A,D1 V4055B,E1 V4062, V90551
1 Use a V4055D, V4055E, V4026D, or V9055D (with valve-closed indication switch) with a V5055C or E ( with double seal) for a Valve Seal Overtravel Interlock.
HO NEYWELL FLAME SAFEGUARD___________
V4062A, OFF-LO-HI FLUID POWER GAS VALVE ACTUATORS
Order No. Application/Description Opening Time Includes
V4062A1008 HI-LO-OFF actuator.1 Low pressure. 26 seconds Damper shaft
Control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand.
1 Actuator can be used with all V5055 bodies; best control and low fire repeatability will result with V5055B with characterized guide.
7616BR Damper Crank Arm (damper arm and clip.)
ACCESSORIES Order No. Description
Valve closed switch indication bag assembly (must be used with V5055C or E).H133569
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 149
4
V8944 DIAPHRAGM GAS VALVES
Order No. Valve Type Gas Size Voltage
Current (Max. Amps at rated
Vac/Hz) Low Fire High Fire
V8944B1027 Two-stage, slow opening Natural 1 1/4" 24V, 50/60 Hz 0.5 0.8" WC 3.5" WC
DUAL STAGE PRESSURE REGULATION
Regulator Set Point1
1 Regulator setpoints adjustable for natural gas-Low Fire, 0.8-2" WC; High Fire, 3-4.5" WC.
Solenoid-operated diaphragm valves that combine the functions of safety shutoff and pressure regulation in a single unit. Suitable for use on atmospheric boilers, commercial water heaters, and rooftop heaters. Valve body of die-cast aluminum with a straight-through pattern.
ReplacesV8844B1028
V9055A MODULATING FLUID POWER GAS VALVE ACUTATORS
Order No. Description Voltage (60 Hz)1 Includes
V9055A1055 Modulating-OFF actuator for use with V5055B2 valve bodies. Low pressure.
120Vac Damper shaft
2 Actuator can be used with all V5055 valve bodies; however, best control and low fire capability will result with V5055B with characterized guide.
Control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied, then modulates to meet firing rate controller demand.
1 Can also be used at 50 Hz; however, opening time (26 seconds) will increase by 20.
___________ HO NEYWELL FLAME SAFEGUARD
INTEGRATED GAS TRAINBuild your Gas train with only an adjustable wrench!
Your custom gas train consists of one or more of the following components:V5097, V4297A, V4297S and C6097A, B
V5097 INDUSTRIAL GAS VALVES
Order No. Application cfh m2/hr
V5097B1002 Low pressure characterized guide (provides slowly increasing gas flow on opening).
665 960
1406 1717 1990
18.8 27.2 39.8
48.6 56.9
V5097B1010 Low pressure characterized guide (provides slowly increasing gas flow on opening).
3620 4250 5230
102.5 120.3 148.0
V5097C1018 Low pressure, double seat (use with actuators having valve seal overtravel interlock).
3620 4250 5230
102.5 120.3 148.0
Pipe Adapter
Valve Capacities1
Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners. Use with natural or LP gases. Mount directly in gas supply line. Seven pipe adapter sizes from 3/4" to 3" have NPT or BSP threaded connections. Provides three 1/4" upstream and two 1/4" downstream tap and plug. Yellow SHUT indicator attached to the valve stem provides an indication of the valve closed position. Order pipe adapters separately..
1 Based on 0.64 specific gravity natural gas at 1" WC pressure drop.
32000109-001 - 3/4" NPT 32000109-002 - 1" NPT 32000109-003 - 1 1/4" NPT 32000109-004 - 1 1/2" NPT 32000109-005 - 2" NPT
32001605-001 - 2" NPT 32001605-002 - 2 1/2" NPT 32001605-003 - 3" NPT
32001605-001 - 2" NPT 32001605-002 - 2 1/2" NPT 32001605-003 - 3" NPT
-
150 www.federalcorp.com
4
V4297S NORMALLY OPEN VENT VALVES
Order No. Description Capacity1(cfh)
V4297S1003 Solenoid Normally Open Vent Valve Small Body, 1" Vent Connection. 110/120 Vac, 50/60 Hz, 5 psi.
714
V4297S1011 Solenoid Normally Open Vent Valve Large Body, 1 1/4" Vent Connection. 110/120 Vac, 50/60 Hz, 5 psi
1115
1 Based on 1" pressure drop for gas with 0.64 sp. gr.
*Used with natural or LP gas.
Provides the vent function in a double block and bleed configuration. The valve is part of the Honeywell Integrated Valve Train System, which allows gas train components to be directly bolted together.
*V4297S valves are normally open valves to be used as vent valves in double block and bleed configurations. The gas flows through the vent connection when the valve is not energized.
*V4297S is not gas flow direction dependent. It can be connected either way in the valve train.
*V4297S valves are used with 110/120 Vac, 50/60 Hz controllers
Old Electro- Mechanical Technology
New Micro Processor Technology
Old Model
7800
Replacement1Prepurge
Timer
R7023 RM7823 N/ARA890 RM7890 N/AR4795 RM7895 ST7800
R7795 RM7895 ST7800R485 RM7885 N/AR4075 RM7885 N/AR4138 RM7838 ST7800
R4140 RM7840 ST7800
BC7000 RM7800 ST7800
7800 SERIES CROSS REFERENCEThe 7800 Series family replaces every Honeywell Flame Safeguard control made before 1992--both the electro-mechancial and basic micro-processor. All 7800 Series products use the same wiring subbase (Q7800) and share the same flame amplifiers and prepurge timers. Optional accessories include S7830 first-out expanded annunciator, S7810 data controlbus module, S7820 remote reset module, QS7800A communications interface with P.C.,ZM7850A software and Q7700A communications base unit.
Description
Semi-automatic primarySemi-automatic primary
Amplifier2
PRIMARIESFlame relay
1 S7800 keyboard display standard on RM7800, optional (recommended) for all other models.2 Flame sensor must match amplifier.
PROGRAMMERSSemi-automatic primary
Full programmer with mechanical cam
Basic microprocessor programmer
Use R7800 Series rectification, infra-red, or ultra-violet amplifiers.
Protecto relay, primary controlPrimary plus pre-purge
Solid state primary, plus prepurge
HO NEYWELL FLAME SAFEGUARD____________
Pipe Diameter(in.) Capacity1(cfh)
3/4" 6501" 700
1 1/4" 7803/4" 1190
1" 14601 1/4" 22601 1/2" 2735
2" 3060
V4297A SOLENOID SAFETY SHUT-OFF VALVEControls gas flow to commercial and industrial burners. The valve is part of the Honeywell Integrated Valve Train system that allows gas train components to be directly bolted together.
Used with natural or LP gases. V4297A normally closed valves are rated for final shutoff service. One valve body applicable to five pipe sizes: 3/4", 1", 1 1/4", 1 1/2", and 2" pipes. Accepts C6097 Pressure Switch mounted directly to flange (upstream pressure tap only). V4297A models will mate only with smaller V5097 or V4297S valve bodies.
1 Ratings are 1" pressure drop for gas with 0.64 sp.gr.
V4297A1013 Solenoid Safety Shutoff Valve, large flow, 110/120Vac, 50/60 Hz, 5 psi
Order No. Description
V4297A1005 Solenoid Safety Shutoff Valve, small flow, 110/120Vac, 50/60 Hz, 5 psi
See TechTip 55 for Enhanced 7800 Cross-Reference
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 151
4
____________ HO NEYWELL FLAME SAFEGUARD
Order No. Application/DescriptionPilot Flame Establishing
Period (PFEP)
Main Flame Establishing
Period (MFEP)1 Postpurge2 Replaces
RM7800L1087Automatic programming control with display, 120/60 4 or 10 seconds 10 or 15 seconds 15 seconds
RM7800L1012 BC7000L+PM720L
RM7800G PROGRAMMERMicroprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. Five LEDs provide sequence information. Five function Run/Test Switch. Local or remote annunciation of operation and fault information (optional). Non-volatile memory retains history files and lockout status after loss of power. With Valve Proving Feature. RM7800L comes standard with enhanced S7800A1142 Keyboard Display.
2 Pre-purge will be determined by which ST7800A Purge Time Card is selected.
Note: Required Components: Q7800 Universal Wiring Subbase, R7847, R7848, R7849, R7886 Flame Safeguard Amplifiers, S7800 Keyboard Module, and ST 7800 Plug-in Purge Timer Cards.
1 The MFEP will be determined by terminals used, configuration jumper or jumper wire addition. See instruction sheet.
RM7823A PRIMARY FLAME SWITCH
Order No. Voltage Switching Replaces1
RM7823A1016 120Vac @ 60Hz Two spdt R7023B,C
Microprocessor-based integrated flame switch for detecting a flame using rectification, ultraviolet (UV) or infrared (IR) source. Provides level of safety, functional capability and features beyond conventional controls. Can be fitted with any 7800 Series Amplifier to provide relay action from two single pole, double throw (spdt) relays when flame is present or not present. RM7823A is a flame detector relay only. Suitable primary control must be used to provide safe-start check, safety lockout, load switching and other functions required in flame safeguard systems. Three LEDs to indicate power, flame and alarm. Non-volatile memory. Shutter drive output.
1 To replace R7023B, select R7847 Flame Signal Amplifier. To replace R7023C, select R7849 Flame Signal Amplifier. Suggested option--S7800 Keyboard Display.
RM7838B SEMI-AUTOMATIC PROGRAMMER
Order No. Description
Pilot Flame Establishing Period
(PFEP) Replaces
RM7838B1021 Semi-automatic industrial primary relay module with S7800 display, 120/60
4 or 10 seconds R4138A , C RM7838A
Microprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. Functions include purge, burner pilot startup, flame supervision, system status indication, system or self diagnosis and troubleshooting. Delays admission of fuel to combustion chamber until pilot flame has been proven and then monitors the flame through the run period while providing system status indication. Includes Keyboard Display Module. Five LEDs provide sequence information. Non-volatile memory retains history files and lockout status after loss of power. Selectable pilot flame establishing period. Provides application flexibility and optional communication interface capability. Includes Valve Proving Feature and Programmable Post Purge.
Note: Required components: Q7800 Universal Wiring Subbase, R7800 Series Flame Signal Amplifiers, and ST7800 Plug-in Purge Timer Card.
-
152 www.federalcorp.com
4
Order No. Description Replaces1
RM7885A1015 Semi-automatic primary control 120/60 R4851 To replace R485, select R7847 Flame Signal Amplifier
Flame signal check during standby.
Operates with the following:
FEATURES
RM7885 SEMI-AUTOMATIC PRIMARY CONTROLMicroprocessor-based integrated burner control for industrial semi-automatically fired gas, oil, coal, or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls.
Compatible with existing Honeywell flame detectors.
Functions include flame supervision, system indication, system or self-diagnostics and troubleshooting.Adaptable to continuous firing, high-low or modulating firing rate for semi-automatic burner sequencing.
*Torch-ignited main burner or torch-ignited pilot using S445A Start-Stop Station, or conventional knee or foot operated station.
*Direct-ignition oil burner or electrically ignited pilot, using S445A Start-Stop StationFive LEDs provide sequence information.Non-volatile memory.
RM7890A, B, C, PRIMARY CONTROL
Order No. Description
Pilot Flame Establishing Period
(PFEP) Replaces1
RM7890A1056² Automatic primary relay module, 120/60, Intermittent Pilot 4 or 10 seconds RA890F,G,H, RM7890A1015RM7890B1048² Automatic primary relay module, 120/60, shutter drive. 4 or 10 seconds RA890F,G,H, RM7890B1014RM7890C1005 Automatic primary relay module, 120/60, Standing Pilot 4 or 10 seconds RA890F,G,H
² Enhanced Version with Pre Ignition Interlock and Valve Proving capability.
Note: Required Components: R7847, R7848, R7849, R7886A Flame Signal Amplifiers and Q7800 Universal Wiring Subbase. S7800 Keyboard Display as an option.
Microprocessor-based integrated primary burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. Five LEDs provide sequence information. Selectable recycle or lockout on loss of flame. Nonvolatile memory retains history files and sequence status after loss of power.
1 To replace RA890F, select R7847A Flame Signal Amplifier. To replace RA890G, select R7849A Flame Signal Amplifier. To replace RA890H, select R7847B Flame Signal Amplifier. Check timings for application requirements.
HO NEYWELL FLAME SAFEGUARD___________ RM7840G, L, M PROGRAMMER
Order No. Application/Description
Pilot Flame Establishing
Period (PFEP)
Main Flame Establishing Period
(MFEP)1 Postpurge2 Replaces
RM7840G1022³ Relay module without display, 120/60 4 or 10 seconds 10, 15, 30 seconds or Intermittment.
Selectable R4140G
RM7840L1075³ Relay module without display, 120/60. Interrupted Pilot.
4 or 10 seconds 10 or 15 seconds Selectable R4140L
RM7840L1026 Relay module without display, 120/60. Interrupted Pilot.
4 or 10 seconds 10 or 15 seconds 15 seconds R4140L
RM7840M1017 Relay module without display, 120/60 4 or 10 seconds 10 seconds 15 seconds R4140M
³ With Valve Proving Feature.
2 Pre-purge is determined by ST7800 Plug-in Timer Card selected. Selectable Postpurge using S7800A1142.
Note: Required Components: Q7800 Universal Wiring Subbase, R7847, R7848, R7849, R7886 Flame Signal Amplifiers, and ST 7800 Plug-in Purge Timer Cards. If Keyboard display ST7800 is recommended (order separately) or order equivalent RM7800 (included).
Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls. Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. Five LEDs provide sequence information. Five function Run/Test Switch. Local or remote annunciation of RM7840 operation and fault information. Non-volatile memory retains history files and lockout status after loss of power.
1 The MFEP will be determined by terminal used, configuration jumper or jumper wire addition. See instruction sheet.
-
OKLAHOMA CITY • (405) 239-7301 TULSA • (918) 249-1918 (800) 289-3331 • FAX: (405) 232-5438 (800) 955-1918 • FAX: (918) 249-9014 153
4
RM7895A/RM7896 FULL FUNCTION PRIMARY CONTROL
Order No. DescriptionAirflow Switch Check (AFSC) Replaces1
RM7895D1011 Interrupted primary relay module with with delayed main valve and pre-purge.
Yes R7795G,H
RM7896D1027 Interrupted primary relay module with delayed main valve plus pre-purge and post-purge.
Yes R7795G,H
Microprocessor-based integrated primary burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. Five LEDs provide sequence information. Selectable recycle or lockout on loss of flame or airflow. Nonvolatile memory retains history files and lockout status after loss of power.
1 To replace R7795A,C,E,F, select R7849A Flame Signal Amplifier. To replace R7795B,D,F,H, select R7847A Flame Signal Amplifier.
___________ HO NEYWELL FLAME SAFEGUARD
RM7898A ENHANCED FULL FUNCTION PRIMARY CONTROL
Order No. DescriptionAirflow Switch Check (AFSC) Replaces1
RM7898A1000 Intermittent primary relay module without AFSC, 120/60 No R7795A,B, RM7895A,C, RM7896A,C
RM7898A1018 Intermittent primary relay module without AFSC, 120/60 No R7795E,F, RM7895A,C
Note: Required Components: Q7800 Universal Wiring Subbase, R7847, R7848, R7849, R7886 Flame Signal Amplifiers, and ST7800 Plug-in Purge Timers.
Microprocessor-based integrated primary burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls. Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting. Five LEDs provide sequence information. Selectable recycle or lockout on loss of flame or airflow. Nonvolatile memory retains history files and lockout status after loss of power. Includes Valve Proving Sequence, Programmable Post Purge, and Pre Ignition Interlock input.
1 Check Cross Reference and application.
Q7800A, B 22-TERMINAL UNIVERSAL WIRING SUBBASES
Order No. Description
Q7800A1005 Universal wiring subbase, panel mountingQ7800B1003 Universal wiring subbase, burner or wall mounting, knockouts
provided in back, top, and bottom for conduit connections.
Burner, panel or wall mount subbases for 7800 SERIES relay modules and S7830A Expanded Annunciator. Makes electrical connections for 7800 SERIES relay modules or S7830A Expanded Annunciator through bifurcated contacts. Provides terminals for field wiring. Twenty-two terminals.
Order No.1
Pilot Flame Establishing
Period
Main Flame Establishing
Period InterlocksR7140G2008 10 sec, 15
sec, 30 sec or Intermittent
4 sec or 10 sec
Running
R7140L2007 10 sec or 15 sec
4 sec or 10 sec
Interrupted Upgrade replacement Programming Control for BC7000L with PM 720L
1Also requires ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.
R7140 PROGRAMMERSThe R7140 Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil, or combination fuel single burner applications. Functions include automatic burner sequencing, flame supervision, system status i