Home Inspection Report
1234 street, Nashville, TN 37013
Inspection Date:Sunday May 6, 2018
Prepared For:John Doe
Prepared By:Busy Bee Home Inspections
5424 Bell Forge Ln E, P.O. box 1383Antioch, TN 37013
(615) [email protected]
Report Number:180506
Inspector:Timothy Pollock
1234 street, Nashville, TN 37013 Page 2
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Receipt/InvoiceBusy Bee Home Inspections5424 Bell Forge Ln E, P.O. box 1383Antioch, TN 37013(615) 205-2059
Property Address1234 streetNashville, TN 37013
Date: May 6, 2018 Inspection Number: 180506
Inspected By: Timothy Pollock Payment Method: Cash
Client: John Doe
Inspection FeeHome Inspection $375.00Home Inspection discount ($375.00)
Total $0.00
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 3
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Report SummaryPotential Safety Hazards
Handyman/extension cord wiring in the attic, breach interior fire wall, potential trip hazard in dining room.
Deferred Cost ItemsRoof evaluation.
Major ConcernsMissing fascia, porch attachment to house, rusting sink in bathroom #2
Items Not OperatingFront door bell not working properly.
Improvement ItemsWater heater catch pan.
Items To MonitorNail pops, condensation lines, fresh caulking in various places.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 4
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Report OverviewScope of Inspection
Main Entrance FacesNorth
State of OccupancyOccupied
Weather ConditionsSunny, high of 87 low of 65.
Recent RainRain 2 days prior to inspection
Ground CoverNone.
Approximate Age15 years
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 5
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
GroundsService Walks
None Not Visible
Material X Concrete Flagstone Gravel Brick Other:
Condition X Satisfactory Marginal Poor Trip hazard Typical cracks Pitched towards homeSettling cracks Public sidewalk needs repair
Comments
Photos
Poured concrete public service walk
Driveway/Parking
None Not Visible
Material X Concrete Asphalt Gravel/Dirt Brick Other:
Condition X Satisfactory Marginal Poor Settling Cracks Typical cracks Pitched towards homeTrip hazard Fill cracks and seal
Comments
Photos
Driveway
Porch
None Not Visible
Condition X Satisfactory Marginal Poor Railing/Balusters recommended
Support Pier Concrete X Wood Other:
Floor X Satisfactory Marginal Poor Safety Hazard
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 6
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Grounds
Front porch
Stoops/Steps
None
Material X Concrete Wood Other: Railing/Balusters recommended
Condition X Satisfactory Marginal Poor Safety Hazard Uneven risers Rotted/DamagedCracked Settled
Comments Cracks indicating signs of movement
Photos
Crack indicating movement
Patio
None
Material X Concrete Flagstone Kool-Deck Brick Other:
Condition X Satisfactory Marginal Poor Settling cracks Trip hazardPitched towards home (see remarks) Drainage provided Typical cracks
Comments
Deck/Patio/Porch Covers
None
Condition Satisfactory X Marginal Poor X Posts/Supports need Repair Earth to wood contactMoisture/Insect damage
Recommend Metal Straps/Bolts/Nails/Flashing X Improper attachment to house None
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 7
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Grounds
5 support post improperly attached to house
Shows improperly secured support post on the front porch.
Fence/Wall
Not evaluated None
Type Brick Block Wood Metal X Chain Link Rusted Vinyl
Condition X Satisfactory Marginal Poor Typical cracks Loose Blocks/Caps
Gate N/A Satisfactory X Marginal Poor Planks missing/damaged Operable: Yes X No
Comments
Photos
Latching hardware modified causing closing mechanism to not work properly.
Recommend Both gate locking mechanisms be evaluated and and repaired
Landscaping affecting foundation
N/A
Negative Grade East West North South X Satisfactory Recommend additional backfillRecommend window wells/covers Trim back trees/shrubberiesWood in contact with/improper clearance to soil
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 8
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Grounds
Recommend not planting against foundation, locks moisture in
Hose bibs
N/A
Condition X Satisfactory Marginal Poor No anti-siphon valve Recommend Anti-siphon valve
Operable X Yes No Not Tested Not On
Comments
Photos
Frost free anti siphon hose bib. Frost free anti siphon hose bib.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 9
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
RoofGeneral
Visibility None X All Partial Limited By:
Inspected From X Roof X Ladder at eaves Ground With Binoculars
Photos
Style of Roof
Type X Gable Hip Mansard Shed Flat Other:
Pitch Low X Medium X Steep Flat
Roof #1 Type: 3-Tab asphalt shingles Layers: Appeared to be 1 layer at the time of the inspection Age: 13 years Location: Whole house
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 10
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
RoofStyle of Roof cont.
Roof #2 X NoneType: Layers: Age: Location:
Roof #3 X NoneType: Layers: Age: Location:
Comments
Photos
Gable roof type.
Ventilation System
None N/A
Type X Soffit Ridge X Gable Roof Turbine Powered Other:
Comments
Photos
Seal and monitor nail head pops
Flashing
Material Not Visible X Galv/Alum Asphalt Copper Foam Rubber Lead Other:
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 11
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
RoofFlashing cont.
Condition Not Visible X Satisfactory Marginal Poor Rusted MissingSeparated from chimney/roof Recommend Sealing Other:
Comments
Photos
Flashing Missing drip edge, and felt paper recommend evaluation and repair by qualified roofing contractor.
Missing drip edge and felt paper. Recommend evaluation and repair by qualified roofing contractor.
Valleys
N/A
Material X Not Visible Galv/Alum Asphalt Lead Copper Other:
Condition Not Visible X Satisfactory Marginal Poor Holes Rusted Recommend Sealing
Comments
Photos
Closed valley appeared to be in good condition
Condition of Roof Coverings
Roof #1 Satisfactory X Marginal X Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles X Nail popping X Granules missing Alligatoring Blistering
X Missing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingX Incomplete/Improper Nailing X Recommend roofer evaluate Evidence of Leakage
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 12
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
RoofCondition of Roof Coverings cont.
Roof #2 X N/A Satisfactory Marginal Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Roof #3 X N/A Satisfactory Marginal Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Comments
Photos
Loose/stray nails Missing shingles, recommend repair/replace by a qualified licensed roofing contractor
Improper nailing, recommend sealing and monitor for water entry
Missing multiple shingles
Plumbing Vents
Not Visible Not Present
Condition Satisfactory X Marginal Poor
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 13
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Roof
Rubber boots around DWV piping starting to show signs of wear/decay.
Recommend resecuring, sealing, and monitor drain waste vent pipe flashing. Potential water entry point
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 14
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Roof Photos
shingles appeared to be lifting/curling
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 15
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
ExteriorGutters/Scuppers/Eavestrough
None
Condition Satisfactory X Marginal Poor Rusting Downspouts needed Recommend repair/replaceX Needs to be cleaned
Material Copper Vinyl/Plastic X Galvanized/Aluminum Other:
Leaking Corners Joints Hole in main run X No apparent leaks
Attachment Loose Missing spikes Improperly sloped X Satisfactory
Extension needed North South East West X N/A
Comments
Photos
Downspout on northwest wall with splash block installed.
North East downspout and gutter system with an extention installed
Downspout North East corner dented, recommend repair/replace.
South exterior wall North East downspout with splashblock
South West downspout with splash block installed
Siding
Material Stone Slate X Block/Brick Fiberboard Fiber-cement Stucco EIFS* Not InspectedAsphalt Wood X Metal/Vinyl Other: Typical cracks Peeling paint Monitor Wood rot
X Loose/Missing/Holes
Condition Satisfactory X Marginal Poor Recommend repair/painting
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 16
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior
Exterior vinyl siding west wall Brick veneer and vinyl on North wall
Hole in the siding on the East wall. Recommend repair/replace by qualified siding contractor
Vinyl siding on the South wall Deformed siding recommend repair/ replace by qualified siding contractor
Trim
Material Wood Fiberboard Aluminum/Steel X Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 17
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior
Some areas of trim were chipped/cracked. Recommend repair.
Corner was damaged recommend repair/ replace by qualified contractor
Soffit
None
Material Wood Fiberboard Aluminum/Steel X Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments
Photos
Soffits along the eaves
Fascia
None
Material Wood Fiberboard X Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition Satisfactory Marginal X Poor
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 18
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior
Missing some of the fascia. Recommend replace by qualified roofing contractor
Flashing
None
Material Wood Fiberboard Aluminum/Steel X Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments
Caulking
None
Condition Satisfactory Marginal PoorX Recommend around windows/doors/masonry ledges/corners/utility penetrations
Comments Recommend maintaining a fresh seal of caulking around all penetrations
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 19
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior
Windows/Screens
Condition Satisfactory X Marginal Poor Wood rot Recommend repair/paintingX Recommend repair/replace damaged screens Failed/fogged insulated glass
Material Wood Metal Vinyl X Aluminum/Vinyl clad
Screens X Torn X Bent X Not installed Satisfactory
Comments
Photos
Some of the screens were torn in multiple areas
Torn window screen. Bent window screen frame.
window screen missing at the time of the inspection. Recommend replacing window screen
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 20
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
ExteriorSlab-On-Grade/Foundation
Foundation Wall Concrete block X Poured concrete Post-Tensioned concrete Not Visible Other:
Condition X Satisfactory Marginal Monitor Have Evaluated Not Evaluated
Concrete Slab N/A Not Visible X Satisfactory Marginal Monitor Have Evaluated
Comments
Service Entry
Location Underground X Overhead
Condition X Satisfactory Marginal Poor Weather head/mast needs repair Overhead wires too low
Exterior receptacles X Yes No Operable: X Yes No Condition: X Satisfactory Marginal Poor
GFCI present X Yes No Operable: X Yes No Safety Hazard Reverse polarity Open ground(s)Recommend GFCI Receptacles
Comments
Photos
Service entry clearance 120/240v system Electric meter was properly attached and was locked
Grounding rod was secured to house
GFCI Receptacle and wet location cover installed and tested properly.
GFCI Receptacle and wet location cover installed and tested properly.
Building(s) Exterior Wall Construction
Type Not Visible X Framed Masonry Other:
Condition Not Visible X Satisfactory Marginal Poor
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 21
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior
Exterior Doors
Main Entrance N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Patio N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Rear door N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Other door X N/A Weatherstripping: Satisfactory Marginal Poor Missing Replace Door condition:Satisfactory Marginal Poor
Comments
Photos
Rear entry door on south wall
Exterior A/C - Heat pump #1
Unit #1 N/ALocation: Condenser unit located on west wall Brand: Trane Model #: 4TWB3030C1000AA Serial #: 12304NAG4FApproximate Age: ~5 years oil
Condition Satisfactory X Marginal Poor Cabinet/housing rusted
Energy source X Electric Gas Other:
Unit type Air cooled Water cooled Geothermal X Heat pump
Outside Disconnect X Yes No Maximum fuse/breaker rating (amps): 60amp
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 22
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
ExteriorExterior A/C - Heat pump #1 cont.
Outside Disconnect cont. Fuses/Breakers installed (amps): 60amp Improperly sized fuses/breakers
Level X Yes No Recommend re-level unit
Condenser Fins Damaged Need cleaning Damaged base/pad Damaged Refrigerant Line X Satisfactory
Insulation X Yes No Replace
Improper Clearance (air flow) Yes X No
Comments
Photos
Trane Heat Pump appears to be charged with R-410a.
Condensing unit on level pad with disconnect
Condensation lines
Condensation lines and high and low pressur lines. Recommend maintaining sealant around these lines
Disconnect location west wall 60amp disconnect for outside unit.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 23
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 24
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Exterior Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 25
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Garage/CarportType
None
Type X Attached Detached X 1-Car 2-Car 3-Car 4-Car Carport
Comments
Photos
Recommend repair sagging weatherstrip.
Recommend maintaining painted areas with paint
Roofing
Material X Same as houseType: 3-Tab asphalt shingles Approx. age: 15 years Approx. layers: 1layer
Comments
Gutters/Eavestrough
Condition Satisfactory X Marginal Poor X Same as house
Comments
Photos
Garage downspout and gutter system
Siding
N/A
Material X Same as house Wood Metal X Vinyl Stucco Masonry Slate Fiberboard
Condition X Satisfactory Marginal Poor Recommend repair/replace Recommend painting
Comments
PhotosThis confidential report is prepared exclusively for John Doe
©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 26
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Garage/Carport
North siding on garage. East siding on garage. South siding of garage
Trim
N/A
Material X Same as house X Wood Aluminum X Vinyl
Condition Satisfactory X Marginal Poor X Recommend repair/replace X Recommend painting
Comments
Photos
Recommend maintaining painted areas.
Floor
Material X Concrete Gravel Asphalt Dirt Other:
Condition X Satisfactory Typical cracks Large settling cracks Recommend evaluation/repairSafety hazard
Source of Ignition within 18" of the floor N/A Yes X No
Comments
Sill Plates
None X Not Visible
Type Floor level Elevated
Condition Rotted/Damaged Recommend repair
Comments
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 27
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Garage/CarportOverhead Door(s)
N/A
Material Wood Fiberglass Masonite X Metal Recommend repair
Condition Satisfactory X Marginal Poor Hardware loose Safety Cable RecommendedWeatherstripping missing/damaged Loose/missing
Recommend Priming/Painting Inside & Edges Yes X No
Comments
Photos
Manual garage door, tension spring.
Electrical Receptacles
X Yes No Not Visible Operable: X Yes No
Reverse polarity Yes X No
Open ground Yes X No Safety Hazard
GFCI Present X Yes No Operable: X Yes No Handyman/extension cord wiringRecommend GFCI Receptacles
Comments
Fire Separation Walls & Ceiling
N/A X Present Missing Recommend repair
Condition Satisfactory X Recommend repair Holes walls/ceiling X Safety hazard(s)
Moisture Stains Present Yes X No
Typical Cracks Yes X No
Fire door Not verifiable Not a fire door Needs repair X Satisfactory
Self closure N/A Satisfactory Inoperative X Missing
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 28
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Garage/Carport
Breach fire wall dryer exhaust vent piping.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 29
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
KitchenCountertops
Condition Satisfactory X Marginal X Recommend repair/caulking
Comments
Photos
Chipped counter top above dishwasher, recommend repair/ replace.
Outlet was GFCI protected and tested properly.
Counter top GFCI protected receptical tested properly.
Cabinets
Condition X Satisfactory Marginal Recommend repair/adjustment
Comments
Photos
Kitchen cabinets
Plumbing
Faucet Leaks Yes X No
Pipes leak/corroded Yes X No
Sink/Faucet X Satisfactory Corroded Chipped Cracked Recommend repair
Functional drainage X Satisfactory Marginal Poor
Functional flow X Satisfactory Marginal Poor
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 30
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Kitchen
Kitchen p-trap and garbage disposal
Faucet wasn't dripping Kitchen sink Hot and Cold water shut off. Braided SS valve water shutoff for dishwasher.
Walls & Ceiling
Condition X Satisfactory Marginal Poor Typical cracks Moisture stains
Comments
Photos
Grease stain on ceiling from dirty hood filter.
Dirty hood filter recommend replacement.
Heating/Cooling Source
X Yes No
Comments
Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 31
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Kitchen
Floor
Condition Satisfactory X Marginal Poor Sloping Squeaks
Comments
Photos
Floor covering material appeared to be damaged.
Damage to floor covering material
Appliances
Disposal N/A Not tested Operable: X Yes No
Oven N/A Not tested Operable: X Yes No
Range N/A Not tested Operable: X Yes No
Dishwasher N/A Not tested Operable: X Yes No
Trash Compactor X N/A Not tested Operable: Yes No
Exhaust fan N/A Not tested Operable: X Yes No
Refrigerator N/A Not tested Operable: X Yes No
Microwave N/A Not tested Operable: X Yes No
Dishwasher airgap Yes X No
Dishwasher drain line looped X Yes No
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI Receptacles: Yes NoPotential Safety Hazard(s)
Open ground/Reverse polarity: Yes X No Potential Safety Hazard
Comments
PhotosThis confidential report is prepared exclusively for John Doe
©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 32
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Kitchen
Dishwasher Range Over the range microwave.
Refrigerator Garbage disposal
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 33
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Laundry RoomLaundry
Laundry sink X N/A
Pipes leak Yes X No Not Visible
Cross connections Yes X No Potential Safety Hazard
Heat source present X Yes No
Room vented Yes X No
Dryer vented N/A X Wall Ceiling Floor Not vented Plastic dryer vent not recommendedNot vented to exterior X Recommend repair X Safety hazard
Electrical Open ground/reverse polarity: Yes X No Safety hazard
GFCI present Yes X No Operable: Yes X No Recommend GFCI Receptacles
Appliances X Washer X Dryer Water heater Furnace/Boiler
Washer hook-up lines/valves X Satisfactory Leaking Corroded Not Visible
Gas shut-off valve X N/A Yes No Cap Needed Safety hazard Not Visible
Comments
Photos
Water Supply valves for washing machine.
Dryer exhaust vent piping and receptacle.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 34
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Bathroom (1)Bath
Location West exterior wall
Sinks Faucet leaks: Yes X No Pipes leak: Yes X No
Tubs N/A Faucet leaks: Yes X No Pipes leak: Yes X No Not Visible
Showers N/A Faucet leaks: Yes X No Pipes leak: Yes X No Not Visible
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Whirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes NoGFCI Recommended
Shower/Tub area X Ceramic/Plastic Fiberglass Masonite Other: Condition: Satisfactory X MarginalPoor Rotted floors Caulk/Grouting needed: X Yes No
Where: Recommend maintaining a fresh bead of caulking around bathtubs, toilets, and sinks. N/A
Drainage X Satisfactory Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window X None Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: X Yes No Noisy
Comments
Photos
Sink stopper is holding water. Hot and Cold water shut off valve for bathroom sink.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 35
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Bathroom (1)
Toilet operating. Water shutoff valve for toilet. Bathtub operating
Bathtub stopper is holding water. GFCI protected bathroom counter receptacle. Tested properly
Exhaust fan was working.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 36
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Bathroom (2)Bath
Location Adjacent to master
Sinks Faucet leaks: Yes X No Pipes leak: Yes X No
Tubs N/A Faucet leaks: Yes X No Pipes leak: Yes X No Not Visible
Showers N/A Faucet leaks: Yes X No Pipes leak: Yes X No Not Visible
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Whirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes NoGFCI Recommended
Shower/Tub area X Ceramic/Plastic Fiberglass Masonite Other: Condition: X Satisfactory MarginalPoor Rotted floors Caulk/Grouting needed: X Yes No
Where: Caulking needed around bathtub toilet base and sink. N/A
Drainage X Satisfactory Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window X None Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: X Yes No Noisy
Comments
Photos
GFCI not tested due to attachment
Sink on the right will need to be replaced, leaking is inevitable.
Faucet does work stopper was not tested.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 37
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Bathroom (2)
Sink- Hot and Cold water supply shut off valve.
Faucet on the left working properly.
Sink on the left. Holding water properly.
Sink- Hot and Cold water supply shut off valve.
Toilet was working properly. Toilet water supply shut off.
Bathtub faucet working properly. Bathtub stopper working properly, holding water.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 38
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Room (1)Room
Location North West corner
Type Bedroom
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor X Recommend repair/replace
Electrical Switches: X Yes No Operable Receptacles: X Yes No OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: X Doors Walls Ceilings
Bedroom Egress restricted N/A X Yes No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
Cracked bedroom door. Recommend repair/ replace.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 39
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Room (2)Room
Location South West corner
Type Bedroom
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No Operable Receptacles: X Yes No OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: X Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassX Broken/Missing hardware
Comments
Photos
Hole in closet door appeared to be caused by faulty door hardware.
Missing screen at the time of the inspection recommend replacement.
Receptacles tested properly.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 40
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Room (2) Photos
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 41
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Room (3)Room
Location North East corner
Type Master Bedroom
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No Operable Receptacles: X Yes No OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
GFCI protected receptacle tested properly.
GFCI protected receptacle tested properly.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 42
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
InteriorStairs/Steps/Balconies
None
Condition X Satisfactory Marginal Poor Loose/Missing
Handrail X Satisfactory Marginal Poor Safety hazard Hand Rail/Railing/Balusters recommended
Risers/Treads X Satisfactory Marginal Poor Risers/Treads uneven Trip hazard
Comments
Photos
Smoke/Carbon Monoxide detectors
Smoke Detector X Present Not Present Operable: X Yes No Not tested Recommend additionalSafety Hazard
CO Detector Present X Not Present Operable: Yes No Not tested Recommend additionalSafety Hazard
Comments
Attic/Structure/Framing/Insulation
N/A
Access Stairs X Pulldown Scuttlehole/Hatch No Access Other: Access limited by:
Inspected from Access panel X In the attic Other
Location X Hallway Bedroom Closet Garage Other
Flooring Complete X Partial None
Insulation X Fiberglass X Batts Loose Cellulose Foam Other Vermiculite Rock woolDepth: 7-8 in. Damaged Displaced Missing X CompressedX Recommend additional insulation
Installed in Rafters/Trusses Walls X Between ceiling joists Underside of roof deck Not Visible
Vapor barriers Kraft/foil faced Plastic sheeting X Not Visible Improperly installed
Ventilation X Ventilation appears adequate Recommend additional ventilation Recommend baffles at eaves
Fans exhausted to Attic: Yes X No Recommend repair Outside: X Yes No Not Visible
HVAC Duct N/A X Satisfactory Damaged Split Disconnected Leaking Repair/ReplaceRecommend Insulation
Chimney chase X N/A Satisfactory Needs repair Not Visible
Structural problems observed Yes X No Recommend repair Recommend structural engineer
Roof structure Rafters X Trusses X Wood Metal Collar ties Purlins X Knee wall Not Visible Other:
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 43
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
InteriorAttic/Structure/Framing/Insulation cont.
Ceiling joists X Wood Metal Not Visible
Sheathing Plywood X OSB Planking Rotted Stained Delaminated
Evidence of condensation Yes X No
Evidence of moisture Yes X No
Evidence of leaking Yes X No
Firewall between units X N/A X Yes No Needs repair/sealing
Electrical No apparent defects X Open junction box(es) X Handyman wiringKnob and tube covered with insulation X Safety Hazard
Comments
Photos
Handyman/extension cord wiring. Exposed wiring (not in junction box) and not properly grounded.
Attic inspection limited due to access restraint.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 44
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
PlumbingWater service
Main shut-off location South wall of garage
Water entry piping Not Visible X Copper/Galv. PVC Plastic CPVC Plastic Polybutylene PlasticPEX Plastic Lead Polyethylene
Lead other than solder joints Yes X No Unknown Service entry
Visible water distribution piping Copper Galvanized X PVC Plastic CPVC Plastic Polybutylene PlasticPEX Plastic Other:
Condition X Satisfactory Marginal Poor
Flow X Satisfactory Marginal Poor Water pressure over 80 psi Recommend plumber evaluateRecommend pressure regulator
Pipes Supply/Drain Corroded Leaking Valves broken/missing Dissimilar metal Cross connection: YesX No Safety Hazard Recommend repair Recommend a dielectric union Satisfactory
Drain/Waste/Vent pipe Copper Cast iron Galvanized X PVC ABS Brass
Condition X Satisfactory Marginal Poor
Support/Insulation N/AType: Rubber
Traps proper P-Type X Yes No P-traps recommended
Drainage X Satisfactory Marginal Poor
Interior fuel storage system X N/A Yes No Leaking: Yes No
Fuel line X N/A Copper Brass Black iron Stainless steel CSST Not Visible GalvanizedRecommend CSST be properly bonded
Condition X N/A Satisfactory Marginal Poor Recommend plumber evaluate
Comments
Photos
Main Water shutoff. Located inside the garage next to the door.
Water heater #1
N/A
General Brand Name: Rheem Serial #: RH 0311400916Capacity: 40Gal Approx. age: 4 years
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 45
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
PlumbingWater heater #1 cont.
Type Gas X Electric Oil LP Other:
Combustion air venting present Yes No X N/A
Seismic restraints needed Yes No X N/A
Relief valve X Yes No Extension proper: X Yes No Missing Recommend repairImproper material
Vent pipe X N/A Satisfactory Pitch proper Improper Rusted Recommend repair
Condition X Satisfactory Marginal Poor
Comments
Photos
Water heater cpvc discharge pipe Water heater supply shut off valve.
Recommend installing a water heater pan to drain.
Rheem 40gal water heater manufacturer plate.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 46
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Heating SystemHeating system
Unit #1 Brand name: Trane Approx. age: 5-6 years
Unknown Model #: GAF2A0A30S21AA Serial #: 122946UK2V X Satisfactory Marginal PoorX Recommended HVAC technician examine
Unit #2 X NoneBrand name: Approx. age:
UnknownModel #: Serial #: X Satisfactory Marginal Poor X Recommended HVAC technician examine
Energy source Gas LP Oil X Electric Solid fuel
Warm air system Belt drive X Direct drive Gravity Central system Floor/wall furnace
Heat exchanger X N/A Sealed Not Visible Visual w/mirror Flame distortion RustedCarbon/soot buildup
Carbon monoxide X N/A Detected at plenum Detected at register X Not testedTester:
Combustion air venting present X N/A Yes X No
Controls Disconnect: X Yes No Normal operating and safety controls observed Gas shut off valve:Yes X No
Distribution Metal duct X Insulated flex duct X Cold air returns Duct board Asbestos-like wrapSafety Hazard
Flue piping X N/A Satisfactory Rusted Improper slope Safety hazard Recommend repair/replace
Filter X Standard Electrostatic X Satisfactory X Needs cleaning/replacement MissingElectronic (not tested)
When turned on by thermostat X Fired Did not fire Proper operation: Yes No X Not tested
Heat pump N/A X Supplemental electric Supplemental gas
Sub-slab ducts X N/A Satisfactory Marginal Poor Water/Sand Observed: Yes No
System not operated due to X N/A Exterior temperature Other:
Comments
Photos
Trane air handler manufacturer plate.
60amp disconnect for air handler Overflow catch pan for air handler and safety shutoff. Pan was dry at the time of the inspection.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 47
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Electric/Cooling SystemMain panel
Location East wall of garage
Condition X Satisfactory Poor
Adequate Clearance to Panel X Yes No
Amperage/Voltage Unknown 60a 100a 150a X 200a 400a 120v/240v
Breakers/Fuses X Breakers Fuses
Appears grounded X Yes No Not Visible
GFCI breaker Yes X No Operable: Yes X No
AFCI breaker X Yes No Operable: X Yes No Not Tested
Main wire Copper X Aluminum Not Visible Double tapping of the main wire Condition: X SatisfactoryMarginal Poor
Branch wire X Copper X Aluminum Solid Branch Aluminum Wiring Not Visible Safety Hazard
Branch wire condition X Satisfactory Poor Recommend electrician evaluate/repair Romex BX cableConduit Knob/Tube Double tapping Wires undersized/oversized breaker/fusePanel not accessible Not evaluated
Reason:
Comments
Photos
Main panel located on the east wall of the garage near the overhead door.
Electric Main disconnect.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 48
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Electric/Cooling System
Labelled breakers - good Evidence of critters in electrical panel.
Aluminum entrance leads with anti oxidation paste - good
200amp breaker Copper and stranded aluminum branch wiring. AFCI breakers tested fine.
Evaporator Coil Section Unit #1
General X Central system Wall unitLocation: Attic Age: 5-6 years
Evaporator coil X Satisfactory Not Visible Needs cleaning Damaged
Refrigerant lines Leak/Oil present Damage Insulation missing X Satisfactory
Condensate line/drain X To exterior To pump Floor drain Other:
Secondary condensate line/drain Present: X Yes No Needed: Yes No Primary pan appears cloggedRecommend technician evaluate
Operation Differential: 22°F
Condition X Satisfactory Marginal Poor X Recommend HVAC technician examine/clean/serviceNot operated due to exterior temperature
Comments
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 49
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Living RoomLiving Room
Location Middle North Wall
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No Operable Receptacles: X Yes No OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
GFCI protected receptacle tested properly
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
1234 street, Nashville, TN 37013 Page 50
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections
Dining RoomDining Room
Location South wall
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes X Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No Operable Receptacles: X Yes No OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors X Walls Ceilings
Doors X None Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
Stretched carpet potential trip hazard recommend evaluation by qualified flooring contractor.
GFCI protected receptacle tested properly.
GFCI protected receptacle tested properly.
This confidential report is prepared exclusively for John Doe©2018 Busy Bee Home Inspections