high & low pressure watermist systems. high pressure water mist system risk: historic building...
TRANSCRIPT
![Page 1: High & Low Pressure Watermist Systems. High Pressure Water Mist System Risk: Historic building – Conference Hall Type of system: Wet - Pre-action Risk:](https://reader036.vdocuments.us/reader036/viewer/2022082709/56649d8d5503460f94a75847/html5/thumbnails/1.jpg)
High & Low PressureHigh & Low Pressure
Watermist SystemsWatermist Systems
![Page 2: High & Low Pressure Watermist Systems. High Pressure Water Mist System Risk: Historic building – Conference Hall Type of system: Wet - Pre-action Risk:](https://reader036.vdocuments.us/reader036/viewer/2022082709/56649d8d5503460f94a75847/html5/thumbnails/2.jpg)
High Pressure Water Mist SystemHigh Pressure Water Mist System
Risk : Historic building – Conference Hall
Type of system : Wet - Pre-action
Risk : OH1 – 830 m2
Nozzle flow rate : 27,5 l/min each
Nozzle Working pressure : 100 bar
System total Flow Rate : 247,5 l/min
Nozzles : No. 120 Semco CEN High Height
Water supply : Semco PU PAH80 ( 4 x 112 l/min)
![Page 3: High & Low Pressure Watermist Systems. High Pressure Water Mist System Risk: Historic building – Conference Hall Type of system: Wet - Pre-action Risk:](https://reader036.vdocuments.us/reader036/viewer/2022082709/56649d8d5503460f94a75847/html5/thumbnails/3.jpg)
High Pressure Water Mist SystemHigh Pressure Water Mist System
Risk : Archives – 3500 m2
Type of system : Deluge – Local applicationNozzle flow rate : 13 l/min eachNozzle Working pressure : 100 barSystem total Flow Rate : 1027 l/min Battery No.1
: 806 l/min Battery No.2: 611 l/min Battery No.3
Total Nozzles : 454 Ultrafog nozzlesWater supply : 31 N2 + 93 H2O Cylinders
![Page 4: High & Low Pressure Watermist Systems. High Pressure Water Mist System Risk: Historic building – Conference Hall Type of system: Wet - Pre-action Risk:](https://reader036.vdocuments.us/reader036/viewer/2022082709/56649d8d5503460f94a75847/html5/thumbnails/4.jpg)
Low Pressure Water Mist SystemLow Pressure Water Mist System
Risk : Gas Turbine Compartment &AuxType of system : Deluge – Local applicationNo of Systems : 23 Italy + 17 TunisieNozzle flow rate : 23,5 l/min eachNozzle Working pressure : 5,5 barSystem total Flow Rate : 376 l/min (GT) + 1100 (Aux)No. Of Nozzles : 16 (GT) + 43 (Aux)Discharge time : 5 minWater Supply : 1000 l + 2200 Pressurized Tanks