Plate No.StandardSTANDARD DETAILS Revised
INSULATED WATERMAIN WAT-11/2019
TYPICAL SECTION
COMPACTED BACKFILL
MINIMUM 2 LAYERS OF HIGHDENSITY POLYETHYLENERIGID INSULATION 8' WIDE BY4" THICK, 6" ABOVEWATERMAIN
BITUMINOUS SURFACE ORGRASSY SURFACE
5'-7' TO TOP OF PIPE
UNDISTURBED SOIL
EXISTING WATERMAIN
TYPICAL INSTALLATION
NOTE:SEAMS SHALL BESTAGGERED IF MORETHAN ONE LAYER ISINSTALLED.
4" MINIMUM
WATERMAIN
HIGH DENSITY POLYETHYLENERIGID INSULATION
8'4'
Plate No.StandardSTANDARD DETAILS Revised
BUTTERFLY VALVE AND BOXTYPICAL INSTALLATION WAT-21/2019
BUTTERFLY VALVE ADAPTOR AS MANUFACTUREDBY ADAPTOR INC. OR APPROVED EQUAL
8 7/8"
END VIEW
8" CONCRETE BLOCK
POWERSEAL VALVE BOX DROP LID ORMUELLER COVERNO. H-10361 OR APPROVED EQUALLABELED 'WATER'
WATER
DROP LID
FINISHED GRADE
ADJUST TOP TO 38" TO 12"BELOW FINISHEDBLACKTOP GRADE OR 1"BELOW FINISHEDBOULEVARD GRADE, ANDSHALL BE SET SO AS TOPROVIDE 12" OF UPWARDADJUSTMENT
BUTTERFLY VALVE BOX DUCTILEIRON POWERSEAL MODEL NO.8860 OR APPROVED EQUAL
BUTTERFLY VALVES 15" ORLARGER, DRESSER 450, ORPRATT GROUNDHOG ORKENNEDY OR APPROVEDEQUAL
BUTTERFLY ADAPTOR ASMANUFACTURED BYADAPTOR INC. ORAPPROVED EQUAL
PROVIDE CONDUCTIVITYSTRAP (TYP.) MINIMUM 1
16" X34" WIDE FLAT COPPER STRAP.
8" CONCRETE BLOCK
EXTENSION PIECES
BOTTOM SECTION
TOP SECTION
7 5/8"
7 3/8" 2"
1 1/2"VARI
ABLE
6 5/8"
7 1/8"
5 3/4"5 1/4"
1 1/2"
VARI
ABLE EXTENSION LENGTHS:
NO. 58- 14"NO. 59- 18"NO. 60- 24"
5 3/4"5 1/4"
1 1/2"
VARI
ABLE
6 1/2"
8"10 1/4"
7 3/8"
2"2"
5 3/4"7 1/8"
7.5'
MIN
. CO
VER
NOTES:NO INSIDE ADJUSTMENT SECTIONSALLOWED.
VALVE AN BOX SHALL BE STRAIGHT,ALLOWING A 4" PVC PIPE TO SLIDEDOWN THE BOX AND OVER THE GATEOPERATING NUT.
OPERATING ROD EXTENSION SHALL BEINSTALLED ON ALL VALVES DEEPERTHAN 9'.
MARK ALL VALVE WITH STEEL POSTAND GATE VALVE SIGN AND LOCATE2.0' TO THE SIDE THAT TRAFFIC ISAPPROACHING. (OFF STREET AREASONLY) SIGN TO FACE TRAFFIC. SEESTANDARD PLATE GEN-5.
OPERATING ROD EXTENSION SHALL BETERMINATED AT A OF 5 FEET BELOWSTREET GRADE.
VALVE BOXES SHALL NOT BE LOCATEDIN CURB AND GUTTER OR WITHIN 12"AWAY FROM LIP OF CURB ANDGUTTER.
FITTINGS SHALL BE FUSION EPOXYCOATED. NUTS AND BOLTS SHALL BECOR-BLUE OR APPROVED EQUAL.
0.5 CY 1 1/2"WASHED ROCK
Plate No.StandardSTANDARD DETAILS Revised
GATE VALVE AND BOXTYPICAL INSTALLATION WAT-31/2019
8 7/8"
POWERSEAL VALVE BOX DROP LID ORMUELLER COVERNO. H-10361 OR APPROVED EQUALLABELED 'WATER'
WATER
DROP LID
FINISHED GRADE
ADJUST TOP TO 38" TO 12"BELOW FINISHEDBLACKTOP GRADE OR 1"BELOW FINISHEDBOULEVARD GRADE, ANDSHALL BE SET SO AS TOPROVIDE 12" OF UPWARDADJUSTMENT
GATE VALVE BOX DUCTILE IRONPOWERSEAL MODEL NO. 8860OR APPROVED EQUAL
GV ADAPTOR ASMANUFACTURED BYADAPTOR INC. OR APPROVEDEQUALSEE DETAIL ABOVE
PROVIDE CONDUCTIVITYSTRAP (TYP) MINIMUM1
16" X 34" WIDE FLATCOPPER STRAP
ALL GATE VALVES SHALLBE OF THE RESILIENTWEDGE TYPECONFORMING TO AWWAC509-80 STANDARDS
8" CONCRETE BLOCKROUND BASE
7 5/8"
7 3/8" 2"
1 1/2"VARI
ABLE
6 5/8"
7 1/8"
5 3/4"5 1/4"
1 1/2"
VARI
ABLE EXTENSION LENGTHS:
NO. 58- 14"NO. 59- 18"NO. 60- 24"
5 3/4"5 1/4"
1 1/2"
VARI
ABLE
6"
7"8 1/8"
7 3/8"
2"2"
5 3/4"7 1/8"
7.5'
MIN
. CO
VER
NOTES:NO INSIDE ADJUSTMENT SECTIONSALLOWED.
VALVE AN BOX SHALL BE STRAIGHT,ALLOWING A 4" PVC PIPE TO SLIDEDOWN THE BOX AND OVER THEGATE OPERATING NUT.
OPERATING ROD EXTENSION SHALLBE INSTALLED ON ALL VALVESDEEPER THAN 9'.
MARK ALL VALVE WITH STEEL POSTAND GATE VALVE SIGN ANDLOCATE 2.0' TO THE SIDE THATTRAFFIC IS APPROACHING. (OFFSTREET AREAS ONLY) SIGN TO FACETRAFFIC. SEE STANDARD PLATEGEN-5.
OPERATING ROD EXTENSION SHALLBE TERMINATED AT A OF 5 FEETBELOW STREET GRADE.
VALVE BOXES SHALL NOT BELOCATED IN CURB AND GUTTER ORWITHIN 12" AWAY FROM LIP OFCURB AND GUTTER.
FITTINGS SHALL BE FUSION EPOXYCOATED. NUTS AND BOLTS SHALLBE COR-BLUE OR APPROVEDEQUAL.
MIDDLE SECTION
EXTENSION PIECES
TOP SECTION
TOP VIEW
SIDE VIEW
9 7/16"7 3/4"
12 9/16"
8 1/4" 1"
14 3/4"
17 1/4"
GATE VALVE ADAPTOR:14" STEEL WITHPROTECTIVE COATING
12" RUBBER GASKETINSTALLED BETWEEN GATEVALVE AND ADAPTOR
0.5 CY 1 1/2"WASHED ROCK
90° BEND45° BEND22 1/2° BEND
0 - SEE NOTE 4
0 - SEE NOTE 4
PLAN 45°BENDS
PLAN 90°BENDS
CONCRETE SHALL BE
IN CONTACT WITH
THIS QUADRANT OF
PIPE
BEDDING MATERIAL
UNDISTURBED EARTH
CONCRETE
SECTION A-APLAN 22 1/2°
BENDS
0 - SEE NOTE 4
3'
MIN.
6"
VARIABLE
90°
D ,D
, D
1 2 3
B
1
A
A
1
B
3
A
A
3
A
2B
2A
BUTTRESS DIMENSIONSPIPE
SIZE
6"
8"
12"
16"
20"
24"
30" -
4'-4"
3'-6"
3'-0"
1'-10"
1'-5"
1'-5"
1
B D
1
1'-5"
1'-5"
1'-10"
2'-0"
2'-8"
3'-0"
- 9'-3"
6'-10"
5'-6'
3'-10"
3'-4"
2'-1"
1'-5"
2
B D
2
1'-5"
1'-6"
2'-0"
3'-0"
3'-4"
3'-10"
6'-0" 17'-0"
9'-8"
8'-4"
6'-2"
4'-9"
2'-8"
2'-1"
3
B D
3
1'-6"
2'-0"
2'-6"
3'-6"
4'-0"
5'-0"
6'-0"
NOTES:
1. SHAPE OF BACK OF
BUTTRESS MAY VERY AS LONG
AS POURED AGAINST FIRM
UNDISTURBED EARTH.
2. DIMENSION C1,C2,C3 SHOULD
BE LARGE ENOUGH TO MAKE
ANGLE 0 EQUAL TO OR LARGER
THAN 45°.
3. DIMENSION A1,A2,A3 SHOULD
BE AS LARGE AS POSSIBLE
WITHOUT INTERFERING WITH
MJ BOLTS.
4. 0 = 45° MINIMUM.
5. PLACE POLYETHYLENE BETWEEN
CONCRETE & PIPE.
C1, C2,
C3
A
A
A
Plate No.StandardSTANDARD DETAILS Revised
CONCRETE THRUST BLOCKING WAT-51/2019
Plate No.StandardSTANDARD DETAILS Revised
IRRIGATION SYSTEM METERINSTALLATION REQUIREMENTS WAT-61/2019
NOTES:1. ANNUAL TESTING OF RPZ REQUIRED.2. REQUIRED EQUIPMENT MUST BE ENCLOSED AND SUPPORTED.3. SLEEVES FOR PIPES IN CONCRETE SLABS SHALL BE PVC OR APPROVED
EQUAL, AND MINIMUM OF ONE NOMINAL SIZE LARGER INDIAMETER THAN THE PIPE.
4. SEE STANDARD PLATE _____ FOR CURB STOP AND WINTERIZINGCURB STOP DETAIL.
PROVIDE SLEEVES(4" MIN) IF PIPEPASSES THROUGHCONCRETE SLAB
PROVIDE SLEEVES(4" MIN) IF PIPEPASSES THROUGHCONCRETE SLAB1"-2" DIAMETER
TYPE "K" COPPERWATER SERVICE
FOR MOREDETAIL SEESTANDARDPLATE WAT-5
90° I.P.T. BRASSBEND & COPPERMECHANICAL JOINT36
" MIN
1"-2" DIAMETERBRASS PIPE
REDUCED PRESSURE ZONEBACKFLOW PREVENTER(RPZ) INCLUDE FULL FLOWBALL VALVES
METER
PRESSURE REDUCINGVALVE REQUIRED BYPLUMBING CODE
FULL FLOWBALL VALVE
C
L
1.5 CUBIC YARD MIN. 1 1/2"WASHED ROCK.COVER WITH POLYETHYLENE.
HYDRANT FLAG ASSPECIFIED
BACKFILL TO BETAMPED
4"X4" VERTICAL BLOCK4"X4" THRUST BLOCK
8" CONCRETE BLOCK
TIE ALL JOINTS WITHMEGALUGS (MIN. 4 REQ.)
3'
5'
8' M
IN.
CONNECT TRACER WIRE TOSNAKE PIT MAGNETIZEDTRACER BOX - CONCRETEDRIVEWAY BOX BYCOPPERHEAD INDUSTRIES,OR EQUAL.
GATE VALVE AND BOXWITH EXTENSION RODGATE VALVE ADAPTORAND 1 1/2" ROCK(SEE WAT - 4)
CONNECT TRACERWIRE TO MAINTRACER WIRE
TOP CURB
TOP NUT
3.0'
RED (WATEROUS ENAMEL NO. V1814-R)
METAL CHAINS
BREAKOFF FLANGEWITH BREAKABLERED COUPLINGS
PLUG DRAIN HOLE WHEREGROUND WATER IS PRESENT
16"
WATEROUS IMPROVED PACER SYTLEWB67-250
2-2.5" HOSE CONNECTION1-4.5" STEAMER CONNECTION
TRACER WIRE:#12 AWG COPPER CLAD STEELMINIMUM 30 MIL HDPE INSULATIONMINIMUM BREAK LOAD:
450 LB (OPEN TRENCH)1,150 LB (DIRECTIONAL DRILL)
Plate No.StandardSTANDARD DETAILS Revised
HYDRANT AND GATE VALVEIN BOULEVARD WAT-71/2019
NOTES:1. ALL HYDRANTS LEADS MUST BE VALVED.2. HYDRANT TO BE 5'-6' BEHIND BACK OF CURB OR 3' BEHIND BIT. TRAIL.3. NO HYDRANTS SHALL BE LOCATED BETWEEN P.C. OR P.T. OF INTERSECTION RADII.4. HYDRANT TO BE WATEROUS W-67-250 PACER W/16' BREAKOFF, #5 NUT, 8' BURY, OPENS LEFT.5. 2 HYDRANT FLAGS PER FIRE HYDRANT ARE REQUIRED (NO SPLINTER PROOF FIBER GLASS AS PRODUCED BY EZ-PRODUCTS IN HUGO, MN
OR APPROVED EQUAL).6. HYDRANT TO BE TIED TO TEE WITH APPROVED RESTRAINING DEVICES, MEGA LUGS OR AS APPROVED BY THE CITY ENGINEER.7. INTERNAL INSERT TOP SECTIONS ARE NOT ACCEPTABLE (FOR G.V. BOX).8. HYDRANTS SHALL BE MARKED WITH APPROVED "OT OF SERVICE" TAGS WHEN INSTALLED.9. "PUMP AFTER USE" PLATES TO BE INSTALLED WHEN "DRAIN HOLES" IN VALVE SEAT ARE OMITTED IN GROUND WATER SITUATIONS.10. ALL GATE VALVES SHALL BE IN ROADWAY.11. 6" GATE VALVES TO BE INSTALLED A MINIMUM OF 7' FROM CENTER OF HYDRANT ON ALL HYDRANT LEADS OR AS CLOSE TO HYDRANT
TEE AS POSSIBLE.12. A ONE-PIECE HEAVY DUTY OPERATING VALVE ROD IS REQUIRED ON HYDRANTS THAT ARE EXTENDED 24" OR MORE.13. WHEN INSTALLING A HYDRANT ROD EXTENSION THE NONBREAKABLE COUPLING SLEEVES GO ON THE BOTTOM AND THE BREAKABLE
SLEEVES GO ON THE TOP OF THE EXTENSION ROD. VERIFY "TOP AND BOTTOM" OF BREAKOFF SECTION.14. THE WB-67-250 PACER REQUIRES THE OIL RESERVIOR BE FILLED WITH FOOD GRADE MINERAL OIL.15. TOUCH UP HYDRANT PAINT (WITH AFC WATEROUS RED) AFTER TURF ESTABLISHMENT AS DIRECTED.16. FITTINGS SHALL BE FUSION EPOXY COATED. NUTS AND BOLTS SHALL BE COR-BLUE OR APPROVED EQUAL.
C
L
1 CUBIC YARD MIN. 1 1/2"WASHED ROCK.COVER WITH POLYETHYLENE.
HYDRANT FLAG ASSPECIFIED
BACKFILL TO BETAMPED
4"X4" VERTICAL BLOCK
4"X4" THRUST BLOCK
8" CONCRETE BLOCK
TIE ALL JOINTS WITHMEGALUGS (MIN. 4 REQ.)
3'
5'
8' M
IN.
CONNECT TRACER WIRE TOSNAKE PIT MAGNETIZEDTRACER BOX - CONCRETEDRIVEWAY BOX BYCOPPERHEAD INDUSTRIES,OR EQUAL.
GATE VALVE AND BOXWITH EXTENSION RODGATE VALVE ADAPTORAND 1 1/2" ROCK(SEE WAT - 4)
CONNECT TRACERWIRE TO MAINTRACER WIRE
TOP CURB
TOP NUT
3.0'
RED (WATEROUS ENAMEL NO. V1814-R)
METAL CHAINS
BREAKOFF FLANGEWITH BREAKABLERED COUPLINGS
PLUG DRAIN HOLE WHEREGROUND WATER IS PRESENT
16"
WATEROUS IMPROVED PACER SYTLEWB67-250
2-2.5" HOSE CONNECTION1-4.5" STEAMER CONNECTION
TRACER WIRE:#12 AWG COPPER CLAD STEELMINIMUM 30 MIL HDPE INSULATIONMINIMUM BREAK LOAD:
450 LB (OPEN TRENCH)1,150 LB (DIRECTIONAL DRILL)
Plate No.StandardSTANDARD DETAILS Revised
HYDRANT AND GATE VALVEIN PAVEMENT WAT-81/2019
NOTES:1. ALL HYDRANTS LEADS MUST BE VALVED.2. HYDRANT TO BE 5'-6' BEHIND BACK OF CURB OR 3' BEHIND BIT. TRAIL.3. NO HYDRANTS SHALL BE LOCATED BETWEEN P.C. OR P.T. OF INTERSECTION RADII.4. HYDRANT TO BE WATEROUS W-67-250 PACER W/16' BREAKOFF, #5 NUT, 8' BURY, OPENS LEFT.5. 2 HYDRANT FLAGS PER FIRE HYDRANT ARE REQUIRED (NO SPLINTER PROOF FIBER GLASS AS PRODUCED BY EZ-PRODUCTS IN HUGO, MN
OR APPROVED EQUAL).6. HYDRANT TO BE TIED TO TEE WITH APPROVED RESTRAINING DEVICES, MEGA LUGS OR AS APPROVED BY THE CITY ENGINEER.7. INTERNAL INSERT TOP SECTIONS ARE NOT ACCEPTABLE (FOR G.V. BOX).8. HYDRANTS SHALL BE MARKED WITH APPROVED "OT OF SERVICE" TAGS WHEN INSTALLED.9. "PUMP AFTER USE" PLATES TO BE INSTALLED WHEN "DRAIN HOLES" IN VALVE SEAT ARE OMITTED IN GROUND WATER SITUATIONS.10. ALL GATE VALVES SHALL BE IN ROADWAY.11. 6" GATE VALVES TO BE INSTALLED A MINIMUM OF 7' FROM CENTER OF HYDRANT ON ALL HYDRANT LEADS OR AS CLOSE TO HYDRANT
TEE AS POSSIBLE.12. A ONE-PIECE HEAVY DUTY OPERATING VALVE ROD IS REQUIRED ON HYDRANTS THAT ARE EXTENDED 24" OR MORE.13. WHEN INSTALLING A HYDRANT ROD EXTENSION THE NONBREAKABLE COUPLING SLEEVES GO ON THE BOTTOM AND THE BREAKABLE
SLEEVES GO ON THE TOP OF THE EXTENSION ROD. VERIFY "TOP AND BOTTOM" OF BREAKOFF SECTION.14. THE WB-67-250 PACER REQUIRES THE OIL RESERVIOR BE FILLED WITH FOOD GRADE MINERAL OIL.15. TOUCH UP HYDRANT PAINT (WITH AFC WATEROUS RED) AFTER TURF ESTABLISHMENT AS DIRECTED.16. FITTINGS SHALL BE FUSION EPOXY COATED. NUTS AND BOLTS SHALL BE COR-BLUE OR APPROVED EQUAL.
0.5 CY 1 1/2"WASHED ROCK
Plate No.StandardSTANDARD DETAILS Revised
PIPE CASINGTYPICAL INSTALLATION WAT-91/2019
IN CASING, PLASTIC SPACERSNOT TO SCALE
MAX 2'FROM END
OF PIPE
MAX 8'EQUALLY SPACED
MAX 8'EQUALLY SPACED
MAX 2'FROM END
OF PIPE
PHOENIX PLASTIC CASING SPACEROR APPROVED EQUAL
WATER MAIN/FORCE MAIN PIPE SUPPORT
CASING PER SPECIFICATION
CARRIER PIPE
FILL VOID AREAWITH SAND (TYP)
VARIABLE PVC
WATERMAIN
(SEE PLAN)
45° BEND
MECH. COMPACTED
SELECT GRANULAR
BACKFILL
OBSTRUCTION
GRADE
45° BEND
2'-0"
45° BEND
SEE PLAN
MIN
. 7.5'
NOTE:1. ALL FITTINGS SHALL BE FUSION BONDED EPOXY COATED DUCTILE IRON TO MEET OR EXCEED
ANSI/AWWA C550 AND C116/A21.16 REQUIREMENTS.
2. MEGALUGS WILL NOT BE ALLOWED ON ANY CIP WATER MAIN.
3. SELECT GRANULAR WILL BE REQUIRED BETWEEN INSULATION, WATER MAIN, AND OBSTRUCTION.
4. ALL BENDS SHALL HAVE MEGALUGS OR TIE RODS WITH BLOCKING IN ACCORDANCE WITH STANDARDPLATE WAT-03.
5. COPPER TRACER WIRER SHALL BE USED ON PVC WATER MAIN.
6. ALL WATER MAIN BOLTS SHALL BE CORE-BLUE OR APPROVED EQUAL.
MIN. 3"
INSULATION
MIN
.
6
"
3/4" STAINLESS OREPOXY COATED TIERODS, ORMEGALUGS.
3/4" STAINLESS OREPOXY COATED TIERODS, OR MEGALUGS.
3/4" STAINLESS OREPOXY COATED TIERODS, OR MEGALUGS.
SELECT GRANLUAR
Plate No.StandardSTANDARD DETAILS Revised
WATERMAIN OFFSET WAT-101/2019
CITY
MAIN
GATE VALVE & BOX
WITH EXTENSION
6" DIP FIRE PROTECTION
FROM CITY WATER MAIN
BASEMENT FLOOR
INDIVIDUAL METERS AND
VALVES PER UNIT.
NOTE: ALL METERS MUST BE LOCATED IN A
CENTRAL ROOM AT POINT WHERE
WATER SERVICE ENTERS BUILDING.
IRRIGATION LINES MUST ALSO HAVE
SEPARATE METER IF LINE IS
CONNECTED PRIOR TO MAIN.
ONE MAIN METER
BILLING GOES TO MANAGEMENT
COMPANY INDIVIDUAL METERS
MAY BE ADDED FOR EACH UNIT
FOR MANAGEMENT BILLING
BREAK DOWN.
TO
FIRE PRO
TECTIO
N
12"
MIN
.
VALVE
VALVE
MAIN
METER
Plate No.StandardSTANDARD DETAILS Revised
MULTIPLE UNITS USINGMAIN WATER METER WAT-111/2019
CITY
MAIN
GATE VALVE & BOX
WITH EXTENSION
6" DIP FIRE PROTECTION
FROM CITY WATER MAIN
BASEMENT FLOOR
INDIVIDUAL METERS AND
VALVES PER UNIT AND
IRRIGATION WATER.
NOTE: ALL METERS MUST BE LOCATED IN A
CENTRAL ROOM AT POINT WHERE
WATER SERVICE ENTERS BUILDING.
IRRIGATION LINES MUST ALSO HAVE
SEPARATE METER IF LINE IS
CONNECTED PRIOR TO MAIN.
INDIVIDUAL METERS
PER UNIT AND EACH UNIT IS
BILLED SEPARATELY.
TO
FIRE PRO
TECTIO
N
12"
MIN
.
Plate No.StandardSTANDARD DETAILS Revised
MULTIPLE UNITS USINGINDIVIDUAL WATER METERS WAT-121/2019
Plate No.StandardSTANDARD DETAILS Revised
WATERMAIN PLUGTYPICAL TIE BACK WAT-131/2019
NOTES:1. TIEING BACK IS TO BE CONSIDERED INCIDENTAL TO INSTALLATION
OF WATERMAIN. NO COMPENSATION WILL BE PAID THEREFORE.2. TIEING BACK OF THE PLUG IS TO BE DONE IN ADDITION TO NORMAL
BLOCKING AGAINST UNDISTURBED SOILS.
RETAINER GLAND (TYP) AS APPROVEDBY THE CITY ENGINEERING DEPT.
58" DIA. THREADED STEELCOATED ROD (MIN. 2PER PLUG)
Plate No.StandardSTANDARD DETAILS Revised
HDPE PIPEWATERMAIN OR SANITARY FORCEMAIN WAT-141/2019
NOTES:1. FOR ALL HDPE PIPE OR EQUAL, INSTALL A TRACER WIRE OF 12 GA.
MINIMUM DIAMETER. APPLIES TO WATERMAIN OR SANITARYFORCEMAIN ONLY.
2. ATTACHE TRACER WIRE SECURELY TO PIPE WITH DUCT TAPE OREQUAL.
3. TRACER WIRE TO BE BROUGHT TO SURFACE AT GATE VALVELOCATIONS AND AIR RELEASE MANHOLES.
DUCT TAPE OR APPROVED EQUAL
GRADE
12 GA. TRACER WIRE ORAPPROVED EQUALHDPE PIPE OR EQUAL
(WATERMAIN OR SANITARYFORCEMAIN)
VARI
ABLE
SEE
PLAN