hidrolik vs elektrik

Upload: amin-danar-noviyanto

Post on 04-Apr-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 Hidrolik vs Elektrik

    1/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 1

    1. Introduction

    Hydraulic systems are in widespread use throughout all fields of modern engineering

    applications. The pump geometry causes volume flow pulsations, which lead to suchdisturbing effects as increased noise development or vibrations, for example, either

    directly or after being converted into structure-borne and/or air-born noise. In addition

    to this, the pulsations put a strain on the pipeline systems and the systems

    connected up downstream, particularly in the vicinity of the resonant frequency.

    The experiments performed in the anechoic room at the Institute of Fluid Power

    Transmission and Control at RWTH Aachen (IFAS) included an investigation into the

    noise development of hydraulic pumps, for example, in order to optimise the

    Automated self-regulating system for a low reflection line

    termination (RALA)

    Dipl.-Ing. S. Schellinger

    Dipl.-Ing. E. Goenechea

    Institute for Fluid Power Drives and Controls (IFAS), RWTH Aachen

    Hydraulic components have been the subject of air-borne, fluid-borne and

    structure-borne noise measurements conducted in the anechoic room at the

    IFAS for many years now. In an effort to avoid the influences exerted on the

    studied components by the hydraulic circuit in the anechoic room, a so-called

    RALA, which is a low reflection line termination (RALA is an abbreviation of the

    German term ReflexionsarmerLeitungsabschluss), is used to terminate the

    high-pressure side of the circuit. This article describes an algorithm, which is

    capable of setting the optimum operating point for a RALA of this nature. In

    future, this will enable measurements to be made with working points which

    alter in real time.

  • 7/29/2019 Hidrolik vs Elektrik

    2/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 2

    vibration, radiation and/or pulsation behaviour. Only the sound phenomenon

    attributable to the pump should be measured and evaluated to enable a comparison

    of the results measured for all pumps. Standing waves, which may be produced byreflections at the end of the line, would make the results measured for the tested unit

    dependent on the system connected to the pump.

    One possible means of suppressing these reflections has already been developed at

    the IFAS. The RALA comprises an adjustable shutter, with volume connected up

    downstream.

    Analogous to a so-called terminating resistor, which is used to prevent reflections at

    the end of the cable in an electrical system, the RALA is fitted between the pumpoutput and the load in a hydraulic system.

    This means that a reflection-free state can be achieved as a function of pressure,

    temperature and volume flow for every operating point by altering the shutter. The

    pulsation at the RALA end of the tested unit is therefore no longer determined by the

    geometry of the hydraulic system.

    Up to now, the RALA developed at the IFAS has been trimmed manually, by

    comparing the shapes of the two pressure signals and then turning an adjusting

    screw to reduce or increase the shutter aperture. Using this method, the ideal

    operating point was characterised by the fact that, apart from phase and amplitude,

    the two pressure signals were identical.

    The development of the self-regulating system has led to a situation in which the

    pressure signals can now be analysed by computer and adjustment of the shutter

    aperture is controlled by a motorised, automated system on the basis of this data, so

    that the RALA adopts the optimum reflection-free operating point for every working

    point of the tested unit without any interaction.

  • 7/29/2019 Hidrolik vs Elektrik

    3/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 3

    Figure 2: The hydraulic circuit with low reflection line termination RALA (5) and

    motorised adjusting unit (9 & 10)

    2. Use of the RALA

    The RALA is part of a hydraulic circuit, as shown in Figure 2. The circuit essentially

    comprises a hydraulic pump (1) with drive motor (2), the high-pressure line (3) with

    two dynamic pressure measuring points (4a and 4b) and the RALA (5). A pressure

    control valve (6) is fitted downstream of the RALA in the hydraulic circuit to simulate a

    load. A static pressure sensor (7) and a temperature sensor (8) enable monitoring of

    the operating pressure and temperature. The high-pressure line, which runs between

    the pump and the RALA must be as smooth and free of interference as possible. The

    two dynamic pressure sensors (4a and 4b) are positioned one meter apart and

    register the pressure pulsation. Made up of piezoelectric elements, the pressure

    sensors supply charge fluctuations, which are converted into voltage signals by

  • 7/29/2019 Hidrolik vs Elektrik

    4/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 4

    measuring amplifiers. These voltage signals used to be compared visually until the

    self-regulating system was developed. A hydraulic actuator was used to adjust the

    shutter of the RALA manually for optimum trimming of the line for the respectiveworking point. The automated self-regulating system now performs this function and

    controls the shutter aperture in such a way as to ensure that the reflection-free state

    is adopted at all times.

    3. The reflection-free terminating resistor

    Theoretically speaking, the RALA constitutes an infinitely long line in the hydraulic

    system. The pulsation wave continues to runs along it until it is transformed by

    dissipation. The reflection factor is zero. There is an electrical analogy to this

    situation.

    Figure 3: Analogies between a hydraulic pipeline and an electrical cable

  • 7/29/2019 Hidrolik vs Elektrik

    5/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 5

    A terminating resistor is connected to the end of an electrical cable to prevent

    induced waves being reflected. All waves are absorbed by the terminating resistor as

    long as it matches the line impedance.There are also electrical analogies for other components in a hydraulic system. This

    is illustrated in Figure 3 with reference to a hydraulic pipeline and an electric cable.

    Figure 4: Equivalent electrical circuit diagram of a hydraulic line and an electricalcable

    Figure 4 shows the equivalent circuit diagram of a line, whereby its characteristic

    wave impedance is given by:

    CjG

    LjRZline +

    +=

    )( where f 2= (1)

    The dashed values are per unit length, i.e. they are given in [unit per metre].

    Figure 5: Equivalent electrical circuit diagram of the hydraulic circuit

  • 7/29/2019 Hidrolik vs Elektrik

    6/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 6

    Figure 5 shows the equivalent electrical circuit diagram of the hydraulic circuit. The

    impedance of the pump and the line impedance are combined into Z1 upstream of thefirst dynamic pressure, and the impedance of the pressure control valve (DBV (6) in

    Figure 2) is combined with the line impedance from the pressure control valve to the

    oil tank, that constitutes the hydraulic zero potential (p = 0 bar), into Z2. The pressure

    pulsations at the two measuring points correspond to the alternating voltage U1 and

    U2 in the equivalent electrical circuit diagram. The terminating resistance is given by:

    2min 1 ZsCRZ volumeshutteratingter += (2)

    The reflection factor is determined by:

    lineatingter

    lineatingter

    ZZ

    ZZsr

    +

    =

    min

    min)( (3)

    In conjunction with (2), this gives the frequency-dependent reflection factor at the

    RALA:

    )(

    )(

    )(

    )()(

    20

    10

    KKs

    KKs

    ZR

    ZRsr

    lineshutter

    lineshutter

    ++

    ++

    +

    = (4)

    where

    2

    0

    1

    ZCK

    volume = (5)

    )(

    11

    lineshuttervolume ZRCK = (6)

    )(

    12

    lineshuttervolume ZRCK

    += (7)

    As far as the trimmed RALA is concerned, the shutter resistance is the same as the

    line impedance

    ( lineshutter ZR = ) and the reflection factor is therefore r(s) = 0.

  • 7/29/2019 Hidrolik vs Elektrik

    7/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 7

    Figure 6: Pole/zero diagram of a low pass

    The following applies if the shutter of the RALA has been closed too far:

    lineshutter ZR > :20

    100)( KKs

    KKsHsr++++= where K1>K2. If the reflection factor is interpreted

    as being a transfer function, the value of the zero (numerator from formula 4) is greater than

    the value of the pole (denominator from formula 4) ( PSNS > ). The pole and zero are

    entered in the diagram in Figure 6. This corresponds to the pole/zero diagram for a low pass.

    If the shutter of the RALA has been opened too far, given by:

    lineshutter ZR < :20

    100)(

    KKs

    KKsHsr

    ++

    ++= where K1

  • 7/29/2019 Hidrolik vs Elektrik

    8/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 8

    4. The algorithm

    The algorithm is based on the assumption that an ideally trimmed RALA prevents

    reflection of the pressure pulsations. The reflection factor of a poorly trimmed RALA,

    on the other hand, has either high pass or low pass characteristics. In this case,

    excitation takes the form of the dynamic pressure fluctuation produced by the volume

    flow pulsation of the connected pump.

    The wave timetables for the three operating states show the way in which the

    respective operating state can be detected from the dynamic pressure signal using

    Fast Fourier Transformation (FFT). To illustrate this, the Fourier coefficients shown in

    the diagram of the wave timetables have been restricted to two orders of different

    frequencies.

    Figure 8: Wave timetable of the trimmed RALA

  • 7/29/2019 Hidrolik vs Elektrik

    9/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 9

    The amplitudes of the pressure pulsations in the hydraulic system are attenuated by

    around 6 dB for all operating frequencies in the experimental set-up. As far as the

    forward wave is concerned, the ratio of the two harmonics at the first pressure sensorremains the same after running through the one-meter long pipe to the second

    pressure sensor (Figure 8). The reflective properties of the RALA are what alter the

    ratio of the harmonics at the two pressure sensors, enabling the algorithm to detect

    the current operating state and to correct it in order to achieve a reflection-free state.

    An untrimmed RALA reflects pressure pulsations as a function of the frequency,

    whereby the reflection factor has low pass characteristics, i.e. low frequencies are

    reflected to a greater extent than high frequencies if the shutter has been closed toofar (Figure 9).

    Figure 9: Wave timetable of the hydraulic system with low pass termination

  • 7/29/2019 Hidrolik vs Elektrik

    10/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 10

    If the shutter has been opened too far, the reflection factor adopts high pass

    characteristics, i.e. high frequencies are reflected to a greater extent than low

    frequencies (Figure 10).

    Figure 10: Wave timetable of the hydraulic system with high pass termination

    The algorithm is based on the Fourier Transformation (FT), which maps the signals

    from the time domain onto the frequency domain. In mathematical terms, this

    transformation is described by

    +

    = dtetfF tj )()( (8)

    and is founded on the theory that each signal can be broken down into a series of

    sinusoidal oscillations of different frequencies and amplitudes. The American

    scientists Cooley und Tukey have devised a number of algorithms which reduce the

    computing time required to form the Fourier integral considerably. These have

    become well known as the Fast Fourier Transformation (FFT) and are frequently

  • 7/29/2019 Hidrolik vs Elektrik

    11/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 11

    used as they reduce the computing time to a minimum while maintaining sufficient

    accuracy.

    Each of the two dynamic pressure sensors detects the sum of the forward and returnpulsation waves at the two measuring points 4a and 4b (refer to Figure 2). The

    control algorithm then forms the FFT for both pressure signals. These pressure

    signals may contain harmonics up to the tenth order, for instance. The control

    algorithm uses two of these harmonics for the calculation and produces ratios for

    both measuring points. The RALA has assumed a reflection-free state if the two

    ratios are the same. If the difference between the two ratios does not equal zero, the

    shutter must be opened or closed according to the sign preceding the difference.5. The hardware

    The algorithm described above was initially tested on a mobile RALA with electrical

    adjustment. The electrical components of the automated RALA can be divided into

    three areas: signal recording, signal processing and control signal output.

    The pulsation signals are recorded by two dynamic pressure sensors. The

    construction of the sensors is such that they supply a charge signal which is

    proportional to the pulsation signal. This charge signal is converted into a voltagesignal in the measuring amplifiers and is routed to the line input of a sound card in

    the computer (Figure 11).

  • 7/29/2019 Hidrolik vs Elektrik

    12/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 12

    Figure 11: Block diagram of the electrical system for the automated RALA

    The computer processes the signals by applying the above-mentioned algorithm to

    them in order to subsequently transmit a control signal to the motor controller via theRS232 interface. A power pack feeds a 24 V / 10 A power supply to this motor

    controller, which then controls the servo motor for the shutter. With 50 to 60

    revolutions per minute, this servo motor produces 10 Nm of torque. The RALA has

    been designed for operating pressures up to 250 bar. The 5 Nm maximum torque

    required to adjust the RALA was determined at its adjusting spindle at this operating

    pressure.

    When the end position of the spindle is reached - determined by the geometry of the

    RALA and interpreted by a ten-turn limit switch potentiometer - a limit switch analyser

    (Figure 12) generates a TTL signal, which is sent to the motor controller (Figure 11)

    and inhibits the appropriate direction of rotation for the motor. This means, for

    example, that when the shutter is closed, the end of the spindle cannot be run into it

    any further, thereby preventing the spindle becoming jammed in the shutter aperture.

  • 7/29/2019 Hidrolik vs Elektrik

    13/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 13

    Figure 12: Circuit diagram of the limit switch analyser

    In Figure 12, component Ref01 supplies a exactly 10 V as the reference voltage.

    This 10 V supply is fed to three potentiometers: the setting potentiometer for the

    upper limiting value (end mark 1), the setting potentiometer for the lower limiting

    value (end mark 2) and the potentiometer on the outside of the RALA, which reads

    out the current position. The potentiometers act as voltage dividers here, which

    means that they supply a voltage between zero and ten volts according to their

    respective positions. Component TL074 contains four operational amplifiers (OP),

    whereby two of them are used. The voltage from the external potentiometer is

    supplied to the negative input of one operational amplifier and the positive input of

    the other. The voltages supplied by the other two potentiometers are fed into the

    other operational amplifier inputs. The operational amplifier compares the two applied

    voltages in the following way: if the voltage at the positive input (+) is greater than at

    the negative input (-), voltage is applied to the output. The output voltage is used to

    give a visual indication with an LED, to generate a TTL signal and to switch a relay. If

    one of the LEDs lights up, this means that the RALA has reached an end position.

    The motor controller uses the two TTL signals to inhibit the motor's respective

    direction of rotation. When one of the end marks is reached, the relay switches a

  • 7/29/2019 Hidrolik vs Elektrik

    14/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 14

    pulsation signal to earth. This measure was initially intended to improve the reliability

    of the system as a whole, with the information about reaching one of the end marks

    being received by both algorithm and computer. However, the algorithm has provedto be so reliable in service that this information is not needed. The measuring

    amplifier can now supply the pulsation signal to the computer directly, without having

    to pass through the analyser.

    An adapter cable is required to supply the pulsation signals to the line input on the sound card.

    This cable has two BNC connectors of the standard type used in metrology at one end and a

    3.5 mm stereo jack plug of the standard type used in PC and hi-fi technology at the other end.The pin assignments are in accordance with the DIN stereo standard for the left and right-

    hand channels when the experimental set-up is arranged in the following way from left to

    right: pump, first pressure sensor, second pressure sensor, RALA. This adapter also offers a

    means of making the pressure signals audible for the human ear through a stereo system as the

    pulsation signals are within the 50 Hz to 5000 Hz range.

    As a rule, the levels used in measuring systems are between 10 V and + 10 V,

    whereas the levels used in hi-fi technology are generally between 1 V and + 1 V.

    To reduce the level of the pressure signals down to sound card level, the gain of the

    measuring amplifier must be reduced to such an extent that the maximum amplitude

    does not exceed 1 volt.

    The pressure signals may be input and the control signal for the motor output via the

    sound card. In this case, the motor should be controlled by means of a pulse-width-

    modulated signal (PWM). The computer is currently reading the two pressure signals

    in via the sound card and outputs the control signal for the motor via the serial RS232

    interface.

    6. Determining the quality of the reflection-free state

    The forms of the two pressure signals are compared in the time domain in order to

    determine the quality of the RALA setting. With the distance between the two

    pressure sensors amounting to approximately one metre, a wave peak (marked in

    green in Figure 13) reaches the second sensor approx. 0.77 ms (where

  • 7/29/2019 Hidrolik vs Elektrik

    15/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 15

    smcl /1300= ) later than the first. Dissipation weakens the amplitude by around

    factor 2)( =G . This corresponds to an attenuation of dBGA 6)(log20)( == .

    Figure 13: The time signals for the pulsations

    Time lag (phase) and amplitude attenuation both depend on numerous factors (e.g.

    temperature and medium). An algorithm which compares the forms of the two signals

  • 7/29/2019 Hidrolik vs Elektrik

    16/16

    O + P lhydraulik und Pneumatik 46 (2002) Nr. 4 16

    in the time domain and, as a result, reflects the quality of reflection freedom,

    therefore presupposes dynamic compensation of these differences.

    The result is output to a virtual oscilloscope. Figure 13(b) shows the oscilloscope for

    a perfectly trimmed RALA. Figure 13(c), on the other hand, shows an RALA setting

    that needs to be re-adjusted. The curve forms are not the same in spite of the

    standardisation. The green curve representing the difference between the two

    pulsation signals, which is a straight line in the ideal case of the perfectly trimmed

    RALA (refer to Figure 13(b)), degenerates into a waveform in Figure 13(c).

    The area under the difference curve is evaluated in order to assess the setting of theRALA. The value of the difference curve and the integral of this value must be

    calculated for this. The RALA is perfectly trimmed if the value of the integral is zero.

    The RALA requires re-adjustment if the value is greater than zero.

    7. Conclusion

    The algorithm discussed in this article offers a faster, more accurate means of

    evaluating a hydraulic pump than has been possible up to now. This is because

    previous methods defined the parameter fields to be measured, which werecharacterised by discrete rpm, pressure and volume flow values, as well as

    temperature values where applicable. The RALA was adjusted manually for each

    working point. The RALA had to be trimmed before conducting the measurements.

    The algorithm finds the optimum reflection-free working point quickly and reliably. As

    a result of this, the developed algorithm can be used to run through extensive ranges

    of pressure, rpm and volume flow values while the RALA adjusts automatically in real

    time. It is now possible to conduct measurements during pump acceleration, whichcover the entire rpm range of the pump and this data can then undergo an order

    analysis, for example. The acquisition of cascade diagrams in real time is also

    conceivable, indicating FFT spectra of the pressure pulsation at the high-pressure

    connection of a pump as a function of the pressure. Measuring techniques like this

    and the ability to measure up to eight sound, pressure and/or acceleration signals at

    the same time facilitate the localisation of resonance effects within a pump

    considerably.