heating demand as frequency controlled regulation power
DESCRIPTION
http://www.ijep.org/paperInfo.aspx?ID=14344 This paper examines the possibility of using heating demand as a source of Demand as Frequency controlled Reserve (DFR) in the electric power system, with focus on heat pumps in conjunction with thermal storage. The potential regulation capacity is estimated and control strategies are discussed. The behaviour of a large number of aggregated on/off regulated heating units with thermal storage is investigated and it is found that their combined response can approach that of a linear proportional control if the operational timescale (given as storage capacity divided by maximum heat consumption) is sufficiently large. The laboratory implementation and testing of DFR with various control algorithms is presented and possible scenarios for practical implementation are discussed. The power system impact of DFR with linear proportional control is assessed via simulations in MATLAB/Simulink and it is found that DFR can have a positive impact ifTRANSCRIPT
www.ijep.org International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014
22
Heating Demand as Frequency Controlled
Regulation Power Claus Nygaard Rasmussen*1, Christian Brandt Rasmussen2, Salih Palivan3, Robin Bogø4
Department of Electrical Engineering, Technical University of Denmark
Elektrovej, bld. 325. DK‐2800 Kgs. Lyngby, Denmark
*[email protected]; [email protected]; [email protected]; [email protected]
Received 6 January 2014; Accepted 16 January 2014; Published 19 May 2014
© 2014 Science and Engineering Publishing Company
Abstract
This paper examines the possibility of using heating demand
as a source of Demand as Frequency controlled Reserve (DFR)
in the electric power system, with focus on heat pumps in
conjunction with thermal storage. The potential regulation
capacity is estimated and control strategies are discussed.
The behaviour of a large number of aggregated on/off
regulated heating units with thermal storage is investigated
and it is found that their combined response can approach
that of a linear proportional control if the operational
timescale (given as storage capacity divided by maximum
heat consumption) is sufficiently large. The laboratory
implementation and testing of DFR with various control
algorithms is presented and possible scenarios for practical
implementation are discussed.
The power system impact of DFR with linear proportional
control is assessed via simulations in MATLAB/Simulink and
it is found that DFR can have a positive impact if the
regulation constant and system delay does not exceed certain
limits; otherwise there is a risk of self‐imposed oscillations. It
is found that with the right form of control, DFR can assist in
ensuring stability in systems with high penetration of
renewable energy sources, by providing a large fraction of
the required regulation capacity.
Keywords
Renewable Energy; System Integration; Thermal Storage; Heat
Pumps; Frequency Control
Introduction
In Denmark there are plans for increasing the amount
of wind power in the electric power system to 50%
within the coming decade, and other countries have
similar plans for large scale introduction of renewable
energy. The stochastic nature of wind‐ and solar power
poses a problem because the fast fluctuating power
from those sources must be continuously matched to
the load demand in order to maintain system stability.
Conventional dispatchable generation units are often
not capable of regulating their power outputs fast
enough and the amount of dispatchable generation
capacity will decrease as the share of stochastic
renewable sources increase.
The solution to this problem will most likely be a
combination of several measures. Increased
transmission capacity can reduce the fluctuations
through aggregation and energy storage units or
generation units with high ramp rates can step in to
close gabs between load and demand.
Another interesting approach is to introduce demand
response by adjusting the load according to the
available generation. Demand response can turn load
into an additional regulation reserve and thereby
potentially help solving the stability problem.
Demand response can be obtained either by direct or
indirect control of loads. Indirect control can be based
on a price signal that loads adjust to or a locally
measurable parameter such as power flow, voltage or
frequency. The idea of using load demand as
frequency controlled regulation reserve is attractive
because the regulation signal is available everywhere
and frequency controlled regulation is already an
essential part of the power system. The concept of
Demand as Frequency controlled Reserve (DFR) has been
studied in relation to partially flexible electric demand
such as household appliances, and in particular
refrigerators and freezers(Xu, Østergaard and Togeby
2011),(Nyeng, Miertz and Østergaard 2010)but such
loads suffer from a lack of freedom to perform real‐
time adjustments of power consumption due to small
buffering capacity and user‐imposed restrictions.
International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014 www.ijep.org
23
In this paper we evaluate frequency controlled
demand as a tool to help solve the power system
stability problem arising due to increased penetration
of stochastic renewable power sources. The Danish
power system is used as an example with focus on the
use of flexibility related to heating with heat pumps.
Heating as DFR is of particular interest in countries
with a large heating demand, and the flexibility of
thermal loads is usually large due to the presence of
significant thermal storage capacity in buildings,
heating systems and storage tanks. The ability of heat
pumps to move highly needed flexibility from the
heating system into the power system makes them
very interesting and DFR is one of the ways to facilitate
this link.
The work presented here is related to the Strategic
Platform for Innovation and Research in Intelligent
power (iPower) which is a national Danish research
project funded by the council for Strategic research and
the council for Technology and Innovation.
Heat Pumps as Regulation Power
The annual electric power consumption in Denmark is
36 TWh and the heating demand is approximately 55
TWh(Dyrelund 2009)corresponding to an average
electric load of 4.1 GW and an average thermal load of
6.3 GW. The heating demand is therefore
approximately 1.5times the electric load – on average.
A large part of the heating demand in Denmark is
covered by district heating and this will likely continue
to be so in the coming decades. But a fraction of the
district heating could also be covered by heat pumps in
order to facilitate the use of cheap excess electricity
from wind power production. According to(Dyrelund
2009) the amount of heating covered by domestic heat
pumps will increase to 7 TWh in 2050, while the
amount of district heating supplied by heat pumps will
increase to approximately 4 TWh. A total of 11 TWh or
20% of the heat demand will thus be covered by heat
pumps and the average heat supplied by heat pumps
will therefore be 1.26 GW. The ability of heat pumps to
act as a link between the heating system and the
electric power system might encourage policy makers
to promote the use of heat pumps and this estimate of
future heat pump penetration could therefore be
regarded as being conservative.
The ratio between moved heat and electric power
consumption of a heat pump is known as its
Coefficient of Performance (COP). The COP decreases
with increasing temperature difference. For domestic
heat pumps working between an ambient temperature
of Ta = 5⁰C and a hot water tank with Th = 50⁰C the COP
value is typically in the range of 3 to 4. Table 1 shows
values leading to a conservative estimate of the future
amount of heat‐based DFR.
TABLE 1 ESTIMATED FUTURE AMOUNT OF DFR BASED ON HEAT PUMPS
Parameter Average
value
Total heat demand [GW] 6.3
Share of demand covered by heat pumps [%] 20
COP of heat pumps 3.5
Electric consumption by heat pumps [MW] 360
Electric consumption by heat pumps [p.u.] 0.09
The estimated average electricity consumed by heat
pumps amounts to 360 MW. This could be compared
to the consumption by refrigerators and freezers,
which has been estimated to approximately 90 MW in
the eastern part of Denmark (Xu, Østergaard and
Togeby 2011) ‐ corresponding to approximately 240
MW in Denmark as a whole.
An operational timescale(τs) for an energy storage unit
or energy buffer can be defined as its maximum energy
storage capacity (Emax) divided by its maximum power
consumption (Pmax).
eq.1
Refrigerators and freezers have much smaller energy
storage capacity than typical domestic or centralised
heating facilities and therefore shorter operational
timescales. Parameter values from (Nyeng, Miertz and
Østergaard 2010)have been used to estimate the
timescale of are frigerator to approximately 20 minutes.
The storage timescale related to heating with heat
pumps is determined by the thermal storage capacity
of the house itself and/or the capacity of a designated
storage unit (typically a hot‐water tank) placed in
conjunction with the heat pump. The storage capacity
of an average Danish house was found to be
approximately 13.3 kWh/K (Bogø 2013). With an
allowed temperature span of 2⁰C and a nominal
thermal load of 6.3kW this leads to a storage timescale
of 4.2 hours.
District heating facilities may have much larger storage
capacities and correspondingly longer storage
timescales. As an example, the heating facility at
Marstal in Denmark is equipped with a 1.5 MWel heat
pump and a storage tank of 2100 m3 (Fjernvarme 2014).
The storage timescale of this facility can be estimated
to ~14 hours by assuming a heat pump COP of 3.5 and
a temperature span of 30⁰C.
www.ijep.org International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014
24
Seasonal Variations
Heat consumption is subject to very large seasonal
variations which strongly affect the ability of heat
pumps to act as DFR. The amount of electricity that
heat pumps consume is influenced by the inside‐to‐
outside temperature difference, both directly and via
the heat pump COP. Figure 1 shows the relative
monthly consumption of electricity by heat pumps.
FIG. 1SEASONAL VARIATIONS IN ELECTRICITY CONSUMED BY
HEAT PUMPS IN A 2050 SCENARIO, IN UNITS OF
AVERAGE(360MW) CONSUMPTION(BOGØ 2013)
Heating with heat pumps cannot be seen as a stable
source ofDFR on a seasonal scale. During the summer
period some heat pumps will continue to supply hot
water or provide air‐conditioning while others remain
completely turned off. The active heat pumps will
maintain power flexibility but the average electric
power consumption dictates the overall amount of
available DFR.During summer, DFR based on heat
pumps will therefore mainly have to be used as
primary regulation on short timescales.
The Need for Frequency Controlled Regulation
It is relevant to make a distinction between two types
of service that DFR potentially could supply.
Type 1 is Frequency controlled Disturbance Reserve
(FDR), where demand acts as stand‐by reserve in case
of disturbances that displaces the grid frequency by
more than ±0.1 Hz. The timescale of this type of
operation would be similar to that of primary (and to
some extend secondary) regulation power, i.e. up to 15
minutes or slightly longer. The secondary generation
reserve must according to rules respond fully within 15
minutes (Bogø 2013) and DFR will therefore not be
required to respond beyond this timescale. But the
response will typically have to be fast (<1 second) and
with high power.
Type 2 is Frequency controlled Normal operation
Reserve (FNR), where demand supplies frequency
controlled regulation power while the frequency
remains within 50 ±0.1 Hz. This operation would be
continuous and therefore supplement primary,
secondary as well as tertiary regulation power. FNR
requires a relatively long storage timescale of
operation (large energy storage capacity) but less
power and not necessarily a fast response. This type of
DFR can reduce the need for continuous regulation
from generators but the required amount of frequency
controlled regulation is usually rather small(Hirth and
Ziegenhagen 2013). The issue of how response time
and operational timescale influence the effect that DFR
has on the power system will be discussed in the next
section.
Presently, the average amount of FNR in Denmark is
23MW (≈0.006 p.u.)(Bogø 2013), and heat pumps
should be able to supply this amount during most of
the time. An increasing amount of wind power in the
system will result in larger power fluctuations on short
timescales. The present standard deviations of ramp
rates in the Danish power system are3.5 MW pr.
minute for load power and 2 MW pr. minute for wind
power(Bogø 2013), resulting in a total standard
deviation of ramp rates in regulation power of 4 MW
pr. minute.
An increase in wind penetration from 21 % to 50 %
would cause the standard deviation of ramp rates in
regulation power to increase to 5.7 MW/min. It seems
reasonable to expect a similar increase in the need for
frequency controlled normal operation reserve (FNR),
that is, up to approximately 33 MW. But this is also a
quite modest amount that could easily be covered by
the projected future amount of DFR.
Fast fluctuations on a timescale from seconds up to
minutes are handled by frequency controlled primary
and secondary regulation, while variations on longer
timescales are handled by manual regulations reserves
(tertiary regulation). Based on data from (Energinet.dk
2013) the average manual regulation reserve in
Denmark can be estimated to approximately 200 MW.
Regulation is therefore primarily manual, taking place
on a longer (>15 minute) timescale with the aim of
closing the gap between day‐ahead planed production
and the actual need for production.
Most types of DFR could possibly perform both types
of frequency control (FDR and FNR). However, if a
large amount of DFR is active there is a risk of over‐
activation, depending on the sensitivity and reaction
time of the DFR controls. This issue will be discussed
in the next section.
International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014 www.ijep.org
25
TABLE 2 EXAMPLE OF LINEAR DFR CONTROL BASED ON FREQUENCY AND TEMPERATURE
f ↓ T → T < Tmin Tmin < T < T0 T0 < T < Tmax Tmax < T
f < fmin P0
, ·
Pmin
fmin < f < f0 ·
f0 < f < fmax · , ·
P0
fmax < f Pmax
Control Options
Frequency control can be performed in several ways,
depending on the type of load and the desired effect on
the power system. The focus here is on thermal loads,
which may be divided into resistive loads and heat
pumps.
One way of controlling heat loads is indirectly via the
thermostat set‐points as proposed by (Xu, Østergaard
and Togeby 2011),(Nyeng, Miertz and Østergaard
2010)and others. In this approach the thermostat set‐
points (Tmin and Tmax) become functions of frequency as
they are shifted up‐wards when the frequency
increases and vice versa. While being simple and
relatively easy to implement, this approach will result
in a partly delayed response that might have
unwanted effects. Other ways of introducing DFR in a
more direct manner will be considered and discussed
in this section.
Linear Proportional Control
Resistive loads could be subjected to linear
proportional control similar to the droop control used
by generators. But there is an important difference
between a generator and a heat‐load DFR. The
generator is capable of delivering continuous
regulation power while the heat‐load is limited by the
energy capacity of its thermal storage. The primary
objective of a heating system is to keep the temperature
within predefined limits and this puts boundaries on
its ability to respond to frequency changes.
Operation schemes that respond to both temperature
and frequency has been suggested by (Bogø 2013) and
(Pehlivan 2013). In the approach suggested in (Bogø
2013) a set of temperature boundaries (Tmin and Tmax)
and frequency limits (fmin and fmax) defines the control.
The power (P0) which is required to maintain the
temperature of the household or water tank at a
constant level is assumed to remain approximately
constant on the timescale of DFR operation. The
electric power consumption (P) varies between Pmin
and Pmax as defined in table 2. Figure 2 shows P(T,f) for
a DFR unit with selected parameters.
This control scheme prevents abrupt changes in power
consumption as the temperature or frequency
approaches the boundaries, and the combined effect of
many DFR units will be to counteract frequency
deviations from f0 (50 Hz) and stabilise the system.
The size of the combined DFR response from many
units will be determined by the control parameters and
obviously the number of active units. The control
response is semi‐proportional and the control ‘constant’
(Kp) depends on the number (N) of active units and the
current status of each unit.
, · , ∑ , eq. 2
Fully proportional control cannot be obtained because
of non‐linear behaviour of units that are either on the
temperature‐ or frequency boundaries or outside these
boundaries.
FIG. 2 EXAMPLE OF POWER AS FUNCTION OF TEMPERATURE
AND FREQUENCY FOR A DFR UNIT WITH LINEAR CONTROL
(BOGØ 2013)
The response from linear DFR seems straightforward
and easy to predict. It will act in parallel with
frequency controlled regulation from generators and
reduce the need for their activation. But there is a
problematic issue related to the possibility of over‐
www.ijep.org International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014
26
reaction, an issue which relates to reaction time and
sampling rate of the DFR control.
Power System Frequency Variations
In order to evaluate the influence of reaction time it is
relevant to look at the timescales on which the power
system frequency varies. Figure 3 shows a plot of
frequency data from the Danish power system during
a 10 hour period (top) and a zoom of 10 minutes
(bottom). The plot shows variations on two different
timescales; a short timescale with a period of ≈1 minute
and a long timescale with a period of 1‐2 hours.
The standard deviation of the measured frequency is
42 mHz and the amplitude of the fast variations is
approximately 40 mHz. From the relation between
frequency and rotational energy in the system it is
possible to estimate the power variations that these
fluctuations correspond to.
FIG.3 MEASURED FREQUENCY VARIATIONS OVER TIME SPANS
OF 10 HOURS (TOP) AND 10 MINUTES (BOTTOM)
The power imbalance can be expressed as:
∆·
· eq.3
With H ≈ 5 seconds being the inertial time constant of
the system and f0 = 50 Hz. A frequency change rate of
40 mHz in 30 seconds corresponds to small power
imbalances of ∆P ≈ 2.7∙10‐4 p.u. or 1.1 MW.
DFR can enforce or generate power‐ and frequency
fluctuations if it reacts too slowly or if the proportional
constant is too high. A short reaction time for DFR (e.g.
a second or less) will tend to reduce the problem
because the frequency will have little time to change
before DFR reacts to it. A fast response could be
implemented for linear resistive loads but the response
time will always be larger than the sampling time and
a sampling rate of one second or less therefore appears
to be necessary.
A more sophisticated PID control could also be
employed. Self‐induced fluctuations could be
dampened by a differential term which will reduce
power change rates. But this approach does not seem
attractive due to high complexity and lack of
knowledge about the system. In praxis it will not be
possible to set the regulation constants to optimal
values.
Longer reaction time obtained with an integral
regulator could to some extend be useful, but this will
prevent a fast response to fast disturbances and FDR
operation would not be possible. In Figure 3 a 5‐
minute moving average of the frequency has been
included. Control based on such an average could be
used for units with delayed response to prevent self‐
induced frequency oscillations. The unit would
respond to general trends rather than fast variations
and this would likely be a better approach to control of
DFR as normal reserve. But abrupt changes in
frequency due to grid disturbances would not result in
an immediate response from such a unit and it is
especially the ability of DFR to respond faster than
most generators that makes it an interesting addition to
a power system with a large fraction of fast fluctuating
power sources.
A possible compromise that would allow DFR to act
both as FNR and FDR would be to react slowly to
small deviations from f0 and faster to large deviations
from f0. In this way FNR could be performed with an
integral regulator or similar, and DFR would be
activated in case of larger disturbances. One example
of such a regulation could be:
·1
, | | ∆
· , | | ∆ eq. 4
Where K1 and K2 are regulation constants and τ is an
appropriate time constant of e.g. 5 minutes. Fast
regulation is activated for frequency deviations above
∆fmax which could be set to 100mHz.
On/off Control
Heat pumps can typically not be regulated with linear
control only. Some heat pumps are entirely on/off
regulated while others can be linearly controlled
within a certain power range. With such constrains the
previously described linear control scheme cannot be
utilised.
International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014 www.ijep.org
27
On/off regulation has been described in e.g.(Biegel, et
al. 2013). The most simple on/off regulation turn the
appliance on when the frequency is above 50 Hz and
off when the frequency is below 50 Hz. With the fast
frequency variations show in figure 3 an aggregation
of loads with such regulators would constantly switch
between on and off and thereby generate large power
fluctuations which would destabilise the system.
Simulations have shown that when the amount of
active DFR exceeds a critical level, synchronised on/off
regulated loads will tend to increase frequency
variations rather than reduce them.
One way to improve the control properties of on/off
regulated units is to introduce a frequency hysteresis
equivalent to the temperature hysteresis normally used
for on/off regulation and thereby prevent fast
fluctuations around 50 Hz. Frequency‐ and
temperature control can be combined to obtain a
hysteresis area as shown in figure 4. Units with
temperature and frequency corresponding to the red
area are off and units in the green area are on. In the
‘maintain state’ area units are in the state in which they
entered that area. This means that only units with
storage temperatures within a certain temperature
range will react instantly to a change in frequency and
the fraction of units that react instantly will be
proportional to the size of the frequency change. In this
way the aggregated response from many units
becomes less abrupt and fast fluctuations between the
two states are prevented.
Assuming that this type of control is implemented on a
large number of heating units with more or less
randomly distributed power levels, thermal storage
capacities, temperature limits and heat loads, what will
then be their aggregated effect on the power system? If
the temperatures of all units have been fully
randomised, then a linear relation will exist between
frequency and the fraction of units in the on‐state. This
means that the aggregated response from a large
number of randomly distributed units will be linear.
But a fully random distribution of temperatures cannot
be expected. There is a risk of synchronisation because
the units will be exposed to similar variations in
ambient temperature and to the exact same frequency
variations. A fraction of units will also be at, or outside,
the temperature limits. This further reduces the extent
to which unit temperatures will be randomly
distributed and thereby producing a linear aggregated
response.
FIG.4 AN EXAMPLE OF DOUBLE HYSTERESIS ON/OFF CONTROL
BASED ON FREQUENCY AND TEMPERATURE
Probabilistic Control
Simulations of the aggregated response from many
on/off regulated units have been made in order to
determine to which extend they can be assumed to
produce a linear response. Such simulations can only
give an indication of the combined behaviour because
the input parameters can be varied over a wide range.
The simulation results show that the timescale of
operation has a strong influence on the linearity of the
aggregated response from on/off controlled units. A
short timescale allows for little freedom of operation
with unit states that are determined by temperature
rather than frequency and this leads to a small amount
of correlation between frequency and DFR power. A
long timescale on the other hand, will result in more
operational freedom and improved linearity.
A total of 100 heat pumps with thermal storage were
modelled, each with a nominal electric power of 2 kW
and a COP of 3.5.In the reference case the average
thermal storage capacity was equal to that of an
average Danish household (Mieritz 2010) and the
temperature span of operation was between 18⁰C and
22⁰C. This results in a timescale of operation of 4.2
hours.
In order to create a semi‐random distribution of unit
states the input parameters where randomly
distributed within certain intervals and the initial
temperatures were randomly distributed within the
allowed temperature span. The simulations ran over 18
hours with a time resolution of approximately 0.3s and
the results from two simulation cases are shown in
figure 5as the relation between frequency and
www.ijep.org International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014
28
aggregated power consumption.
FIG.5AGGREGATED RESPONSE FROM 100 ON/OFF REGULATED
UNITS WITH AVERAGE (TOP) AND LONG (BOTTOM)
TIMESCALE OF OPERATION
The top graph shows the reference case in which the
timescale of operation is equal to that of an average
household (4.2 hours). There is a modest correlation
between frequency and power, and a linear fit gives a
coefficient of determination (R2) equal to 0.63.
In the bottom graph the timescale has been increased
to 42 hours and heat pumps are therefore free to
operate in relation to frequency. This result in a much
more linear relation between frequency and power and
a linear fit gives a coefficient of determination (R2)
equal to 0.93.
A long operational timescale can be obtained either by
increasing the thermal storage capacity, by increasing
the allowed temperature span of operation or, by
reducing the heat consumption and thereby the
required nominal power of the heat pump. Future
buildings will most likely have long thermal timescales
due to improved thermal insulation and build‐in
thermal storage such as phase‐change materials. An
example of an existing modern household with very
long thermal timescale is the Energy Flex house
operated by the Danish Technological Institute(Ravn
og Grimmig 2011).
Another issue that needs to be considered is delayed
response from individual units. The ‘maintain state’
area in figure 4 will prevent units from fast toggling
between on and off, but in order to protect heat pumps
it might in any case be necessary to add a constrain
saying that it must remain in a given state for a certain
amount of time. This limits the change‐rate of the
combined response but it also tends to prevent self‐
induced oscillations in case of over‐reaction.
Voltage Controlled Reserve
Flexible loads such as heat pumps could also act as
Demand as Voltage controlled Reserve (DVR). This type of
control can be seen as a counterpart to DFR but its
effect on the power system is different. Voltage can be
viewed is a local parameter while frequency is a
system‐level parameter and this has several
implications on the way that DVR affects the system.
Loads cause voltage drops in the local system and
proportional DVR control will be a stabilising factor.
But a few relatively large loads may have a large local
effect, especially if they are placed in areas with ‘weak’
connections. This increases the risk of over‐reaction
and self‐induced oscillations but it also increases the
possibilities for active use of loads in relation to system
stability etc.
The simplest way of implementing DVR is with linear
proportional control as stated in equation 5.
· eq.5
Where V0 is a reference voltage (e.g. 230 V) and K is a
regulation constant which must depend on the size
and placement of the actual DVR‐controlled unit.
Voltage is also influenced by the reactive power
consumption and this makes voltage control more
complicated.
A detailed evaluation of the effects of voltage control
must be done for a specific network and such an
evaluation is beyond the scope of this work. But DVR
is a very interesting control option for e.g. low voltage
grids with large penetration of photovoltaic generation
and/or electric vehicles.
Experimental Testing
Testing of the DFR (and DVR) concepts have been
made with the set‐up sketched in figure 6. The central
component in the testing is the DFR smart‐box(P. J.
Douglass, R. Garcia‐Valle, et al. 2012), (P. J. Douglass,
et al. 2011)which has been developed at the Technical
University of Denmark, Centre for Electric Power and
Energy (CEE). The DFR smart‐box records voltage and
frequency and usually controls a relay or a thermostat.
In this set‐up the DFR box controls a Pulse Width
Modulation (PWM) circuit which can operate either
with a high switching frequency to provide linear
regulation or as a relay to provide on/off regulation.
The PWM circuit, which is shown in figure 7, uses an
optic coupling to provide galvanic insulation between
the DFR box and the AC line‐voltage.
International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014 www.ijep.org
29
The thermal system consists of an electric heater and a
water‐tank with a circulation pump to ensure a
uniform temperature distribution. The water
temperature measurement is returned to the computer
via the DFR‐box and the computer also receives
voltage‐ and frequency data.
A display‐ and control user interface has been
implemented in MATLAB(Klingest 2012) and this
interface has been further developed to allow the user
to test various control algorithms (Pehlivan 2013).The
user controls the system via the computer but it is
possible to store the control software as embedded
MATLAB on a Digital Signal Processor (DSP) which
can then be included in the DFR smart‐box. In this way
it is possible to implement a chosen control algorithm
via the DFR smart‐box.
FIG. 6 SKETCH OF EXPERIMENTAL SET‐UP
FIG. 7 PWM CIRCUIT FOR CONTROL OF THERMAL LOAD
(PEHLIVAN 2013)
The tests have provided ‘proof of concept’ for several
control algorithms but the actual implementation of
DFR will be a trade‐off between control options and
ease of implementation. Various ways of practical
implementation will be discussed in the last section of
this paper.
Power System Impact
The objective of introducing DFR is to increase power
system stability and provide additional regulation
power. In order to evaluate the extent to which it is
able to do this, afew relatively simple power system
models have been made and tested. The models were
implemented in MATLAB/Simulink assuming a
system like the one sketched in figure 8. In order to
limit complexity it was decided to model the DFR
response as being linear and the decision to do so was
based on the results obtained from simulation of
aggregated on/off controlled units.DFR can therefore
in this simulation be viewed as operating in parallel
with frequency controlled generators, but with a
smaller time‐delay.
The issue of response time is a trade‐off; between a fast
response with a corresponding risk of over‐reaction
and self‐induced oscillations, and a slower response,
that does not fully utilise the benefits of DFR as
disturbance reserve but prevents oscillations.
FIG. 8 SKETCH OF A SIMPLIFIED POWER
SYSTEM CONTAINING DFR
DFR acting as Disturbance Reserve
The effect of DFR as disturbance reserve is illustrated
by figure 9. A load step of 0.6 % will, according to
equation 3, cause the frequency to drop at a rate of
approximately 25mHz/s. The frequency will drop until
a sufficient amount of controllable generation has been
activated, but the limited generation ramp rate delays
this activation and the frequency drops by 112mHz
before it starts to increase again.
FIG. 9 SIMULATED RESPONSE TO A LOAD
STEP OF 0.6 % (BOGØ 2013)
www.ijep.org International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014
30
The situation is different when fast‐acting DFR is
present. The power imbalance is matched within a few
seconds, the frequency only drops by approximately
6mHz and the stationary error is also smaller. This
indicates that DFR has a large potential as disturbance
reserve in systems with small amounts of controllable
generation.
DFR as Frequency Controlled Normal Reserve
In order to investigate the situation when DFR is acting
as frequency controlled normal reserve (FNR) two time
series (of wind power and load consumption) are
needed as input data. Data from 2013, available on the
homepage of the Danish transmission system operator
with a temporal resolutionof5 minutes were used.
When DFR acts as FNR the effect is to move part of the
actual regulation from generators to DFR. Since DFR
and generators act in parallel, the amount of regulation
supplied by each part will depend on the relative
amounts of active control power and their regulation
constants. When the amount of regulation supplied by
generators decrease, their ramp rates also decrease.
Figure 10 shows the simulated influence of DFR on
generator ramp rates and system frequency. With the
introduction of 0.1 p.u. of DFR the standard deviation
of generator ramp rates is reduced from1.4∙10‐3p.u. pr.
minute to 1.2∙10‐3 p.upr. minute and large ramp rates
are almost eliminated.
FIG.10 SIMULATED EFFECT OF DFR ON GENERATOR RAMP
RATES AND FREQUENCY IN A SYSTEM WITH 21 % WIND
PENETRATION
The introduction of DFR also results in a reduction in
standard deviation of the frequency due to the extra
regulation capacity which results in a stronger
regulation response. Lower ramp rates allow for less
utilisation of controllable generation but it is more
difficult to evaluate the benefits of smaller frequency
deviations.
The amount of DFR and the length of its response
delay turn out to be critical parameters. If DFR
responds too strongly to a frequency change, or with
too much delay, then self‐induced oscillations may
occur and the presence of DFR tends to have a negative
effect on the system, with larger frequency deviations
and increased generator ramp rates.
DFR in Conjunction with Scheduled Power
Another way to evaluate DFR is to assume that
conventional generation from e.g. combined heat and
power plants (CHP) only provides scheduled power
and DFR therefore has to cover the entire need for
regulation. Figure 11 shows an example of simulated
system balance over a period of 120 hours with wind
power data multiplied by a factor of approximately 2.5
to reach a wind penetration of 50 %. The conventional
(CHP) power follows an hourly schedule with small
adjustments to remove stationary frequency errors.
The maximum ramp rate of conventional power is 2%
pr. Minute in this simulation and the DFR control is
proportional with a regulation constant of KDFR = 1 p.u.
/Hz. The maximum ramp rate of conventional
regulation is essential for the outcome of the
simulation because it determines how much regulation
that must be provided by DFR. A maximum of 2% pr.
minute is a rough estimate based on data from
(Suwannarat 2007).
When load exceeds wind power DFR provides the
necessary regulation power to close the gap between
load and scheduled generation.
DFR is capable of keeping the frequency deviations
within 0.1 Hz. The maximum DFR power is 0.1 p.u.
but during 96% of the time it remains within 0.03
p.u.This means that even without intra‐hour regulation
it is possible to supply the required regulation and
maintain system stability with 0.1 p.u. of DFR.
The energy buffering that DFR needs to perform is
found as the integral of the DFR power. Figure 11
shows that this power integral remains below 1.5
p.u.∙ minute. The amount of DFR in the system is equal
to 0.1 p.u. and the required energy buffer therefore
corresponds to nominal DFR power for 15 minutes.
This is small compared to the earlier estimated
domestic heating timescale of 4.2 hours.
International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014 www.ijep.org
31
FIG.11 RESULT OF POWER SYSTEM SIMULATION WITH 50% WIND PENETRATION AND DFR REGULATION
Implementationof DFR
In the previous sections we have discussed the
properties and effects of DFR but unsolved issues
remain with regard to practical implementation. The
technical issues relate e.g. to the type of control, where
the control hardware should be physically placed and
how the input parameters should be chosen. There are
also economic aspects to consider as well as the role of
DFR seen in relation to e.g. price signal control or
direct control of load demand.
There are several possible scenarios with regard to
implementation of DFR; a selection is listed below:
1) Control hardware with imbedded software is built
into the appliance (e.g. a heat pump) at the
manufacturer. A few control parameters may be set by
the user but most of them are fixed. There is no
payment to the consumer for DFR services but a
discount could be given to customers who choose this
option. The discount could be paid for by the
transmission system operator (TSO) and added to the
cost of electricity or paid for by savings in payment for
frequency controlled reserve supplied by generators.
2) DFR control hardware and software is sold as add‐
ons for existing appliances. This option is difficult and
not likely to be used because the individual add‐on has
to work with the control that is already built into the
appliance. This means that e.g. thermostat set‐points
must be changed by the add‐on and it must therefore
be custom‐made to the appliance control. But for
simple resistive loads the add‐on option could be
attractive and easy to use. The cost of such add‐ons
could be returned to the consumers by the TSO or DSO
via an electricity price reduction for customers who
purchase DFR add‐ons.
3) DFR control could be one of the features of smart‐
grid control boxes or advanced smart‐meters installed
in private homes and industry. Possibly the DSO or
TSO would have the option to set certain critical
control parameters in order to be able to adjust the
strength of the DFR response. The main feature of such
a control box would likely be control based on
electricity prices and price forecasts, with DFR as a
possible supplement. This option seems attractive since
DFR in itself will likely not be attractive enough to
make costumers interested.
4) DFR is implemented only in relation to large central
loads and generation, such as, district heating plants,
combined heat‐and‐power plants, large public or
residential buildings and large industry. This is a
realistic scenario since it can be done with minor
changes to the present praxis. Larger loads (e.g. above
100kW) will in this scenario be able to sell frequency
controlled regulation capacity to the TSO and provide
it with their own equipment.
5) Another possibility is that the need for frequency
controlled regulation will not become large enough to
make DFR relevant. The need for fast regulation will
increase but the amount of conventional generation
will remain large enough to cover the relatively
www.ijep.org International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014
32
modest needs for decades to come. Even if the amount
of conventional generation is reduced dramatically a
large fraction of the regulation requirement could most
likely be obtained via electricity‐price based control as
part of a smart‐grid.
Conclusions
The analysis presented here shows that heat pumps
with thermal energy storage in a likely future (year
2050) scenario will constitute at least 0.09 p.u. and
thereby have sufficient regulation capacity to be able to
supply the full need for frequency controlled
regulation in the Danish power system, and even be
able to cover a substantial part of the inter‐hour
regulation requirement. The simulations have
indicated that the concept of Demand as Frequency
controlled Reserve (DFR) is useful and relevant but
there are potential complications. There is a danger of
overreaction and self‐induced oscillations if the DFR
response is too strong or too slow compared to the
system response. If managed the right way, DFR is
found to have a positive impact on the power system,
with smaller ramp rates of conventional generation
and smaller frequency deviations.
Simulations have also indicated that the combined
response from a large number of on/off regulated DFR
heating units may approach a proportional response if
the individual units are in random temperature states,
but large thermal energy storage capacity is required to
ensure this.
Experimental testing of a range of control algorithms
has shown how the concept can be implemented in
conjunction with thermostat regulation to maintain
user satisfaction and supply frequency regulation at
the same time. The exact choice of control algorithm
must be based on a range of technical requirements,
user requirements and power system requirements.
The issue of practical implementation of DFR remains
open. There is currently no obvious way for system
operators to measure and pay individual consumers
for this service and it is unclear how regulation
parameters should be controlled to ensure a positive
impact on the system. A possible first step could be to
expand the current market for frequency controlled
regulation power to include large flexible loads. Later
on, DFR control could be built into flexible devices,
primarily heat pumps and electric vehicle chargers and
ultimately it could perhaps become a short‐timescale
supplement to price control, as one of several features
of smart‐homes and smart‐grids.
ACKNOWLEDGEMENT
Part of this work has been financed by the
Danishipower project. The authors would like to thank
the council for Strategic research and the council for
Technology and Innovation for their support to this
project.
REFERENCES
Biegel, Benjamin, Lars Henrik Hansen, Palle Andersen,
and Jakob Stoustrup. “Primary Control by ON/OFF
Demand‐Side Devices.” IEEE Transactions on smart
grid, 2013: 2061‐2071.
Bogø, Robin Alexander. Investigation into demand as
frequency reserve. Copenhagen: Technical University
of Denmark, 2013.
Douglass, Philip J, Rodrigo Garcia‐Valle, Preben
Nyeng, Jacob Østergaard, and Mikael Togeby.
“Demand as Frequency Controlled Reserve:
Implementation and practical demonstration.” IEEE
PES Innovative Smart Grid Technologies Conference
Europe. Manchester, 2011.
Douglass, Philip J. Demand as frequency controlled reserve:
Water Treatment, Reley‐controlled Loads, Micro‐grid.
Copenhagen: Technical University of Denmark,
2012.
Douglass, Philip J., Rodrigo Garcia‐Valle, Preben
Nyeng, Jacob Østergaard, and Mikael Togeby.
“Smart Demand for Frequency Regulation:
Experimental Results.” IEEE TRANSACTIONS ON
SMART GRID, 2012.
Dyrelund, Anders. Heat plan Denmark. Copenhagen:
Ramboll, 2009.
Energinet.dk.
http://www.energinet.dk/DA/El/Engrosmarked/.
Energinet.dk. 2013. (accessed 2013).
Fjernvarme, Marstal. www.marstal.dk. 2014. (accessed
January 21, 2014).
Hirth, Lion, and Anka Ziegenhagen. “Control Power
and Variable Renewables: A Glimpse at German
Data .” 10th International Conference on the European
energy Market. Stockholm, 2013.
Klingest, Adam Hoffmann. Præsentation og analyse af
on‐line målinger vha. DFR‐smartbox. Copenhagen:
Technical University of Denmark, 2012.
International Journal of Energy and Power (IJEP) Volume 3 Issue 2, May 2014 www.ijep.org
33
Mieritz, Casper Falkenstrøm. Aggregate modeling and
simulation of price responsive heat pumps. Copenhagen:
Technical University of Denmark, 2010.
Nyeng, Preben, Casper F. Miertz, and Jacob
Østergaard. “Modelling and simulation of power
system balcancing by distributed energy resources
and flexible demand.” IEEE Transactions on Power
systems 513 (2010).
Pehlivan, Salih Aki. Demand as frequency controlled
reserve. Copenhagen: Technical University of
Denmark, 2013.
Ravn, Ole, and Mikael Grimmig. Energy Flex House,
Developing energy efficient technologies ‐ Meeting the
global challenges. Copenhagen: Danish Technological
Institute, 2011.
Suwannarat, Akarin. Integration and control of wind
farms in the Danish electricity system. Aalborg:
Aalborg University , 2007.
Xu, Zhao, Jacob Østergaard, and Mikael Togeby.
“Demand as frequency controlled reserve.” IEEE
Transactions on power systems 26 (2011): 1062‐1071.
Claus Nygaard Rasmussen received a M.Sc. (Eng.) and a
Ph.D. from the Technical University of Denmark in 1997 and
2004. He is now Associate Professor at the Centre for Electric
Power and Energy (CEE) at the Technical University of
Denmark.
Christian Brandt Rasmussenreceived a B.Sc. (Eng.) from the
Technical University of Denmark in 2008. He currently works
as Development Engineer and Project Manager at the Centre
for Electric Power and Energy (CEE) at the Technical
University of Denmark.
Salih Palivan received a M.Sc. (Eng.) from the Technical
University of Denmark in 2013.
Robin Bogø received a M.Sc. (Eng.) from the Technical
University of Denmark in 2013. He is currently employed at
the Danish National Railways.