heating / air conditioning pulsar radiant panel / air conditioning pulsar radiant panel quality...
TRANSCRIPT
Heating / Air Conditioning
Pulsar Radiant Panel
Quality management systemsISO 9001 – Cert. n° 0545/5
ENVIRONMENTAL COMFORT
CONTENTS• INTRODUCTION Page 3• MAIN ADVANTAGES OF THE PULSAR Page 4• TECHNICAL SPECIFICATIONS Pages 5 / 20• MEAN SURFACE TEMPERATURE OF THE PULSAR PANEL Page 21• LOWEST WATER FLOW Page 21• PRESSURE DROP Pages 21 / 22• WATER CONNECTION DIAGRAM Page 23• OPERATING LIMITS Page 23• SUGGESTED LOWEST INSTALLATION HEIGHT Page 23• TABLE OF POSSIBLE COMBINATIONS Page 24• POSSIBLE CONNECTIONS Page 24• ACCESSORIES Page 25 / 26• HANGING SYSTEMS Page 27• INTEGRATION WITHIN FALSE CEILINGS Page 28• PULSAR WITH PERFORATED PANEL Page 28• NON-ACTIVE AESTHETIC PANEL Page 29• ACCESSORIES FOR PANELS NOT INSTALLED INTO FALSE CEILINGS Page 30
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time,without the requirement to promptly update this piece of literature, any changes that it considers usefulfor the purpose of improvement or for any other manufacturing or commercial requirements.
ENVIRONMENTAL COMFORT
HeatingAir Conditioning
Pulsar
3
SABIANA is the leading company in Europe in the design, production and sale of radiant panelsoperating on hot water, high temperature hot water and steam.
Since 1971, over 5 million square metres of panels installed in different environments (small, mediumand large industries, hangars, gyms and theatres, small and large offices) prove the quality of theSABIANA radiant heating system and products.
Heat by radiation means absolute silence, no movement of air and a uniform temperature in theentire environment. In effect, being distributed better, the heat is more pleasant and comfort isoptimised, without increasing the air temperature. The result is a feeling of absolute comfort withan air temperature that is 3°C lower than the operative temperature perceived by people.
The efficiency of the SABIANA radiant panels is also economic. In fact, besides the energy savingsdue to the fact that the operative temperature is different from the air temperature, this totally staticproduct does not, unlike the traditional systems, have an electric motor and does not requiremaintenance nor the consumption of electricity.
This translates into long-lasting efficiency. The SABIANA radiant panels have a practically unlimitedduration.
The SABIANA radiant panels can be described as the hygienic heating system par excellence.The system does not create noise nor movement of air and therefore dust. In addition, it avoidsannoying streams of air and the circulation of germs, dust and fragrances and thus representsan important contribution to the prevention of allergies and illnesses.
INTRODUCTION
Pulsar
4
THERMAL PERFORMANCE
- The PULSAR radiant panel is totally static (no circulation of air and no movement of dust).- Very low thermal gradient between the floor and the ceiling.- Extremely fast response to changes in settings, without thermal inertia.- The operating principle of the PULSAR radiant panels is reversible, and thus cooling operation is possible using the radiant ceiling panels, by connection to a chiller or heat pump.
APPEARANCE
- None of the peripheral walls are affected by the installation.- The PULSAR radiant panel can be perfectly integrated into all types of false ceiling.- The visible side is perfectly smooth, adapting to any type of architecture.- Other RAL colours available on request.
MODULARITY
- Given its modular dimensions and the design of the water connections, the PULSAR panels can be installed in sequence with ceiling light panels, in complete compliance with the regulations on artificial lighting.
HYGIENE
- The design of the PULSAR panel allows it to be installed in any building, including hospitals and clinics. Indeed, its completely smooth visible surface is recommended, as it allows sanitisation by spraying for combating nosocomial illnesses in hospitals.- The radiation concept, by avoiding considerable movements of air, prevents the spreading of microbes and bacteriological pollution.
SAFETY
- The PULSAR radiant panels are inaccessible to the people in the room. Therefore there is no risk of burning or electric shock in schools and paramedical environments.- No risk of vandalism, in any environment.
COMFORT
- By design, the PULSAR radiant panel guarantees a uniform temperature in all seasons.- The PULSAR radiant panel is a totally static heating system without the circulation of air and without lifting dust.- The operation of the PULSAR is completely silent.- In summer, the PULSAR panel can be used for cooling without creating steams of air and with a uniform temperature throughout the environment.
SAVINGS
- The heating requirement of a building heated with the PULSAR radiant panels is, according to the EN 12831 standard, much lower than the requirement with traditional heating systems.- The experience acquired by SABIANA in the field of radiant panels guarantees the reliability of the PULSAR over time.- The PULSAR does not require special maintenance and consequently has no maintenance costs.
ASSEMBLY
- The dimensions of the PULSAR radiant panels make them easy to handle on site.- The panels are connected by flexible pipes without welding.
CONNECTIONS SUPPLIED NOT MOUNTED
MAIN ADVANTAGES OF THE PULSAR
Pulsar
The SABIANA PULSAR radiant panels are supplied in four sizes, which can be perfectly integrated into any falseceiling.
Indeed, the lengths of 1.20, 1.80, 2.40 and 3.00 m ensure optimum integration into 600 x 600 mm modular ceilings,the standard dimension for false ceiling panels in Europe.
The visible side is perfectly flat, meaning that the PULSAR radiant panels can match all types of false ceiling panelsavailable on the market.
As standard, the panels are supplied in the colour RAL 9016, with a satin finish created by an epoxy-polyester coatdried in a furnace at 180°C. Other RAL colours are also available for the architect to choose from.
The PULSAR radiant panels are made of a radiating galvanized steel plate, 1 mm thick.On the panel is fixed a copper pipe, 0.75 mmthick and with 22 ± 0,5 mm of external diameter.The pipe is oblong-shaped in order to optimizethe contact surface with the radiant panel.The galvanized hanging strips welded to thepanels hold the correct spacing of the tubesand secure the best surface contact betweenthe tube and the panel.
The paint complies with the European Standard 76/769/EEC.
Class of reaction to fire: A1
Emission of the radiant surface: � = 0,96
The PULSAR is supplied with an insulating layerof mineral wool (30 mm thick)protected by an aluminium sheet (25 micron thick)to be mounted on the top of the panel.
Insulation specifications:Class A1 according to EN 13501-1 standards
Thermal conductivity 0,037 W/mK(according to UNI CTI 7745 and UNI FA 112 standard)
Density 14 kg/m3
Thermal resistance 0,81 m2K/W
TECHNICAL SPECIFICATIONS
Technical description
5
P Model
R Model
W Model
Pulsar
6
TECHNICAL SPECIFICATIONS
11951795
13.820.7
1.32.0
P.1P.2
00830900083150
12
SizeP STANDARD Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar P STANDARD
Weights and Dimensions
Pulsar P.1 - Code 0083090
Pulsar P.2 - Code 0083150
Pulsar P installed within false ceilings
Pulsar
7
TECHNICAL SPECIFICATIONS
23952995
27.634.5
2.83.5
P.3P.4
00832100083270
34
SizeP STANDARD Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar P STANDARD
Weights and Dimensions
Pulsar P.3 - Code 0083210
Pulsar P.4 - Code 0083270
Pulsar P installed within false ceilings
Pulsar
8
11951795
13.820.7
1.32.0
PA.1PA.2
00830910083151
12
SizePA Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar PA
Pulsar PA.1 - Code 0083091
Pulsar PA.2 - Code 0083151
TECHNICAL SPECIFICATIONS
Weights and Dimensions
Pulsar P installed within false ceilings
Pulsar
9
23952995
27.634.5
2.83.5
PA.3PA.4
00832110083271
34
SizePA Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar PA
Pulsar PA.3 - Code 0083211
Pulsar PA.4 - Code 0083271
TECHNICAL SPECIFICATIONS
Weights and Dimensions
Pulsar P installed within false ceilings
Pulsar
10
TECHNICAL SPECIFICATIONS
11951795
13.820.7
1.32.0
PB.1PB.2
00830920083152
12
SizePB Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar PB
Pulsar PB.1 - Code 0083092
Pulsar PB.2 - Code 0083152
Weights and Dimensions
Pulsar P installed within false ceilings
Pulsar
11
TECHNICAL SPECIFICATIONS
23952995
27.634.5
2.83.5
PB.3PB.4
00832120083272
34
SizePB Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar PB
Pulsar PB.3 - Code 0083212
Pulsar PB.4 - Code 0083272
Weights and Dimensions
Pulsar P installed within false ceilings
Pulsar
12
TECHNICAL SPECIFICATIONS
Weights and Dimensions
12341858
1421
1.32.0
W.1W.2
00831000083160
12
SizeW STANDARD Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar W STANDARD
Pulsar W.1 - Code 0083100
Pulsar W.2 - Code 0083160
Pulsar W not installed within false ceilings
Pulsar
13
TECHNICAL SPECIFICATIONS
Weights and Dimensions
24823106
2835
2.83.5
W.3W.4
00832200083280
34
SizeW STANDARD Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar W STANDARD
Pulsar W.3 - Code 0083220
Pulsar W.4 - Code 0083280
Pulsar W not installed within false ceilings
Pulsar
14
TECHNICAL SPECIFICATIONS
12341858
1421
1.32.0
WA.1WA.2
00831010083161
12
SizeWA Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar WA
Pulsar WA.1 - Code 0083101
Pulsar WA.2 - Code 0083161
Weights and Dimensions
Pulsar W not installed within false ceilings
Pulsar
15
TECHNICAL SPECIFICATIONS
24823106
2835
2.83.5
WA.3WA.4
00832210083281
34
SizeWA Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar WA
Pulsar WA.3 - Code 0083221
Pulsar WA.4 - Code 0083281
Weights and Dimensions
Pulsar W not installed within false ceilings
Pulsar
16
TECHNICAL SPECIFICATIONS
12341858
1421
1.32.0
WB.1WB.2
00831020083162
12
SizeWB Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar WB
Pulsar WB.1 - Code 0083102
Pulsar WB.2 - Code 0083162
Weights and Dimensions
Pulsar W not installed within false ceilings
Pulsar
17
TECHNICAL SPECIFICATIONS
24823106
2835
2.83.5
WB.3WB.4
00832220083282
34
SizeWB Length
(mm)Weight
(kg)Water content
(litres)Model Code
Pulsar WB
Pulsar WB.3 - Code 0083222
Pulsar WB.4 - Code 0083282
Weights and Dimensions
Pulsar W not installed within false ceilings
Pulsar
18
12551855
14.922.3
1.32.0
R.1R.2
00831100083170
12
SizeR STANDARD Length
(mm)
527.5550
23
HolesP N°
Weight(kg)
Water content(litres)Model Code
TECHNICAL SPECIFICATIONS
Pulsar R STANDARD
Weights and Dimensions
Pulsar R for plasterboard ceilings
Pulsar R.1 - Code 0083110
Pulsar R.2 - Code 0083170
Pulsar
19
24553055
29.737.1
2.83.5
R.3R.4
00832300083290
34
SizeR STANDARD Length
(mm)
563571
45
HolesP N°
Weight(kg)
Water content(litres)Model Code
TECHNICAL SPECIFICATIONS
Pulsar R STANDARD
Weights and Dimensions
Pulsar R for plasterboard ceilings
Pulsar R.3 - Code 0083230
Pulsar R.4 - Code 0083290
Pulsar
20
56789101112131415
2228323843475358636974
Δtm With insulationCooling emission
°C W/m3847556473819099
108117127
W/m2
30374350576471798693
100
Without insulationW/m
5263748698
110122134146158171
W/m2
8988878685848382818079787776
582574567559552544537529522515507500492485
Δtm Emission°C W/m
7574737271706968676665646362
478470463456448441434427419412405398391383
Δtm Emission°C W/m
6160595857565554535251504948
376369362355348341334327320313306299292285
Δtm Emission°C W/m
4746454443424140393837363534
279272265258251245238231225218211205198192
Δtm Emission°C W/m
3332313029282726252423222120
185179172166160153147141134128122116110104
Δtm Emission°C W/m
W = 396 W = 596 W = 797 W = 997Pulsar 1 Pulsar 2 Pulsar 3 Pulsar 4
Cooling emissions in accordance with the European Standard EN 14240
Thermal emissions in accordance with the European Standard EN 14037
05
Characteristic curve of the PULSAR taken from tests carried out as per the EN 14037 standard:
Q = K • (ΔTm)n Q = emission W/m K = heating coefficient of the unit = 3,28086 W/m� ΔTm = difference between the mean water temperature and the room temperature n = heating exponent of the unit = 1,1536
The emission of the Sabiana PULSAR radiant panels has been certifiedby the laboratory at the University of Stuttgart H.L.K. applying the harmonised European Standard EN 14037,with the report number DC205 D12.2108
Example:Nominal emission for a meter of Pulsar panels with ΔTm = 55°C : 334 W/mTotal nominal emission of Pulsar panels with ΔTm = 55°C
Emission
EN 14037Ceilingradiant panels
TECHNICAL SPECIFICATIONS
�tm = difference between the average water temperature and the room temperature
Example:
Water temperature 17/21°C,air temperature 28°C - 50%means �tm = 9°C.
The cooling emissionof the PULSAR is 43 W/m.
Pulsar
21
3780
4860
6540
Lowest water flow l/h Leaving water temperature °C
LOWEST WATER FLOW
Lowest water flow to be supplied in order to obtain the correct emission.
PRESSURE DROP
MEAN SURFACE TEMPERATUREOF THE PULSAR PANEL
Pulsar
23
Maximum water temperature °C m5060708090
2.52.72.93.13.3
Water circuit Maximum water pressure: 4 bar Maximum entering water temperature: +90°C
SUGGESTED LOWEST INSTALLATION HEIGHT (in m above the floor)
OPERATING LIMITS
WATER CONNECTION DIAGRAM
Pulsar
24
W ModelP Model
W.1W.2W.3W.4
2 x W.2W.2 + W.3
2 x W.3W.3 + W.4 ou 3 x W.2
2 x W.42 x W.3 + 1 x W.2
3 x W.32 x W.4 + 1 x W.3
3 x W.4
−−−
W.1 + Panel + W.1−
W.2 + Panel + W.2−
W.3 + Panel + W.3−
W.4 + Panel + W.4−
W.3 + Panel + W.3 + Panel + W.3−
1,201,802,403,003,604,204,805,406,006,607,208,409,00
P.1P.2P.3P.4
2 x P.2P.2 + P.32 x P.3
P.3 + P.4 ou 3 x P.22 x P.4
2 x P.3 + 1 x P.23 x P.3
2 x P.4 + 1 x P.33 x P.4
−−−
P.1 + Panel + P.1−
P.2 + Panel + P.2−
P.3 + Panel + P.3−
P.4 + Panel + P.4−
P.3 + Panel + P.3 + Panel + P.3−
Totallength (m)
Composition withoutintermediate panel
Compositionwith intermediate panel
Composition withoutintermediate panel
Compositionwith intermediate panel* *
Connection in series
This may be a false ceiling panel, a light or one of the PULSAR non-active aesthetic panels*
Connection in parallel
POSSIBLE CONNECTIONS
TABLE OF POSSIBLE COMBINATIONS
Longer length possible according to suitable Δp
Pulsar
25
NOTE: two kits of fittings must be used for PA, PB, WA and WB panels (1 kit = 2 fittings).
ACCESSORIES
Screw fittings (CALEFFI)
FITTINGS
Pressfittings (GEBERIT)
Code 9083455
Code 9083456
1. Ring nut
2. Metal ring
3. Black O-ring seals
4. Fitting
Pulsar
26
0083091008315100832110083271
0083101008316100832210083281
0083092008315200832120083272
0083102008316200832220083282
1234
ModelPA
CodeWA
1234
ModelPB
CodeWB
14502000
60835216083522
Flexible pipe lengthmm
Code
ACCESSORIES
Flexible pipe compliant with CSTB standard
Assembly of 5 PA / WA and PB / WB panels
- Diameter 1/2”- Made of: EPDM rubber
- With external stainless steel layer- Operation between -20°C and +110°C
Assembly of 2 Standard Pulsar
Assembly of 3 Standard Pulsar
Pulsar
27
Kit 210with hanger
Kit 220with steel
clamp
Kit 230with rail
Kit 250with screwfor wood
Kit 251with wedge
anchor
Code 9080390 Code 9080397 Code 9080391 Code 9080392 Code 9080393
HANGING SYSTEMS
37373737
44.544.544.544.5
155.5155.5155.5155.5199199199199
127.5127.5127.5127.5171171171171
595595595595610610610610
912151210561356864
148810561368
00830900083150008321000832700083100008316000832200083280
Pulsar P.1Pulsar P.2Pulsar P.3Pulsar P.4Pulsar W.1Pulsar W.2Pulsar W.3Pulsar W.4
11951795239529951234185824823106
EDCBACode Description L
Pulsar P.1 and P.2 / W.1 and W.2
Pulsar P.3 and P.4 / W.3 and W.4
Typical hanging options
Hanging brackets
The maximum vertical bending f of the Pulsar radiant panels between two suspension points is less than 2 mm.The maximum bending from the longitudinal axis of the 3m panels is 5mm.
Pulsar
28
Special version with perforated panel:it is supplied with extra thermal acoustic insulation,which allows the attenuationof noise reverberation in the room.
Weights and dimensions likeStandard panel.
False ceiling structure Covered false ceiling structure
INTEGRATION WITHIN FALSE CEILINGS
P Model
PULSAR WITH PERFORATED PANEL
Pulsar
29
NON-ACTIVE AESTHETIC PANEL - P Model
NON-ACTIVE AESTHETIC PANEL - W Model
Hanging holeson the lateral sides of the panel.
Hanging holes on the sidesof the hanging brackets (distance 521 mm).
The aesthetic panels are used when the active panels do not need to be installed and when, foraesthetic reasons or local specifications, a non-active panel has to be installed to complete a strip.
Available in 2 models:
Can be cut to measure on site.
5951195
Length (mm)90833509083410
Code12
Size
Hanging holeson the lateral sides of the panel.
Hanging holes on the sidesof the hanging brackets (distance 521 mm).
The aesthetic panels are used when the active panels do not need to be installed and when, foraesthetic reasons or local specifications, a non-active panel has to be installed to complete a strip.
Available in 2 models:
Can be cut to measure on site.
6101234
Length (mm)90834809083490
Code12
Size
Pulsar
30
ACCESSORIES FOR PANELSNOT INSTALLED INTO FALSE CEILINGS - W Model
Inspection panelCode: 9083476
End closing kitCode: 9083466
Make up jointsCode: 9083461
Heating / Air ConditioningPulsar Radiant Panel
PULS
AR -
EX
- 11
/12
COD
. A4
8301
00
D/11
/12
Sabiana s.p.a. • via Piave, 53 • 20011 Corbetta • Milano • Italy • phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576fax +39.02.9777282 / +39.02.9772820 • www.sabiana.it • [email protected]
ENVIRONMENTAL COMFORT