health clinic – las mercedes, honduras janelle barth, stephanie chang, greer mackebee, walter li

20
Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Upload: jadzia

Post on 11-Jan-2016

41 views

Category:

Documents


0 download

DESCRIPTION

Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li. Structural Design. Current Footprint – 60’x80’. Notes - Footprint. Cut and fill enough to fill hole without extra soil left over Strip footing Soil – mostly clay Minimum 5’ from boundaries - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Health Clinic – Las Mercedes, Honduras

Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Page 2: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Structural Design

Page 3: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Current Footprint – 60’x80’

Page 4: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Notes - Footprint

• Cut and fill enough to fill hole without extra soil left over

• Strip footing• Soil – mostly clay• Minimum 5’ from boundaries• Allow space for latrine

Page 5: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Current Floor Plan

Page 6: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Notes - Plan

• Use spaces on exterior – optimize sunlight• Kitchen on right – minimize distance to latrine• Sink near shower – minimize piping• Delivery near kitchen for access to hot water (as

opposed to being connected to Recovery)• 8’ hallways for easy maneuverability (i.e. moving

beds, etc.)• 2 entrances – main (to waiting area) and kitchen

(to load supplies/easy access to latrine)

Page 7: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Other Notes

• Roof – corrugated tin and corrugated translucent material (optimize sunlight)

• 10’ walls• Materials: CMU (8”x8”x16”), rebar, poured

concrete base, wood beams for roof support system

• Sketch-up Model

Page 8: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Next steps

• Convert to metric• Determine optimal base depth for cut and fill• Design roof structure• Determine loads• Find North for solar panel/roof design

Page 9: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Standard Solar Powered System Design

Page 10: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Our System6 x Isofoton 75 Watt solar panel

Xantrex 40 amp + 30 amp charge controller

12 V 115 amp hr Nautlius deep cycle battery

WyckomarUV-250 UV water filters

3 x Low powered laptops

600 watt power inverter

Sunfrost Vaccine Refrigerator

Thin-Lite DC fluorescent lights

Page 11: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Location of Load componets

Battery /Charge Controller/InverterStorage

13 watt lights

30 watt lights

Vaccine Fridge

13 watt lights

13 watt lights/Laptops

Page 12: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Calculations for Total Power Consumption• Total power consumption =

Σ Appliance Wattage rating * Hours used/day*Total number of Appliance

Appliance Watts Hours /Day Quantity Total WattsSunfrost Vaccine Fridge

54 7.5 1 380

Thin-Lite 30 watts Fluorescent lights

30 6 3 540

Thin-Lite 13 watts Fluorescent lights

13 6 8 624

Laptops 8 4 3 96UV filter 30 4 1 120Total 1760

Page 13: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Sizing the solar panel

Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec

4.39 5.26 5.97 6.14 5.60 5.48 5.56 5.65 5.24 4.64 4.31 4.13

• Solar panels are tested at 1000 W/m at 25 ⁰ C • The solar panel should be able provide the required wattage at both the summer and winter

hours• For temperature ranges between 25⁰ and 40⁰ C, the power output is close to linear

http://www.reuk.co.uk/Effect-of-Temperature-on-Solar-Panels.htm]• 75 watt panels = 75/1000 = 0.075 % efficiency• At lowest solar isolation of 4.13 kWh/m2/day produces 4.13 * 0.075 = 310 watts per panel• Total number of panels needed = Total power consumption/watts per panel

= 1760/310 = 5.6 panels ≈ 6 panels minimumTo compensate for cloudy days and system losses, 7-8 solar panels may be necessary

Monthly Averaged Insolation Incident On A Horizontal Surface (kWh/m2/day)

Page 14: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Sizing the battery system• Nautilius Deep cycle are rated at 115 amp hrs and 12 volts for a total of

1380 watt hrs • Although deep cycles can be discharged to 80 %, they have a much larger

cycles is discharged at lower percentages• This is a graph comparing cycles of discharge vs. discharge %

Page 15: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

• We want both a long lifespan for our system and also the power the solar fridge for several days if there are consecutive cloudy or rainy days/solar panel malfunctions

• Aiming for optimally 20 % discharge rate, each battery would be able to provide 0.2* 1380 = 276 Watt hours

• Number of batteries needed = Total wattage/ Watt hour per battery = 1760 /276 = 6.3 ≈ 7 batteries

• After 2 days, total watt hours available = (0.8)2 * 7 * 1380 = 6048 watt hrsThis can still provide 16 days of the vaccine fridge running by itself

• At 20% discharge rate, the batteries will last for 2500 cycles. • Assuming 1 cycle per day for each battery = 2500/365 = 6.8 years before

replacement. This will probably be 6 years, due to some over discharging.

Page 16: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Sizing the Charge controller• The charge controller prevents the batteries from

overcharging/discharging, maintains the rates of charging/discharging, keeps power from batteries from going back into solar panels, and also converts the variable voltage from the solar panels into a steady voltage

• For 75 watt solar panel, should be at 75 watts/12 volts = 6 amps, however this current can spike up to 8 amps. For our solar system, 7 * 8 amps = 56 amps. Thus we could use two charger controllers, a 40 amp and a 30 amp charge controller.

Page 17: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Sizing the Inverter• A 600 watt system will have enough capacity to power 5 amp tools, fans,

and also our needs for a water filter, and laptops. • The water filter = 30 watts • 3 laptops total = 24 watts • The 600 watt system will exceed our daily needs but will allow greater

expansion of AC appliances.

Page 18: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Choosing the laptop • Netbooks are very power efficient• The Dell mini 9 makes if easy to upgrade RAM and hard drive• The solid-state hard drive is less likely to fail• Linux drive Operating System can be re-installed and rebooted from a USB

drive, and thus making system recovery very easy

Page 19: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

Choosing the Vaccine Fridge

• Sunfrost energy specifications• Energy Consumption (12 volt) making 2.2 kg ice/day

.38 kWh/day @ 32° C (90° F)

Running Current: 4.5 amps for 12 volt system, 2.3 amps for 24 volt system Starting Current: 15 amps for 12 volt system, 7.5 amps for 24 volt system

Room Temperature 21° C (70° F) 32° C (90° F) 43° C (110° F)

Refrigerator Temperature 3° C (38° F) 3° C (38° F) 3° C (38° F)

Freezer Temperature -11° C (12° F) -9° C (15° F) -5° C (23° F)

Page 20: Health Clinic – Las Mercedes, Honduras Janelle Barth, Stephanie Chang, Greer Mackebee, Walter Li

• The Sunfrost Fridge:– has been approved by the World Health

Organization– is very power efficient– can maintain a fridge temperature of 3° C at a

large range of temperatures