hcm 132 report
TRANSCRIPT
-
8/8/2019 Hcm 132 Report
1/24
STANDARD BTSENGINEERING DOCUMENTS
OF HCM-132
-
8/8/2019 Hcm 132 Report
2/24
SAMSUNG Electronics Co., Ltd.
SITE INFORMATION
SITE NAME HCM-132ADDRESS 317 Cong Hoa Str, Tan Binh Ward, Dist 13, HCMC
OWNER SNAME
Mr. Thu
PHONENUMBER
0908 375 089
TYPE NEW SITE
-
8/8/2019 Hcm 132 Report
3/24
SAMSUNG Electronics Co., Ltd.
EQUIPMENT LISTItems Quantity Serial Number Specification
BTS
SSIR 1 S33L821742
EV-DO+1x(1FA) Configuration
UACA 1 S61L807069
UETA 1 S61L806405
UPCA 2 S61L809149 / S61L809153
UIFA 1 S61L809068
UEPA 1 S61L917010 / S61L916990
AMAU 3S4EL800359 / S4EL800353
S4EL803362
UFRU 3 S61L807551/ S61L807552S61L807558
FEBB 1 S33L823035
UMBB 1 S33L822558
Rectifier 1 60051
Type : SPS-2600Using 2 Modules (type: CRM-100V, Output : 27V,100A) and 4Batteries(150Ah)
AC Power 3 Phase
Surge 1 P005179
Transmission 1E1 Optical Fiber
Air-con 2 Indoor:D769PAIL700016F,D769PAIL7001242 Samsung Type
-
8/8/2019 Hcm 132 Report
4/24
SAMSUNG Electronics Co., Ltd.
ANTENNA INFORMATION
SECTION E F K
ANT
Model XDC-13-60-OT XDC-13-60-OT XDC-13-60-OT
Quantity 1 1 1
BeamWidth 60 0 60 0 60 0
Power 43dBm 43dBm 43dBm
Orientation 30 0 100 0 280 0
Tilt 90 90 90
Gain ( dBi) 15 15 15
-
8/8/2019 Hcm 132 Report
5/24
SAMSUNG Electronics Co., Ltd.
FEEDER CABLE INFORMATIONNo Description Specification Unit Quantity
1 ANTENNATYPE XDC-13-60-0T
Dual,15.0 dBi (min),60m/sec,824MHz~894Mhz
SET 3
2 ANTENNA FIXINGPIPE(GAL)
60.5 x 4t H: 2.5M EA 3
3 ANTENNA PIPE FIXING'U' BOLT(GAL.)
M12 x 112L, CENTER:76 EA 6
4Antenna Jumper Cable Kit
1/2" HARNESS2M,HARNESS ASS'Y(Outside),DIN-M(1/2) to DIN-Fe(1/2)
SET 6
57/8" Feeder Cable LS 7/8" M 25 x 6
67/16 DIN-(7/8")Connector DIN-MALE FOR LCF 7/8" EA 12
-
8/8/2019 Hcm 132 Report
6/24
SAMSUNG Electronics Co., Ltd.
FEEDER CABLE INFORMATIONTx/RxAntenna
7/16 DIN male,for 1/2 feeder
7/16 DIN female,for 1/2 feeder
7/16 DIN male,for 7/8 feeder
Jumper cable 1/2
( 2m)
7/16 DIN male,for 7/8 feeder
-
8/8/2019 Hcm 132 Report
7/24
SAMSUNG Electronics Co., Ltd.
Connect feeder cable indoor :
FEEDER CABLE INFORMATION
IGB /Bulk Head
-
8/8/2019 Hcm 132 Report
8/24
SAMSUNG Electronics Co., Ltd.
Detail connection at Bulk- Head
H eat Shrink Tube
7/16 Din Male
1/2 Feeder Line
RF Arrestor
RF Arrestor Connector (Din-Male)
RF Arrestor Connector (Din-Female)
RF Connector (Din-Female)
7/8 Feeder Line(Din-Female)
Pressure Terminal(2 H )
Brass Blot/Nut
GPS Cable(LMR400)
GPS Cable(LMR400)
Bulk-Head
Ground Wire
IGB
FEEDER CABLE INFORMATION
-
8/8/2019 Hcm 132 Report
9/24
SAMSUNG Electronics Co., Ltd.
No Description Specification Unit Quantity
1 ARRESTER DIN-Fe to DIN-Fe(1/2) EA 6
2 Antenna Jumper Cable Kit1/2" HARNESS3M,HARNESS ASS'Y(Inside),N-M(1/2) to
DIN-M(1/2)SET 6
3 BULK HEAD(7/8") 350 x 99 x 160(mm) SET 1
4 COPPER BAR(IGB) 310 x 50 x 5T,CU EA 1
5 ROXTEC WALL TYPE(7/8") EA 1
6FEEDER LINE NAME
PLATE (ENGLISH)70 x 50 x 2T, AL SET 2
FEEDER CABLE INFORMATION
-
8/8/2019 Hcm 132 Report
10/24
SAMSUNG Electronics Co., Ltd.
GPS SPEC. INFORMATION
GPS PositionLength
( Antenna toBulk Head )
Remarks
A On the roof 17m On the third floor
B On the roof 15m On the third floor
-
8/8/2019 Hcm 132 Report
11/24
SAMSUNG Electronics Co., Ltd.
GPS SPEC. INFOMATION
MODEL GA-1575
FREQUENCY 1575.42 MHz (L1) s 5MHz
OPERATING TEMP - 40 0C - + 80 0C
DC VOLTAGE +5 V s 10%
DC CONSUMPTION CURRENT 33 mA max
TOTAL GAIN 38 dB min
GAIN FLATNESS s 0.5 dB max
NOISE FIGURE 1.5 dB max
IMPEDANCE 50;
POLARIZATION RHCP
V.S.W.R. (I/O) 2.5.0 max
CONNECTOR TNC(F)
ELECTRICAL SPECIFICATIONS :
-
8/8/2019 Hcm 132 Report
12/24
SAMSUNG Electronics Co., Ltd.
GROUNDING CABLE INFORMATION
-
8/8/2019 Hcm 132 Report
13/24
SAMSUNG Electronics Co., Ltd.
GROUNDING CABLE INFORMATION
GROUND CABLE RUNNING LIST
-
8/8/2019 Hcm 132 Report
14/24
SAMSUNG Electronics Co., Ltd.
POWER CABLE
CABLELIST
SPEC EA UNIT LENGTH FROM TO
AC cable FR-8 25mm2 x 1C 1 m ( 5x4)m ACPDB RECT
DC cable F-CV50mm2 x 1C 2 m ( 5x2)m RECT SSRI 1
-
8/8/2019 Hcm 132 Report
15/24
SAMSUNG Electronics Co., Ltd.
POWER CABLE
POWER CABLE RUNNING LIST
-
8/8/2019 Hcm 132 Report
16/24
SAMSUNG Electronics Co., Ltd.
POWER CABLE
No Discription Specification Unit
1POWER CABLE GRAND BRACKET
ASS'Y(2HOLE)
W:130,D:45.4,H:100,AL 2T,MEDIU
M GREY,Rubber 15mm
SET
2 600V F-CV CABLE(BLACK)600V F-CV CABLE(BLACK)F-CVCABLE 50 x 1C(BLACK), 14.5mm, UL
M
3 PRESSURE TERMINAL(2 HOLE)38 (2 HOLE DIST :16mm, D2 :6.5,
E:9.4EA
4 HEAT SHRINK TUBE D:20 (Blue) M
5 HEAT SHRINK TUBE D:20 (RED) M
Table Materials for cable
-
8/8/2019 Hcm 132 Report
17/24
SAMSUNG Electronics Co., Ltd.
DDF CABLINGDDF ALARM CONFIGURATION
EMI BTSAlarm name Air-con Rectifier
Order Pair colour Line colour
1 White+BlueWhite A/C 0 On/Off + White
Blue A/C 0 On/Off - Blue
2 White+OrangeWhite A/C 0 Function Fail + White
Orange A/C 0 Function Fail - Orange
3 White+Green
White A/C 0 Compressor Operation +
White
GreenA/C 0 Compressor
Operation - Green
4 White+BrownWhite A/C 0 On/Off + White
Brown A/C 0 On/Off - Blue
5 White+GrayWhite A/C 0 Function Fail + White
Gray A/C 0 Function Fail - Orange
6 Red+Blue
Red A/C 0 Compressor Operation +
White
Blue A/C 0 Compressor
Operation -Green
7 Red+OrangeRed A/C Input Fail Purple
Orange D/C Output Fail Gray
8 Red+GreenRed D/C Over Current Red/White
Green Battery Fail Yellow/Red
9 Red+BrownRed Unit Fail Blue/White
Brown Common(D-Ground) White/Red
10 Red+GrayRed
Gray
-
8/8/2019 Hcm 132 Report
18/24
SAMSUNG Electronics Co., Ltd.
Frequency Spectrum for S-TelecomFrequency Spectrum for S-Telecom
FA_ID FA_NUM FA
1 181 875.43
2 222 876.66
3 263 877.89
4 304 879.12
5 345 880.35
-
8/8/2019 Hcm 132 Report
19/24
SAMSUNG Electronics Co., Ltd.
Repeater ConnectionsRepeater Connections
TXCU-CS ConfigurationIN ( E, F, K)These ports are for linking outputs of UIFA E, F, K( A side: UIFA #0, B side:UIFA #1)OUT (E , F, K)
These ports are for linking inputs of AMAU ( A side: AMAU #0#2#4, B side:AMAU #1#3#5)CPL (E , F, K)These ports are for linking IN connector of TXCM-C
TXCU-CS Configuration
-
8/8/2019 Hcm 132 Report
20/24
SAMSUNG Electronics Co., Ltd.
Repeater ConnectionsRepeater ConnectionsTHPM Configuration
- IN_A, B, C: Inputting the main receiving signal of repeater - IN_a, b, c: Inputting the receiving diversity signal of repeater - OUT_A, B, C: Connecting the repeaters main receiving signal and the systems
receiving signal- OUT_a, b, c: Connecting the repeaters receiving diversity signal and the systems
receiving signal
TXCM-C Configuration- IN1, 2: Input port of TXCU-CS coupling signal_1, 2- OUT: Output port of combined coupling signal_1- CPL: Measuring port for the combined coupling signal level
THPMTXCM-C
-
8/8/2019 Hcm 132 Report
21/24
SAMSUNG Electronics Co., Ltd.
Repeater ConnectionsRepeater Connections
Case 1 FA, 2 FA, 3 FA
-
8/8/2019 Hcm 132 Report
22/24
SAMSUNG Electronics Co., Ltd.
Repeater ConnectionsRepeater Connections
Case 3 FA beacon
- Installation HPCU-CS ( indoor BTS)- 2 Tx cables from UIFA 0&1 connect to IN ports 1&2 of HPCU-CS- Connecting cable from OUT ports ( HPCU-CS) to IN ports (TXCU-CS)
HPCU-CS
-
8/8/2019 Hcm 132 Report
23/24
SAMSUNG Electronics Co., Ltd.
Beacon ConnectionsBeacon ConnectionsCase 1 FA beacon, 2 FA beacon: normalCase 3 FA beacon:- Installation one more UIFA- Installation HPCU-CS- Connecting Tx cable from UIFA 0&1 to IN port 1&2 HPCU-CS- Connecting cable from OUT port (HPCU-CS) to AMAU
Case 2 FA beacon
-
8/8/2019 Hcm 132 Report
24/24
SAMSUNG Electronics Co., Ltd.
Thank YouThank YouThank YouThank You