harmonic filters fn 3420 / fn 3430 ecosine™ active - the ... · pdf file3983343 fn...

2
Harmonic filters FN 3420 / FN 3430 ECOsine™ Active - the compact, fast, and flexible solution for better Power Quality Approvals n Global or selective compensation of harmonic currents up to the 50th order n Compensation of displacement power factor n Load balancing capability n Response time of less than 300 micro- seconds n Compact solution for easy installation and intuitive operation FN 3420: 30A to 100A UL recognized Typical applications ECOsine™ Active is the new generation of active harmonic filters (AHF). It reliably miti- gates harmonics and compensates voltage dips as well as reactive power. ECOsine™ Active’s functionality can be com- pared to waves in the ocean: If two waves of the same height and intensity meet, they can- cel each other out. The same principle can be applied also to power networks. The AHF analyzes network disturbances and provides an opposing compensation current. In doing so, ECOsine™ Active actively adapts to fluctuations and responds in less than half a millisecond. Its compact dimensions, sim- ple installation, and digital intelligence allow for a quick and straight forward integration in the most diverse applications. n Building automation n Data and banking centers n HVAC installations n Machines and automation ship propulsion n Tunnel ventilation n UPS n Motor drives n Welding equipment n Water/wastewater treatment n Automotive manufacturing Features and benefits Nominal operating voltage*: 380 to 480V ±10% (FN 3420: 3-wire) 380 to 415V ±10% (FN 3430: 4-wire) Operating frequency: 47 to 63Hz Rated compensation current: 30 to 300A @ 40°C (FN 3420) 30 to 300A @ 40°C (FN 3430) Total harmonic current distortion THID**: <5% Total demand distortion TDD: According to IEEE-519, table 10-3 Compensation capability: Odd harmonics up to the 50th order Response time: <300µs Protection category: IP20 (30 to 100A) IP54 (200 to 300A) Cooling: Forced air cooling (30 to 100A) Forced air cooling, internal liquid cooling (200 to 300A) Overload capability: 2.5x rated comp. current for 10ms (peak value) Ambient temperature: 40°C, derating up to 55°C, 2%/K Altitude: 1000m, derating up to 4000m, 1%/100m Parallel operation: Up to 5 filters Interfaces: Ethernet, RS485, ModBus Controller topology: Digital with FFT analysis Current limitation: Nominal current Current transformers (not included): 100:5 to 50000:5 Design corresponding to: UL 508, CE (LVD 2006/95/EC) MTBF @ 40°C/400V: Up to 100,000 hours Technical specifications * different ratings upon request. ** depending upon the rated compensation current of the selected filter in relation to the compensation requirement. FN 3420: 200A to 300A UL listed HyTEPS B.V. Binderseind 55a 5421CH Gemert Nederland T +31 (0)492 37 12 12 [email protected] www.hyteps.nl

Upload: dangkhue

Post on 08-Mar-2018

255 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: Harmonic filters FN 3420 / FN 3430 ECOsine™ Active - the ... · PDF file3983343 FN 3430-100-400-4 100 300

Harmonic filtersFN 3420 / FN 3430

ECOsine™ Active - the compact, fast, and flexible solution for better Power Quality

Approvalsn Global or selective compensation of harmonic currents up to the 50th ordern Compensation of displacement power

factorn Load balancing capabilityn Response time of less than 300 micro- secondsn Compact solution for easy installation

and intuitive operation

FN 3420: 30A to 100A UL recognized

Typical applications

ECOsine™ Active is the new generation of

active harmonic filters (AHF). It reliably miti-

gates harmonics and compensates voltage

dips as well as reactive power.

ECOsine™ Active’s functionality can be com-

pared to waves in the ocean: If two waves of

the same height and intensity meet, they can-

cel each other out. The same principle can

be applied also to power networks.

The AHF analyzes network disturbances and

provides an opposing compensation current.

In doing so, ECOsine™ Active actively adapts

to fluctuations and responds in less than half

a millisecond. Its compact dimensions, sim-

ple installation, and digital intelligence allow

for a quick and straight forward integration

in the most diverse applications.

n Building automation

n Data and banking centers

n HVAC installations

n Machines and automation ship propulsion

n Tunnel ventilation

n UPS

n Motor drives

n Welding equipment

n Water/wastewater treatment

n Automotive manufacturing

Features and benefits

Nominal operating voltage*: 380 to 480V ±10% (FN 3420: 3-wire) 380 to 415V ±10% (FN 3430: 4-wire)Operating frequency: 47 to 63HzRated compensation current: 30 to 300A @ 40°C (FN 3420) 30 to 300A @ 40°C (FN 3430)Total harmonic current distortion THID**: <5%Total demand distortion TDD: According to IEEE-519, table 10-3Compensation capability: Odd harmonics up to the 50th orderResponse time: <300µsProtection category: IP20 (30 to 100A) IP54 (200 to 300A)Cooling: Forced air cooling (30 to 100A) Forced air cooling, internal liquid cooling (200 to 300A)Overload capability: 2.5x rated comp. current for 10ms (peak value)Ambient temperature: 40°C, derating up to 55°C, 2%/KAltitude: 1000m, derating up to 4000m, 1%/100mParallel operation: Up to 5 filtersInterfaces: Ethernet, RS485, ModBusController topology: Digital with FFT analysisCurrent limitation: Nominal currentCurrent transformers (not included): 100:5 to 50000:5Design corresponding to: UL 508, CE (LVD 2006/95/EC)MTBF @ 40°C/400V: Up to 100,000 hours

Technical specifications

* different ratings upon request.

** depending upon the rated compensation current of the selected filter in relation to the compensation requirement.

FN 3420: 200A to 300A UL listed

HyTEPS B.V. Binderseind 55a 5421CH Gemert Nederland

T +31 (0)492 37 12 [email protected] www.hyteps.nl

Page 2: Harmonic filters FN 3420 / FN 3430 ECOsine™ Active - the ... · PDF file3983343 FN 3430-100-400-4 100 300

Filter selection table

SchaffnerECOsine™Active

Power line supply

Load

Compensation current

Without ECOsine™ Active: Harmonics and reactive power stress the electrical installation and lead to problems

With ECOsine™ Active: Reactive power and harmonics are actively compensated, thus ensuring better power quality

Block schematic

Install ConfigureMeasure

+

For more details, please ask for the ECOsine™ Active brochure and the user manual.

Plug-and-play: 3 simple steps to better power quality

Article Filter* Rated phase Rated neutral line Power loss Cooling air Noise level Dimensions Weight number comp. current comp. current requirement [1m] [WxHxD]

[A rms] [A rms] [W] [m3/h] [dB(A)] [mm] [kg]3983319 FN 3420-30-480-3 30 <900 <350 65 360x590x290 473983327 FN 3420-50-480-3 50 <1300 <550 65 360x590x290 473983335 FN 3420-100-480-3 100 <2200 <1400 68 468x970x412 1053983350 FN 3420-200-480-3 200 <5000 <2600 70 800x2000x760 4153983376 FN 3420-250-480-3 250 <6000 <3100 70 800x2000x760 4153983392 FN 3420-300-480-3 300 <7500 <3400 70 800x2000x760 415 4321824 FN 3430-30-400-4 30 90 <950 <400 63 415x840x300 704321832 FN 3430-60-400-4 60 180 <1800 <600 63 415x840x300 703983343 FN 3430-100-400-4 100 300 <3000 <1700 69 468x1460x412 1453983368 FN 3430-200-400-4 200 600 <5500 <2800 70 800x2000x760 4953983384 FN 3430-250-400-4 250 750 <6300 <3300 70 800x2000x760 4953983400 FN 3430-300-400-4 300 750 <8500 <3600 70 800x2000x760 495

3983418 Software AHF Viewer

Your local partner: To find your local partner within Schaffner’s global network, please go to www.schaffner.com March 2010