gw-7553 (modbus rtu master) example for simatic step 7 · gw-7553 (modbus rtu master) example for...
TRANSCRIPT
![Page 1: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/1.jpg)
1
GW-7553 (Modbus RTU master)
example for SIMATIC STEP 7
Example 1:Reads DO module data from GW-7553(Modbus FC01).
Example 2: Reads DI module data from GW-7553(Modbus FC02).
Example 3: Reads AO module data from GW-7553(Modbus FC03).
Example 4: Reads AI module data from GW-7553(Modbus FC04).
Example 5: Writes DO module data from GW-7553(Modbus FC05,15).
Example 6: Writes AO module data from GW-7553(Modbus FC06,16).
![Page 2: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/2.jpg)
2
Example 1: PLC reads DO module data from GW-7553.
(Modbus FC01)
Read a Modbus RTU DO module (PROFIBUS Slave & Modbus RTU/Master)
![Page 3: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/3.jpg)
3
SIMATIC STEP7 Configuration:
Step 1: Setup the GW-7553 module
1. Select GW-7553 module
2. Add a System setting module
![Page 4: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/4.jpg)
4
3. Add “Output Relay/Coil – 1 byte” and “Input Relay/Coil – 1byte”
![Page 5: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/5.jpg)
5
Step 2: Setup the parameters of the GW-7553
1. Double click GW-7553 icon
2. Select “Parameter Assignment”
3. Set common parameters of the GW-7553
Common parameters
Baud rate: 115200; Parity: none; Data: 8 data bit; Stop bit: 1 stop bit; Modbus type: Master
Modbus Format: Modbus RTU; Byte Order: Big Endian
![Page 6: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/6.jpg)
6
4. Set module parameters of the GW-7553
(1)Double click “Output Relay/Coil – 1 byte” module
(2)Select “Parameter Assignment”
5. Setup “Output Relay/Coil – 1 byte” module parameter
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0))
![Page 7: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/7.jpg)
7
6. Set module parameters of the GW-7553
(1)Double click “Input Relay/Coil – 1 byte” module
(2)Select “Parameter Assignment”
7. Setup “Input Relay/Coil – 1 byte” module parameter
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0))
Module Type: Read DO, click ok.
![Page 8: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/8.jpg)
8
Step 3: Download the HW settings into SIMATIC PLC
1. Save and Compile
2. HW settings into SIMATIC PLC
![Page 9: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/9.jpg)
9
Step 4: Insert a new Organization Block (OB1,OB82,OB86)
\
![Page 10: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/10.jpg)
10
Step 5: Edit OB1
Variables used in the example LD Program:
Double Click
![Page 11: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/11.jpg)
11
![Page 12: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/12.jpg)
12
Step 6: Download the settings into SIMATIC PLC
![Page 13: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/13.jpg)
13
Step 7: Make sure the RUN LED of the GW-7553 is on and the switch of the GW-7553 is at
Normal mode.
Now the setting procedure has been finished and the user can read the data to
the Modbus DO module at address IB0.
![Page 14: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/14.jpg)
14
Example 2: PLC reads DI module data from GW-7553.
(Modbus FC02)
Read a Modbus RTU DI module (PROFIBUS Slave & Modbus RTU/Master)
![Page 15: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/15.jpg)
15
SIMATIC STEP7 Configuration:
Step 1: Setup the GW-7553 module
1. Select GW-7553 module
2. Add a System setting module
![Page 16: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/16.jpg)
16
3. Add “Input Relay/Coil—1 byte” module
Step 2: Setup the parameters of the GW-7553
1. Double click GW-7553 icon
2. Select “Parameter Assignment”
![Page 17: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/17.jpg)
17
3. Set common parameters of the GW-7553
Common parameters
Baud rate: 115200; Parity: none; Data: 8 data bit; Stop bit: 1 stop bit; Modbus type: Master
Modbus Format: Modbus RTU; Byte Order: Big Endian
4. Set module parameters of the GW-7553
(1)Double click “Input Relay/Coil—1 byte” module
(2)Select “Parameter Assignment”
![Page 18: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/18.jpg)
18
5. Setup “Input Relay/Coil—1 byte” module parameters
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0))
Module Type: Read DI, click ok.
Step 3: Download the HW settings into SIMATIC PLC
1. Save and Compile
![Page 19: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/19.jpg)
19
2. HW settings into SIMATIC PLC
Step 4: Insert a new Organization Block (OB1,OB82,OB86)
![Page 20: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/20.jpg)
20
Double Click
![Page 21: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/21.jpg)
21
Step 5: Edit OB1
Step 6: Download the settings into SIMATIC PLC
![Page 22: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/22.jpg)
22
Step 7: Make sure the RUN LED of the GW-7553 is on and the switch of the GW-7553 is at
Normal mode.
Now the setting procedure has been finished and the user can read the data of
the Modbus DI module at address PIB0.
![Page 23: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/23.jpg)
23
Example 3: PLC reads AO module data from GW-7553.
(Modbus FC03)
Read a Modbus RTU AO module (PROFIBUS Slave & Modbus RTU/Master)
![Page 24: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/24.jpg)
24
SIMATIC STEP7 Configuration:
Step 1: Setup the GW-7553 module
1. Select GW-7553 module
2. Add a System setting module
![Page 25: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/25.jpg)
25
3. Add “Onput Register – 1 word” and “Input Register – 1 word”
![Page 26: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/26.jpg)
26
Step 2: Setup the parameters of the GW-7553
1. Double click GW-7553 icon
2. Select “Parameter Assignment”
3. Set common parameters of the GW-7553
Common parameters
Baud rate: 115200; Parity: none; Data: 8 data bit; Stop bit: 1 stop bit; Modbus type: Master
Modbus Format: Modbus RTU; Byte Order: Big Endian
![Page 27: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/27.jpg)
27
4. Set module parameters of the GW-7553
(1)Double click “Output Register – 1 word” module
(2)Select “Parameter Assignment”
5. Setup “Output Register – 1 word” module parameters
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0)), click ok.
![Page 28: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/28.jpg)
28
6. Set module parameters of the GW-7553
(1)Double click “Intput Register – 1 word” module
(2)Select “Parameter Assignment”
5. Setup “Input Register – 1 word” module parameters
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0)), click ok.
Module Type: Read AO, click ok.
![Page 29: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/29.jpg)
29
Step 3: Download the HW settings into SIMATIC PLC
1. Save and Compile
2. HW settings into SIMATIC PLC
![Page 30: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/30.jpg)
30
Step 4: Insert a new Organization Block (OB1,OB82,OB86)
![Page 31: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/31.jpg)
31
Step 5: Edit OB1
Variables used in the example LD Program:
Double Click
![Page 32: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/32.jpg)
32
![Page 33: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/33.jpg)
33
Step 6: Download the settings into SIMATIC PLC
![Page 34: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/34.jpg)
34
Step 7: Make sure the RUN LED of the GW-7553 is on and the switch of the GW-7553 is at
Normal mode.
Now the setting procedure has been finished and the user can write the data to
the Modbus AO module at address PIW256.
![Page 35: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/35.jpg)
35
Example 4: PLC reads AI module data from GW-7553.
(Modbus FC04)
Read a Modbus RTU AI module (PROFIBUS Slave & Modbus RTU/Master)
1
![Page 36: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/36.jpg)
36
SIMATIC STEP7 Configuration:
Step 1: Setup the GW-7553 module
1. Select GW-7553 module
2. Add a System setting module
![Page 37: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/37.jpg)
37
3. Add “Input Register—1 word” module
Step 2: Setup the parameters of the GW-7553
1. Double click GW-7553 icon
2. Select “Parameter Assignment”
![Page 38: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/38.jpg)
38
3. Set common parameters of the GW-7553
Common parameters
Baud rate: 115200; Parity: none; Data: 8 data bit; Stop bit: 1 stop bit; Modbus type: Master
Modbus Format: Modbus RTU; Byte Order: Big Endian
4. Set module parameters of the GW-7553
(1)Double click “input register—1 word” module
(2)Select “Parameter Assignment”
![Page 39: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/39.jpg)
39
5. Setup “input register—1 word” module parameters
Module parameters
Modbus Slave Device ID: 1; Slave Address: 0 (Protocol address (base 0))
Module Type: Read AI, click ok.
Step 3: Download the HW settings into SIMATIC PLC
1. Save and Compile
![Page 40: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/40.jpg)
40
2. HW settings into SIMATIC PLC
Step 4: Insert a new Organization Block (OB1,OB82,OB86)
![Page 41: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/41.jpg)
41
Double Click
![Page 42: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/42.jpg)
42
Step 5: Edit OB1
Step 6: Download the settings into SIMATIC PLC
![Page 43: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/43.jpg)
43
Step 7: Make sure the RUN LED of the GW-7553 is on and the switch of the GW-7553 is at
Normal mode.
Now the setting procedure has been finished and the user can read the data of
the Modbus AI module at address PIW256.
![Page 44: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/44.jpg)
44
Example 5: PLC writes DO module data to GW-7553.
(Modbus FC05,FC15)
Write a Modbus RTU DO module (PROFIBUS Slave & Modbus RTU/Master)
![Page 45: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/45.jpg)
45
SIMATIC STEP7 Configuration:
Step 1: Setup the GW-7553 module
1. Select GW-7553 module
2. Add a System setting module
![Page 46: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/46.jpg)
46
3. Add “Onput Relay/Coil—1 byte” module(For FC15,multiple coils, please select more than 1 byte
module)
Step 2: Setup the parameters of the GW-7553
1. Double click GW-7553 icon
2. Select “Parameter Assignment”
![Page 47: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/47.jpg)
47
3. Set common parameters of the GW-7553
Common parameters
Baud rate: 115200; Parity: none; Data: 8 data bit; Stop bit: 1 stop bit; Modbus type: Master
Modbus Format: Modbus RTU; Byte Order: Big Endian
4. Set module parameters of the GW-7553
(1)Double click “Output Relay/Coil—1 byte” module
(2)Select “Parameter Assignment”
![Page 48: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/48.jpg)
48
5. Setup “Output Relay/Coil—1 byte” module parameters
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0)), click ok.
Step 3: Download the HW settings into SIMATIC PLC
1. Save and Compile
![Page 49: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/49.jpg)
49
2. HW settings into SIMATIC PLC
Step 4: Insert a new Organization Block (OB1,OB82,OB86)
![Page 50: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/50.jpg)
50
Double Click
![Page 51: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/51.jpg)
51
Step 5: Edit OB1
Variables used in the example LD Program:
![Page 52: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/52.jpg)
52
![Page 53: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/53.jpg)
53
Step 6: Download the settings into SIMATIC PLC
Step 7: Make sure the RUN LED of the GW-7553 is on and the switch of the GW-7553 is at
Normal mode.
![Page 54: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/54.jpg)
54
Now the setting procedure has been finished and the user can write the data to
the Modbus DO module at address QB3.
![Page 55: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/55.jpg)
55
Example 6: PLC writes AO module data to GW-7553.
(Modbus FC06, FC16)
Write a Modbus RTU AO module (PROFIBUS Slave & Modbus RTU/Master)
![Page 56: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/56.jpg)
56
SIMATIC STEP7 Configuration:
Step 1: Setup the GW-7553 module
1. Select GW-7553 module
2. Add a System setting module
![Page 57: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/57.jpg)
57
3. Add “Output Register—1word” module(For FC16,multiple registers, please select more than 1 word
module)
Step 2: Setup the parameters of the GW-7553
1. Double click GW-7553 icon
2. Select “Parameter Assignment”
![Page 58: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/58.jpg)
58
3. Set common parameters of the GW-7553
Common parameters
Baud rate: 115200; Parity: none; Data: 8 data bit; Stop bit: 1 stop bit; Modbus type: Master
Modbus Format: Modbus RTU; Byte Order: Big Endian
4. Set module parameters of the GW-7553
(1)Double click “Output Register—1word” module
(2)Select “Parameter Assignment”
![Page 59: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/59.jpg)
59
5. Setup “Output Register—1 word” module parameters
Module parameters
Modbus Slave Device ID: 2; Slave Address: 0 (Protocol address (base 0)), click ok.
Step 3: Download the HW settings into SIMATIC PLC
1. Save and Compile
![Page 60: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/60.jpg)
60
2. HW settings into SIMATIC PLC
Step 4: Insert a new Organization Block (OB1,OB82,OB86)
![Page 61: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/61.jpg)
61
Double Click
![Page 62: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/62.jpg)
62
Step 5: Edit OB1
Variables used in the example LD Program:
![Page 63: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/63.jpg)
63
Using T2 trigger T1 If counter (C1) add 1 and Tri will add 1 every 1s.
If Tri is equal to 256 then reset counter (C1).
![Page 64: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/64.jpg)
64
Step 6: Download the settings into SIMATIC PLC
Step 7: Make sure the RUN LED of the GW-7553 is on and the switch of the GW-7553 is at
Normal mode.
![Page 65: GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 · GW-7553 (Modbus RTU master) example for SIMATIC STEP 7 Example 1:Reads DO module data from GW-7553(Modbus FC01). ... Read](https://reader031.vdocuments.us/reader031/viewer/2022021809/5c39571d09d3f211338c255f/html5/thumbnails/65.jpg)
65
Now the setting procedure has been finished and the user can write the data to
the Modbus AO module at address PQW256.