gujarat technological university · 2018-07-05 · are multiple non-idealities in the pcc voltage,...

24
INVESTIGATION INTO POWER QUALITY ISSUES AND HARMONIC MITIGATION IN MODERN POWER SYSTEMS A A Synopsis submitted to Gujarat Technological University in Electrical Engineering by PATIL KALPESHKMAR ROHITBHAI 119997109007 under supervision of Dr. Hiren H. Patel GUJARAT TECHNOLOGICAL UNIVERSITY

Upload: others

Post on 08-Feb-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

INVESTIGATION INTO POWER QUALITY ISSUES AND

HARMONIC MITIGATION IN MODERN POWER SYSTEMS

A

A Synopsis submitted to Gujarat Technological University

in

Electrical Engineering

by

PATIL KALPESHKMAR ROHITBHAI

119997109007

under supervision of

Dr. Hiren H. Patel

GUJARAT TECHNOLOGICAL UNIVERSITY

Page 2: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

1

1. Abstract

Over the last couple of decade electrical power utility has observed a rapid change in electrical power

generation, transmission, as well as distribution sector. It has resulted mainly due to the deregulation and

restructuring process, advancement in technology and increased concern about the environmental

impacts.

The power generation is no longer restricted to centralized power plants, but allows energy generation

from distributed energy resources (DERs) or distributed generators (DGs). Unlike the centralized

converters that are connected directly to the utility, the DRs usually require some kind of power

electronic converters for grid interface. Various power electronic converters (often referred as FACTS

devices) with faster and sophisticated control, are also incorporated in the system to improve the

transmission and distribution capabilities and to improve the stability of the electrical power system. Not

only the utility, but the domestic and industrial consumers have also seen the proliferation of power

electronic converter to satisfy the requirements of precise control, increased efficiency and compulsion to

meet the statute/regulations set by the regulatory bodies.

These power electronic converters, which are intended to improve the capability of the system or load,

also introduce certain challenges in their designing, commissioning, operation and control; otherwise they

may degrade the performance of the network or the connected system. With increase in the penetration

level (number and size) of the converters in the existing network, the gravity of the issues presented by

these converters increase. These issues include proper synchronization, power flow control, injection of

harmonics and/or imbalance, voltage and frequency instability, resonance, change in the network

impedance, reverse power flow etc. Hence, it is must to devise a proper control scheme for the converters

to keep the undesired effect to the minimum.

One of the critical aspects in achieving the precise operation and control of the converters is the proper

synchronization of the converters with the utility. This requires the proper estimation of the phase,

frequency and magnitude of the voltage/current at the Point of Common Coupling (PCC). However, there

are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by

non-linear loads and power converter based DGs. This leads to inaccurate estimation of phase and

magnitude of voltage/current, which finally affects the performance of the converters. This further inserts

harmonics and/or imbalance in the system deteriorating the power quality of the voltage/currents at the

PCC and the connected system.

The research is aimed to investigate performance of various phase/frequency estimation techniques

under various non-ideal conditions like voltage imbalance, harmonics, dc-offset etc. It is observed that

most of the methods are not capable of estimating the frequency when the grid signals are characterized

Page 3: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

2

by dc-offset. A frequency estimation technique named modified dual second order generalized

(MDSOGI) is presented which precisely estimates the frequency under all the non-ideal conditions. The

results are validated experimentally. The scheme is further integrated with the instantaneous reactive

power theory to develop a control scheme for a shunt active power filter capable of working under such

conditions. The experimental prototype is developed to signify the improved performance.

2. Brief description on the state of the art of the research topic

The environmental concern is rapidly replacing the fossil fuels based electricity generation by the

renewable energy sources i.e. wind, solar, fuel cell etc. based electricity generation. Hence, the modern

power plant is characterized by the presence of large number of power electronics converter based

distributed generation along-with traditional power plants. Almost all these power electronics converters

are committed to provide a controlled and high quality power exchange to the utility or local linear/non-

linear loads connected at the point of common coupling (PCC). Besides the power converters used for

DGs, power electronic converters are also incorporated into the system to improve the systems

performance. The power converters commonly referred as FACTS devices (name derived from flexible

AC transmission systems) are quite popular for reactive power compensation, improving static and

dynamic stability, imbalance mitigation, congestion management etc [1].

The power converters are even utilized for loads like electrical drives, uninterruptible power supply,

electrical heating and furnaces, lightings, chargers etc. These power electronic converters based load

introduce harmonics into the system causing the degradation of the power quality. The major contributor

to the power quality deterioration is the uncontrolled diode bridge rectifiers as they introduces low order

5th

and 7th

harmonics with significant amplitude. Traditionally, passive LC filters [2] were used to limit

the injection of harmonics into the utility. These filters are now replaced by the advanced power

electronics compensator known as active power filters in the modern electrical power system [3-5]. Out

of the various active power filter configurations (series, shunt and hybrid), shunt active power filter

(SAPF) is quite popular to remove harmonics locally at the load side making the utility free of harmonics

[6-11]. Unlike passive LC filters, which are simple in design, cheap, large and heavy, tuned to particular

frequency [5]; the APFs are complex and costly; however, relatively smaller, fast, free from problem of

resonance, and adaptive in nature and hence, can compensate various harmonics of different types of non-

linear loads. The performance of the SAPF is greatly dependent on how precisely the reference

compensating current is computed. The task of generating this reference compensation current is

challenging, especially when the system operates in a weak grid or micro-grid, which is very likely to

have distorted supply voltage, harmonics, imbalance in three-phase load, imbalance in supply voltage etc

[12-15]. Under such case for computing reference compensation current, it is must to accurately compute

the fundamental positive sequence components (PSCs) of grid voltage. The accuracy of the fundamental

Page 4: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

3

PSCs depends on the accurate information derived about the phase, frequency and amplitude of grid

voltage. It is also termed as the grid synchronization.

Just like active filters, all other grid-connected power electronic converters, irrespective of the

application, require proper synchronization with the grid. They also demand the correct information of

the phase, frequency and amplitude of the grid voltage for their proper operation. Otherwise instead of

improving the performance of the utility or load, they may affect the system adversely.

Various grid synchronization techniques or the phase angle estimation have been reported. These

approaches can be broadly categorized into frequency and time domain (FD and TD) techniques. The FD

techniques based on digital Fourier transform are complex to implement, require more memory and

increase in the computational burden under distorted grid signal [16]. Hence, TD approach based on

phase-locked loop (PLL) which has advantages like simplicity, better dynamic response, low sensitivity

to the variations and distortion in grid voltage etc. is preferred. Further, it has higher accuracy and is

relatively more stable and reliable. The PLL comprises of the phase detector (PD) block, filter and a

voltage controlled oscillator (VCO). The gain of VCO, whose output signal is synchronized (in terms of

phase and frequency) with the input reference signal, depends on the output of PD. The classification of

PLL based on various PD is reported and their performance is evaluated under the different grid severity

for a single-phase system [17]. The three-phase conventional PLL based on the synchronous reference

frame (SRF) have superior performance in the balanced grid voltage signal. But, it gives the oscillatory

response for the estimated fundamental frequency, if measured grid voltage signal is unbalanced or

distorted [18]. The poor performance of the conventional PLL was improved by the technique reported in

[19], which employs decoupled double synchronous reference frame PLL (DDSRF-PLL). The DDSRF-

PLL decouples the fundamental positive and negative sequence components to estimate the frequency. It

results into accurate estimation in case of unbalanced grid voltage signal. However, performance

deteriorates when grid signal is distorted. The PD structure based on generalized integrator (GI) is an

attractive solution to accurately estimate phase/frequency. However, in case of non-sinusoidal input

signals and varying frequency conditions it results into erroneous performance [20-21]. Unlike it, the

second-order GI based PLL (SOGI-PLL) shows accurate performance with the distorted input signals and

is even suitable for variable frequency applications. To compute the frequency, the SOGI-PLL

continuously utilizes the estimated frequency as a feedback for SOGI block, Unlike it, the frequency-

locked loop (FLL) adaptively obtains the frequency information avoiding the need of PLL. It further

improves the response [22-23]. The performance can further be improved by employing two SOGI-FLL

(DSOGI-FLL), resulting into better transient response and stability in the presence of grid abnormalities

[17]. However, even with DSOGI-FLL the frequency estimation is erroneous when the input signal bears

a dc-offset [24-30]. Modified SOGI-FLL structure known as modified adaptive notch filter (ANF) is

Page 5: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

4

reported to tackle the issue of dc-offset in estimation of frequency for single phase systems. Three such

ANFs are required for three-phase systems [26].

Apart from these disturbances, presence of dc component affects the performance of synchronization

schemes or phase angle estimation. The probable source of dc component can be the measurement errors,

conversion errors resulting through the data converters, inaccurate signal conditioning circuits, injection

from DG due to their improper control, saturation of magnetic components etc. The performance of

conventional PLLs, DSOGI-PLL and DSOGI-FLL is severely hampered in presence of the dc-offset. The

estimated frequency under such case is characterized by presence of low frequency component

superimposed on the average value. This aspect (frequency estimation in presence of the dc-offset) is not

fully explored. To target this issue, few methods have been reported [24-29]. However, they are complex

and/or suggested for single-phase system. Hence, in order to eliminate errors in frequency estimation

caused due to presence of the dc-offset and other grid abnormalities (e.g. unbalance, harmonics,

frequency variation, magnitude variation etc.), it is needed to investigate further into this area to provide a

better alternative of phase/frequency estimation under such non-ideal conditions.

3. Definition of the Problem

The injection of harmonics by the non-linear loads connected at the PCC and by other power

electronic converters in the grid may distort the source current and the voltage at the PCC in the modern

power system. The consumption of this current deteriorates the performance of the various electrical

equipments connected to the utility and reduces the life expectancy of them. The deteriorated quality of

voltages and/or currents further introduces the challenge in correct detecting the zero-crossing of the grid-

voltage and hence, its phase, frequency and magnitude estimation. Also, protective devices connected to

the utility may mal-operate. The major problem is faced by the power electronic converters, which

requires the accurate phase and frequency estimation of the grid voltages and currents for various

functions like active-reactive power control, harmonic mitigation, imbalance mitigation, improving

system stability etc., for which they are employed. This leads to the deviation in their operation from the

desired one and hence, lead to further deterioration of the power quality making the challenge of phase

and frequency estimation still complex. Different three phase time domain approaches based on PLL and

FLL have been studied so far to estimate positive sequence components as well fundamental frequency in

circumstances likes imbalance, frequency jump, phase jump, harmonics etc. in grid utility. However, this

estimation is affected if any dc-offset error is introduced to the sensed grid signal. This dc component

results due to inaccurate A/D conversion process, measurement errors, dc injection from distributed

generation systems, and so on. Hence, it is advisable to have a phase and frequency detection technique

that can accurately estimate the phase and frequency even when the voltage at the PCC is highly distorted

and bears non-idealities like harmonics, imbalance and dc-offset. Accordingly, the goal is set to provide

Page 6: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

5

a robust fundamental frequency/positive sequence extraction scheme to cope up the effect of the dc-offset

component.

4. Objective and Scope of work

The objective of the research area is summarized as under:

“To investigate the issues related to the modern power system which is characterized by the

presence of power electronic converters for applications like interfacing DGs, improving system

performance, and for meeting the need of modern domestic and industrial loads. As proper operation

of these converters require accurate phase (or frequency) and magnitude information of the grid

voltage and or currents for applications like synchronization, active-reactive power control, load

sharing, harmonic compensation etc., it is intended to devise a suitable PLL OR FLL scheme for

estimating the fundamental frequency/positive sequence components under non-ideal conditions (like

voltage unbalance, harmonics, dc-offset etc.), to enhance the performance of power electronics

converters and to utilize the scheme in designing control strategy for power electronic converters to

provide system support benefits like reactive power and harmonic current compensation.”

The scope of work includes:

1. To study and evaluate various fundamental frequency estimation/positive sequence extraction

techniques in terms of their capabilities to estimate the frequency when the grid voltage is

distorted (i.e. characterized by harmonics, imbalance, dc-offset)

2. To suggest and implement the fundamental phase angle estimation technique which can correctly

estimate the frequency under all such non-idealities.

3. To explore and prepare the performance comparison of these techniques using simulation in

MATLAB/Simulink and also to validate the same with experiments.

4. To evaluate the effect of these frequency estimation techniques on operation of power electronic

converters on one or more aspects like reactive power compensation, harmonic compensation,

synchronization, protection schemes of converters etc. through simulation and experimental

studies.

5. Original contribution by the thesis

The main contributions in the thesis are

1. Evaluation of various frequency estimation techniques in terms of their capability to estimate the

frequency when the grid/supply voltage is characterized by harmonics, imbalance and dc-offset.

With traditional frequency estimation techniques, the oscillatory response is observed in the

frequency estimation when the grid voltage has the dc-offset component.

2. Development, analysis and experimental verification of conventional and proposed method for

fundamental frequency/positive sequence components estimation under distorted grid conditions:

Page 7: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

6

The proposed modified DSOGI-FLL (MDSOGI-FLL) technique can eliminate the effect of

the dc-offset.

The performance is analyzed for different grid voltage conditions from the simulation as well

as experimental implementation.

3. Development, analysis and experimental verification of this proposed MDSOGI-FLL method for

estimating the reference compensating current for the SAPF

The performance is tested for different grid voltage conditions: ideal sinusoidal balanced grid

voltage, imbalance voltages with and without distortion, sinusoidal voltage with dc-offset,

imbalance voltages with dc-offset etc.

The simulation and experimental validation is carried out for grid tied SAPF.

It is highlighted that the SAPF based on modified DSOGI-FLL accurately tracks the

fundamental frequency as well positive sequence components under all conditions as

compared to traditional techniques. It gives satisfactory performance of the SAPF even when

grid voltage is characterized by the dc-offset.

6. Methodology of Research, Results / Comparisons

Various techniques that are available for the estimation of the frequency and magnitude of the grid

voltage/current are reviewed. The techniques can be classified as shown in the Fig. 1. Another way of

classification is based on whether they employ time or frequency domain approach. The time domain

techniques are very popular compared to the frequency domain techniques as they involve complexity in

implementation, gives better dynamic performance, and are robust in various grid abnormalities.

Fig. 1 Classification of synchronization scheme

Synchronization methods for converter sytems

Single-phase system Three-phase system

Closed-loop

Transport-

delay (T/4)

Inverse Park

transformation

Hilbert

transformation

EPLL

ANF

PSF

SSI

SOGI-PLL

SOGI-FLL

Kalman

Classical

single-phase

PLL

Enhanced PLL

(EPLL)

Vector-based

PLL

(based on

orthogonal

component

generation)

Modification

on

Classical

single-phase

PLL

ALOF-PLL

Fourier-

based PD

Symmetrical

component-

based PD

Adaptive

PLLClassical

SRF-PLL

Enhanced

PLL

(EPLL)

DFT based

Improvements/

Modifications

On

Classical SRF-PLL

Adding

filters

Extracting

symmetrical

components

Stationary

Reference

frame

Synchronous

rotating frame DDSRF-PLL

Neural-network

based

2nd order

LPF-based

Kalman

Adaline

LPF

MAF

Resonant

filter

DFT-based

controller

Notch filters

Closed-loop

Orthogonal

component-based

techniques

Page 8: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

7

6.1. Analyzing the performance of various frequency estimation techniques

Out of the various frequency estimation (or grid synchronization) techniques SRF-PLL and its

variants are widely employed [16]. Recently DSOGI-PLL due to its superiority over SRF-PLL has been

advocated by many researchers [17-18]. The comparison of fundamental frequency estimation algorithms

like SRF-PLL, DDSRF-PLL, DSOGI-PLL and DSOGI-FLL has been investigated using MATLAB

simulink modeling for three-phase system. The performance analysis of these techniques have been

investigated when the supply voltage experience imbalanced (single-phase sag) condition from healthy

condition at time t=0.1s. Also frequency jump in input signal (50 Hz to 45 Hz) occurs at t=0.25 s. The

tracking of the fundamental frequency 𝜔′ (rad/s) is accurately done by the DSOGI-FLL algorithm as

compared to other conventional PLL. Fig. 2 shows the relative performance of some of the frequency

estimation techniques. Apart from it, the performance of aforesaid algorithms is investigated when the

grid signal undergoes various abnormalities like phase jump, presence of harmonics components etc. The

performance of DSOGI-FLL for fundamental frequency estimation is superior for all type of grid

disturbances.

Fig. 2 Frequency estimation ω’ (rad/s) using different estimation algorithm in case supply voltage undergoes sag at time

t=0.15s and frequency step (50 Hz to 45 Hz) at 0.25s.

6.2 Proposed MDSOGI-FLL technique for frequency and magnitude estimation

This section presents the basic configuration of proposed MDSOGI-FLL. Fig. 3(a) shows structure of

basic conventional MDSOGI-FLL. The Clarke transformation is utilised to transform time-domain

signals from a natural three-phase coordinate system (abc) into a two-phase stationary reference frame

αβ0. The shaded block showing two MSOGI-QSG that represents modified dual second-order

generalized integrators is the key part of PLL or FLL structure. The details of MSOGI-QSG are shown in

Fig. 3(b). The y’’α and qy’’α signals forms a pair of quadrature signals where qy’’α lags y’’α by 90º. These

signals are used to extract positive sequence components through the Positive Sequence Calculator (PSC

shown in Fig. 3(a)) in the αβ stationary reference frame. The positive sequence components y’α and y’β

can be utilized to estimate the positive sequence (𝑦𝑎𝑏𝑐𝑠+ ) of the distorted grid input signal. A simple auto

tune block shown in Fig. 3(c) is used to adapt the center frequency 𝜔′ of the SOGI resonator to the input

Page 9: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

8

frequency. The frequency is estimated through the Frequency-Locked Loop (FLL) block in MDSOGI-

FLL and thus it discards the PLL block required in DSOGI-PLL. Hence, in the grid abnormalities like

sag, swell, variations, phase jump, harmonics etc., the MDSOGI-FLL performs extremely well, fast and

precisely as compared to conventional SRF-PLL and DSOGI-FLL based schemes. Fig. 3(b) shows the

DC-Loop’, which is added to the conventional SOGI to tackle the issue of dc-offset. For conventional

SOGI (i.e. in absence of the DC-loop), if the input voltage is characterized by the presence of the dc-

offset, the y’’β also contains dc-offset resulting into erroneous estimation of the frequency.

(a)

(b) (c) Fig. 3. Basic structure of MDSOGI-FLL: (a) abc to α

+ computation (b) MSOGI-QSGs and (c) FLL-block.

It is worth noting from the above section that the conventional DSOGI-FLL fails to estimate the

frequency accurately when sensed grid signals are characterized by the dc-offset. The inclusion of third

integrator into the proposed MDSOGI-FLL structure shown in Fig.3 (a) results into large attenuation of

fundamental component (also higher order frequencies to a certain extent) allowing only the low order

frequencies to pass. Thus, it helps to estimate and eliminate the dc-offset accurately from input signals

vs/iL of Fig. 3(b).

The effectiveness of the proposed MDSOGI-FLL is demonstrated through the simulation results

obtained in MATLAB/Simulink. The parameter values used in the MDSOGI-FLL simulation model are

as follows: k1=1.28, kdc=0.26 and γ=40. The performance is evaluated when the supply voltage is having

abcyMSOGI

y

y

"y 'y

'y

PSC

'

"qy

"y

sT

MSOGI

2

1

2

1

2

1

2

1

"qy

'

Ls qiqv '/'

Ls iv /

1x

2x

dck

Ls iv '/'

DC Loop

1k'

x1

+

+

100C

.

2)(2)(

x2

num

den

k1

Page 10: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

9

imbalance along with the dc-offset. In Fig. 4, step change in amplitude of the grid signal is considered

only for phase ‘a’. At t=0.15s, the amplitude of phase ‘a’ voltage decreases from 1pu to 0.5pu. Also the

dc-offset of 0.1pu is introduced at t=0.15s. In addition, at t=0.25s frequency of grid signal suddenly

changes from 50Hz (314rad/s) to 45Hz (282.6rad/s). The ripple in the estimated frequency of DSOGI-

FLL is observed. The MDSOGI-FLL shows superior performance. As a result, the grid signal frequency

is quickly and accurately tracked. Apart from it, the positive sequence components y’α and y’β for

MDSOGI-FLL are free from offset, unlike that observed for DSOGI-FLL.

(a)

(b)

Fig. 4. Performance under unbalanced sag conditions: (a) Three-phase grid voltage signals. (b) Estimated frequency.

Table I shows the settling time for these frequency estimation techniques in response to a step change

in the frequency at t=0.25s. SRF-PLL and MDSOGI-PLL are relatively faster than other techniques. It

must be noted that except MDSOGI-FLL all other techniques show sustained oscillations in the estimated

frequency. Hence, the settling time for these techniques is determined as the time from the step change

till the estimated frequency waveform reaches a stage where sustained oscillations with a constant

average (dc) value is achieved. The proposed MDSOGI-FLL performs well on all the aspect even when

the dc-offset is present. Thus, it is not only fast but also accurate under all grid abnormalities.

TABLE I

TIME RESPONSE FOR DIFFERENT FREQUENCY ESTIMATION TECHNIQUES

PLL-type Estimated time

(ms)

Observed time

(ms)

SRF-PLL 40 50

DDSRF-PLL 40 70

DSOGI-PLL 40 45

DSOGI-FLL 40 60

MDSOGI-FLL 40 50

Page 11: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

10

The experimental results are included to validate the effectiveness of the proposed MDSOGI-FLL.

The different cases considered for simulation are verified experimentally using dSPACE DS1104 DSP

board as control system. The values of various parameters for which the MDSOGI-FLL is tuned are k1=

1.28. kdc=0.26 and γ=40, while those for DSOGI-FLL are k1 =1.41 and γ=100. The fundamental

frequency of the three-phase supply voltage and the sampling frequency are 50Hz and 10kHz,

respectively. The same parameters that are considered for simulation study carried out in

MATLAB/Simulink are adopted for experimental verification.

For the comparison of the proposed MDSOGI-FLL structure against the conventional DSOGI-FLL,

experimental results for one of the cases in which, voltage sag of 50% is introduced in just one of the

phases along-with the dc-offset in all the three phases, are shown in Fig. 6.. The three-phase unbalanced

voltage signals are shown in Fig. 5(a). Fig. 5(b) represents the comparison of the estimated frequency by

both these methods. Frequency obtained through DSOGI-FLL approach shows that the estimated

frequency is characterized by an oscillatory response, with a 100Hz frequency ripple. Frequency

estimated by MDSOGI-FLL not only is free from oscillations, but also has lower frequency dip

corresponding to sudden frequency decrease. Thus, the overshoot with the step response with MDSOGI-

FLL is less indicating a better transient response.

w’ (50 V/div)

Vabc

(5 V/div)

Frequency

Jump

25 ms/div

Single Phase

SagInitial Condition Regain

(a)

DSOGI-FLLMDSOGI-FLL

25 ms/div

(b)

Fig. 5. Experimental results with imbalance and dc-offset in supply voltage: (a) Three-phase grid voltage (b) Estimated

frequency with DSOGI-FLL and MDSOGI-FLL.

6.3 Harmonic mitigation with SAPF based on MDSOGI-FLL

The proposed MDSOGI-FLL is integrated with the instantaneous reactive power theory (p-q theory) to

design a control scheme for a SAPF, which can effectively operate even when grid-voltage is

characterized by abnormalities like, harmonics, imbalance, dc-offset etc. The details of the control

technique and the simulation and experimental set-up are explained next.

Fig.6 shows the system configuration of the MDSOGI-FLL based SAPF, which is connected at the

point of common coupling (PCC) to supply the harmonics generated by the non-linear load. As a non-

Page 12: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

11

linear load, a three phase uncontrolled rectifier feeding a resistive load (RL) is considered. The input

current, iLabc of the rectifier is characterized by the harmonics of the order 6n±1 (where n = 1, 2, 3...).

The SAPF injects compensation currents iCabc at the PCC through the coupling inductance Lf making the

supply current (isabc) free from the harmonics. In addition, the SAPF also supplies the reactive power

demand of the load to achieve a unity power factor operation of the grid (at the PCC). Semikron’s

Voltage Source Inverter (VSI) employing self-controlled Insulated Gate Bipolar Transistor (IGBTs)

switches S1 through S6, is used as the SAPF. The sensor card (LV-25-600) is used to sense dc bus

capacitor voltage vdc. Load current (iLabc) and the inverter output currents (iCabc) are sensed through

current transformers (CT) and processed through signal conditioning circuits before feeding to the

dSPACE MicroLabBox-1202.The supply voltage is stepped down through transformers and then fed to

dSPACE MicroLabBox-1202, which controls the VSI to act as the SAPF. The software implementation

Fig. 6 Circuit configuration of three-phase SAPF.

of reference current generation (RCG) and PWM hysteresis current control algorithm is implemented in

MATLAB/Simulink and fused in the processor of dSPACE MiroLabBox-1202 to finally generate the

switching signals, which are applied to the IGBTs of VSI through PWM isolator driver card (Edutech

Application Specific kit-30).

The control strategy employs the instantaneous power theory commonly known as p-q theory which

is being utilized to calculate the reference compensating current. The Clarke’s transformation transforms

these three-phase quantities to two-phase stationary reference frame voltages vsαβ0, and currents iLαβ0,

respectively. Apart from this, the reference current generation through the conventional DSOGI-FLL and

proposed MDSOGI-FLL is explained. However, it is very challenging task to calculate the reference

compensating current 𝑖𝐶,𝑎𝑏𝑐 ∗ when the utility is distorted by the various grid-load tie-up situation in

micro-grid, weak grid etc.

vdc

Cai

PW

M Iso

lato

r

Driv

er C

AR

D

Sig

nal S

en

sing

an

d

Pro

cessin

g C

ard

vsa

vsb

vsc

isa

isb

isc

iCa iCb iCc

iLa

iLb

iLcRL

iLa

iLb

iLc

vdc

VSI

Lf Lf Lf

C

PCC

iCa

iCb

iCc

S1--S6

E

dS

PA

CE

Mic

roL

abB

ox-1

202

G

C

Page 13: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

12

6.3.1. RCG based on MDSOGI-FLL

The calculation of reference current 𝑖𝐶,𝑎𝑏𝑐 ∗ is carried out through the p-q theory [5]. The three-phase

grid voltage vsabc (voltage at PCC) and three-phase load currents iLabc, are sensed and converted to

stationary reference frame (vsα , vsβ and iLα , iLβ in αβ reference frame) using Clarke’s transformation.

These two phase quantities are used to calculate the instantaneous active and reactive power as follows:

𝑝 = 𝑣𝑠∝ ∙ 𝑖𝐿𝛼 + 𝑣𝑠𝛽 ∙ 𝑖𝐿𝛽 = 𝑝 + 𝑝 (1)

𝑞 = 𝑣𝑠𝛽 ∙ 𝑖𝐿𝛼 − 𝑣𝑠𝛼 ∙ 𝑖𝐿𝛽 = 𝑞 + 𝑞 (2)

where, 𝑝 and 𝑝 represents the average and oscillating components of the instantaneous real power,

respectively. Similarly, 𝑞 and 𝑞 represents the average reactive power and oscillating components of the

instantaneous reactive power, respectively. The fundamental components of iLabc in the αβ reference

frame, 𝑖′𝐿𝛼 and 𝑖′𝐿𝛽 , depend only on the average active power and reactive power. Hence,

𝑖′𝐿𝛼 ,𝑝 and 𝑖′𝐿𝛽 ,𝑝 , the components of iLabc, that contribute only to average active power consumed by the

load are expressed by (3).

𝑖′𝐿𝛼 ,𝑝

𝑖′𝐿𝛽 ,𝑝 =

1

𝑣𝑠𝛼2 + 𝑣𝑠𝛽2

𝑣𝑠𝛼𝑣𝑠𝛽

𝑝 (3)

As the SAPF is intended to supply only the reactive power and harmonic currents, the reference

compensating current 𝑖𝐶,𝑎𝑏𝑐 ∗ is derived using (4).

𝑖𝐶𝑎𝑏𝑐 ∗ = 𝑖𝐿,𝑎𝑏𝑐 – [𝑖′𝐿,𝑎𝑏𝑐

] (4)

where 𝑖′𝐿,𝑎𝑏𝑐 is the obtained using αβ-abc transformation expressed by (5).

[𝑖′𝐿,𝑎𝑏𝑐

] =

𝑖′𝐿𝑎𝑖′𝐿𝑏𝑖′𝐿𝑐

=2

3

1 0

−1

2

3

2

−1

2− 3

2

𝑖′𝐿𝛼 ,𝑝

𝑖′𝐿𝛽 ,𝑝 (5)

To maintain the voltage vdc constant, it is required to compensate for the parasitic losses occurring in the

capacitor and the losses in the inverter. This can be achieved by using 𝑝 expressed by (6) in (3).

𝑝 = 𝑣𝑠𝛼 𝑖′𝐿𝛼 + 𝑣𝑠𝛽 𝑖′𝐿𝛽 + 𝑝𝑙𝑜𝑠𝑠 (6)

The term ploss represents the active power required to meet the losses of inverter and capacitor, to

regulate the voltage at dc-bus. It can be obtained through proportional-integral (PI) controller by

processing the difference of the reference and actual voltage at the dc-bus. The fundamental positive

sequence components vs (and iL) is obtained from MDSOGI-FLL structure mentioned in Fig. 3. Fig. 3 (a)

comprises of two modified SOGI, commonly known as dual SOGI (DSOGI) structure. It estimates

filtered in-phase and quadrature components y’α, and y’β of the measured quantity y. Thus, two such

Page 14: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

13

structures are used: one each for grid-voltages and load currents to obtain the in-quadrature components:

v’sα, and v’sβ for voltages and i’Lα and i’Lβ for currents. The αβ components derived from three-phase ‘abc’

signals using Clarke’s transformation are no longer sinusoidal under distorted supply conditions and

hence, may affect the reference current generation. Hence, the SOGI acts on these αβ components to filter

out the harmonics and to yield a set of in-quadrature sinusoidal signals (y” and qy”) at the fundamental

frequency. From these set of in-quadrature signals derived from the two SOGIs, which are even utilized

to estimate the frequency, the PSC y’α and y’β (v’sα, and v’sβ from grid voltages and i’Lα and i’Lβ from load

currents) are derived. The filtered in-quadrature positive sequence components, v’α, and v’β and i’Lα and

i’Lβ, are utilised in the instantaneous power theory, to compute the compensating current. Thus, in (6),

𝑣𝑠𝛼 and 𝑣𝑠𝛽 are replaced by v’sα, and v’sβ. i’Lα and i’Lβ are the positive sequence load current components

derived as shown in Fig. 3(b). Fig. 7 shows the reference current generation for the MDSOGI-FLL based

SAPF, which fundamental load current i’Labc is compared with the actual sensed load current iLabc to get

the iCabc*. The difference of this reference current and inverter output current iCabc is control via hysteresis

current control loop to obtain the six switching pulses.

Fig. 7 Reference current calculation block.

6.3.2 Simulation and experimental results analysis

RCG discussed in section 6.3.1 is employed for load harmonic compensation using the SAPF system

configuration of Fig. 6. The simulation results obtained using MATLAB/Simulink and the experimental

results with the prototype of Fig. 8 are included in this section. The system parameters are tabulated in

Table II. The performance evaluation is compared for both the conventional DSOGI-FLL and MDSOGI-

FLL reference current generation scheme to highlight the superior performance of the MDSSOGI-FLL

based SAPF.

TABLE II

SYSTEM PARAMETERS

Supply voltage (RMS) 110V (phase voltage), 50 Hz

Non linear load Three phase bridge rectifier with Resistive Load of RL = 90Ω

DC-link capacitor C = 1100µF

DC-link voltage 300 V

Coupling inductor Filter inductance Lf = 5 mH

Source impedance Rs = 0.02 Ω , Ls = 1µH

Inverter rating 25kVA

Eqa. (6)

'v

Li' Li'

pLi ,'

pLi ,'

αβ/ abc

Labci'

Labci

+

-

Cabci*

'v

-PI

Vdc*

Vdc

+ploss

Page 15: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

14

Fig. 8 Hardware setup for SAPF

Figs. 9 and 10 show the response of the SAPF with the DSOGI and MDSOGI based control

algorithms, respectively. Figs. 9(a) and 10(a) show supply voltage in which phase-a has a dc-offset of

10% of the fundamental phase-voltage (RMS). Phase-a further experiences a voltage sag of 20% at

t=0.3s. The SAPF is turned on at t=0.2s.

Fig. 9(b) and 10(b) show, that in-quadrature components vsα and vsβ for both the approaches are of

similar nature. The dc-offset is observed in vsα. In addition, after t=0.3s when the supply voltage is

unbalanced, the components vsα and vsβ, though sinusoidal are distinct in magnitudes. The dc-offset is

even present in v’sβ with the DSOGI structure as observed in Fig. 9(c). The reason behind the presence of

dc-offset in v’sβ is the inability of the DSOGI to attenuate the low frequency component from it. Unlike it,

Fig. 10(c) shows that both v’sα and v’sβ, obtained with the MDSOGI structure, are not only identical in

magnitude but also free from dc-offset. Similarly, DSOGI structure can yield sinusoidal i’Lα and i’Lβ [Fig.

9(e)] components from the non-sinusoidal components iLα and iLβ [Fig. 9(d)]. However, i’Lβ also shows the

dc-offset. The dc-offset also leads to the ripple (oscillation) of 100Hz in the estimated frequency [Fig.

9(f)]. This ultimately, affects the reference current generation, leading to offset in the grid current as well.

The THD analysis of the grid current (for phase-a) shown in Fig. 9(g) is displayed as Fig. 9(h). It shows

SEMIKRON VSI ModuledSPACE-MicroLabBox-1202

PWM Isolator Driver Card

Sensor Card

PCC

Bridge Rectifier

RL

Lf

PC

Linear Load

Page 16: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

15

the presence of dc-component. In addition, the 100Hz ripple in the estimated frequency results into 2nd

harmonic in the grid current leading to the THD of 5.82%.

Fig. 10(e) shows that just like v’sα and v’sβ the i’Lα and i’Lβ components obtained through the

MDSOGI structure is free from the dc-offset. The filtering effect of the ‘DC-loop’ shown in Fig. 3(b)

helps in removing the oscillations in the estimated frequency. Fig. 10 (f) shows the ripple-free estimated

frequency. As a result, it helps in accurately generating the reference compensating current, leading to a

sinusoidal source current which is free of dc-offset. Fig. 10(e) shows the source current while the

harmonic spectrum for the phase-a source current is shown in Fig. 10(g). The harmonic spectrum

confirms the absence of the dc component from the source current. Even the second harmonic is absent.

The THD of the current is noted as 3.57% with MDSOGI structure against the 5.82% observed with the

DSOGI structure.

Experimental results are included in form of Figs.11 through 13 to justify the superior performance of

MDSOGI-FLL based SAPF over that of DSOGI-FLL based SAPF. Fig. 11 shows the performance of

the DSOGI-FLL based SAPF when operating with unbalanced supply voltage (without any dc-offset).

Fig. 11(a) shows that phase-a voltage undergo sag of 20% of fundamental. It shows that, as soon as the

SAPF is activated, the grid current not only becomes sinusoidal but also remains in phase with the phase

voltage resulting into unity power factor operation. The components vsα and vsβ [Fig. 11(b)], obtained

through Clarke’s transformation on the supply voltages, are not identical. The current components iLα and

iLβ [Fig. 11(c)] are also not identical and deviate from sinusoidal conditions. However, the voltage

components v’sα and v’sβ [Fig. 11(b)], and the current components i’Lα and i’Lβ [Fig. 11(c)] are sinusoidal

and nearly equal in magnitude, demonstrating the filtering capability of the SOGI structure. As a result,

the frequency is correctly estimated and shows a constant value (ripple free) as shown in Fig. 11(d). The

harmonic spectrums for the uncompensated source current and the compensated source currents (i.e.

when SAPF is active) are shown in Figs. 11(e) and 11(f), respectively. Reduction of THD from 10.7% to

2.47% is observed with the incorporation of the SAPF.

Fig. 12(a) shows the 3-phase unbalanced supply voltage where the phase-a not only experiences sag

(20% of fundamental) but also has a dc-offset (10% of fundamental). Such offset may be present in a

weak grid. Even if it is not present in the utility voltage, it may enter into the computation due to the error

in sensing and processing the signals. The experimental results shown here consider that the offset is not

in the actual grid signal, but has resulted from measuring or signal processing errors. Thus, the

waveforms of Fig. 11(a) represents the sensed supply voltages. Unlike the earlier case, the dc-offset is

observed in vsα. As a result, the dc-offset is also observed in v’sβ [Fig. 11(b)]. Fig. 11(c) shows that the

offset is also reflected in the waveforms of iLα and i’Lβ. Hence, unlike the earlier case, the nature of the

estimated frequency ω’ is oscillatory in nature.

Page 17: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

16

Fig. 9 Simulation results for DSOGI-FLL based SAPF. Fig. 10 Simulation results for MDSOGI-FLL based SAPF.

vsa vscvsb

SAPF on Phase-a sag

dc-offset

v sab

c (V)

(a) vsa vscvsb

SAPF on Phase-a sag

dc-offset

v sab

c (V

)

(a)

vsα vsβ

v sαβ

(V)

(b) vsα vsβ

v sα

β (V

)

(b)

v’sαv’sβ

v’sα

β (V

)

(c) v’sα v’sβ

v’sα

β (V

)

(c)

iLα iLβ

i Lα

β (A

)

(d)

i Lα

β (A

)

iLα iLβ (d)

i’Lα

β (A

)

i’Lα i’Lβ (e)

i’L

αβ (A

)

i’Lα i’Lβ (e)

ω’ (rad/s)

Vdc (V)

(f)

ω’,

Vdc

ω’ (rad/s)

Vdc (V)

(f)

ω’,

Vdc

isa isb isc

i sa

bc

(A)

(g)

Time (s)

i sa

bc (

A)

isa isb isc

Time (s)

(g)

Page 18: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

17

Fig. 11(d) shows that the estimated frequency is having a ripple of 100Hz. The supply current is also

characterized by the dc-offset resulting into a higher THD of the source current. The harmonic spectrum

of source current is shown in Fig. 12(f), which displays THD of 5.94%. Thus, DSOGI based SAPF is

unable to negate the effect of the dc-offset resulting into the computation of an inaccurate compensating

current. This finally leads to a grid current with a dc-offset and higher THD.

Fig. 13 shows the performance with MDSOGI-FLL based SAPF. The similar test conditions, as

considered for results of Fig. 12, are maintained. The MDSOGI structure estimates the dc-offset

component present in the input signal through integral action of the DC-loop shown in Fig. 3. It is

illustrated through Fig. 13(b) that the waveform of v’sα and v’sβ are sinusoidal, free of dc-offset and

identical in magnitude. Even-though vsα is characterized by the presence of dc-offset, it is not observed in

either v’sα or v’sβ. The same is true for i’Lα and i’Lβ [Fig. 13(c)]. Unlike the earlier case [Fig. 12(d)], the

estimated grid-signal frequency shown in Fig. 13(d) is free from 100Hz ripple. Hence, MDSOGI-FLL

based SAPF accurately calculates the reference compensating current resulting into a source current with

lower THD [Fig. 13(f)]. Reduction of THD from 10.9% to 2.09% is observed when the MDSOGI-FLL

based SAPF is activated. Thus, the proposed MDSOGI based SAPF shows superior performance under

all types of grid voltage abnormalities.

vsa vsbvsc isa

SAPF off

vsβvsα

v’sα v’sβ

iLα iLβ i’Lα i’Lβ

(a) (b) (c)

w’

vdc

(d) (e) (f)

Fig. 11 Experimental results for DSOGI-FLL based SAPF with unbalanced supply voltage having no dc-offset error.

Page 19: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

18

vsavsb

vsc

isa

SAPF off

vsα vsβ

v’sα v’sβ

iLα iLβ i’Lα i’Lβ

(a) (b) (c)

w’

vdc

(d) (e) (f)

Fig.12 Experimental results for DSOGI-FLL based SAPF when the supply voltage is unbalanced and has dc-offset in phase-

a.

vsa vsbvsc

isa

v’sα v’sβ

vsα vsβ

iLα iLβi’Lα i’Lβ

(a) (b) (c)

w’

vdc

(d) (e) (f)

Fig.13 Experimental results for MDSOGI-FLL based SAPF with voltage sag and dc offset in phase-a.

iCa*

iCa

Page 20: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

19

7. Achievements with respect to objectives

The necessity of the phase angle estimation and synchronization using PLL techniques is required

for wide range of application power electronics converters i.e. synchronization, reactive power

compensation, distributed power generation, active power filtering, load sharing, activation of protection

schemes etc. Hence, it is essential that phase and supply frequency of the voltage/current should be

estimated accurately to achieve the desired objective for the various applications mentioned above.

The effects of the various non-idealities/abnormalities in the PCC voltage like harmonics, imbalance

and dc-offset on the various phase and frequency estimation schemes have been investigated.

Simulation results and experimental investigations have been included to highlight that most of the

techniques fail in presence of dc-offset in the sense voltage/current. [Publication 5]

The proposed MDSOGI-FLL included in this research article has a robust performance in estimating

the fundamental frequency and magnitude among all the PLL studied above in various grid

abnormalities, even in case when the PCC voltage has dc-offset. Publication [1-2]

Fig. 14 shows the comparison of different frequency estimation techniques when subjected to a step

change in the supply frequency. The supply voltage is considered to have the harmonics, unbalance

and the dc-offset. The comparison is carried out for ωn = 2π50 rad/s, ζ= 0.707 to have the settling

time of 40ms.

Fig. 14 Performance comparison of different frequency estimation methods.

The inability of the conventional schemes to estimate the phase and frequency correctly under the

non-ideal supply voltage conditions, affects the performance of the power electronic converters. To

evaluate the performance of these PLL schemes under non-ideal voltage conditions on converter’s

performance, simulation and experimental studies are performed for a 3-phase shunt active filter. It is

demonstrated that even the DSOGI-FLL, which is quite accurate in estimating the phase/frequency

and magnitude of a PCC voltage infected by harmonics, fails when the same PCC voltage is

characterized by the dc-offset. Publication [3]

The feature of the MDSOGI-FLL to work effectively even with the PCC voltage having harmonics,

imbalance and dc-offset is utilized to design a 3-phase active filter that gives better performance

under all such non-idealities. The performance is examined through simulation results as well as

experimentally with the real time implementation. Publications [4]

Page 21: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

20

8. Conclusion

This research article presents a MDSOGI-FLL algorithm to estimate the positive sequence components of

distorted grid signal having harmonics, imbalance and dc-offset. The proposed technique estimates the dc

component from the input signal and rejects its effect in fundamental frequency/positive sequence

components calculation. The estimation is relatively fast and accurate compared to other conventional phase

angle estimation techniques.

An active filter based on DSOGI-FLL is designed for harmonic components mitigation. Effect of any

offset error in measurement, data conversion processes (A/D or D/A) or in the grid voltage is nullified through

the proposed MDSOGI-FLL technique. Hence, positive sequence components are estimated correctly for

further calculation of reference current generation of SAPF. Experimental results justify the robustness of the

proposed technique in unbalanced grid voltage having the dc-offset component.

9. Copies of papers published and a list of all publications arising from the thesis

[1] K. R. Patil and Hiren H. Patel, “Modified dual second-order generalised integrator FLL for

synchronization of a distributed generator to a weak grid,” in Proc. 16th

Annu. Conf. IEEE-EEEIC,

June 2016.

[2] K. R. Patil and Hiren H. Patel, “Modified dual second-order generalized integrator FLL for frequency

estimation under various grid abnormalities,” in Transactions on Environment and Electrical

Engineering, vol. 1, no. 4, pp. 10-18, October-2016.

[3] K. R. Patil and Hiren H. Patel, “Performance of shunt active power filter with DSOGI-FLL under

distorted grid voltage,” in 2nd

Annu. Conf. IEEE- ICECCT, February 2017.

[4] K. R. Patil and Hiren H. Patel, “Shunt active power filter based on MDSOGI-FLL to address the issue

of dc-offset,” submitted to IEEE Tans. on Ind. Electronics.

[5] K. R. Patil and Hiren H. Patel, “Review of fundamental frequency estimation techniques for non-ideal

utility voltages ,” to be submitted to international coference/journal.

10. References

[1] J. Dixon, L. Moran, J. Rodriguez and R. Domke, “Reactive power compensation technologies: State-

of the-Art Review,” in Proceedings of the IEEE, vol. 93, no. 12, pp. 2144-2164, December 2005.

[2] R. N. Beres, X. Wang, M. Liserre, F. Blaabjerg and C. L. Bak, "A review of passive power filters for

three-phase grid-connected voltage-source converters," in IEEE Journal of Emerging and Selected

Topics in Power Electro., vol. 4, no. 1, pp. 54-69, Mar 2016.

[3] H. Akagi, “New trends in active filters for power conditioning,” in IEEE Trans. on Indu. Appl., vol.

32, no. 6, pp. 1312-1322, December 1996.

[4] H. Akagi, "Active Harmonic Filters," in Proceedings of the IEEE, vol. 93, no. 12, pp. 2128-2141,

December 2005.

Page 22: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

21

[5] H. Akagi, E. H. Watanabe, and M. Aredes, Instantaneous Power Theory and Applications to Power

Conditioning, M. E. El-Hawari, Ed. New York: Wiley, 2007.

[6] M. I. M. Montero, E. R. Cadaval and F. B. Gonzalez, "Comparison of control strategies for shunt

active power filters in three-phase four-wire systems," in IEEE Trans. on Power Electron., vol. 22,

no. 1, pp. 229-236, January 2007.

[7] B. Singh and J. Solanki, "An implementation of an adaptive control algorithm for a three-phase shunt

active filter," in IEEE Trans. on Ind. Electron., vol. 56, no. 8, pp. 2811-2820, August 2009.

[8] Q. N. Trinh and H. H. Lee, “An advanced current control strategy for three-phase ahunt active power

filters,” in IEEE Trans. on Ind. Electron., vol. 60, no. 12, pp. 5400-5410, December 2013.

[9] P. Kanjiya, V. Khadkikar and H. H. Zeineldin, "A noniterative optimized algorithm for shunt active

power filter under distorted and unbalanced supply voltages," in IEEE Trans. on Ind. Electron., vol.

60, no. 12, pp. 5376-5390, December 2013.

[10] P. Kanjiya, V. Khadkikar and H. H. Zeineldin, “Optimal control of shunt active power filter to meet

IEEE std. 519 current harmonic constraints under nonideal supply condition,” in IEEE Trans. on Ind.

Electron., vol. 62, no. 2, pp. 724-73, February 2015.

[11] D. Dinh, N. D. Tuyen, G. Fujita and T. Funabashi, “Adaptive notch filter solution under unbalanced

and/or distorted point of common coupling voltage for three-phase four-wire shunt active power filter

with sinusoidal utility current strategy,” in IET Generation, Transmission & Distribution, vol. 9, no.

13, pp. 1580-1596, January 2015.

[12] V. M. Moreno, A. P. Lopez and R. I. D. Garcias, "Reference current estimation under distorted line

voltage for control of shunt active power filters," in IEEE Trans. on Power Electron., vol. 19, no. 4,

pp. 988-994, July 2004.

[13] G. W. Chang and Tai-Chang Shee, "A novel reference compensation current strategy for shunt active

power filter control," in IEEE Trans. on Power Del., vol. 19, no. 4, pp. 1751-1758, October 2004.

[14] S. K. Chauhan, M. C. Shah, R. R. Tiwari and P. N. Tekwani, "Analysis, design and digital

implementation of a shunt active power filter with different schemes of reference current generation,"

in IET Power Electronics, vol. 7, no. 3, pp. 627-639, March 2014.

[15] R. Panigrahi, B. Subudhi and P. C. Panda, “Model predictive-based shunt active power filter with a

new reference current estimation strategy,” in IET Power Electron., vol. 8, no. 2, pp. 221-233,

February *2015.

[16] C. H. da Silva, R. R. Pereira, L. E. B. da Silva, G. Lambert-Torres, B. K. Bose and S. U. Ahn, “A

digital PLL scheme for three-phase system using modified synchronous reference frame,” in IEEE

Trans. on Ind. Electron., vol. 57, no. 11, pp. 3814-3821, November 2010.

Page 23: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

22

[17] R. Teodorescu, M. Liserre and P. Rodriguez, “A thesis on grid converters for photovoltaic and wind

power systems,” 2011, ISBN: 978-0-470-05751-3.

[18] V. Kaura and V. Blasco, “Operation of a phase locked loop system under distorted utility conditions,”

IEEE Trans. Ind. Appl., vol. 33, no.1, pp. 58–63, January 1997.

[19] P. Rodriguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos and D. Boroyevich, “Decoupled double

synchronous reference frame PLL for power converters control,” in IEEE Trans. on Power Electron.,

vol. 22, no. 3, pp. 1078-1078, May 2007.

[20] P. Rodriguez, A. Luna, I. Candela, R. Teodorescu, and F. Blaabjerg, “Grid synchronization of power

converters using multiple second-order generalized integrators,” in Proc. 34th

Annu. Conf. IEEE Ind.

Electron., pp. 755–760, November 2008.

[21] P. Rodrıguez, A. Luna, R. Santiago M. Aguilar, I. E. Otadui, R. Teodorescu, and F. Blaabjerg, “A

stationary reference frame grid synchronization system for three-phase grid-connected power

converters under adverse grid conditions,” IEEE Trans. Power Electron., vol. 27, no. 1, pp. 99-112,

January 2012.

[22] Y. Han, M. Luo, X. Zhao, J. M. Guerrero and L. Xu, “Comparative performance evaluation of

orthogonal-signal-generators-based single-phase PLL algorithms—A survey,” in IEEE Trans. on

Power Electron., vol. 31, no. 5, pp. 3932-3944, May 2016.

[23] J. Matas, M. Castilla, J. Miret, L. Garcia de Vicuna, and R. Guzman, “An adaptive prefiltering

method to improve the speed/accuracy tradeoff of voltage sequence detection methods under adverse

grid conditions,” IEEE Trans. on Ind. Electron., vol. 61, no. 5, pp. 2139-2151, May-2014.

[24] M. Ciobotaru, R. Teodorescu and V. G. Agelidis, “Offset rejection for PLL based synchronization in

grid-connected converters,” Proc. 23rd

Annu. IEEE Appl. Power Energy Conf. Expo., pp. 1611–1617,

February 2008.

[25] M. Karimi Ghartemani, S. Khajehoddin, P. Jain, and A. Bakhshai. “Comparison of two methods for

addressing dc component in phase-locked loop (PLL) systems,” in Proc. IEEE ECCE, pp. 3053-3058,

September 2011.

[26] M. Karimi-Ghartemani, S. Khajehoddin, P. Jain, A. Bakhshai and M. Mojiri, “Addressing dc

component in PLL and notch filter algorithms,” IEEE Trans. Power Electron. , vol. 27, no. 1, pp. 78-

86 January 2012.

[27] S. Hwang, L. Liu, H. Li, and J. M. Kim, “DC offset error compensation for synchronous reference

frame PLL in single-phase grid-connected converters,” IEEE Trans. Power Electron. , vol. 27, no. 8,

pp. 3467-3471, August 2012.

Page 24: GUJARAT TECHNOLOGICAL UNIVERSITY · 2018-07-05 · are multiple non-idealities in the PCC voltage, especially in the modern power system characterized by non-linear loads and power

23

[28] Fengjiang Wu, Dongyang Sun, Lujie Zhang and Jiandong Duan, “Influence of plugging DC offset

estimation integrator in single-phase EPLL and alternative scheme to eliminate effect of input DC

offset and harmonics,” IEEE Trans. on Ind. Electron., vol. 62, no. 8, pp. 4823-4831, May 2014.

[29] S. Golestan, Josep M. Guerrero and G.B. Gharehpetian, “Five approaches to deal with problem of DC

offset in phase-locked loop algorithm: Design consideration and performance evaluation,” IEEE

Trans. Power Electron. , vol. 31, no. 1, pp. 648-661, January 2016.

[30] S. Golestan, J. M. Guerrero and J. C. Vasquez, "DC-Offset Rejection in Phase-Locked Loops: A

Novel Approach," in IEEE Trans. on Ind. Electron., vol. 63, no. 8, pp. 4942-4946, August 2016.