Page 1: Guides & Standards For Facility Pipe  · PDF fileSuggested Standards For Marking Pipes & Valves ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes   | 1-800-788-5572

Facility Pipe MarkingGuides & Standards For

PIPE LABELING AND VALVE TAGGING GUIDELINES FOR YOUR FACILITY

©2011 Graphic Products, Inc.

Facility Pipe Marking in commercial, public, school & retail buildings

Page 2: Guides & Standards For Facility Pipe  · PDF fileSuggested Standards For Marking Pipes & Valves ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes   | 1-800-788-5572

Suggested Standards For Marking Pipes & Valves

ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes

www.DuraLabel.com | 1-800-788-5572

ABBR. SERVICE TYPE PIPE LABEL VALVE TAG BAND COLOR BACKGROUND AND LETTERING COLORSCHWR Chilled Water Return CHWR (BLDG.)-CHV-##

BLUE GREEN BACKGROUND, WHITE LETTERINGCHWS Chilled Water Supply CHWS (BLDG.)-CHV-##CWR Condenser Water Return CWR (BLDG.)-CWV-##

GREEN GREEN BACKGROUND, WHITE LETTERINGCWS Condenser Water Supply CWS (BLDG.)-CWV-##CWGLR Chilled Water Glycol Return CWGLR (BLDG.)-CGLV-##

GOLD GREEN BACKGROUND, WHITE LETTERINGCWGLS Chilled Water Glycol Supply CWGLS (BLDG.)-CGLV-##HWGLR Hot Water Glycol Return HWGLR (BLDG.)-HGLV-##HWGLS Hot Water Glycol Supply HWGLS (BLDG.)-HGLV-##CTYW City Water CITY WATER (BLDG.)-CTWV-##

LIGHT BLUE GREEN BACKGROUND, WHITE LETTERINGDCWR Domestic Cold Water Return DCWR (BLDG.)-DCV-##DCWS Domestic Cold Water Supply DCWS (BLDG.)-DCV-##DHWR Domestic Hot Water Return DHWR (BLDG.)-DHV-##DHWS Domestic Hot Water Supply DHWS (BLDG.)-DHV-##DRAIN Drains* DRAIN (BLDG.)-DRAIN-## BROWN REFER TO ANSI STANDARDS BELOWDTR Dual Temp Return DTR (BLDG.)-DTV-##

BLACK GREEN BACKGROUND, WHITE LETTERINGDTS Dual Temp Supply DTS (BLDG.)-DTV-##FO Fuel Oil FO (BLDG.)-FOV-## WHITE YELLOW BACKGROUND, BLACK LETTERINGHPR Heat Pump Return HPR (BLDG.)-HPV-##

TEAL GREEN BACKGROUND, WHITE LETTERINGHPS Heat Pump Supply HPS (BLDG.)-HPV-##LTHWR Low-Temp Hot Water Return LTHWR (BLDG.)-HWV-##

YELLOW GREEN BACKGROUND, WHITE LETTERINGLTHWS Low-Temp Hot Water Supply LTHWS (BLDG.)-HWV-##MTHWR Medium-Temp Hot Water Return MTHWR (BLDG.)-MTV-##

ORANGE GREEN BACKGROUND, WHITE LETTERINGMTHWS Medium-Temp Hot Water Supply MTHWS (BLDG.)-MTV-##HTHWR High-Temp Hot Water Return HTHWR (BLDG.)-HTV-##

RED GREEN BACKGROUND, WHITE LETTERINGHTHWS High-Temp Hot Water Supply HTHWS (BLDG.)-HTV-##STM Steam STEAM (BLDG.)-STV-##

PINK YELLOW BACKGROUND, BLACK LETTERINGCOND Condensate COND (BLDG.)-CNDV-##NG Natural Gas GAS (BLDG.)-GASV-## GRAY YELLOW BACKGROUND, BLACK LETTERINGCA Compressed Air COMP AIR (BLDG.)-CAV-##

PURPLE BLUE BACKGROUND, WHITE LETTERINGVAC Vacuum VACUUM (BLDG.)-VACV-##

MATERIAL PROPERTIES BACKGROUND AND LETTERING COLORS

FLAMMABLEFluids which are a vapor or produce vapors that can ignite and continue to burn in air YELLOW BACKGROUND, BLACK LETTERING

COMBUSTIBLE Fluids that may burn but are not flammable BROWN BACKGROUND, WHITE LETTERING

TOXIC & CORROSIVE Fluids which are corrosive or toxic or will produce corrosive or toxic substances ORANGE BACKGROUND, BLACK LETTERING

FIRE QUENCHINGWater and other substances used in sprinkler fire-fighting piping systems RED BACKGROUND, WHITE LETTERING

OTHER WATERAny other water, except for water used in sprinkler and fire-fighting piping systems GREEN BACKGROUND, WHITE LETTERING

COMPRESSED AIRAny vapor or gas under pressure that does not fit a category above BLUE BACKGROUND, WHITE LETTERING

DEFINED BY USER Defined by user BLACK BACKGROUND, WHITE LETTERINGDEFINED BY USER Defined by user WHITE BACKGROUND, BLACK LETTERINGDEFINED BY USER Defined by user PURPLE BACKGROUND, WHITE LETTERINGDEFINED BY USER Defined by user GRAY BACKGROUND, WHITE LETTERING

NOTE: Valve Tags need to comply with ANSI standards. Pipe Labels should be near valve to identify pipe content.*There are no standards for Drains. Follow ANSI Standards for background and letter colors; abbreviations may vary by facility.

Pipe Marker Placement and Pipe Marker Size Chart on the back.

Page 3: Guides & Standards For Facility Pipe  · PDF fileSuggested Standards For Marking Pipes & Valves ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes   | 1-800-788-5572

1 2 3 4 5

1. ABBREVIATIONSAbbreviations for Ammonia System Components -Print abbreviations in black on yellow.

2. PHYSICAL STATE LIQ - Liquid - Black or white printed on orangeVAP - Vapor - Black or white printed on blue*LIQ/VAP - Use both if both states exist*DuraLabel Sky Blue Premium Vinyl is recommended.

IIAR standards require the posting of a component identification and abbreviation reference chart to explain pipe marking in areas that are conspicuous to operating personnel. The reference chart shall be made of durable material that will remain legible. (IIAR #114 Section 7.0)

3. MARKER BODY“AMMONIA” printed in black on yellow

4. PRESSURE LEVELHIGH Pressure (+70 psig) - Black or white printed on redLOW Pressure (=/-70 psig) - Black or white printed on green

5. FLOW DIRECTIONDirection of flow of the system contents is indicated by arrows. Place arrows at one or both ends of the label.

Ammonia Refrigeration System Pipe MarkingComplies with IIAR (International Institute of

Ammonia Refrigeration) Standards

www.DuraLabel.com | 1-800-788-5572 www.DuraLabel.com | 1-800-788-5572

ABBR. SYSTEM PHYSICAL STATE PRESSURE LEVEL

BD Booster Discharge VAP LOWCD Condenser LIQ HIGHDC Defrost Condensate LIQ HIGHES Economizer Suction VAP LOWEQ † Equalizer VAP HIGHFG † Foul Gas VAP LOWHG † Hot Gas VAP HIGHHGD Hot Gas Defrost VAP HIGHHPL High Pressure Liquid LIQ HIGHHSD High Stage Discharge VAP HIGHHSS High Stage Suction VAP LOWHTRL High Temperature Recirculated Liquid LIQ LOWHTRS High Temperature Recirculated Suction LIQ/VAP HIGHHTS † High Temperature Suction VAP LOWLD † Liquid Drain LIQ LOWLIC Liquid Injection Cooling LIQ HIGHLSS Low Stage Suction VAP LOWLT † Liquid Transfer LIQ LOWLTRL Low Temperature Recirculated Liquid LIQ/VAP LOWLTRS Low Temperature Recirculated Suction LIQ LOWLTS † Low Temperature Suction VAP LOWMTRL † Medium Temperature Recirculated Liquid LIQ LOWMTRS † Medium Temperature Recirculated Suction LIQ/VAP LOWMTS † Medium Temperature Suction VAP LOWPL † Purge Line VAP HIGHPO † Pump Out — —PU † Purge LIQ HIGHRV Relief Vent VAP HIGHTSR Thermosyphon Return LIQ/VAP HIGHTSS Thermosyphon Supply LIQ HIGH

† Abbreviations marked with this symbol are popularly used, but non-IIAR approved. Pipe Marker Placement and Pipe Marker Size Chart on the back.

Page 4: Guides & Standards For Facility Pipe  · PDF fileSuggested Standards For Marking Pipes & Valves ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes   | 1-800-788-5572

www.DuraLabel.com | 1-800-788-5572 www.DuraLabel.com | 1-800-788-5572

Pipe Marker Size ChartLetter and Label Dimensions in accordance with pipe diameter. NOTE: It is recommended that pipes less than .75" in diameter be labeled with a permanent tag.

Pipe Marker Placement• Indicate direction of flow by labeling with arrows at one or both ends of the label• Visible from the point of normal approach • Near valves, flanges & changes in pipe direction • Both sides of ceiling, wall or floor penetrations • At any line entry or re-entry point• Every 25 feet to 50 feet is typical*• On straight pipe runs in intervals sufficient for identification• Ammonia Only: minimum of 1 per area through which the refrigeration piping passes *Every 40 feet for Ammonia pipe marking

Below: Orientation of Labels

Above: Label placement in relation to point of normal approach

“We did a thorough review of the various printers, and selected the DuraLabel PRO 300. . . It’s easy to use, supplies are in-expensive, and the support is by far the best of all the printer manufacturers we’ve dealt with.” - Darcy, Electrical Software Company

Visit www.DuraLabel.com or call 1-800-788-5572 for information about pipe marker printers.

Prints 1/2" to 4" Tape WidthsDURALABEL PRO 300

DISCLAIMER: We know of no national codes covering the color coding of water pipes. Please check local and state building codes before implementing a color coding system. The suggested coding system presented here is not an official standard. Graphic Products, Inc. makes no representations or warranties of any kind, express or implied. Information in this guide is subject to change without notice. Except as expressly provided for in writing, the liability of Graphic Products, Inc. arising from the use of this guide is specifically excluded and Graphic Products, Inc. disclaims all warranties and any liability for damages of any kind and any liability whether in contract, tort under statute or otherwise for any injury, damage or loss whatsoever. No reliance should be placed on information contained or to be implied or inferred in this guide, and users of this guide should verify all information.

www.DuraLabel.com | 1-800-788-5572

This label complies with the Suggested Standards For Marking Pipes & Valves

.75" - 1.25"1.5" - 2"2.5" - 6"8" - 10"

Over 10"

Outside Pipe DiameterIncluding Covering

Minimum Length ofLabel Field Color

Minimum Heightof Letters

13 mm19 mm32 mm64 mm89 mm

.5".75"

1.25"2.5"3.5"

203 mm203 mm305 mm610 mm813 mm

8"8"

12"24"32"

19 - 32 mm38 - 51 mm64 - 152 mm203 - 254 mmOver 254 mm

Page 5: Guides & Standards For Facility Pipe  · PDF fileSuggested Standards For Marking Pipes & Valves ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes   | 1-800-788-5572

www.DuraLabel.com | 1-800-788-5572

DuraLabeling Software

Pipe Marking made easy!The DuraSuite™ Labeling Software makes creating pipe markers fast and easy. Enter the pipe diameter, select the pipe contents, and pick an arrow to show the flow direction. The software automatically picks the right size and color for the label material and automatically sets the correct font size. In just a few moments the pipe markers you need will be in your hands ready to be installed.

DuraSuite also includes software for other applications such as arc flash labels, RTK labels, and even custom labeling!

Over 800 Symbols Included for Customizing!

• Identify dirty, oily and rusty pipes• Apply label to sleeve, then curl around pipe• Sizes fit pipe diameters 1"-5.2"• Custom lengths and larger diameters available

• Display labels in harsh conditions• Label indoors/outdoors• Easily attach to equipment• Scratch & fade resistant• Color-coded

• Portability • Label in any location - indoor/outdoor• No set up required• Administrative Rights not required • Preloaded with printer drivers, DuraSuite™ Labeling Software, templates, symbols and more!• Designed to meet military security specs

• Compliance with industry standards• Rain & moisture resistance• Indoor/outdoor lighting conditions• Abrasion resistance• Chemical resistance• Overall longevity & durability

www.DuraLabelSupplies.comOver 50 types of supplies which can be applied to almost any

surface in nearly any setting, check out our website now!

Page 6: Guides & Standards For Facility Pipe  · PDF fileSuggested Standards For Marking Pipes & Valves ANSI/ASME A13.1 - 2007 Standard for the Identification of Pipes   | 1-800-788-5572

www.DuraLabel.com | 1-800-788-5572 www.DuraLabel.com | 1-800-788-5572

Labeling Software

Pipe Marking Labeling

Extreme Temperature

Labeling

Valve Tags

Arc Flash Labeling

Reflective Labeling

Electrical Labeling

Military Labeling Safety Signs

DuraLabel 70004" to 7" Tape Widths

DuraLabel 90004" to 9" Tape Widths

DuraLabel 40001" to 4" Tape Widths

DuraLabel PRO 3001/2" to 4" Tape Widths

DuraLabel 20001/2" to 2" Tape Widths

Picture the Possibilities.www.DuraLabelSupplies.com

CALLTODAY!

Wayfinding