GUARANTEED TECHNICAL PARTICULARS FOR ACSR ZEBRA CONDUCTOR S.No. Particulars Unit Standard Value offered 1 Manufacturer's Name and Address (a) E.C.Grade Aluminium Rod/Ingots BALCO,NALCO,HINDALCO, any other ISI manufacturer (b) High Tensile Galvanized Steel Wire Hulas Wires,Aarti Steels, MLHL, any other ISI manufacturer (c) Complete Conductor Mahavir Transmission Udyog Pvt. Ltd. A11 – 13 S, Industrial Estate, Vikasnagar248198, Dehradun (Ukd.) 2 Indian Standards (a) For Conductor IS :398(PartII) :1996 IS :398(PartII) :1996 (b) For Drum IS :1778 :1980 IS :1778 :1980 3 E.C.Grade Aluminium Rod (a) Indian Standards IS :5484 : 1978 IS :5484 : 1978 (b) Composition % Purity 99.5(Min.) Purity 99.5(Min.) 4 High Tensile Galvanized Steel Wire (a) Indian Standards IS :4826 :1979 IS :4826 :1979 (b) Chemical Composition % C=0.50 to 0.85 C=0.50 to 0.85 P=0.035 (Max.) P=0.035 (Max.) S=0.045 (Max.) S=0.045 (Max.) Si=0.10 to 0.35 Si=0.10 to 0.35 Mn=0.50 to 1.10 Mn=0.50 to 1.10 5 Galvanizing (a) Indian Standards IS :4826 :1979 IS :4826 :1979 (b) Purity of Zinc % 99.95 (Min) 99.95 (Min) (c) Process of Galvanizing Hot Dip Hot Dip 6 Aluminium Strands (a) Diameter i) Nominal mm 3.18 3.18 ii) Maximum mm 3.21 3.21 iii) Minimum mm 3.15 3.15 (b) Cross sectional area of nominal diameter wire mm 2 7.942 7.942 (c) Minimum Weight Kg/Km 21.47 21.47 (d) Breaking Load(Min) i)Before stranding KN 1.29 1.29 ii)After stranding KN 1.23 1.23 (e) Electrical Resistance at 20°C Ohm/Km 3.626 3.626 (f) Coefficient of linear expansion per o C 23.0 x 10 6 23.0 x 10 6 (g) Modulus of elasticity Kg./cm 2 0.70 x 10 6 0.70 x 10 6 (j) Minimum UTS of Strand KN./mm2 0.163 0.163 Page 1 of 3

Upload: tarun-aggarwal

Post on 13-Jan-2016

112 views

Category:

Documents


6 download

DESCRIPTION

for Himachal

TRANSCRIPT

Page 1: GTP Acsr Zebra Conductor

GUARANTEED TECHNICAL PARTICULARS FOR ACSR ZEBRA CONDUCTOR               

S.No.  Particulars  Unit  Standard  Value offered  

1  Manufacturer's Name and Address          

(a)  E.C.Grade Aluminium Rod/Ingots    BALCO,NALCO,HINDALCO, any other ISI 

manufacturer 

(b)  High Tensile Galvanized Steel Wire    Hulas Wires,Aarti Steels, MLHL, any other ISI 

manufacturer 

(c)  Complete Conductor    Mahavir Transmission Udyog Pvt. Ltd.           A11 – 13 S, Industrial Estate, Vikasnagar‐ 

248198, Dehradun (Ukd.) 

2  Indian Standards          (a)  For Conductor     IS :398(Part‐II) :1996  IS :398(Part‐II) :1996 (b)  For Drum     IS :1778 :1980  IS :1778 :1980 

3  E.C.Grade Aluminium Rod          

(a)  Indian Standards     IS :5484 : 1978  IS :5484 : 1978 (b)  Composition  %  Purity 99.5(Min.)   Purity 99.5(Min.)  4  High Tensile Galvanized Steel Wire          (a)  Indian Standards     IS :4826 :1979  IS :4826 :1979 (b)  Chemical Composition  %  C=0.50 to 0.85  C=0.50 to 0.85          P=0.035 (Max.)  P=0.035 (Max.)          S=0.045 (Max.)  S=0.045 (Max.)          Si=0.10 to 0.35  Si=0.10 to 0.35          Mn=0.50 to 1.10  Mn=0.50 to 1.10 5  Galvanizing          (a)  Indian Standards     IS :4826 :1979  IS :4826 :1979 (b)  Purity of Zinc  %  99.95 (Min)  99.95 (Min) (c)  Process of Galvanizing     Hot Dip  Hot Dip 

6  Aluminium Strands          

(a)  Diameter             i) Nominal  mm  3.18  3.18    ii) Maximum  mm  3.21  3.21    iii) Minimum  mm  3.15  3.15 

(b) Cross sectional area of nominal diameter wire  

mm2  7.942  7.942 

(c)  Minimum Weight  Kg/Km  21.47  21.47 (d)  Breaking Load(Min)             i)Before stranding  KN  1.29  1.29    ii)After stranding  KN  1.23  1.23 (e)  Electrical Resistance at 20°C  Ohm/Km  3.626  3.626 

(f)  Co‐efficient of linear expansion   per oC  23.0 x 10‐6  23.0 x 10‐6 

(g)  Modulus of elasticity    Kg./cm2  0.70 x 106   0.70 x 106  

(j)  Minimum UTS of Strand   KN./mm2  0.163  0.163 

Page 1 of 3

Page 2: GTP Acsr Zebra Conductor

S.No.  Particulars  Unit  Standard  Value offered  

7  Steel Strands          

(a)  Diameter             i) Nominal  mm  3.18  3.18    ii) Maximum  mm  3.24  3.24    iii) Minimum  mm  3.12  3.12 

  Cross sectional area of nominal diameter wire  

mm2  7.942  7.942 

(b)  Minimum Weight  Kg/Km  61.95  61.95 (c)  Breaking Load(Min)             i) Before stranding  KN  10.43  10.43    ii) After stranding  KN  9.91  9.91 

d) Elongation of 200mm gauge length on breaking (Elongation Test) 

        

   i) Before stranding  %  4  4    ii) After stranding(Min)  %  3.5  3.5 

(e) No.of twist on a length equal to 100 times the diameter of wire (Torsion Test) 

       

   i) Before stranding  Nos.  18(Min.)  18(Min.)    ii) After stranding  Nos.  16Min.)  16Min.) (f)  Minimum Weight of Zinc Coating             i)Before Stranding  gm/m2  250  250 

   ii)After Stranding  gm/m2  237.5  237.5 (g)  Uniformity of Zinc Coating          

   No. of dips for 1minute duration which the strands can withstand    (Precee Test) 

       

   i)Before Stranding(Min)  Nos.  3  3 

   ii)After Stranding(Min)  Nos. 2 x 1min + 1 x 

1/2min. 2 x 1min + 1 x 

1/2min. (h)  Co‐efficient of linear expansion   per oC  11.5 x 10‐6  11.5 x 10‐6 

(i)  Modulus of elasticity    Kg./cm2  1.9 x 106    1.9 x 106   

(j) Minimum UTS of Strand                        

KN/MM²  1.315  1.315 

Page 2 of 3

Page 3: GTP Acsr Zebra Conductor

S.No.  Particulars  Unit  Standard  Value offered  

8  Complete Conductor          

(a)  Code     Zebra ACSR  Zebra ACSR 

(b)  Standard Nominal Copper  Area  mm2  260  260 

(c)  Equivalent Nominal Aluminim Area  mm2  420  420 

(d)  Sectional Aluminim Area  mm2  428.9  428.9 

(e)  Total Sectional Area  mm2  484.5  484.5 

(f)  Overall Diameter  mm  28.62  28.62 (g)  Strands & Wire Diameter             i)Aluminium  Nos/mm  54/3.18  54/3.18    ii)Steel  Nos/mm  7/3.18  7/3.18 (h)  Lay Ratio             i) Steel ‐ 6Wire  Max‐28 / Min‐13  Max‐28 / Min‐13    ii) Aluminium ‐ 12Wire  Max‐17 / Min‐10  Max‐17 / Min‐10    iii) Aluminium ‐ 18Wire  Max‐16 / Min‐10  Max‐16 / Min‐10    iv) Aluminium ‐ 24Wire  Max‐14 / Min‐10  Max‐14 / Min‐10 (i)  Calculated Breaking Load  KN  130.32  130.32 

(j)   Modulus of Elasticity  Kg./cm2  .69 x 106    .69 x 106   

(k)  Co‐efficient of Linear Expansion  per oC  19.3x10‐6  19.3x10‐6 

(l)  Minimum Weight              i) Aluminium  Kg/Km  1185  1185    ii) Steel  Kg/Km  436  436    iii) ACSR Conductor  Kg/Km  1621  1621 

(m) Continuous max. current rating of conductor in still air at 45 oC  ambient temperature      

Ampere  AS Per ISS  AS Per ISS 

(n)  Calculated Resistance at 20ºC  Ω/Km  0.06868  0.06868 (o)  Standards Length  Meters  1500  1500 (p)  Tolerance on Standard Length  %  5  5 (q)  Random Length  %  10  10 (u)  Drum Dimensions  mm As per Availability As per Availability(v)  Joints in Strands             i) Steel 6 Wire     No Joints  No Joints    ii) Aluminium 24 Wire     No Joints  No Joints 

   iii) Aluminium 18 Wire    No two joints within 

15 meters No two joints within 

15 meters 

   iv) Aluminium 12 Wire    No two joints within 

15 meters No two joints within 

15 meters 

(x)  Method of making joints    As per clause no.6.0 of IS398(Part‐II) 

As per clause no.6.0 of IS398(Part‐II) 

Page 3 of 3