GT- PM Jobs Date:-S.No. Activities Remarks
1 TB tightness & cleaning done for GRP panel
GENERATOR PROTECTION RELAY MICOM 343
2
3
4
5
Rotor E/F protection relays operation & tripping checked6 64B tripping checked
7
8
9
10
11
1213 30E &30F relay operation & tripping checked
14
15
16 B/U Impedance protection relay 21 and Auxillary 21x 17 Overload protection relay 51 .1 and auxillary 51.1x
P343 checked for differential protection with o/p relays operation.86U master relay tripping also checked.
P343 Checked for Voltage controlled O/c protection at both Normal & undervoltage(<33% V) with o/p relays operation.86G master relay tripping also checked.
P343 Checked for under frequency operation with o/p relays operation.
P127 (voltage controlled o/current protection) operation & alarm checked
Generator transformer differential KBCH (87GT) operation & tripping checked with o/p relays operation
64ST relay operation & tripping checked with o/p relays operation
49AX & 49TX relay operation & tripping checked with o/p contacts
63AX,63TX,26AX &26TX relay operation & tripping checked with o/p contacts
86U &86 G relay operation & tripping checked From GPR(P343)
30A,30B,30C &30D relay operation & tripping checked From GPR(P343)
30G,30H,30J,30K auxillary relay operation & tripping checked From GPR(P343)
Reverse Power protection relay 32 and auxillary 32 X operation
![Page 2: Gt Relay Testing Format](https://reader031.vdocuments.us/reader031/viewer/2022020106/55cf9a1e550346d033a089e9/html5/thumbnails/2.jpg)
S.No CT CT Ratio 1 Generator Differential (Ct-4,5,6,7,8,9) 3000/12 Reverse Power Protection (Ct-1,2,3) 3000/1
3 3000/14 Stator Earth fault protection( Ct-19) 3000/1
Secondary Injected Current
Primary Current Reading
Generator Transformer Differential (16,17,18)
![Page 3: Gt Relay Testing Format](https://reader031.vdocuments.us/reader031/viewer/2022020106/55cf9a1e550346d033a089e9/html5/thumbnails/3.jpg)
GT - GRP PANEL TEST FORMAT Checked on :
SL NO PROTECTION RELAY SETTING PROTECTION CHECKING PROCEDURE REMARK
1 MICOM 343
V>1 Function : DT Operating voltage : 30B :-
V>1 Voltage Set : 121 V Operating time:
V>1 Time Delay : 0.3s Operation checked:
2 Over voltage : Stage 2 (TRIP) MICOM 343
V>2 Function : DT Operating voltage : 30T :-
V>2 Voltage Set : 132.0 V Operating time: 86G :-
V>2 Time Delay : 2.000 s Operation checked:
3 P 127 (51G)
I set : 0.7 In Operating current: 51G RL 2, 3 5:
DT Time delay :
Time delay : 6s Operating checked :-
4 Over current (Voltage controlled) MICOM 343
V Dep OC Char : IEC S Inverse
V Dep OC I> Set : 800 mA Current inj (2xIs) 30R :
V Dep OC TMS : 0.3 OP Time (Nor Vol): 86G :- Time shall be 1.5sec
V Dep OC V<1 Set 35 V OP Time (Red Vol): Time shall be 0.64sec
V Dep OC k Set : 0.4 Operation checked:
5 Back up eart fault (Open Delta) P 125 (64B)Ue> 5.5V Operating current : 64B RL1,2,3,4.5
Time delay : 1.0sec Operating time: 86U :-
6 MICOM 343
I2> : Current Set 60mA Operating current : 30P :-
I2>1 Time Delay : 10.0s Operating time:
Operation checked:
7 MICOM 343
I2>2 Current Set 80.00mA
I2>2 k Setting 9.000 s Operating current : 30H :-
I2>2 kRESET 9.000 s Operating time:
I2>2 tMAX 500.0 s Operation checked: 86G :-
I2>2 tMIN 3.000 s
AUX / 86 RELAY OPERATION
Over voltage : Stage 1 (DVR C/O)
Inject voltage after isolating Prot. PT with links in PT circuit
Check the Output at DVR panel also
Inject voltage after isolating Prot. PT with links in PT circuit
Over current definite time / Thermal overload (Alarm)
Inject current in B phase of Protection CT
Inject current in CT terminalsR1 TB-1 5,6,7,8
Inject voltage after isolating the links at R1 TB-34, 35
Negative phase sequence protection (Alarm)
Inject 3 phase current with reverse phase sequence
Negative phase sequence protection (Trip)
Inject 3 phase current with reverse phase sequence
![Page 4: Gt Relay Testing Format](https://reader031.vdocuments.us/reader031/viewer/2022020106/55cf9a1e550346d033a089e9/html5/thumbnails/4.jpg)
GT - GRP PANEL TEST FORMAT Checked on :
8 Stator Earth fault 95% (NGT) MICOM 343
VN>1 Function DT
VN>1 Voltage Set : 7.0 V Operating voltage : GPR RL 17, 24 :-
VN>1 Time Delay : 1.0 s Time delay : 86U :-
Operation checked:
9 MICOM 343
Xa1 : 9.5 ohms Operating voltage : 30L :
Xb1 : 164 ohms Operating current :
Time delay: 0.1 s Operating phase angle: 86G :
FFail1 DO Timer : 1.0 s Time delay :
10 MICOM 343
Xa2 : 9.5 ohms Operating voltage : GPR RL 15,16 :-
Xb2 : 164 ohms Operating current :
Time delay: 2.0 s Operating phase angle: 86G :-
Ffail2 DO Timer : 1.0 s Time delay :
11 VAEM
Operation checked: 64F1 :-
2/64F1 (timer)
12 Rotor earth fault – Stage 2 CAEM
Operation checked: 64F2 :-
64F2X:
86U :-
13 Reverse power (Stage –1) MICOM 343-P>1 Setting : 4.0 W Operating current : 30K :-
Power1 TimeDelay : 1.0 s Operating time: 86G :-
14 Reverse power (Stage 2) (MWTU14)Is : 4.0mA Operating current : 30Q :
Ts :1.5 s Operating time: 86G:-
15 Generator differential MICOM 343
Is1- 50 mA OP current (O/P side): 30J: -
K1- 0% OP current (Neu side): 86U :-
Is2 – 1.2A
K2 – 150%
Inject voltage in the PT input from NGT after isolating PT
with links in PT Circuit
Loss of excitation/Field failure ( with U/V)
Inject voltage below 77Volts and change the angle of
current to operate the relay
Loss of excitation/Field failure (without U/V)
Inject voltage above 77Volts and change the angle of
current to operate the relay
Rotor earth fault – Stage 1 (Alarm)
Inject PT voltage in RY phase to check operatin of relay
Inject PT voltage and current in reverse direction
Inject PT voltage and current in reverse direction
Inject current in both OP side and Neutral side CT input in all
phase
![Page 5: Gt Relay Testing Format](https://reader031.vdocuments.us/reader031/viewer/2022020106/55cf9a1e550346d033a089e9/html5/thumbnails/5.jpg)
GT - GRP PANEL TEST FORMAT Checked on :
16 MICOM 343F<1 Setting 48.50 Hz Operating volt 30C :-
(MICOM 343) F<1 Time Delay 2.000 s Operating Freq: 30D :-
17Under frequency – Stage 2 (trip)
MICOM 343F<2 Setting 47.50 Hz Operating volt 30S :-
(MICOM 343) F<2 Time Delay 2.000 s Operating Freq: 86G :-
18 100% stator E/F MICOM 343
VN3H< Enabled
VN3H< 500.0mV 30N:
VN3H< Delay 1.0 s
V< Inhibit set 100.0 V 86U :-
P< Inhibit Enabled
P< Inhibit set 4.0 W
100% St EF VN3H> 1.0 V
VN3H> Delay 1.0 s
19Over Frequency
MICOM 343
GPR RL 14
(MICOM 343) 86G :
20 Generator Overall Diff prot KBCH
86U :-
OP current (HV side): 87GT RL0 :
OP current (LV side): 87GT ,RL1 :
21 REF KBCH
OP current: 87GT RL5 :
87GT ,RL6 :
86U :-
21 Over fluxing (Alarm) KBCH
Operating vol:
Operating Freq: 87GTX1:-
Operating time :
22 Gen TR. S/B E/F (64ST) P 122Is : 0.4 In ( 0.4 x 5A) Operating Current : 64ST RL1,2,3,4 Inject current in R2 TB1-12,13
Time : 1.5s Operating time : 86U :-
23 Over fluxing (TRIP) KBCH
Operating vol:
Operating Freq: 87GTX2:-
Operating time : 86U :-
Under frequency – Stage 1 (Alarm) Inject voltage and reduce the
frequency
Inject voltage and reduce the frequency
Check the operation of 86U by shorting the DO of MICOM
relay
Inject current in both HV side and LV side CT input in all
phase
Inject current after bypassing stab resistance in REF input
Inject RY voltage and reduce frequency
Inject RY voltage and reduce frequency
![Page 6: Gt Relay Testing Format](https://reader031.vdocuments.us/reader031/viewer/2022020106/55cf9a1e550346d033a089e9/html5/thumbnails/6.jpg)
GT - GRP PANEL TEST FORMAT Checked on :
24 TR Winding Temp (Alarm) MVAAM 1395 deg C Operation checked: 49AX :-
25 TR Winding Temp (Trip) MVAAM 13105 deg C Operation checked: 49T X:-
86U:-
26 TR Oil Temp (Alarm) MVAAM 1385 deg C Operation checked: 26AX :-
27 TR Oil Temp (Trip) MVAAM 1395 deg C Operation checked: 26TX:-
86U:-
28 TR Buchholz (Alarm) MVAAM 13
Operation checked: 63AX:-
29 TR Buchholz (Trip) MVAAM 13
Operation checked: 63TX:-
86U:-
30 TR PRD Trip MVAAM 13
Operation checked: 63PX:-
86U:-
31 OIL Level Alarm MVAAM 13
Operation checked: 63OLX:-
32 MARK -V TRIP MVAAM 11Operation checked: 30AX1:-
86U:-
33 CO2 PNL TRIP MVAAM 11Operation checked: 30AX2:
86U:
34 DVR PNL TRIP MVAAM 11Operation checked: 86G :
TESTED BY : CHECKED BY :
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Operation to be checked from TR. Marshalling box
Check operation by shorting R2 TB2- 30,31
Check operation by shorting R2 TB2- 32,33
Check operation by shorting R2 TB2- 13,14