grx-ci-prg programming control interfacegrx-ci-prg control interfaces 369363 rev. b 1 06.02.11...

6
® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: GRX-CI-PRG Control Interfaces 369363 Rev. B 1 06.02.11 GRX-CI-PRG Programming Control Interface Description • Integrates a GRAFIK Eye® lighting control system with a PC or other digital equipment that supports RS232 and TCP/IP communication. • Provides a basic serial string command set that allows a PC to monitor and control lighting. • Built-in astronomic timeclock provides ability to schedule lighting events. Example: Lobby lights turn on to scene 1 at 7:30 a.m. or 10 minutes after sunrise. • Enables use of a PC to set up GRX-3500 and GRX-4500 control units. • Comes with easy-to-use, “point-and-click” Windows®-compatible LIAISONTM software for scheduling the astronomic timeclock and using the programmer Interface. • Functionality is selected using DIP switches. • Operates with or without a PC connected. • May be programmed to control any combination of one to eight GRAFIK Eye® 3000 or 4000 series control units. • GRX-3100, GRX-4100, and GXI-3100 control units may utilize the astronomic timeclock function of the GRX-CI-PRG. • GRX-3500, GRX-4500, and GXI-3500 control units may utilize all functions of the GRX-CI-PRG.

Upload: others

Post on 10-Feb-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

  • ® SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    GRX-CI-PRG Control Interfaces

    369363 Rev. B 1 06.02.11

    GRX-CI-PRG Programming Control Interface

    Description

    •IntegratesaGRAFIKEye®lightingcontrolsystemwithaPCorotherdigitalequipmentthatsupportsRS232andTCP/IPcommunication.

    •ProvidesabasicserialstringcommandsetthatallowsaPCtomonitorandcontrollighting.

    •Built-inastronomictimeclockprovidesabilitytoschedulelightingevents.Example:Lobbylightsturnontoscene1at7:30a.m.or10minutesaftersunrise.

    •EnablesuseofaPCtosetupGRX-3500andGRX-4500controlunits.

    •Comeswitheasy-to-use,“point-and-click”Windows®-compatibleLIAISONTMsoftwareforschedulingtheastronomictimeclockandusingtheprogrammerInterface.

    •FunctionalityisselectedusingDIPswitches.•OperateswithorwithoutaPCconnected.•MaybeprogrammedtocontrolanycombinationofonetoeightGRAFIKEye®3000or4000seriescontrolunits.

    •GRX-3100,GRX-4100,andGXI-3100controlunitsmayutilizetheastronomictimeclockfunctionoftheGRX-CI-PRG.

    •GRX-3500,GRX-4500,andGXI-3500controlunitsmayutilizeallfunctionsoftheGRX-CI-PRG.

  • ® SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    GRX-CI-PRG Control Interfaces

    369363 Rev. B 2 06.02.11

    Specifications

    Standards

    •CaliforniaEnergyCommission(CEC)Listed

    Power

    •IECPELV/NEC®Class2•OperatingVoltage:12V 125mA

    24V 65mA

    Environment

    •32to104°F(0to40°C).•Relativehumiditylessthan90%non-condensing.

    Basic Command Set

    •Monitoring:Sceneselectionandscenestatusupdates.

    •Control:Sceneselection,scenelockout,sequencing,zonelockout,zoneraise/lower.

    Astronomic Timeclock

    •Allowslightingchangestooccurautomaticallybasedontimeofdayand/ordayofweek/month,aswellasrelativetosunriseandsunset.

    •Supportsfourscheduleswith60lightingeventsperscheduleandoneSuperSequence.

    •Allowsusertostart,pause,andstopschedulesfromaPCoraWallstation.

    •Providescommandstosetandmonitorthetimeclock’stime,date,anddayofweek,andreportsunriseandsunset.

    •Ifalossofpoweroccurs,theprogrammedschedulesandthetimeofdaywillberetainedforaminimumof10years.

    Programmer Interface

    PermitscompletesetupofthefollowingonGRX-3500,GRX-4500,orGXI-3500controlunitsviaanIBM®-compatiblePC:

    •Scenes,includinglightlevelsin1%incrementsandfadetimes.

    •Loadtypesettings.•Tamper-proofprotectionofscenes.•Assignmentofcommunicationbetweencontrolunitsandwallstations.

    •Dimmerpanelzoneandloadassignment

    AllowsaWindows®-compatiblePCtoqueryGRX-3500,GRX-4500,andGXI-3500controlunitsfortheirsetup,includingtypeofcontrolunitandnumberofzones.

    LIAISONTM Software

    •ControloverTCP/IPrequiresLIAISONTMversion4.0orlater.

    •AllowsuseofaPCtocreatetimeclockschedulesforallGRX-3000,GRX-4000,andGXI-3000seriescontrolunits.

    •AllowsuseofaPCtocreatesetupsforGRX-3500,GRX-4500,andGXI-3500controlunits.

    •ProvidesdownloadingofschedulesandsetupstoGRX-CI-PRGinterfaceandcontrolunits.

    •WorksonanyPCoperatingwithWindows®95Windows®NT4.0,XP,orlater(excludingWindows®VistaandWindows®7).

    •SuppliedbyLutron.Updatesareavailableonlineatwww.lutron.com

    System Communications and Capacity

    •IECPELV/NEC®Class2wiringconnectsGRX-CI-PRGinterfacetocontrolunitsandothercomponents.

    •OneGRX-CI-PRGInterfaceperGRAFIKEye®3000or4000orGXI-3000system.Automaticallyoccupieswallstationaddress16.

    •50ft(15m)maximumfromGRX-CI-PRGInterfacetoPCorotherRS232source.

    •328ft(100m)maximumfromGRX-CI-PRGInterfacetoPCorotherEthernetsource.

  • ® SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    GRX-CI-PRG Control Interfaces

    369363 Rev. B 3 06.02.11

    Functions

    DIP Switch Function

    When set to ON

    When set to OFF

    1 ZoneLockRetain Ifpowergoesout,lockedzonesstaylockedwhenpowerreturns.

    Powercyclingunlockslockedzones.

    2 SceneLockRetain Ifpowergoesout,lockedscenesstaylockedwhenpowerreturns.

    Powercyclingunlockslockedscenes.

    3 SequenceRetain Ifpowergoesout,sequencingresumeswhenpowerreturns.

    Powercyclingstopssequencing.

    4 SequencingSceneRange Sequencingloopsthroughscenes5to16.

    Sequencingloopsthroughscenes1to4.

    5 NotUsed DonotsettoOn. Factorypreset;donotchange.

    6 ButtonFeedback Interfacereportscontrolunitandwallstationbuttonpresses.

    Noreportingonbuttonpresses.

    7 SceneStatus Interfacereportsscenechanges. Noreportingonscenechanges.

    8 AstronomicTimeclockSchedules

    Enablesinternaltimeclock. Disablesinternaltimeclock.

    1 2 3 4 5 6 7 8

  • ® SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    GRX-CI-PRG Control Interfaces

    369363 Rev. B 4 06.02.11

    Dimensions2.47in

    (62.7mm)

    3.75in(95.3mm)

    4.26in(108.2mm)

    5.26in(133.6mm)

    1.06in(26.9mm)

    Mountingholes

    Mounting

    1.Mountthecontrolinterfacedirectlyonawall,asshownintheMountingDiagram,usingscrews(notincluded).Whenmounting,providesufficientspaceforconnectingcables.

    TheunitcanalsobeplacedintheLUT-19AV-1UAVrackusingthescrewsprovidedwiththeunit.TheLUT-19AV-1Uwillholduptofourunits.

    Ifconduitisdesiredforwiring,theLUT-5x10-ENCcanbeusedtomountoneunit.

    2.Strip4in(10mm)ofinsulationfromwires.Eachdatalinkterminalwillacceptuptotwo18AWG(1.0mm2)wires.

    3.ConnectwiringasshownintheWiringDiagram(nextpage).LED1lightscontinuously(Power)andLED7blinksrapidly(DataLinkRX)whentheIECPELV/NEC®Class2DataLinkisinstalledcorrectly.

    LUT-19AV-1U

    WireStripLength

    4in(10mm)

    5.26

    4.263.75

    2.50

    1.06

    ControlInterface

    Wall

    Mounting Diagrams

    LUT-5x10-ENC

    0.25(6.4)

    0.34(8.6)dia.

    0.18(4.6)dia.

    0.18(4.6)dia.

    #6or#8(M3orM4)screwrecommended(notincluded)

    Mounting Hole DetailDimensions:in(mm)

  • ® SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    GRX-CI-PRG Control Interfaces

    369363 Rev. B 5 06.02.11

    RS232 Link Wiring

    1 2 3 4 5 6 71 2 3 4 5 6 7 8

    RJ45jack:Ethernetlink(toPCorA/Vequipment)

    Ethernetlink/

    activity

    Ethernetspeed

    DataLink(tocontrolunits,processors,andwallstations)

    DIPswitches

    CAT5Cable:maximum328ft(100m)

    ToPCorAVequipment.ForEthernetlink,useaCAT5cabletoconnecttoauxiliaryequipment.TheEthernetlinkLEDwilllightcontinuouslywhenlinkispresentandwillflashwhenthereislinkactivity.AdditionalEthernetnetworkequipmentandcablesprovidedbyothers.

    12or24V tooutlet(withoptionaltransformer).Donotwireterminal2onDataLinkwhenusingoptionaltransformer.TopowerseparatelyfromtheDataLink,orderthefollowingLutrontransformermodelnumbers:120V :T120-15DC-9-BL240V :TE240-15DC-9-BL240V (UK):TU240-15DC-9-BL

    RS232Cable:maximum50ft(15m)

    COM

    TxD

    RxD

    ToPCorAVequipment:UseastandardDB9maletoDB9femalecable,orfollowthechartbelow.

    RS232PinConnectWiring

    TypicalPCor PinonRS232Interface A/Vequipment 9-pincableCommon Com 5Transmit TxD 3Receive RxD 2

    LED1:PowerLED2:EthernetlinkLED3:UnusedLED4:RS232linkTXLED5:RS232linkRXLED6:DatalinkTXLED7:DatalinkRX

  • ® SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    GRX-CI-PRG Control Interfaces

    369363 Rev. B 6 06.02.11

    IEC PELV/NEC® Class 2 Terminal Connections•Installinaccordancewithallapplicableregulations.•Donotconnectlinevoltage/mainspowertodevice.•ThiscontrolcanuseIECPELV/NEC®Class2wiringmethods.Checkwithyourlocalelectricalinspectorforcompliancewithnationalandlocalcodesandwiringpractices.

    •Makedaisy-chainconnectionstotheIECPELV/NEC®Class2datalinkterminalsontheendofthecontrolinterface.

    •DonotuseT-taps.Runallwiresinandoutoftheterminalblock.•Eachterminalacceptsuptotwo18AWG(1.0mm2)wires.

    ZONE 6ZONE 4

    HOT/LIVESSA

    CU WIRE ONLY

    ZONE 2ZONE 3ZONE 5

    NEUTRAL

    ZONE 1

    CLASS 21 2 3 4

    USAClass 2IECPELV

    4 3 2 1

    Toadditionalwallstations/controlinterfaces(16maximum;3poweredfromoneGRAFIKEye® controlunitwithoutexternal12V powersupply;GRX-CI-PRGcountsastwodevicestowardthemaximumofthreeconnectedtooneGRAFIKEye®3000controlunitwhennotusingoptionaltransformer)

    Control Interface Wiring: GRX-3000 or GXI-3000 Control Unit

    RearViewofGRAFIKEye®ControlUnit(GRX-3106shown)

    UseLutronCableGRX-CBL-346Sorequivalent

    DataLink

    DataLink:

    4:MUX

    3:MUX

    Oneshielded,twistedpair18AWG(1.0mm2)fordatalink(terminals3and4)

    IECPELV/NEC®Class2Powerwiring:

    2:12V Power1:Common

    Two18AWG(1.0mm2)conductorsforCommon(terminal1)and12V (terminal2)

    4 3 2 1

    IECPELV/NEC®Class2Powerwiring:

    1:Common2:24V Power

    (2)18AWG(1.0mm2)pigtails,6in(15mm)maximumlengthDonotwirePin2whenusingoptionaltransformer.

    D:Drain/Shield

    (2)12AWG(2.5mm2)

    (2)12AWG(2.5mm2)

    DataLink:(1)shielded,twistedpair18AWG(1.0mm2)

    4:MUX

    3:MUX

    Control Interface Wiring: GRX-4000 Control Unit

    Note:12AWG(2.5mm2)conductorsforCommon(terminal1)and24V power(terminal2)willnotfitinterminals;use18AWG(1.0mm2)pigtails(<6in/15mm).

    Note: Donotconnectdrain/shieldtoground(earth)orwallstation/controlinterfaces.Connectthebaredrainwiresandcutofftheoutsideshield.

    UseLutronCableGRX-CBL-46L

    ToOutlet(withoptionaltransformer).DonotwirePin2whenusingtransformer.

    B: G: 1A: C: D: E: F: H: 2I: 3J: 4K: 5L: 6