greenhouse and energy management (three phase … aug17/replacement...  · web viewgreenhouse and...

85
Greenhouse and Energy Minimum Standards (Air Conditioners and Heat Pumps) Determination 201x 1 Greenhouse and Energy Minimum Standards Act 2012 I, JOSH FRYDENBERG, Minister for the Environment and Energy, make this Determination under sections 23 and 35 of the Greenhouse and Energy Minimum Standards Act 2012. Dated xx 201x [NOT FOR SIGNATURE] JOSH FRYDENBERG Minister for the Environment and Energy DRAFT ONLY

Upload: lamnga

Post on 30-Jan-2018

216 views

Category:

Documents


3 download

TRANSCRIPT

Greenhouse and Energy Minimum Standards (Air Conditioners and Heat Pumps) Determination 201x1

Greenhouse and Energy Minimum Standards Act 2012

I, JOSH FRYDENBERG, Minister for the Environment and Energy, make this Determination under sections 23 and 35 of the Greenhouse and Energy Minimum Standards Act 2012.

Dated xx 201x

[NOT FOR SIGNATURE]

JOSH FRYDENBERG

Minister for the Environment and Energy

DRAFT ONLY

DRAFT ONLY

COPYRIGHT

© 2017 Commonwealth of Australia

This Determination includes material from Australian Standards and/or Australian/New Zealand Standards, which are copyright Standards Australia Ltd. Apart from reproduction for personal and non-commercial use, and uses permitted under the Copyright Act 1968, Standards Australia Ltd material may not be reproduced without permission or licence.

With the exception of the Commonwealth Coat of Arms, Commonwealth copyright material is licensed under the Creative Commons Attribution-Non-Commercial-ShareAlike 4.0 International Licence. To view a copy of this license, visit https://creativecommons.org/licenses/by-nc-sa/4.0/ .

You are free to copy, communicate and adapt the Commonwealth copyright material, so long as you attribute the Commonwealth of Australia.

Complete Australian/New Zealand Standards are available for purchase from Standards Australia Ltd. Requests and inquiries concerning other reproduction and rights pertaining to standards should be directed to SAI Global Limited.

2 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

1 Name of DeterminationThis Determination is the Greenhouse and Energy Minimum Standards (AirConditioners and Heat Pumps) Determination 201x.

2 Commencement, Revocation and Replacement(1) This Determination comes into force XXX.(2) This Determination revokes and replaces the Greenhouse and Energy

Minimum Standards (Air Conditioners and Heat Pumps) Determination 2013.

3 Definitions(1) Standards in this Determination:

AHRI 1230:2010 means Air-Conditioning, Heating, & Refrigeration Institute Standard 1230 Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment, as it existed on the date this Determination came into force.Note 1: AHRI 1230:2010 is available from www.ahrinet.orgNote 2: AHRI 1230:2010 includes all amendments and changes through Addendum

2, June 2014

AS/NZS 3823.1.1:2012 means Australian/New Zealand Standard 3823.1.1:2012 Performance of electrical appliances – air conditioners and heat pumps – Part 1.1: Non-ducted air conditioners and heat pumps – testing and rating for performance, as it existed on the date this Determination came into force.Note: AS/NZS 3823.1.1:2012 is available from Standards Australia Limited.

AS/NZS 3823.1.1:2012 means Australian/New Zealand Standard 3823.1.1:2012 Performance of electrical appliances – air conditioners and heat pumps – Part 1.1: Non-ducted air conditioners and heat pumps – testing and rating for performance, as it existed on the date this Determination came into force.Note: AS/NZS 3823.1.1:2012 is available from Standards Australia Limited.

AS/NZS 3823.1.2:2012 means Australian/New Zealand Standard 3823.1.2:2012 Performance of electrical appliances – air conditioners and heat pumps – Part 1.2: Ducted air conditioners and heat pumps—Testing and rating performance, as it existed on the day this Determination came into force.Note: AS/NZS 3823.1.2:2012 is available from Standards Australia Limited.

AS/NZS 3823.1.3:2005 means Australian/New Zealand Standard 3823.1.3:2005 Performance of electrical appliances – air conditioners and heat pumps. Part 1.3: Water-source heat pumps—Water-to-air and brine-to-air heat pumps—Testing and rating of performance, as it existed on the date this Determination came into force. Note 1: AS/NZS 3283.1.3:2005 is available from Standards Australia Limited.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

3

DRAFT ONLY

Note 2: AS/NZS 3283.1.3:2005 includes all amendments up to and including AS/NZS 3283.1.3:2005/Amdt 1 made on 22 September 2011.

AS/NZS 3823.1.4:2012 means Australian/New Zealand Standard 3823.1.4:2012 Performance of electrical appliances – Air conditioners and heat pumps. Part 1.4: Multiple split-system air conditioners and air-to-air heat pumps–Testing and rating for performance (ISO 15042:2011, MOD), as it existed on the date this Determination came into force.Note: AS/NZS 3823.1.4:2012 is available from Standards Australia Limited.

AS/NZS 3823.1.5:2015 means Australian/New Zealand Standard 3823.1.5:2015 Performance of electrical appliances – Air conditioners and heat pumps. Part 1.4:Non-ducted portable air-cooled air conditioners and air-to-air heat pumps having a single exhaust duct – Testing and rating for performance, as it existed on the date this Determination came into force.Note: AS/NZS 3823.1.5:2015 is available from Standards Australia Limited.

AS/NZS 3823.4.1:2014 means Australian/New Zealand Standard 3823.4.1:2014 Performance of electrical appliances – Air conditioners and heat pumps. Part 4.1: Air-cooled air conditioners and air-to-air heat pumps–Testing and calculating methods for seasonal performance factors – Cooling seasonal performance factor (ISO 16358-1:2013, (MOD)), as it existed on the date this Determination came into force.Note 1: AS/NZS 3283.4.1:2014 is available from Standards Australia Limited.Note 2: AS/NZS 3283.4.1:2014 includes all amendments up to and including

AS/NZS 3283.4.1:2014/Amdt 1 made on 8 May 2017.

AS/NZS 3823.4.2:2014 means Australian/New Zealand Standard 3823.4.2:2014 Performance of electrical appliances – Air conditioners and heat pumps. Part 4.2: Air-cooled air conditioners and air-to-air heat pumps–Testing and calculating methods for seasonal performance factors – Heating seasonal performance factor (ISO 16358-2:2013, (MOD)), as it existed on the date this Determination came into force.Note 1: AS/NZS 3283.4.2:2014 is available from Standards Australia Limited.Note 2: AS/NZS 3283.4.2:2014 includes all amendments up to and including

AS/NZS 3283.4.2:2014/Amdt 1 made on 8 May 2017.

AS/NZS 4755.3.1:2014 means Australian/New Zealand Standard 4755.4.1:2014 Demand response capabilities and supporting technologies for electrical products Interaction of demand response enabling devices and electrical products - Operational instructions and connections for air conditioners, as it existed on the date this Determination came into force.Note: AS/NZS 4755.3.1:2014 is available from Standards Australia Limited.

AS/NZS 4776.1.1:2008 means Australian/New Zealand Standard 4776.1.1:2008 Liquid-chilling packages using the vapour compression cycle – Part 1.1: Method of rating and testing performance – Rating, as it existed on the date this Determination came into force.Note: AS/NZS 4776.1.1:2008 is available from Standards Australia Limited.

AS/NZS 4965.1:2008 means Australian/New Zealand Standard 4965.1:2008 Performance of close control air conditioners – Part 1:

4 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Testing for rating, as it existed on the date this Determination came into force.Note: AS/NZS 4965.1:2008 is available from Standards Australia Limited.

EN 12102:2013 means European Standard 12102:2013 Air conditioners, liquid chilling packages, heat pumps and dehumidifiers with electrically driven compressors for space heating and cooling. Measurement of airborne noise. Determination of the sound power level, as it existed on the date this Determination came into force.Note: EN 12102:2013 is available from Standards Australia Limitedthe European

Committee for Standardization.

EN 14511:2013 means European Standard EN 14511:2013 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling, as it existed on the date this Determination came into force. Note: EN 14511:2013 is available from the European Committee for

Standardization.

ISO 5151:2010 means International Organization for Standardization Standard 5151:2010 Non-ducted air conditioners and heat pumps - Testing and rating for performance, as it existed on the date this Determination came into force.Note: ISO 5151:2010 is available from the International Organization for

Standardization.

ISO 13253:2011 means International Organization for Standardization Standard 13253:2011 Ducted air conditioners and heat pumps - Testing and rating for performance, as it existed on the date this Determination came into force.Note: ISO 13253:2011 is available from the International Organization for

Standardization.

ISO 15042:2011 means International Organization for Standardization Standard 15042:2011 Multiple split-system air-conditioners and air-to-air heat pumps - Testing and rating for performance, as it existed on the date this Determination came into force.

Note: ISO 15042 is available from the International Organization for Standardization.

(2) Terms in this Determination:Act means the Greenhouse and Energy Minimum Standards Act 2012.add-on cooler means a cooling only, ducted split-system designed to ‘add-on’ to a ducted gas heater. They may or may not use their own fan for circulating the indoor air.AHRI certificate means a certified test certificate from the Air-Conditioning, Heating, and Refrigeration Institute for the relevant product class of air conditioner. See www.ahrinet.org for details.Note: Further information on AHRI certification can be found at www.ahrinet.org.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

5

DRAFT ONLY

air conditioner means an encased assembly or assemblies designed to provide conditioned air to an enclosed space, room or zone (conditioned space), that:(a) may be either a single-package or split system; and (b) comprises a primary source of refrigeration for cooling and

dehumidification; and(c) may include means for heating other than a heat pump, as well as

means for circulating, cleaning, humidifying, ventilating or exhausting air; and

(d) may be provided in more than one assembly; the separated assemblies of which (split systems) are designed to be used together.

Annual Coefficient of Performance (ACOP) is the measure of the energy efficiency of the heating function of air conditioners or heat pumps and incorporates Weighted Average Inactive Power Consumption (Pia). It is calculated in section 6(3). Annual Energy Efficiency Ratio (AEER) is the measure of the energy efficiency of the heating function of air conditioners or heat pumps and incorporates Weighted Average Inactive Power Consumption (Pia). It is calculated in section 6(3). Australian Standard means a standard that is published by Standards Australia Limited denoted by the letters “AS” and identifying numbers and letters.Australian/New Zealand Standard means a standard that is jointly published by Standards Australia Limited and Standards New Zealand, is applicable in both countries and denoted by the letters “AS/NZS” and identifying numbers and letters.average true power factor means the average true power factorratio over a given time calculated byof the measured kilowatt hours (kWh) divided by the measured kilo volt ampere hours (kVAh). Note: It is not the average of regular instantaneous power factor measurements.

ceiling cassette means a type of indoor unit for a split system whose chassis is installed within the ceiling space. The fascia/panel/grille assembly includes an air inlet and multiple outlets and is the only component visible from within the conditioned room.circumvention device means any control, control device, software, component or part that alters the operating characteristics during any test procedure, resulting in measurements that are unrepresentative of the appliance’s true characteristics that may occur during normal use under comparable conditions. Generally, circumvention devices save energy during an energy test, but not during normal use.Note: An example of a circumvention device would be a mechanism that de-

activates a crankcase heater or other energy-consuming devices during the test.

close control air conditioner means a unitary air conditioner designed for high sensible heat ratio applications that are capable of maintaining close

6 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

control of both temperature and humidity. A close control air conditioner consists of one or more factory-made assemblies, which include a compressor, a direct expansion evaporator, an air-moving device and air-filtering devices, and may include a condenser, a humidifier or a reheating function. Note: This is the same meaning as in clause 4.1 of AS/NZS 4965.1:2008.

Coefficient of Performance (COP) means a ratio of the heating capacity to the power input to the device at any given set of rating conditions (watts/watts).cooling full-load operation means operation with the equipment and controls configured for the maximum continuous refrigeration capacity specified by the manufacturer and allowed by the unit controls. Unless otherwise regulated by the automatic controls of the equipment, all indoor units and compressors must be functioning during the full-load operation.Note 1: Unless otherwise regulated by the automatic controls of the equipment, all

indoor units and compressors shall must be functioning during the full-load operation.

Note 2: This is the same meaning as in clause 3.11 of AS/NZS 3823.4.1:2014.

Cooling Seasonal Energy Consumption (CSEC) means the total annual amount of energy consumed by the equipment when it is operated for cooling in active mode and is calculated according to the method set out in subclause 6.4.4 of AS/NZS 3823.4.1.degradation coefficient means the coefficient that indicates efficiency loss caused by cyclic operation.Note: This is the same meaning as in clause 3.6 of AS/NZS 3823.4.1:2014.

dehumidifier means an encased assembly designed to remove moisture from its surrounding atmosphere using either an electrically operated refrigeration system or a desiccant type of material. It also includes a means to circulate air and a drain arrangement for collecting and storing and/or disposing of the condensate.Note: This is the same meaning as in clause 3.4 of AS/NZS 3823.1.5:2015

demand response means the automated alteration of an electrical product’s normal mode of operation in response to an initiating signal originating from or defined by a remote agent.Note: This is the same meaning as in subclause 1.3.6 of AS/NZS 4755.3.1:2014.

demand response capability refers to compliance with AS/NZS 4755.3.1:2014.means the ability of an electrical product, in this case an air conditioner or heat pump, to provide demand response.Note: This is the same meaning as in subclause 1.3.7 of AS/NZS 4755.3.1:2014.

ducted air conditioner means an air conditionerencased assembly or assemblies designed primarily to provide ducted delivery of conditioned air to an enclosed space, room or zone (conditioned space)., that: They may be either a single-package or split system.

[(a)] may be either a single-package or split system; and

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

7

DRAFT ONLY

[(b)] comprises a primary source of refrigeration for cooling and dehumidification; and

[(c)] may include means for heating other than a heat pump, as well as means for circulating, cleaning, humidifying, ventilating or exhausting air; and

[(d)] may be provided in more than one assembly; the separated assemblies of which (split systems) are designed to be used together.

Note: This is the same meaning as in clause 3.1 of AS/NZS 3823.1.2:2012.

ducted heat pump means a heat pump an encased assembly or assemblies designed primarily to provide ducted delivery of conditioned air to an enclosed space, room or zone (conditioned space). They may be either a single-package or split system., including a prime source of refrigeration or heating, that:may be constructed to remove heat from the conditioned space and discharge it to a heat sink if cooling and dehumidification are desired from the same equipment; andmay include means for circulating, cleaning, humidifying, ventilating or exhausting air; andmay be provided in more than one assembly; the separated assemblies of which (split systems) are intended to be used together. Note: This is the same meaning as in clause 3.2 of AS/NZS 3823.1.2:2012.

Energy Efficiency Ratio (EER) means the ratio of the total cooling capacity to the power input to the device at any given set of rating conditions (watts/watts).Eurovent certificate means a certified test certificate from the European Association of Air Handling and Refrigerating Equipment Manufacturers for the relevant product class of air conditioner. Note: Further information on Eurovent certification can be found at

www.eurovent-certification.com

evaporatively cooled condenser refers to a heat exchanger that condenses refrigerant vapour by rejecting heat to a water and air mixture causing the water to evaporate and increase the enthalpy of air.Note 1: For the purposes of this Determination, evaporatively cooled condensers

may be found in unitary single or double duct air conditioners.

Note 2: Such condensers are fed by a supplementary water tank.

Note 3: This is the same meaning as clause 3.8 of AS/NZS 3823.1.5.

extra-low temperature heating capacity test means the heating capacity test at temperature condition H3 as set out in Table 1 of AS/NZS 3823.4.2.Note: This value may be tested or rated.

fixed capacity unit means an air conditioner and/or heat pump that is unable to change its capacity.fixed head type means a multi-split system air conditioner or heat pump incorporating a single refrigerant circuit with a single outdoor unit and two

8 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

or more indoor units, each of which can be individually controlled. The outdoor unit has a dedicated set of refrigeration ports for each individual indoor unit. The maximum number of indoor units that can be connected is limited by the number of dedicated ports on the outdoor unit.ground-loop heat pump means a brine-to-air heat pump using a brine solution circulating through a subsurface piping loop functioning as a heat source/heat sink.Note 1: The heat exchange loop may be placed in horizontal trenches or vertical

bores, or be submerged in a body of surface water.

Note 2: The temperature of the brine is related to climatic conditions and may vary from minus 5 degrees Celsius to 40 degrees Celsius.

Note 3: This is the same meaning as the term ‘ground-loop heat pump application’ in clause 3.1.3 of AS/NZS 3823.1.3:2005.

ground-water heat pump means a water-to-air heat pump using water pumped from a well, lake or stream functioning as a heat source/heat sink.Note 1: The temperature of the water is related to climatic conditions and may vary

from 5 degrees Celsius to 25 degrees Celsius for deep wells.

Note 2: This is the same meaning as the term ‘ground-water heat pump application’ in clause 3.1.2 of AS/NZS 3823.1.3:2005.

H1 means a heating test at standard rating conditions of:(a) 20 ˚C dry-bulb and 15 ˚C wet-bulb inside; and(b) 7 ˚C dry-bulb and 6 ˚C wet-bulb outside.H2 means a heating test at standard rating conditions of:(a) 20 ˚C dry-bulb and 15 ˚C wet-bulb inside; and(b) 2 ˚C dry-bulb and 1 ˚C wet-bulb outside.H3 means a heating test at standard rating conditions of:(a) 20 ˚C dry-bulb and 15 ˚C wet-bulb inside; and(b) -7 ˚C dry-bulb and -6 ˚C wet-bulb outside.heating extended-load operation means operation of the equipment at maximum continuous refrigeration capacity at a higher compressor capacity than full-load operation at H2 or H3 conditions, where this mode is available.Note: This is the same meaning as in clause 3.13 of AS/NZS 3823.4.1:2014.

heating full-load operation means operation with the equipment and controls configured for maximum continuous refrigeration capacity at H1, H2 or H3 conditions; the compressor setting is the same for all conditions.Note: This is the same meaning as in clause 3.12 of AS/NZS 3823.4.1:2014.

heat pump means an encased assembly or assemblies designed to provide conditioned air to an enclosed space, room or zone (conditioned space), including a prime source of refrigeration or heating, that:(a) may be constructed to remove heat from the conditioned space and

discharge it to a heat sink if cooling and dehumidification are desired from the same equipment; and

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

9

DRAFT ONLY

(b) may include means for circulating, cleaning, humidifying, ventilating or exhausting air; and

(c) may be provided in more than one assembly; the separated assemblies of which (split systems) are intended to be used together.

Heating Seasonal Energy Consumption (HSEC) means the total annual amount of energy consumed by the equipment, including make-up heat, when it is operated for heating in active mode. It is calculated by the method set out in subclause 6.4.4 of AS/NZS 3823.4.2.Note: This is the same meaning as in clause 3.4 of AS/NZS 3823.4.4:2014.

Heating Seasonal Performance Factor (HSPF) means the ratio of the total annual amount of heat that the equipment, including make-up heat, can add to the indoor air when operated for heating in active mode to the total annual amount of energy consumed by the equipment during the same period, as calculated by the method set out in clause 6.1 of AS/NZS 3823.4.2.Inactive Energy Consumption (IAEC) means the power consumed by a unit when not performing an air conditioning service and is calculated by the method set out in Annex B of AS/NZS 3823.4.1 or AS/NZS 3823.4.2.Note: Annex B of both AS/NZS 3823.4.1 and AS/NZS 3823.4.2 will yield the

same value.

liquid-chilling package means a factory-made and prefabricated assembly (not necessarily shipped as one package) of one or more compressors, condensers and evaporators, with interconnections and accessories, designed for the purpose of cooling water, and is a machine specifically designed to make use of a vapour compression refrigeration cycle to remove heat from water and reject the heat to a cooling medium, usually air or water.Note: This is the same meaning as in clause 4.10 of AS/NZS 4776.1.1:2008

low temperature cooling capacity test means the cooling capacity test at the outdoor temperature of 29˚C, as defined in Table 1 of AS/NZS 3823.4.1.Note: This value may be tested or rated.

low temperature heating capacity test means the heating capacity test at temperature condition H2 as defined in Table 1of AS/NZS 3823.4.2.Note: This value may be tested or rated.

multi-split outdoor unit means the outdoor unit of a multi-split system containing the compressor, condensing heat exchanger and fan/s, and refrigeration ports. They are designed to connect to two or more independently controlled indoor units. They can be of either fixed head or variable refrigerant flow (VRF) type.multi-split system means a split system air conditioner or heat pump with a refrigeration system having two or more independently controlled indoor units of either fixed head or variable refrigerant flow (VRF) type.multi-stage capacity unit means an air conditioner and/or heat pump that can vary its capacity by three or four steps.

10 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Note: This is the same meaning as in clause 3.9 of AS/NZS 3823.4.1:2014.

noise means the sound power level (dB(A)) as determined under EN 12102.non-ducted air conditioner means an encased assembly or assemblies designed primarily to provide free delivery of conditioned air to an enclosed space, room or zone (conditioned space), that:(a) may be either single-package or split system; and (b) comprises a primary source of refrigeration for cooling and

dehumidification; and(c) may include means for heating other than a heat pump, as well as

means for circulating, cleaning, humidifying, ventilating or exhausting air; and

(d) may be provided in more than one assembly; the separated assemblies of which (split systems) are designed to be used together.

Note 1: This is the same meaning as in clause 3.1 of AS/NZS 3823.1.1:2012.

Note 2: Spot coolers, dehumidifiers and unitary units are defined separately.

non-ducted heat pump means an encased assembly or assemblies designed primarily to provide free delivery of conditioned air to an enclosed space, room or zone (conditioned space) and includes a prime source of refrigeration or heating, that:(a) may be constructed to remove heat from the conditioned space and

discharge it to a heat sink if cooling and dehumidification are desired from the same equipment; and

(b) may include means for circulating, cleaning, humidifying, ventilating or exhausting air; and

(c) may be provided in more than one assembly; the separated assemblies of which (split systems) are intended to be used together.

Note 1: This is the same meaning as in clause 3.2 of AS/NZS 3823.1.1:2012.

Note 2: Spot coolers, dehumidifiers and unitary units are defined separately.

outdoor unit only means the outdoor component of a split system air conditioner or heat pump that consists of the compressor, condensing heat exchanger and fan/s, a refrigerant supply port and a refrigerant return port. They are designed to be connected to a pre-existing indoor unit.portable unitary double duct air conditioner and portable unitary double duct heat pump means a product that is designed to be portable in nature whose ducts temporarily fit, via a specialised attachment, to a partially opened window or door. It must only be sold and advertised for portable applications. Being portable, it must have the following features:(a) casing that encloses the entire unit, including the back; and(b) castors, wheels or feet; and(c) flexible ductwork supplied for adapting to various portable

installation situations; and(d) a length of power cord with a mains plug.Being portable, it must not have the following features:

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

11

DRAFT ONLY

(a) permanent wall or window mounting brackets, either on the unit, in the packaging, or as a separately supplied accessory; or

(b) available instructions that demonstrate how to fix the product to a wall or window; or

(c) other accessories, such as pipes and flanges, designed to allow permanent wall or window mounting.

potentially demand response capable means the ability of an electrical product, in this case an air conditioner or heat pump, to provide demand response capability after the fitting of an extra part or component that is not otherwise supplied with every unit.rated value means a value claimed by the manufacturer. Note: An example of a rated value would be the rated total cooling capacity for the

standard cooling full capacity test.

single-phase means a model where all components in the air conditioning system that require an external power supply require only single-phase power.split system means an air conditioner or heat pump with separate indoor and outdoor components that are connected with refrigerant piping. The indoor unit usually lies within the conditioned space and may be installed or portable or mobile.Note: The indoor unit in some configurations may feed into a duct system. Some

split ducted system indoor units may have no fan and are designed to operate with an existing system (for example, with a gas heater).

standard means an Australian Standard, an Australian/New Zealand Standard, a CIE Standard, an IEC Standard or any other equivalent document.standard cooling full capacity test means the total cooling capacity at full load operating conditions at temperature condition:(a) T1 for units within the scope of AS/NZS 3823.1.1, AS/NZS 3823.1.2

or AS/NZS 3823.1.4:[(b)] Table 12 of AS/NZS 3823.1.3 for cooling for water loop heat pumps;

or(b)[(c)] Table 6.1 of AS/NZS 3823.1.5 for unitary single duct heat pumps.Note: These values may be tested or rated.

standard heating full capacity test means the heating capacity at full-load operating conditions at temperature condition:(a) H1 for units within the scope of AS/NZS 3823.1.1, AS/NZS 3823.1.2

or AS/NZS 3823.1.4:[(b)] Table 1 2 of AS/NZS 3823.1.3 for water-to-air heat pumps; or(b)[(c)] Table 5.1 of AS/NZS 3823.1.5 for unitary single duct air

conditioners.Note: These values may be tested or rated.

12 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

solar-boosted air conditioner means a single-phase or three-phase non-ducted or ducted air conditioner of the vapour compression type, having provision for the input of energy from a solar source and which can be configured to operate as an air air conditioner or heat pump (with little or no solar input).spot cooler means an encased assembly air conditioner that lies wholly within a conditioned space and that draws air for both the evaporator and condenser from the conditioned space and expels both of these back into the conditioned space. Usually portable.Note: This is the same meaning as in clause 3.29 of AS/NZS 3823.1.5:2015

supplementary water tank means a tank designed as an integral part of the unit to contain external supplementary water which is fed to the evaporatively-cooled condenser.Note 1: For the purposes of this Determination, supplementary water tanks may be

found in unitary single or double duct air conditioners.

Note 2: This is the same meaning as clause 3.31 of AS/NZS 3823.1.5.

tested value means a value determined by a physical or simulation test.Note: An example of a tested value would be the tested total cooling capacity for

the standard cooling full capacity test.

three-phase means a model where at least one component in the air conditioning system requires an external three-phase power supply.Note: Where a system has more than one power supply (e.g., a split system), the

whole system is considered to be three-phase where at least one of the external power supply systems is three-phase.

test simulation software means a computer-based software package that uses simplified measurements and other data to estimate relevant air conditioner and heat pump performance without the need for a full, physical test. Total Cooling Seasonal Performance Factor (TCSPF) means the ratio of the total annual amount of heat that the equipment can remove from the indoor air to the total annual amount of energy consumed by the equipment, including the active and inactive energy consumption as calculated by the method set out in Annex B of AS/NZS 3823.4.1.twin (or triple) split system means an a split system air conditioner and/or heat pump comprising a single outdoor unit with and two (or three) indoor units that are controlled by a single controller. Note: Twin or triple split systems are treated as a non-ducted single-split system

and tested to AS/NZS 3823.1.1.

two (2)-stage unit means an air conditioner or heat pump that can vary its capacity by two steps.unitary air conditioner means an air conditioner or heat pump where the evaporator, condenser and associated refrigeration components (for example, the compressor) are contained within a single casing.Note: Unitary air conditioners may be non-ducted (for example, window/wall

units) or ducted (for example, single packaged units).

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

13

DRAFT ONLY

unitary heat pump means a heat pump where the evaporator, condenser and associated refrigeration components (for example, the compressor) are contained within a single casing.Note: Unitary heat pumps may be non-ducted (for example, window/wall units) or

ducted (for example, single packaged units).

unitary double duct air conditioner means an unitary air conditioner that sits wholly within the conditioned space. They use one duct to draw outside air into the casing to cool the condenser and a second duct to expel that air back outside. They can be of either portable or wall mounted type.Note 1: Such air conditioners comprise a primary source of refrigeration for cooling

and dehumidification. They can also include means for heating other than a heat pump, as well as means for circulating, cleaning, humidifying, ventilating or exhausting air.

Note 2: They may be designed to be portable or wall mounted.

unitary double duct heat pump means a unitary heat pump that sits wholly within the conditioned space. They use one duct to draw outside air into the case as the source for the evaporator and a second duct to expel that air back outside. They can be of either portable or wall mounted type.Note 1: Such heat pumps can be constructed to remove heat from the conditioned

space and discharge it to a heat sink if cooling and dehumidification are desired from the same equipment. They can also include means for circulating, cleaning, humidifying, ventilating or exhausting air.

Note 2: They may be designed to be portable or wall mounted.

unitary single duct air conditioner means an unitary air conditioner that is an encased assembly, designed primarily to provide free delivery of conditioned air to an enclosed space, room or zone. It takes its source of air for cooling the condenser from the conditioned space, and discharges this air through a duct to the outdoor space.Note 1: Such air conditioners comprise a primary source of refrigeration for cooling

and dehumidification. They can also include means for heating other than a heat pump, as well as means for circulating, cleaning, humidifying, ventilating or exhausting air.

Note 2: They may be designed to be portable or wall mounted

Note 3: This is the same meaning as in clause 3.18 of AS/NZS 3823.1.5:2015

unitary single duct heat pump means a unitary heat pump that is an encased assembly designed primarily to provide free delivery of conditioned air to an enclosed space, room or zone and includes a prime source of refrigeration for heating. It takes its source of air for the evaporator from the conditioned space, and discharges this air through a duct to the outdoor space.Note 1: Such heat pumps can be constructed to remove heat from the conditioned

space and discharge it to a heat sink if cooling and dehumidification are desired from the same equipment. They can also include means for circulating, cleaning, humidifying, ventilating or exhausting air.

Note 2: They may be designed to be portable or wall mounted.

14 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Note 3: This is the same meaning as in clause 3.19 of AS/NZS 3823.1.5:2015

variable capacity unit means an air conditioner and/or heat pump that can vary its capacity by five or more steps to represent continuously variable capacity.Note: This is the same meaning as in clause 3.10 of AS/NZS 3823.4.1:2014.

variable refrigerant flow (VRF) type means a multi-split system air conditioner or heat pump incorporating a single refrigerant circuit with one or more outdoor units and two or more indoor units each of which can be individually controlled. The outdoor unit module has a set of refrigeration ports that services the network of indoor units through branch piping and/or distribution devices.wall mounted unitary double duct air conditioner and wall mounted unitary double duct heat pump means a unitary double duct product that has design features that allows it to be permanently wall or window mounted. These may be part of the unit or be available as additional accessories. Note: A product that is able to be wall mounted as well as portable is considered to

be wall mounted for the purposes of this Determination.

water-cooled condenser means a component which uses refrigerant-to-water heat transfer, causing the refrigerant to condense and the water to be heated.water-to-air (or brine-to-air) heat pump means a heat pump which consists of one or more factory-made assemblies which normally include an indoor conditioning coil with air-moving means, compressor(s), and refrigerant-to-water or refrigerant-to-brine heat exchanger(s), including means to provide both cooling and heating, cooling-only, or heating-only functions.Note 1: When such equipment is provided in more than one assembly, the separated

assemblies should be designed to be used together.

Note 2: Such equipment may also provide functions of sanitary water heating, air cleaning, dehumidifying, and humidifying.

Note 3: This is the same meaning as in clause 3.1 of AS/NZS 3823.1.3:2005.

Note 4: Water-to-air heat pumps include three subtypes:

(a) water-loop heat pumps (covered by this Determination)

(b) ground-water heat pumps (not covered by this Determination)

(c) ground-loop heat pumps (not covered by this Determination)

water-loop heat pump means a water-to-air heat pump using liquid circulating in a common piping loop functioning as a heat source/heat sink.Note 1: The temperature of the liquid loop is usually mechanically controlled within

a temperature range of 15 °C to 40 °C.

Note 2: This is the same meaning as the term ‘water-loop heat pump application’ in clause 3.1.3 of AS/NZS 3823.1.3:2005.

Note 3: Several other words and expressions used in this Determination have the meaning given by section 5 of the Act. For example:

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

15

DRAFT ONLY

category A product

covered by

family of models

GEMS

GEMS labelling requirements

GEMS level requirements

model

product classes

4 Interpretation

Applicable definitions of terms or phrases

(1)If there is inconsistency in the definitions of words or expressions, words or expression will be interpreted in the following order of priority to the extent of any inconsistency:(a) the Act;(b) this Determination;(c) the Standards.

(2)A word or expression defined in a standard mentioned specifically in section Error: Reference source not found of this Determination has the meaning given to it in the relevant standard.Note: Notwithstanding this, for convenience to users, the key terms for

ascertaining if a product is covered by this Determination are defined in this Determination.

Applicable version of documents incorporated into standards

(3)For the purposes of this Determination the applicable version of any:(a) Standard; or (b) other document that:

(i) is referred to in a standard under the heading ‘Referenced Documents’, or under an equivalent heading in a standard; and

(ii) must be applied to give effect to this Determination or a standard referred to in this Determination,

is the version of the standard or other document that existed at the date this Determination came into force.

Note: For example clause 5.1 of AS/NZS 3823.4.1 requires that the accuracy of all test instrumentation used for tests are those defined in AS/NZS 3823.1.1, AS/NZS 3823.1.2 and AS/NZS 3823.1.4. The applicable versions of AS/NZS 3823.1.1, AS/NZS 3823.1.2 and AS/NZS 3823.1.4 are the versions that existed at the date this Determination comes into force.

16 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

5 Specified product class covered by this Determination(1) This Determination covers single and three-phase air conditioners and heat

pumps of the vapour compression type in the product classes set out in subsection (2).

Note 1: For the purposes of determining the relevant product class, rated total standard cooling full capacity shall must be rounded to the nearest 0.1 kW.

Note 2: This subsection specifies products that are covered by the Determination. See subsection (3) for products that are not covered.

(2) The product classes are as follows:Product Class

Products Covered by Class Product Class Characteristics

1

Non-ducted air-cooled air conditioners and non-ducted air-to-air heat pumps (excluding unitary single duct and unitary double duct air-cooled air conditioners and air-to-air heat pumps)

This product class comprises products with the following characteristics:

(a) non-ducted;(b) unitary air conditioner;[(c)] rated total cooling capacity

of less than 19 kW.single-phase or three-phase.

2

Non-ducted air-cooled air conditioners and non-ducted air-to-air heat pumps

This product class comprises products with the following characteristics:

(a) non-ducted;(b) split system (excluding

multi-split outdoor units); (c) rated total cooling capacity

of less than 4kW.[(d)] single-phase or three-phase.

3

Non-ducted air-cooled air conditioners and non-ducted air-to-air heat pumps

This product class comprises products with the following characteristics:

(a) non-ducted;(b) split system (excluding

multi-split outdoor units);(c) rated total cooling capacity

from 4kW to less than 10kW.[(d)] single-phase or three-phase.

4 Non-ducted air-cooled air conditioners and non-ducted air-to-air heat pumps

This product class comprises products with the following characteristics:

(a) non-ducted;(b) split system (excluding

multi-split outdoor units);[(c)] rated total cooling capacity

from 10kW to less than 19kW.single-phase or three-

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

17

DRAFT ONLY

phase.

5

Ducted air-cooled air conditioners and ducted air-to-air heat pumps (excluding multi-split units)

This product class comprises products with the following characteristics:

(a) ducted;[(b)] rated total cooling capacity

of less than 19kW.single-phase or three-phase.

6

Multi-split outdoor unitDucted air-cooled air conditioners, non-ducted air-cooled air conditioners, ducted air-to-air heat pumps and non-ducted air-to-air heat pumps

This product class comprises products with the following characteristics:a rated total cooling capacity of less than 4kW.multi-split outdoor unit; rated total cooling capacity of less than 4kW.single-phase or three-phase.

7

Multi-split outdoor unitDucted air-cooled air conditioners, non-ducted air-cooled air conditioners, ducted air-to-air heat pumps and non-ducted air-to-air heat pumps

This product class comprises products with a rated total cooling capacity from 4kW to less than 10kWthe following characterist.ics:multi-split outdoor unit;rated total cooling capacity from 4kW to less than 10kW.single-phase or three-phase.

8

Multi-split outdoor unitDucted air-cooled air conditioners, non-ducted air-cooled air conditioners, ducted air-to-air heat pumps and non-ducted air-to-air heat pumps

This product class comprises products with a rated total cooling capacity from 10kW to less than 19kW. the following characteristics:multi-split outdoor unit;rated total cooling capacity from 10kW to less than 19kW.single-phase or three-phase.

9

Ducted air air-cooled air conditioners, non-ducted air-cooled air conditioners, ducted air-to-air heat pumps and non-ducted air-to-air heat pumps, air cooled multi-split outdoor units (excluding unitary single duct and unitary double duct air-cooled air conditioners and air-to-air heat pumps)

This product class comprises products with the following characteristics:a rated cooling capacity from 19kW to less than 39 kW.

rated total cooling capacity from 19kW to less than 39kW;single-phase or three-phase.

10 Ducted air air-cooled air conditioners, non-ducted air-cooled air conditioners, ducted air-to-air heat pumps and non-

This product class comprises products with a rated total cooling capacity of 39kW or greater.the following characteristics:

18 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

ducted air-to-air heat pumps, air-cooled multi-split units (excluding unitary single duct and unitary double duct air-cooled air conditioners and air-to-air heat pumps)

rated total cooling capacity of 39kW or greater;

single-phase or three-phase.

11

Air conditioners with water-cooled condensers, water-to-air heat pumps and brine-to-air heat pumps

This product class comprises products with the following characteristics:a rated total cooling capacity of less than 39Kw.

rated total cooling capacity of less than 39kW;single-phase or three-phase.

12

Air conditioners with water-cooled condensers, water-to-air heat pumps and brine-to-air heat pumps

This product class comprises products with a rated total cooling capacity of 39kW to 65KW.the following characteristics:rated total cooling capacity from 39kW to 65kW;single-phase or three-phase.

13

Wall mounted unitary double duct air-cooled air conditioners and wall mounted unitary double duct air-to-air heat pumps

This product class comprises products with the following characteristics:

[(a)] unitary air conditioner;single-phase or three-phase.

14

Portable unitary double duct air-cooled air conditioners and portable unitary double duct air-to-air heat pumps

154

Unitary single duct air-cooled air conditioners and unitary single duct air-to-air heat pumps

This product class comprises products with the following characteristics:

[(a)] unitary air conditioner;single-phase or three-phase.

165

Outdoor unit only, air-cooled This product class comprises products designed to create a non-ducted single split system of rated total cooling capacity of less than 4kW. with the following characteristics:

designed to create a non-ducted single, twin or triple split system of rated total cooling capacity of less than 4kW;

single-phase or three-phase176 Outdoor unit only, air-cooled This product class comprises

products designed to create a non-ducted single split system of rated

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

19

DRAFT ONLY

total cooling capacity from 4kW to less than 10kW.with the following characteristics:designed to create a non-ducted single, twin or triple split system of rated total cooling capacity from 4kW to less than 10kW;single-phase or three-phase

187

Outdoor unit only, air-cooled This product class comprises products designed to create a non-ducted single split system of rated total cooling capacity from 10kW to less than 19kW. with the following characteristics:designed to create a non-ducted single, twin or triple split system of rated total cooling capacity from 10kW to less than 19kW;single-phase or three-phase

198

Outdoor unit only, air-cooled This product class comprises products designed to create a ducted single split system of rated total cooling capacity of less than 19kW.with the following characteristics:designed to create a ducted split system of rated total cooling capacity of less than 19kW;single-phase or three-phase

2019

Outdoor unit only, air-cooled This product class comprises products designed to create a ducted or non-ducted single split system of rated total cooling capacity 19kW to 39kW.with the following characteristics:designed to create a ducted or non- ducted single, twin or triple split system of rated total cooling capacity from 19kW to less than 39kW;single-phase or three-phase

210 Outdoor unit only, air-cooled This product class comprises products designed to create a ducted or non-ducted single split system of rated total cooling capacity of 39kW or greater.with the following

20 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

characteristics:designed to create a ducted or non- ducted single, twin or triple split system of rated total cooling capacity of 39kW or greater;single-phase or three-phase

Note 1: Product classes 9 and 10 incorporate multi-split systems that have the specified characteristics.

Note 2: Product classes 5, 9 and 10 incorporate add-on coolers that have the specified characteristics.

(3) For subsection 23 (2) of the Act, this Determination does not cover:(a) close control air conditioners(b) liquid-chilling packages;(c) evaporative coolers or any other cooling systems that are not of the

vapour compression type;(d) ground-water heat pumps or ground-loop heat pumps;(e) spot coolers;(f) dehumidifiers;(g) air conditioners powered by mains electricity specifically designed

and sold only for installation in end-use mobile applications of caravans, mobile homes, camper vans, boats and rail cars;

(h) air conditioners powered by mains electricity specifically designed and sold only for installation in specialised high temperature industrial applications, such as crane cabins used over blast furnaces; or

(i) products that solely deliver conditioned outdoor air to an indoor conditioned space.

Note 1: Regarding paragraph (a), products used for close control applications in which the outdoor unit of a split-system configuration contains the compressor are included in the application of this Determination.

Note 2: Regarding paragraphs (a) and (b), some products excluded from the application of this Determination are subject to the application of other GEMS Determinations.

Note 3: Regarding paragraph (c), air conditioners of the vapour compression type that have an enhancement or option to assist the operating energy efficiency (for example, solar-boosted air conditioners) are not excluded from this Determination.

Note 4: Regarding paragraph (d), water-loop heat pumps are included in the application of this Determination.

Note 5: Regarding paragraph (g), units for end-use mobile applications listed at paragraph (g) are air conditioners that have been designed to cater for the expected vibrations, repetitive bumping and shock and other rough use conditions of the intended mobile application, and have design specifications and test evidence of complying with Australian/New Zealand Standard or IEC Standard requirements under such conditions.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

21

DRAFT ONLY

Note 6: Regarding paragraph (h), units installed in portable buildings are included in the application of this Determination.

6 GEMS level requirements

Energy use (MEPS levels)[(1)] For paragraphs 24 (1) (a) and 25 (a) of the Act, the specified requirements

for energy use requirements for products covered by this Determination are the requirements set out in subsectionthat the product’s efficiency must not be less than the applicable minimum values specified in Table 2.

Table 2Energy use requirements (MEPS levels) at standard cooling full capacity

and standard heating full capacityThe Minimum Energy Performance Standards (MEPS for both tested and rated values are as follows:

Product Class

Product description (MEPS)Minimum value

1 Non-ducted unitary <19 kW 3.10 AEER/ACOP2 Non-ducted split systems <4 kW 3.66 AEER/ACOP3 Non-ducted split systems, 4 kW to <10 kW 3.22 AEER/ACOP4 Non-ducted split systems, 10 kW to <19 kW* 3.10 AEER/ACOP5 Ducted systems, <19 kW 3.10 AEER/ACOP6 Multi-split units, <4 kW 3.66 AEER/ACOP7 Multi-split units, 4 kW to <10 kW 3.22 AEER/ACOP8 Multi-split units, 10 kW to <19kW 3.10 AEER/ACOP9 All configurations, 19 kW to 39 kW (excluding

product classes 11-21)3.10 AEER/ACOP

10 All configurations, >39 kW (excluding product classes 11-21)

2.90 AEER/ACOP

11 Water-to-air (or brine-to-air) heat pump, <39 kW 3.50 AEER/ACOP12 Water-to-air (or brine-to-air) heat pump, 39 kW to

65 kW3.20 AEER/ACOP

13 Wall mounted unitary double duct 3.10 AEER/ACOP2.50 EER/COP

14 Portable unitary double duct 2.50 EER/COP154 Unitary single duct 2.50 EER/COP165 Outdoor unit for non-ducted split systems <4 kW 3.66 AEER/ACOP176 Outdoor unit for non-ducted split systems 4 kW to

<10 kW3.22 AEER/ACOP

187 Outdoor unit for non-ducted split systems 10 kW to <19 kW

3.10 AEER/ACOP

198 Outdoor unit for ducted split systems <19 kW 3.10 AEER/ACOP2019 Outdoor unit for ducted and non-ducted split 3.10 AEER/ACOP

22 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

systems, 19 kW to 39 kW210 Outdoor unit for ducted and non-ducted split

systems, >39 kW 2.90 AEER/ACOP

Note 1: Reverse cycle products must meet the requirements for both heating and cooling.

Note 2: In the case of reverse cycle products, the relevant Minimum Energy Performance Standards (MEPS) for heating and cooling are both based on the rated total cooling capacity class.

Note 3: The values specified in Table 2 apply to both tested and rated values.

Energy use – Compliance at part load [(2)] Variable capacity units (except for those in product classes 13 14 and 1415)

which do not meet the requirements specified in Table 2 while operating at 100 per cent of standard cooling/heating full capacity (full load) are deemed to comply if they meet both (a) and (b) below:[(a)] The rated and tested AEER, ACOP, or both (as applicable), as per

subsection (3) is within not less than 95 per cent of the applicable requirement in Table 2.

(a)[(b)] The tested AEER, ACOP, or both (as applicable), at a part load point nominated by the supplier demonstrates that the product meets or exceeds the requirement in Table 2 by one of the following two methods:(i) For an output in the range of 83.3 per cent to 100 per cent of

capacity for subsection (3), the tested AEER, ACOP, or both (as applicable), meets or exceeds the requirement in Table 2.

(ii) For an output in the range 50 per cent to 83.3 per cent of rated capacity, the tested AEER, ACOP, or both (as applicable), meets or exceeds the MEPSpart load given in the following equation:

MEPSpart load ≥[1.25−Output part load

Output ratedcapacity× 0.3]× MEPS rated capacity

Where:Outputpart load is the power output at the nominated part load point for cooling or heating.Outputrated capacity is the rated power output at 100% of standard cooling full capacity at the rated standard cooling full capacity test or the rated standard heating full capacity test.MEPSrated capacity is the applicable minimum value specified in Table 2.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

23

DRAFT ONLY

Energy use – Calculation of AEER and ACOP(1)[(3)] The energy efficiency metric for products in all product classes, other

than those in product classes 14 and 15, for assessing compliance with subsection (1) is the Annual Coefficient of Performance (ACOP) for heating and the Annual Energy Efficiency Ratio (AEER) for cooling. Unless subject to the requirements of subsection (2), these values must be at 100% of rated capacity at the standard cooling full capacity test and the standard heating full capacity test. These values must be calculated in accordance with the following formula:

AEER∨ACOP= Cooling∨heating output (rated∨tested ) ×2000(Cooling∨heating power input ×2000 )+(Pia× 6.76)

Where:Cooling or heating output (rated or tested) is the output (capacity) value in kW for the standard cooling full capacity test or standard heating full capacity test.Cooling or heating power input (rated or tested) is the power input value in kW for the standard cooling full capacity test or standard heating full capacity test.2000 is the assumed hours of operation per year in cooling or heating mode.Pia is the Weighted Average Inactive Power Consumption as defined in Annex B of AS/NZS 3823.4.1 and AS/NZS 3823.4.2.6.76 is a factor that converts power (watts) to energy (kWh) for (8760 – 2000) hours per year.Note 1: The calculation of both rated and tested values for AEER and ACOP are

required to meet MEPSthe specified GEMS level requirements using this formula.

Note 2: Unless subject to the requirements of subsection (8), these tested and rated values must be at 100% of capacity at the rated standard cooling full capacity test and the rated standard heating full capacity test.

Note 13: Pia represents a single, annual, inactive power consumption figure that applies equally to both cooling and heating cycles. It can be measured/calculated once using Annex B of either AS/NZS 3823.4.1 or AS/NZS 3823.4.2.

Note 2: The energy efficiency metric for products in product classes 14 and 15 is the Energy Efficiency Ratio (EER) and the Coefficient of Performance (COP).

Conducting tests(2)[(4)] Subject to subsections 6 (4) to 6 (30) of this Determination, for

paragraphs 24 (1) (a) and 25 (b) of the Act, , the specified requirements for conducting tests are the requirements mentioned in: (a) for products in product classes 1 to 10, 13, 14 and 16 to 21, section 5

of AS/NZS 3823.4.1 and AS/NZS 3823.4.2 (as applicable);

24 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

(b) for products in product classes 11 and 12, sections 4 and 6 of AS/NZS 3823.1.3; and

(c) for products in product class 15, sections 5.1 and 6.1 of AS/NZS 3823.1.5.

Note 1: Regarding paragraph (a) AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.1 for non-ducted unitary units, unitary double ducts, non-ducted single and twin (triple) split systems. For example, AS/NZS 3823.4.1 specifies the required cooling tests and conditions while AS/NZS 3823.1.1 specifies the test tolerances, measurement equipment and installation requirements.

Note 2: Regarding paragraph (a) AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.2 for ducted unitary units, including add-on coolers. However, AS/NZS 3823.1.2 instructs small ducted units with determined external static pressure (ESP) for rating purposes of less than 25 Pa to be tested using the non-ducted test standard AS/NZS 3823.1.1.

Note 3: Regarding paragraph (a) AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.4 for multi-split units.

Conducting tests – Rounding and significant figures(3)[(5)] Unless otherwise stated, numbers must be rounded and recorded to five

significant figures.

Conducting tests – Circumvention devices(4)[(6)] Circumvention devices must not be used.

Conducting tests – solar-boosted air conditioners and heat pumps

(5)[(7)] Solar-boosted air conditioners and heat pumps must be tested with any solar input minimized or disconnected, as far as possible.

Conducting tests – use of test simulation software

[(8)] Subject to subsection (9), products in the The following product classes may elect to use test simulation software instead of a physical test for the mandatory cooling tests of AS/NZS 3823.4.1 and the mandatory heating tests of AS/NZS  3823.4.2, except for the low temperature heating capacity test (H2):[(a)] All products with a rated cooling capacity of ≥30 kW, except products

in product classes 11, and 12 and 15.[(b)] All products with a rated cooling capacity of <30 kW, except products

in product classes 11 to 154, where the supplier provides an undertaking that combined Australian and New Zealand sales of that model will bhave been or will bee less than 10 units per in the financial year in which registration occurred, and each subsequent financial year.

Note 1: The GEMS Regulator may request evidence of sales volumes to demonstrate compliance with paragraph (b), under section 56 of the ActThe supplier must provide annual sales data by

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

25

DRAFT ONLY

Note 2: In all cases, the results of a physical test take precedence over the results from test simulation software.

Conducting tests – authorisation of test simulation software

[(9)] Once satisfied that a test simulation software package has an accuracy equivalent to the relevant physical test, the GEMS Regulator Test simulation software may be authorised that software package for all subsequent use for products in the same product class of the same typewith a product type once the GEMS Regulator is satisfied that the software has an accuracy equivalent to the relevant physical test. The physical test standards for each class of product are the following:[(a)] Non-ducted air conditioners and heat pumps – AS/NZS 3823.1.1[(b)] Ducted air conditioners and heat pumps – AS/NZS 3823.1.2[(c)] Multi-split air conditioners and heat pumps – AS/NZS 3823.1.4Note 1: Test simulation software must be authorised by the GEMS Regulator?? for

each product class in this subsection that the supplier intends to use it for.

Note 12: Evidence that software has equivalent accuracy to a physical test may include (but is not be limited to) a full physical test report and a full simulation test report on the same product.

Note 21: Test simulation software must be authorised by thThe GEMS Regulator?? may require separate evidence of the accuracy of the software package for each product class/type combination in this subsection thatfor which the supplier intendswishes to use it for.

Note 3: The relevant physical test standard for each class of product are the following:

(a) Non-ducted air conditioners and heat pumps – AS/NZS 3823.1.1;(b) Ducted air conditioners and heat pumps – AS/NZS 3823.1.2; and(c) Multi-split air conditioners and heat pumps – AS/NZS 3823.1.4

Conducting tests – H2/H3 heating test requirements

(6)[(10)] All low temperature heating capacity tests (H2) and extra-low temperature heating capacity tests (H3) may be conducted using either:(a) The air enthalpy method as outlined in AS/NZS 3823.1.1, AS/NZS

3823.1.2 or AS/NZS 3823.1.4 (as applicable).(b) A shortened calorimeter room test spanning three complete defrost

cycles.

Conducting tests – use of default test values in AS/NZS 38232.4.1

[(11)] Fixed speed capacity products may elect to use the default values of Table 1 of AS/NZS 3823.4.1 for the low temperature cooling capacity test, rather than perform a physical test at these conditions.Note: These defaults are based on tested values from the standard cooling full

capacity test. The total cooling capacity is multiplied by 1.077 and the power input is multiplied by 0.914.

26 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Conducting tests – rating variable speed capacity products as fixed speedcapacity products

[(12)] Variable speed capacity, two-stage, and multi-stage products may elect to be tested and rated as a fixed speed capacity product for the purposes of testing to Table 1 of AS/NZS 3823.4.1 and/or AS/NZS 3823.4.2.

Note 1: A low temperature cooling capacity test may be performed using the locking instructions for the standard cooling full capacity test. Alternatively, the default values may be used as per subsection (10).

Note 2: A low temperature heating capacity test at full capacity may be performed using the locking instructions for the standard heating full capacity test.

Conducting tests – degradation coefficient of AS/NZS 3823.4

(7)[(13)] The value for the Degradation Coefficient (CD) of Table 1 in both AS/NZS 3823.4.1 and AS/NZS 3823.4.2 may not be changed from the default value of 0.25.

Conducting tests – commercial and domestic residential ratings

[(14)] All product classes, except those in product classes 11, 12, and 15, will be rated according to the method set out in clause 6 of AS/NZS 3823.4.1 and AS/NZS 3823.4.2 (as applicable) using the domesticresidential-based temperature bins of Tables 3.1, 3.2 and 3.3 of both AS/NZS 3823.4.1 and AS/NZS 3823.4.2, and the commercial-based temperature bins set out below:

Commercial cooling outdoor temperature distribution bins

Outdoor temperature tj °C Hot/humid zone hrs Mixed zone hrs Cold zone hrs

15 0 0 181

16 0 0 183

17 0 0 170

18 100 229 177

19 117 238 175

20 141 251 185

21 185 225 165

22 235 242 143

23 256 208 118

24 282 185 112

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

27

DRAFT ONLY

25 290 178 82

26 306 129 72

27 304 125 69

28 265 89 45

29 271 70 66

30 219 39 40

31 137 52 45

32 101 39 32

33 85 21 22

34 57 21 11

35 30 18 6

36 17 17 5

37 13 14 0

38 4 14 0

39 0 2 0

40 0 3 0

41 0 2 0

Totals 3415 2411 2104

Commercial heating outdoor temperature distribution bins

Outdoor temperature tj °C

Hot/humid zone hrs

Mixed zone hrs Cold zone hrs

-7 0 0 0

-6 0 0 2

-5 0 0 4

-4 0 1 4

-3 0 0 8

-2 0 1 11

28 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

-1 0 2 17

0 0 6 14

1 0 6 17

2 0 9 28

3 0 18 29

4 0 16 38

5 3 15 48

6 4 23 62

7 7 29 122

8 14 33 127

9 15 48 176

10 18 52 163

11 15 77 222

12 28 87 197

13 27 126 184

14 30 170 0

15 38 210 0

16 62 221 0

17 0 0 0

Totals 261 1150 1473

Note 1: Suppliers may nominate which rating they use in advertising, etc as long as this is made clear to consumers.

Note 2: Both ratings will be publicly available through the Energy Rating website.

Note 3: Only the domestic residential ratings may be used for the energy label.

Note 4: Water-source products within product classes 11 and 12 and unitary single duct products within product class 15 are not rated using AS/NZS 3823.4.

(8)[(15)] When performing a commercial rating using the temperature bins of subsection (14), the calculations must be conducted according to subclause 6.2 of both AS/NZS 3823.4.1 and AS/NZS 3823.4.2, using the following t0 and t100 values for the purposes of Formula 2:

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

29

DRAFT ONLY

AS/NZS 3823.4 zone Standard t0 (°C) t100 (°C)

Hot/humid AS/NZS 3823.4.1 17 33

Hot/humid AS/NZS 3823.4.2 17 0

Mixed AS/NZS 3823.4.1 17 35

Mixed AS/NZS 3823.4.2 17 0

Cold AS/NZS 3823.4.1 14 35

Cold AS/NZS 3823.4.2 14 0

Conducting tests – test reports

[(16)] All product registrations must include a test report demonstrating all required tested values. Two-stage, multi-stage and variable speed products must include instructions on how to obtain the stated capacities (e.g. inverter locking instructions, fan seeds, etc) that would allow a check-testing laboratory to replicate all rated test values. Subsequent capacity setting instructions may be required for check-testing by the GEMS Regulator and must be supplied on request, otherwise the registration may be cancelled.

Conducting tests – calorimeter versus air enthalpy test methods

[(17)] Subject to subsections (8) to (1110), products must use a calorimeter room test method or an indoor air enthalpy test room method according to the following table:

Calorimeter room only Calorimeter room or indoor air enthalpy room

Single-phase non-ducted unitary units

Three-phase non-ducted unitary units

Single-phase non-ducted split systems

Three-phase non-ducted split systems

Unitary single duct units Ducted units

Single-phase unitary double duct units

Three-phase unitary double duct units

Split-systems with a ceiling cassette as the indoor unit

Multi-split units

30 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Outdoor unit only products

Water-to-air heat pumps

Air conditioners with water-cooled condensers

Products not displaying an energy label as a result of the exclusion at subsection 7 (5)

(9) Except for the provisions of subsections (11) and (17), a calorimeter room test method must be used for the following products:[(a)] Single-phase non-ducted unitary units.[(b)] Single-phase non-ducted split systems (except for the provisions of

subsection (25)).[(c)] Unitary single duct units[(d)] Single-phase unitary double duct units.

[(18)] Except for the provisions of subsection (11), an indoor air enthalpy test method or a calorimeter room test method must be used for the following products:[(a)] Three-phase non-ducted unitary units.[(b)] Three-phase non-ducted split systems.[(c)] Ducted units.[(d)] Three-phase unitary double duct units.[(e)] Split-systems with a ceiling cassette as the indoor unit.[(f)] Multi-split units.[(g)] Outdoor unit only products.[(h)] Water-to-air heat pumps.[(i)] Air conditioners with water-cooled condensers.[(j)] Products granted an exemption from physical labelling under Section

7, subsection XXXXXXXX.

Conducting tests – certification schemesalternative test methods for VRF multi-split units and products >30 kW

[(19)] VRF multi-split units or products greater than 30 kW cooling capacity, except those in product classes 11, or 12 or 15, may submit a test report based onconduct tests according to the methods set out in the following standards:(a) EN 14511.(b) A standard based on ISO 5151 (non-ducted units, any VRF multi-split

and fixed head multi-split greater than 30 kW cooling capacity).(c) A standard based on ISO 13253:2011 (ducted units).

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

31

DRAFT ONLY

(d) A standard based on ISO 15042:2011 (multi-splits).(e) AHRI 1230(f) An AHRI certificate(g) A Eurovent certificateNote: Performance must be based on an electrical supply voltage of 230 V single-

phase or 400 V three-phase, a frequency of 50 Hz and the T1 and H1 test conditions.

Conducting tests – specific requirements for non-ducted unitary unitsseasonal rating tests

(10)[(20)] Subject to the requirements of subsections (11) and (12), air conditioners in product classes 1 to 10, 13, 14 and 16 to 21 must be tested to the required test points identified in Table 1 in AS/NZS 3823.4.1 for cooling, as per their product type (that is, fixed capacity, two-stage, multi-stage or variable capacity). Any of the optional tests may also be performed.Note: These product classes cover all products except unitary single ducts and

water-to-air (or brine-to-air) products.

(11) Subject to the requirements of subsection (12), heat pumps <30 kW rated cooling capacity in product classes 1 to 10, 13, 14 and 16 to 21 must be tested to the required test points identified in Table 1 in AS/NZS 3823.4.2 for heating, as per their product type (that is, fixed capacity, two-stage, multi-stage or variable capacity). Any of the optional tests may also be performed.Note: These product classes cover all products except unitary single ducts and

water-to-air (or brine-to-air) products.

(12) Subject to the requirements of subsection (12), heat pumps ≥30 kW rated cooling capacity in product classes 1 to 10, 13, 14 and 16 to 21 may be tested to the required test points identified in Table 1 in AS/NZS 3823.4.2 for heating, as per their product type (that is, fixed capacity, two-stage, multi-stage or variable capacity). In this situation, any of the optional tests may also be performed. If these products are not tested to Table 1 in AS/NZS 3823.4.2, they must be tested and rated as per the standard heating full capacity test (H1) of AS/NZS 3823.1.1, AS/NZS 3823.1.2 or AS/NZS 3823.1.4 (as applicable).Note: These product classes cover all products except unitary single ducts and

water-to-air (or brine-to-air) products.

(13) Except for the provisions of subsections (18) and (19), non-ducted unitary air conditioners must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.1 for cooling as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(21)] Except for the provisions of subsection (19), non-ducted unitary heat pumps <30 kW rated cooling capacity must be tested to the mandatory test

32 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(22)] Except for the provisions of subsection (19), non-ducted unitary heat pumps ≥30 kW rated cooling capacity may test to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). In this situation, suppliers may also elect to perform any of the optional tests.Note: AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.1 for non-ducted

unitary units.

Conducting tests – specific requirements for non-ducted split systems

[(23)] Except for the provisions of subsections (18) and (19), non-ducted split system air conditioners must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.1 for cooling as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(24)] Except for the provisions of subsection (19), non-ducted split system heat pumps <30 kW rated cooling capacity must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(25)] Except for the provisions of subsection (19), non-ducted split system heat pumps ≥30 kW rated cooling capacity may test to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). In this situation, suppliers may also elect to perform any of the optional tests.Note 1: AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.1 for non-ducted

split systems.

Note 2: Twin (or triple) split systems are included in this clause.

Conducting tests – specific requirements for ducted systems

[(26)] Except for the provisions of subsections (18) and (19), ducted air conditioners must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.1 for cooling as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(27)] Except for the provisions of subsection (19), ducted heat pumps <30 kW rated cooling capacity must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

33

DRAFT ONLY

[(28)] Except for the provisions of subsection (19), ducted heat pumps ≥30 kW rated cooling capacity may test to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). In this situation, suppliers may also elect to perform any of the optional tests.Note 1: AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.2 for ducted

units.

Note 2: AS/NZS 3823.1.2 instructs small ducted units with determined external static pressure (ESP) for rating purposes of less than 25 Pa to be tested using the non-ducted test standard AS/NZS 3823.1.1.

Note 3: Add-on coolers are included in this subsection. They are tested using AS/NZS 3823.1.2

Conducting tests – specific requirements for multi-split units

(14)[(29)] The registration of a multi-split system is based on the outdoor unit (i.e. the multi-split unit). Systems comprising multiple outdoor units do not need registering if the base outdoor units are already registered as part of another system. The outdoor unit model number is registered and the complete system performance using a representative combination of indoor units is used to confirm compliance with the requirements of this Determination. The representative combination of indoor units must:(a) Not be less than the manufacturer's specified minimum number of

indoor units for a VRF unit.(b) Consist of a dedicated indoor unit for each refrigeration port on the

outdoor unit for a fixed head product.(c) Provide a combined rated total cooling capacity for the system which

has a cooling capacity ratio of indoor units to outdoor unit equal to 1, or as close as possible to 1 within the range of the manufacturer’s specified connectable indoor units.

(d) Be the same for all heating and cooling tests.(e) Be configured with a remote control for each indoor unit (unless the

controls are integral to the indoor unit).(f) Be nominated by model number and quantity.(g) Include the rated capacity for each unit when used in the

representative combination.(h) Use a clearly defined configuration and test setup. Complete setup

instructions, including but not limited to piping lengths and layouts, capacity fixing methods, refrigerant charge and system specifications must be provided. This may take the form of a printout from the manufacturer’s sales selection software.

[(30)] Except for the provisions of subsections (18) and (19), multi-split air conditioners must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.1 for cooling as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

34 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

[(31)] Except for the provisions of subsection (19), multi-split heat pumps <30 kW rated cooling capacity must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(32)] Except for the provisions of subsection (19), multi-split heat pumps ≥30 kW rated cooling capacity may test to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). In this situation, suppliers may also elect to perform any of the optional tests.Note: AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.4 for multi-

splits.

Conducting tests – specific requirements for unitary double duct units

[(33)] Wall mounted unitary double duct units must be tested as peruse the test procedures of AS/NZS 3823.1.1. They must be installed on the wall ofin the test chamber with the air intake and exhaust ducts as short as possible as per the manufacturer’s installation instructions.

[(34)] Except for the provisions of subsections (18) and (19), unitary double duct air conditioners must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.1 for cooling as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(35)] Except for the provisions of subsection (19), unitary double duct heat pumps <30 kW rated cooling capacity must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(36)] Except for the provisions of subsection (19), unitary double duct heat pumps ≥30 kW rated cooling capacity may test to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). In this situation, suppliers may also elect to perform any of the optional tests.

[(37)] Portable unitary double ducts units must use the general test procedures of AS/NZS 3823.1.1. However, both the exhaust and inlet ducts shall be installed as per Appendices A2.1 to A2.5 of AS/NZS 3823.1.5.

(15) Portable unitary double duct units that contain a condensate container must not have a test interrupted by a full condensate container triggering a cut-off switch. If necessary, condensate containers must be modified to drain away excess condensate into a larger container in the test chamber before the volume that activates the cut-off switch is reached.Note 1: Some portable unitary double duct units may have an in-built hose to

facilitate the draining of condensate.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

35

DRAFT ONLY

Note 2: Some portable unitary double duct units are designed to collect condensate and evaporate it on the condenser. This process should be allowed to occur during testing.

Note 3: The testing requirements of this subclause mirror the requirements for unitary single duct products as detailed in AS/NZS 3823.1.5.

(16)[(38)] Portable unitary double ducts might contain a supplementary water tank designed to provide additional water to an evaporatively cooled condenser. All cooling tests may be performed using this feature as per the manufacturer’s instructions provided they meet the requirements of subsection (27). Water added to a unit’s supplementary water tank must be 35°C ± 1°C.Note 1: Some portable unitary double ducts are fitted with a supplementary water

evaporation feature designed to provide additional water for the evaporatively cooled condenser and/or compressor. They generally require the user to fill the water tank and manually select an operational mode via the unit’s control panel or remote control that turns this function on. This operational mode may override other thermostat and fan settings and is designed to achieve higher cooling capacities and greater energy efficiency while this feature is active. When these units deactivate their supplementary water evaporation feature (for instance, when insufficient water is detected in the supplementary water tank), they may automatically revert to cooling without the aid of the supplementary water evaporation feature, or they may automatically switch off.

Note 2: This provision is not applicable to wall mounted unitary double duct products within product class 13.

Note 3: The testing requirements of this subsection mirror the requirements for unitary single duct products as detailed in AS/NZS 3823.1.5.

Note 4: AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.1 for unitary double ducts.

(17)[(39)] Portable unitary double duct units within product class 14 that contain a supplementary water tank must have the duration of the tank determined during the standard cooling full capacity test. While the test setup and test conditions (T1) must be as per AS/NZS 3823.1.1, determining the duration of the supplementary water evaporation feature must be performed as per Appendix B of AS/NZS 3823.1.5.

(18)[(40)] If the calculated run-time of the supplementary water tank during the standard cooling full capacity test is ≥ 4 hours, the cooling tests of subsection (28) may use the supplementary water evaporation feature. A dual rating for the standard cooling full capacity must be used if the product reverts to air-to-air cooling once the supplementary water tank is empty. A single rating based on the supplementary water evaporation feature must be used if the product ceases operation once the supplementary water tank is empty. Compliance to subsection (1) (the MEPS levels) is based on using the supplementary water evaporation feature for those products that have a calculated tank run time of ≥4 hours. These requirements are summarised, below:

36 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Supplementary water

tank?

Unit can operate without

supplementary water?

Required cooling tests

Calculated tank run

timeAllowable

ratings

No N/A Test without supplementary water

N/A Single rating without supplementary water

Yes No Test with supplementary water and measure water usage to calculate tank run time

Shall be 4 h

Single rating with supplementary water

Yes Yes Test without supplementary water, then test with supplementary water and measure water usage to calculate tank run time

<4 h Single rating without supplementary water

4 h Dual rating with and without supplementary water. Supplementary water rating may be used for MEPS.

Conducting tests – specific requirements for unitary single duct units

(19)[(41)] Unitary single duct units must be tested to the following tests of AS/NZS 3823.1.5:(a) The cooling capacity test of Clause 5.1.(b) For products with a supplementary water evaporation feature,

Appendix B.(c) The heating capacity test of Clause 6.1 (if applicable).

Conducting tests – specific requirements for water-source units

(20)[(42)] Water-to-air (or brine-to-air) heat pumps and products with water-cooled condensers within Product Classes 11 and 12 of section 5 (2) must be tested to the cooling and heating (if applicable) capacity tests of AS/NZS 3823.1.3.Note: While the determination of seasonal performance to AS/NZS 3823.4 is not

required for water-source products, they may be tested for part load performance as per the provisions of subsection (2). Part load testing is defined in AS/NZS 3823.1.3.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

37

DRAFT ONLY

Conducting tests – specific requirements for outdoor unit only products

[(43)] An outdoor unit only product must have its model number registeredbe tested with indicative system performance using a representative indoor unit. The representative indoor unit must:[(a)] Be the same type of indoor air distribution as the outdoor unit is being

registered and marketed for (i.e. ducted or non-ducted).[(b)] Generate tested total cooling capacity and rated heating capacity for

the outdoor unit that meet the requirements of subsection (9).[(c)] Be nominated by make and model number and be readily available for

possible check-testing purposes.(a)[(d)] Be the same for all cooling and heating tests.(b)[(e)] Be configured with a remote control unless the controls are integral

to the indoor unit.

[(44)] Except for the provisions of subsections (18) and (19), outdoor unit only air conditioners must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.1 for cooling as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(45)] Except for the provisions of subsection (19), outdoor unit only heat pumps <30 kW rated cooling capacity must be tested to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). Suppliers may also elect to perform any of the optional tests.

[(46)] Except for the provisions of subsection (19), multi-split heat pumps ≥30 kW rated cooling capacity may test to the mandatory test points of Table 1 in AS/NZS 3823.4.2 for heating as per their product type (i.e. fixed speed, two-stage, multi-stage or variable speed). In this situation, suppliers may also elect to perform any of the optional tests.Note: AS/NZS 3823.4 uses the test procedures of AS/NZS 3823.1.1 for non-ducted

systems and AS/NZS 3823.1.2 for ducted systems.

7 GEMS labelling requirements

Labelling and communication requirements

(1) For paragraphs 24 (1) (b), 26 (1) (a) and 26 (1) (b) of the Act, the specified labelling and communication requirements are the requirements of this section.

Products that must display an energy label – non-ducted, single-phase products

(2) The following products must display an energy label:

38 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

[(a)] single-phase products <30 kW rated cooling capacity in product classes 1 to 4, 9, and 13 and to 15.

[(b)] non-ducted, single-phase products <30 kW rated cooling capacity in product class 9.

Note: Products for which displaying an energy label is voluntary are described in subsection (6).

Products that must not display an energy label – multi-split systems

(3) Products in product classes 6 to 10 that are multi-split units, must not display an energy label.

Products that must not display an energy label – air conditioners with water cooled condensers etc.

(4) Products in product classes 11 or 12 must not display an energy rating label.

Energy labelling exclusion – non-domestic residential applications

(5)Subject to subsection (3), products otherwise covered by subsection (2) are excluded from the requirements of this section if they are:[(a)] designed for non-domesticresidential applications;(a)[(b)] not on display for sale through retail outlets; and(b)[(c)] not promoted in any catalogue or advertising material that could be

interpreted as suitable for some residential applications.

Voluntary labelling provisionsProducts that may display an energy label

(6) The following products may elect to display an energy label:[(a)] ducted products <30 kW rated cooling capacity in product classes 5

and 9;[(b)] three-phase products <30 kW rated cooling capacity in product classes

1 to 4, and 9 and 13 to 15; and(a)[(c)] products covered by subsection (5).

(7) Where an election to display an energy label is made under subsection (6), the label must comply with the requirements of this section.

Temperature bins for energy label calculations

[(7)] All information displayed on the energy label must be based on the domesticresidential temperature bins of clause 6.3 of AS/NZS 3823.4.1 and AS/NZS 3823.4.2. The commercial temperature bins of section 6(14) must not be used for the energy label.

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

39

DRAFT ONLY

Calculating Annual Energy Consumption

[(8)] Subject to subsection (10), For products other than product class 14 that are applying the energy label in accordance with subsections (3) or (7), the Annual Energy Consumption (AEC) figures for the energy label must be calculated as follows:(a) Cooling Annual Energy Consumption (kWh per year): Cooling

Seasonal Energy Consumption (CSEC, or CCSE) as calculated in accordance with clause 6 of AS/NZS 3823.4.1, plus 60 per cent of the annual Inactive Energy Consumption (IAEC, or CIAE) as calculated in accordance with Annex B of AS/NZS 3823.4.1. An AEC figure must be calculated for each climate zone.

(b) Heating Annual Energy Consumption (kWh per year): Heating Seasonal Energy Consumption (HSEC, or CHSE) as calculated in accordance with clause 6 of AS/NZS 3823.4.2, plus 40 per cent of the annual Inactive Energy Consumption (IAEC, or CIAE) as calculated in accordance with Annex B of AS/NZS 3823.4.2. An AEC figure must be calculated for each climate zone.

Note 1: The GEMS registration system will automatically calculate these values.

Calculating Annual Energy Consumption for unitary single duct products

(8)[(9)] Unitary single duct products within product class 15 must calculate Annual Energy Consumption (AEC) figures for each climate zone of the energy label for cooling and heating (if applicable). The AEC is calculated by multiplying the rated power input by the hours of operation set out in subsection (11).Note 1: The GEMS registration system will automatically calculate these values.

[(10)] The hours of operation for calculating the AEC for unitary single duct products within product class 15 are as follows:

Zone Cooling hours Heating hours

Hot 2247 277

Average 840 1291

Cold 545 2660

(9)[(11)] Unitary single duct products that can be rated with an evaporatively-cooled condenser must use the rated power input derived from the standard cooling full capacity test using the evaporatively-cooled condenser in accordance with the additional requirements of Appendix B of AS/NZS 3823.1.5. Products that cannot be rated with an evaporatively-cooled condenser must use the rated power input derived from the standard cooling full capacity test.

40 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Calculating the star rating

(10)[(12)] Subject to subsection (15):(a) the cooling star rating is based on the Total Cooling Seasonal

Performance Factor (TCSPF, or FTCSP) calculated in accordance with Annex B of AS/NZS 3823.4.1; and

(b) the heating star rating is based on the Heating Seasonal Performance Factor (HSPF, or FHSP) calculated in accordance with clause 6.1 of AS/NZS 3823.4.2.

(11)[(13)] The TCSPF and HSPF correspond to a star rating as per the following table:

TCSPF or HSPF value Star rating

TCSPF/HSPF< 2 0

2 ≤ TCSPF/HSPF < 2.5 ½

2.5 ≤ TCSPF/HSPF < 3 1

3 ≤ TCSPF/HSPF < 3.5 1½

3.5 ≤ TCSPF/HSPF < 4 2

4 ≤ TCSPF/HSPF < 4.5 2½

4.5 ≤ TCSPF/HSPF < 5 3

5 ≤ TCSPF/HSPF < 5.5 3½

5.5 ≤ TCSPF/HSPF < 6 4

6 ≤ TCSPF/HSPF < 6.5 4½

6.5 ≤ TCSPF/HSPF < 7 5

7 ≤ TCSPF/HSPF < 7.5 5½

7.5 ≤ TCSPF/HSPF < 8 6

8 ≤ TCSPF/HSPF < 8.5 6½

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

41

DRAFT ONLY

TCSPF or HSPF value Star rating

8.5 ≤ TCSPF/HSPF < 9 7

9 ≤ TCSPF/HSPF < 9.5 7½

9.5 ≤ TCSPF/HSPF < 10 8

10 ≤ TCSPF/HSPF < 10.5 8½

10.5 ≤ TCSPF/HSPF < 11 9

11 ≤ TCSPF/HSPF < 11.5 9½

11.5 ≤ TCSPF/HSPF 10

(12)[(14)] Unitary single duct products within product class 15 must always display a star rating of zero for cooling and heating (if applicable) in all climate zones on the energy label.

Capacity on the energy label

(13)[(15)] Subject to subsections (17) and (18), the following capacity information must be included on the energy label:(a) Rated total cooling capacity from the standard cooling full capacity

test.(b) Rated heating capacity from the standard heating full capacity test for

products with a heat pump feature.(c) Rated heating capacity from the low temperature heating capacity test

for products with a heat pump feature.Note: Regarding paragraph (c), as per Table 1 of AS/NZS 3823.4.2, the rated

heating capacity for the low temperature heating capacity test must be for the heating extended-load operation mode when technically possible. Otherwise, this capacity must be for heating full-load operation.

Note 2: Wall mounted unitary double ducts within product class 13 are included in this clause.

Capacity on the energy label – Unitary single duct products

(14)[(16)] The energy label for a unitary single duct product within product class 15 must include the following capacity information:

42 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

(a) Rated total cooling capacity from the standard cooling full capacity test. For products with a supplementary water tank that comply with the operating time of Appendix B of AS/NZS 3823.1.5, capacity both with and without supplementary water must be given.

(b) Rated heating capacity from the standard heating full capacity test for products with a heat pump feature.

Capacity on the energy label - Portable unitary double duct products

(15)[(17)] The energy label for a portable unitary double duct product within product class 14 must include the following capacity information:(a) Rated total cooling capacity from the standard cooling full capacity

test. For products with a supplementary water tank that complies with the operating time of Section 6 (27), capacity both with and without supplementary water must be given.

(b) Rated heating capacity from the standard heating full capacity test for products with a heat pump feature.

(c) Rated heating capacity from the low temperature heating capacity test for products with a heat pump feature.

Note: Regarding paragraph (c), as per Table 1 of AS/NZS 3823.4.2, the rated heating capacity for the low temperature heating capacity test must be for the heating extended-load operation mode when technically possible. Otherwise, this capacity must be for heating full-load operation.

Communication of noise (sound power)

(16)[(18)] For all product types, the requirements for the communication of noise (sound power) are as follows:

Product type Noise type

Non-ducted split systems indoor and outdoor noise levels

Ducted units (both split and unitary units)

outdoor noise level only

Non-ducted unitary units (e.g. Product Class 1)

indoor and outdoor noise levels

Unitary double duct units indoor noise level only

Unitary single duct units indoor noise level only

Multi-split units outdoor noise level only

Outdoor unit only outdoor noise level only

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

43

DRAFT ONLY

Note: Non-ducted twin (or triple) split systems are required to provide indoor sound power for a single indoor unit only.

Conducting tests – noise (sound power) testing

(17)[(19)] All products covered by this Determination <30 kW rated cooling capacity must have sound power tests according to EN 12102:2013, except for Product Classes 11 and 12.

(18)[(20)] Tests shall be conducted using the installation and operating conditions of the standard cooling full capacity test or the standard heating full capacity test for heating only products.

(19)[(21)] The product shall be considered to comply with the requirements if the maximum sound power level does not exceed more than 2 dB(A) of the declared value.

Format of label

(20)[(22)] The relevant format for the energy label is set out in Schedule 1 to this Determination.

Affixing the label

(21)[(23)] The energy label must be adhered, or attached as a swing tag (either a double-sided swing tag or a single-sided, non-rotating swing tag), on the front of the unit or display front. The label may be attached to the exterior of the packaging.

(22)[(24)] The energy label must be attached to the unit when the unit is removed from its packaging for display purposes. It is not necessary for the label to be physically attached to the product while it is not in display as long as the label is included in the packaging. All labels, including those on swing tags, must be suitably affixed to the product to ensure that they remain in place and visible while on display at the point of sale. If the product is not removed from the packaging but the packaged product forms the display itself, the packaging must display an energy label.

Date of manufacture – all product classes

(23)[(25)] The date of manufacture must be marked permanently on the product and may be non-encrypted, encrypted or able to be determined from a serial number or other markings on the product. It must be visible when the product is in its position of normal use. Information on how to determine the date of manufacture must also be provided.

44 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Advertising material – commercial or residential ratings

(24) Either commercial or residential ratings (or both) as per subsection 6 (14) may be used for sales literature. In such circumstances, the basis for the rating must be stipulated.

Transitional labelling requirements

(25) xxxxx

8 Other GEMS requirements

Product performance – average true power factor (1) For subsection 24 (2) and paragraph 27 (1) (b) of the Act, the specified

product performance requirements for products in all product classes in relation to average true power factor are as follows:(a)[(d)] Air conditioners with a rated power input of less than or equal to

850 W must have:(iii) a measured input that does not exceed 1000 VA; and(iv) a measured average true power factor greater than or equal to

0.5.(b)[(e)] Air conditioners with a rated power input of greater than 850 W and

a rated capacity of less than or equal to 15 kW must have a measured average true power factor greater than or equal to 0.85.

(c)[(f)] Air conditioners with a rated capacity of greater than 15 kW and less than or equal to 20 kW must have a measured average true power factor greater than or equal to:

0.85−( rated capacity (kW )−15100 )

(d)[(g)] Air conditioners with a rated capacity of greater than 20 kW must have a measured average true power factor greater than or equal to 0.80.

(2) The average true power factor must be determined over a period of not less than 5 minutes of operation at rated capacity.

(3) The calculation of the average true power factor value is based on the results of the standard cooling full capacity test, the standard heating full capacity test, or both, as applicable. The values may not be calculated through simulation testing.

Product performance - demand response capability[(4)] For subsection 24 (2) and paragraph 27 (1) (b) of the Act, the specified

product performance requirements for products in all product classes …Where an air conditioner isthat are demand response capable, or potentially demand response capable, as perare the requirements mentioned in sections 2 and 3 of AS/NZS 4755.3.1,

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

45

DRAFT ONLY

(4) the following information must be provided:(a) Whether the model is demand response capable as supplied or

whether it is potentially demand response capable (i.e. with the addition of a separately supplied part or component).

(b) If the model is potentially demand response capable, the identifier of the part or component required to make it demand response capable.

Conducting tests(5) For subsection 24(2) and paragraph 27 (1) (e) of the Act, the specified

requirements for conducting tests in relation to paragraph 27 (1) (b) of the Act, are the requirements mentioned in section 5 of AS/NZS 4755.3.1.

9 Families of modelsFor section 28 of the Act, two or more models of a product class covered by this Determination are in the same family of models if those models:(a) are marketed in the same category or class of product; and(b) have the same energy performance characteristics of

(i) electrical phase;(ii) true power factor;(iii) rated power inputs; (iv)rated capacities; and

[(c)] have identical same physical characteristics that are relevant to complying with sections 6 and 7 of this Determination; and

(c)[(d)] are included on a single test report which was prepared prior to the application for registration for the model being made under section 41 of the Act.

Note 1: Regarding paragraph (b), the relevant performance characteristics are electrical phase, true power factor, rated power inputs and rated capacities.

10 Product categoryFor section 29 of the Act, the products covered by this Determination are category A products.

11 Registrations affected by this DeterminationFor section 36 of the Act, this Determination does not affect the registration of any model registered against the Greenhouse and Energy Minimum Standards (Air Conditioner and Heat Pump) Determination 2012.

Note: If a model’s registration is not affected the model is taken to be registered against this Determination. See section 36 of the Act.

46 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Schedule 1 Format of label

1. Colour and text details for the energy label (1) The example labels in Item 2 of the Schedule show the parts of the label

referred to within these instructions. (2) The example labels in Item 3 of this Schedule show the colour and text

requirements for the energy label. (3) The label must be printed on a white background using the following colours:

a. for red—Pantone Warm red;b. for yellow—Pantone 116; andc. for black—Pantone Black.

(4) The entire label, excluding the star ratings, must be in only one font, which can be any one of the following:

a. Gill Sans (preferred);b. Humanist 521; orc. Hammersmith.

(5) The star ratings must be in the font Meta OT. (6) For each relevant heating and cooling function, a star rating must be shown in

numerals in a star, positioned as detailed below. There must be a set of such ratings for each geographical region. Further details on the rating star and star band are provided in Items 5 and 6. A product that does not provide either a cooling or heating service must not place a rating star on the star band for that service. See Item 8 labels (i) and (ii) for examples.

a. The cooling function star rating must be shown in a blue star within a square box with black outline; this is the ‘rating star’. A rating of 0 must be shown in a grey star. A rating of 0.5 must be shown in a star whose left half is blue and right half grey.

b. The heating function rating star must be shown as a red star within a square box with black outline. A rating of 0 must be shown in a grey star. A rating of 0.5 must be shown in a star whose left half is red and right half grey.

c. The rating star must be vertically centred on the centre of the relevant star in the star band. For example, if the rating is ‘4 stars’ then the rating star aligns with the fourth star in the band; this obscures the fourth star, and some of the third. Rating stars from 0 to 1 are placed in the same location; the centre of the rating star must sit on the centre of the first star in the star band. For a rating involving a half star, the rating star must bisect the gap between the stars that bracket the value.

d. The coloured band for the star rating must extend to the edge of the rating star box.

(7) The brand and model of the product must: a. be inserted where indicated by ‘a’ in Item 2 base label (i);b. be complete and concise;

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

47

DRAFT ONLY

c. not exceed a width of 58 mm;d. not exceed a height of 17 mm (or 4 lines of text); ande. be left aligned in the area allowed.

(8) The product’s capacity must be shown for the relevant heating and cooling functions. Products in any of the below categories that are cooling only or heating only must contain only the relevant cooling or heating declaration as per example Item 8 base label (i) and Item 8 base label (ii). Paragraphs (c) and (d), should be interpreted consistently with subsection 6(27), while paragraphs (e) and (f) use the same conventions as in Table B1 of AS/NZS 3823.1.5.

a. Examples of how capacity should be displayed for non-ducted air-cooled air conditioners and non-ducted air-to-air heat pumps covered by product classes 1–4, 9 and 10 (excluding multi-splits) are shown in the Items below. A label for such a device should:

i. show rated standard cooling full capacity for an outdoor temperature of 35°C as indicated by ‘b’ in Item 2 base label (i); and

ii. show rated standard heating full capacity for an outdoor temperature of 7°C and rated low temperature heating capacity at 2°C as indicated by ‘c’ in Item 2 base label (i).

b. Examples of how capacity should be displayed for ducted air-cooled air conditioners and ducted air-to-air heat pumps covered by product classes 5, 9 and 10 (excluding multi-splits) are shown in the Items below. A label for such a device should:

i. show rated standard cooling full capacity for an outdoor temperature of 35°C as indicated by ‘b’ in Item 2 base label (i) in Item 2; and

ii. show rated standard heating full capacity for an outdoor temperature of 7°C and rated low temperature heating capacity at 2°C as indicated by ‘c’ in Item 2 base label (i).

c. Examples of how capacity should be displayed for unitary double duct air-cooled air conditioners and unitary double duct air-to-air heat pumps covered by product class 13 and those covered by product class 14 that either contain an evaporatively cooled condenser as defined and tested by subsections 6 (25), 6 (26) and 6 (27) that only operates with the evaporatively cooled condenser, or do not contain an evaporatively cooled condenser are shown in the Items below. A label for such a device should:

i. show rated standard cooling full capacity for an outdoor temperature of 35°C as indicated by ‘b’ in Item 2 base label (i) in Item 2; and

ii. show rated standard heating full capacity for an outdoor temperature of 7°C and rated low temperature heating capacity at 2°C as indicated by ‘c’ in base label (i) in Item 2.

48 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

d. Examples of how capacity should be displayed for unitary double duct air-cooled air conditioners and unitary double duct air-to-air heat pumps covered by product class 14 with an evaporatively cooled condenser as defined and tested by subsections 6 (45), 6 (46) and 6 (47) that can operate without the evaporatively cooled condenser operating are shown in the Items below. A label for such a device should:

i. show rated standard cooling full capacity both with and without the evaporative condenser operating, as indicated by ‘b’ in Item 2 base label (ii); and

ii. show rated standard heating full capacity for an outdoor temperature of 7°C and rated low temperature heating capacity at 2°C as indicated by ‘c’ in Item 2 base label (i).

e. Examples of how capacity should be displayed for unitary single duct air-cooled air conditioners and unitary single duct air-to-air heat pumps as covered by product class 15 that either do not contain an evaporatively cooled condenser or contain an evaporatively cooled condenser as defined and tested by Appendix B of AS/NZS 3823.1.5 that can only operate with the evaporatively cooled condenser operating are shown in the Items below. A label for such a device should:

i. show rated standard cooling full capacity as indicated by ‘b’ in Item 2 base label (iii); and

ii. show rated standard heating full capacity as indicated by ‘c’ in Item 2 base label (iii).

f. Examples of how capacity should be displayed for unitary single duct air-cooled air conditioners and unitary single duct air-to-air heat pumps as covered by product class 15 with an evaporatively cooled condenser as defined and tested by Appendix B of AS/NZS 3823.1.5 that can operate without the evaporatively cooled condenser are shown in the Items below. A label for such a device should:

i. show rated standard cooling full capacity both with and without the evaporative condenser operating, as indicated by ‘b’ in Item 2 base label (iv); and

ii. show rated standard heating full capacity as indicated by ‘c’ in Item 2 base label (iii).

(9) The product’s annual energy consumption for heating and cooling as per subsections 8 to 11 must be shown for each of the three geographical regions, as indicated by ‘d’ in Item 2 base label (i).

(10)The noise level in decibels as per subsections 13 to 16 must be shown where indicated ‘f ’ in Item 2 base label (i). Details on the correct symbols are given in Item 7.

a. For a non-ducted product covered under paragraph 8(a) above, the indoor decibel rating must be shown inside the house symbol and the outdoor decibel rating must be shown outside the house symbol, as per Item 2 base label (i) and Item 7 diagram (ii).

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

49

DRAFT ONLY

b. For a ducted product covered under paragraph 8(b) above, only the outdoor decibel rating must be shown outside the house symbol together with the fixed ducted air conditioner symbol, as per Item 7 diagram (ii).

c. For a unitary double duct product covered under paragraphs 8(c) or 8(d) above, only the indoor decibel rating must be shown together with the double duct symbol, as per base label (ii) in Item 2 and diagram (iii) in Item 7.

d. For a unitary single duct product covered under paragraphs 8(e) or 8(f) above, only the indoor decibel rating must be shown together with the single duct symbol, as per base labels (iii) and (iv) in Item 2 and diagram (iv) in Item 7.

(11)Every label must contain the map of Australia and New Zealand with three climate zones as indicated by ‘g’ in base label (i) in Item 2. The national, state and territory capital cities must be marked on the map.

50 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

2. Parts of the energy label—diagram

The following base label diagrams label the parts of the energy label, and give examples of possible labels.

Base label (i) shows the general parts of air conditioner energy labels. Subsequent labels, (ii)–(iv), show variations that are required for unitary single and double duct units.

Base label (i)

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

51

DRAFT ONLY

Base label (ii)

Base label (iii)

52 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Base label (iv)

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

53

DRAFT ONLY

3. Text requirements for the energy label—diagram

The following base label diagrams show the text requirements for the energy label. All type weights regular unless otherwise specified.

Base label (i) shows the main text requirements for all air conditioner energy labels. Subsequent labels, (ii)–(iv), show variations that are required for unitary single and double duct units.

Base label (i)

54 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Base label (ii)

Base label (iii)

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

55

DRAFT ONLY

Base label (iv)

56 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

4. Object requirements for the energy label—diagram

The following diagram shows the object requirements for the energy label.

Base label (i) shows the main object requirements for all air conditioner energy labels.

Base label (i)

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

57

DRAFT ONLY

5. Physical layout requirements for the label

The following diagrams show the object requirements for the energy label.

Base label (i) shows the main dimensions for all air conditioner energy labels. Subsequent labels, (ii)–(iv), show variations that are required for unitary single and double duct units.

Base label (i)

58 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

Base label (ii)

Base label (iii)

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

59

DRAFT ONLY

Base label (iv)

60 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

6. Star band requirements for the energy label

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

61

DRAFT ONLY

7. Decibel rating requirements for the energy label

The following figures show the appropriate decibel rating icons for different types of air conditioners, and their dimensions.

Diagram (i)

Diagram (ii)

Diagram (iii)

Diagram (iv)

Diagram (v)

62 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY

DRAFT ONLY

8. Example air conditioner labels

The following figures show other variations of the label types, including heating and cooling only layouts and the full label to be used for ducted air conditioner units.

Base label (i)

Base label (ii)

Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

63

DRAFT ONLY

Base label (iii)

Note1. All legislative instruments and compilations are registered on the Federal Register of

Legislative Instruments kept under the Legislation Act 2003. See https://www. legislation.gov.au.

64 Greenhouse and Energy Minimum Standards (Air Conditioners and HeatPumps) Determination 201x

DRAFT ONLY