googol qta5400 g1 2000kw 2500kva

10

Click here to load reader

Upload: mark-wang

Post on 14-Apr-2017

288 views

Category:

Engineering


3 download

TRANSCRIPT

Page 1: Googol qta5400 g1 2000kw 2500kva

Datasheet of Honny Googol 2000kW/2500kVA Diesel Generator (Water Cooled)

Guangdong Honny Power tech Co.,ltd Engine Model

QTA5400G1

Engine Application:

Generator set& Pump

Drive

No.2 North Road,Songshan Lake Industrial Park,Donguan, China Tel:

86-769-22780359, Fax: 86-769-22780357Engine control Parts list

CPL:5400-4000

Chief Engineer:

Jin ling. Ni

Engine data sheet( No. of Data Sheet )

DS 20140401-QTA5400G1Publication Date:

01-04-2014

Generator Model HGM2750

Genset Prime Power 2000kW/2500kVA

Engine Ratings:

Engine Speed (RPM) 1500

Generator set Frequency (Hz) 50

Engine Standby Power (LTP) (kW) 2280Engine Prime Power (PRP) (kW) 2073

Engine Continuous Power (COP) (kW) 1700Single Fan Power (kW) 22

Single Fan Consumption (kW) 20

Quantity of Fan (Sets) 4

All Fan Consumption (kW) 80

Engine Net Standby Output (LTP) (kW) 2280

Page 2: Googol qta5400 g1 2000kw 2500kva

Engine Net Prime Output (PRP) (kW) 2073Engine Net Continuous Output (COP) (kW) 1700

BMEP for Standby Output (bar) 20.71BMEP for Prime Output (bar) 18.83

BMEP for Continuous Output (bar) 15.44Typical Generation Standby Output (kVA) 2750Typical Generation Standby Output (kW) 2200Typical Generation Prime Output (kVA) 2500Typical Generation Prime Output (kW) 2000

Typical Generation Continuous Output (kVA) 2050Typical Generation Continuous Output (kW) 1640

Typical Alternator Efficiency ≥ 96.5%Power Factor 0.8

Speed droop (static) elect. Gov. 0-5%

Governing standards to ISO 8528 Parts 1 and 5 G3

Max. step load acceptance, 1st step(% PrimeOutput)

43%

Basic Performance Datasheet

Aspiration Type Turbocharger, air-water After- cooler

Turbocharger Type 2*R151

Injection Type Direct Injection

Configuration Vee

No. of Cylinders 20

Displacement (liters) 88.5

Page 3: Googol qta5400 g1 2000kw 2500kva

Bore (mm) 170

Stroke (mm) 195

Compression Ratio 13.5:1

Piston Speed (m/s) 9.75

Rotation Direction (from flywheel) Counter Clockwise

Number of Flywheel Teeth 218

Flywheel House Size SAE00-21

Lubrication System

Lube Oil Specification AFI-CF4

Oil Capacity ( Liters) 300

Max. Permissible Oil Temperature (°C) 110

Low Oil Pressure Warning (kPa) 300

Low Oil Pressure Shutdown (kPa) 200

Oil consumption (as % of fuel consumption) ≤0.5

Cooling System

Coolant Capacity for Engine ( Liters) 200

Max. Permissible Temperature (°C) 82

Max. Coolant Warning Temperature (°C) 85

Max. Coolant Shutdown Temperature (°C) 90

Thermostat Open Temperature (°C) 71

Radiator Cooling Flow (m³/min) 3400

Flow of Coolant pump (m³/h) 80+75

Heat dissipation (engine radiator) (kW) 751

Page 4: Googol qta5400 g1 2000kw 2500kva

Heat dissipation (CAC) (kW) 369Heat dissipation (convection) (kW) 128

Radiator Model QSCN7000

Fuel System

Governor Type Electrical Control

Engine Output at generator set prime output (kW) 2073Fuel Consumption at 25% of generator set prime

output(l/h) 147.93

Fuel Consumption at 50% of generator set prime

output(l/h) 245.85

Fuel Consumption at 75% of generator set prime

output(l/h) 318.85

Fuel Consumption at 100% of generator set prime

output(l/h) 476.98

Lowest Fuel Consumption Ratio g/kW.hr 191.75

Intake & Exhaust System(On Standby Output)

Combustion Air Consumption (m³/min) 229.85

Max. Intake Restriction (Kpa) 2

Max. Exhaust Temperature(Before Turbo) (°C) 630

Max. Exhaust Temperature(After Turbo) (°C) 510

Max. Exhaust Back Pressure (Kpa) 2

Exhaust Gas Flow (m³/min) 581.67

Exhaust Flange Diameter (mm) 2*250

Page 5: Googol qta5400 g1 2000kw 2500kva

Electrical System

Charging Alternator Voltage (V) 28

Charging Alternator Capacity (A) 55

Starting Voltage (V) 24

Starting Motor Capacity (kW) 2*13

Minimum Battery Capacity (Ah) 4*200

Minimum Temperature for Unaided Cold Start (℃) 10

Engine Dimension

Length (mm) 4110

Width (mm) 1459

Height (mm) 1820

Engine Dry Weight w/o Cooling System (kg) 7600

Note:

1,All engine parameters are in accordance with ISO3046, ISO8528

2,All engine parameters are based on 25°C / 100kPa environment condition

3,No power decrease with below 40ºC environment temperature and 1500 meter altitude

4,More than 40ºCand 1500m above sea level , decrease 2% per 10ºC , and 4% per 300m

5,At calorific value 42700 kJ/kg + 5%, density 0,835 kg/dm3 , temperature 280 K

6,Above data is only the testing data in our laboratory, it can't used to be the data on all contract

Page 6: Googol qta5400 g1 2000kw 2500kva

Alternator

Alternator model MXL-2000-4 Marathon

Rating Voltage(V) 400/230V,380/220V adjustable

Rating Capacity(KW/KVA) 2000/2500

Eff.% 96.8%

Power Factor 0.8

Exciting type Brushless self-exciter AVR

Voltage regulation ±1%

No. of Phase 3 phase 4 wire

Enclosure Class IP22

Class of Insulation H

Page 7: Googol qta5400 g1 2000kw 2500kva

CONTROL MODULE MAIN FEATURES. ( UK DSE)KEY FEATURES• Comprehensive synchronising & loadsharing capabilities• Built-in governor and AVR control• Base load (kW export) functionality• Mains (utility) de-coupling protection• Generator power (kW, kV Ar, kV A & pf) monitoring• Overload (kW & kV Ar) protection• Reverse power (kW & kV Ar) protection• Unbalanced load protection• Independent earth fault protection

Standard Accessory

Battery 4X200AH 12V

Battery Wires 1 set

Flexible Pipe 10*2 inch

Industry Silencer 10*2 inch

Optional Accessory5

VCB Breaker Panel

Fuel Tank 2000 Liter

Fuel-water Separator

Heater Coolant & Oil Heater

Page 8: Googol qta5400 g1 2000kw 2500kva

• Advanced integral PLC editor• 11 Configurable inputs• 8 Configurable outputs• Configurable flexible sensor inputs• DSENet® expansion compatibility• User configurable RS232, RS485 and Ethernet communications• Remote SCADA monitoring via various DSE software applications• MODBUS RTU & TCP support• User configurable MODBUS pages• Advanced SMS control and fault messaging (additional GSM modem required)• Easy access diagnostic pages including modem diagnostic pages• Data logging and trending• CAN, MPU and Frequency speed sensing• Tier 4 CAN engine support• “Protections disabled” feature• Front panel editing with PIN protection• Fully configurable using DSE Configuration Suite PC software via USB• 4 Line back-lit LCD text display• LED and LCD alarm indication• Configurable display languages• USB connectivity• Customisable status screens• Five key menu navigation• 3 Configurable maintenance alarms• Multiple date and time run scheduler• Manual fuel pump control

Page 9: Googol qta5400 g1 2000kw 2500kva

• Fuel usage monitor and low fuel level protection• Charge alternator failure protection• Load switching (load shedding and dummy load control)• Configurable event log (250)• Backed up real time clock

OPTIONAL FEATURE

CHP or CCHP- Complete CHP or CCHP System

FUEL SYSTEM- Fuel Water Separator- Fuel Level Alarming- Auto Fuel Pump SupplyingSystem

HEATER- Coolant Heater- Lube Oil Heater- Alternator Space Heater

SWITCHGEAR- MCCB, VCB Breaker Panel- ATS Panel- Parallel Panel- LV & HV Switchgear

EXHAUST SYSTEM- Exhaust Silencer-Residential- Flexible Pipe- Installation Kits

BATTERY & CHARGER- Starting Battery- 24V /12VDC, 3A, 220V AC Input- 24V /12VDC, 5A, 220V AC Input

VOLTAGE SELECTION- Low Voltage- Middle Voltage- High Voltage

CONTROL SYSTEM- AMF Controller- Sync & Load Sharing Controller

CANOPY- Silent Canopy- Weather proof Canopy.

Page 10: Googol qta5400 g1 2000kw 2500kva

- Sync to Grid Controller- Communication Interface &software

- Moving Trailer- Weather and sound proofcontainer.

More View at : http//:honny1992.en.alibaba.com/

http://honnypower.gmc.globalmarket.com/

http://honnydg.en.made-in-china.com/