GOLD & COMPACT
Overview
Energy-efficient, compact and flexible air handling units
2
Air handling units with unbeatable advantages
Economical control functionsA large number of functions, including communication, are integrated into the control system and are ready to be activated via a hand-held micro terminal. Several of the functions provide unique opportunities for saving energy.
Fast installation and Plug-and-playThe work of installing the air handling units can be done quickly and easily and for the accessories, such as cooling units and air heaters, there are ready-to-use control functions and all connec-tions are made using cables with quick-fit connectors. Plug-and-play!
Saves spaceSwegon’s air handling units have compact dimensions and what’s more sharp duct bends can be connected directly to the air handling unit without pressure losses. This saves you space in the fan room.
Optimum operating economyEnergy-saving fans, efficient heat recovery and full control of temperatures, airflows and operating times provide optimum operating economy.
Contents
ALLMÄNT GOLD & COMPACT 2
Technical Description 5Complements and accessories 6Overview – Airflows 8Sizing - GOLD RX 9Sizing - GOLD PX 13Sizing - GOLD CX 14Sizing - GOLD SD 16Sizing - GOLD LP 18
Technical Description 19Complements and accessories 20Overview – Airflows 21
Sizing - COMPACT Unit 22Sizing - COMPACT Top 22Sizing - COMPACT Air 23Sizing - COMPACT Heat 23
3
Revolutionary control system in the new GOLD version E
Groundbreaking stepWith the new GOLD version E, Swegon takes a groundbreaking step in the further development of the air handling unit, which for some time has been seen as standard in the industry.
Revolutionary control systemThe most striking new feature is the revolutionary control sys-tem, IQlogic. In addition to several smart and user friendly func-tions, significantly greater options are provided for communica-tion and remote control through main control systems, laptops, tablets or mobile phones. Communication between a handheld terminal and the GOLD unit can occur wirelessly via WLAN. It is just as easy to use a computer, tablet or mobile phone via Wi-Fi.
User friendly multi-touch screenThe new handheld terminal, IQnavigator, features a multi-touch screen and is very simple and easy-to-use. Commissioning and settings are performed with an intuitive user interface, and informative help texts.
Set and read values for component parts in GOLD are presented in a flow chart on the screen. On a specific log page it is possible to select one or more parameters to be read in a diagram with a timeline and a size axis. The parameters can be read in real time or as logged values.
GOLD LP and COMPACTFor GOLD LP and COMPACT the control system is designed for small air handling units.
The user interface is available in a large number of languages, selected on the handheld terminal.
4
Exceptional energy efficiencyEnergy-efficient fans of international calibre! Swegon’s fans are of the new generation of energy-efficient fans. The motors are of EC type and have been developed on a new platform that offers the best energy efficiency on the market. Swegon’s EC motors can achieve a peak efficiency of more than 90%. This is more than 10 percentage units better than traditional AC motors with frequency inverters and the difference becomes greater the more the speed of rotation is regulated to decelerate.
Every improvement in motor efficiency can be directly translated into a reduction in operating costs.
Several new fan sizes have been added for GOLD, which gives greater freedom to choose exactly the right unit size and fan variant to suit the needs of the installation.
Optimized heat recovery and cooling energy recoverySwegon’s rotary heat exchangers (GOLD RX/LP and COMPACT) offer unbeatable temperature efficiency, up to 85%. The rotary heat exchanger recovers cooling energy just as efficiently and version RE-COsorptic also recovers moisture. This reduces the costs for cooling equipment.
However, in some applications, the airflow paths must be completely separate from one another. Such applications call for the use of a cross-flow plate heat exchanger (GOLD PX) or coil heat exchang-ers (GOLD CX/SD) as alternatives. Both have an effective freeze protection function that measures both the temperature and the humidity, which provides high efficiency.
GOLD PX can be chosen with RECOfrost, a newly developed anti-frost system that takes energy efficiency for this type of heat exchanger to a completely new level.
Plug-and-play saves time and moneyFast installation, limited space requirement and Plug-and-play type accessories connection mean low installation costs. Here are a few examples:
• The air handling units are complete with direct-driven supply air and extract air fans, supply air and extract air filters, heat exchanger and built-in control equipment.
• The air handling units have short installation length and are easy to handle at the building site. If needed, they can be simply split into sections for transport within the site. The cables between the sections have quick-fit connectors.
• The air handling units take up little space and the fans are designed to manage sharp duct bends arranged directly from the unit without pressure losses. Several of the air handling units can also be ordered with top-mounted duct connection spigots.
• Quick-fit connectors are used for connecting the hand-held micro terminal, supply air temperature sensor, air heater and communi-cation. Other accessories and external functions are connected to an easily accessible row of wiring terminals.
Example of a space-saving and compact installation of GOLD with cooling unit
Energy-efficient Fans
Rotary heat exchanger
Cross-flow plate heat exchanger
5
The GOLD RX/PX/CX/LP one-piece units are complete air handling units with direct-driven supply air and extract air fans, supply air and extract air filters and heat exchanger. The heat exchanger is either a rotary heat exchanger (RX/LP), plate heat exchanger (PX) or coil heat exchang-ers (CX).
The GOLD SD single-direction units are supply air/extract air handling units with one direct-driven supply air or extract air fan. Optional filters are available for all sizes. Coil heat exchangers and unmounted pipework packages can be selected for the size 12-120 units.
The casing is composed of cover panels and inspection doors. The exte-rior colour of the GOLD RX/PX/CX/SD is beige (NCS S2005-Y30R) and that of the GOLD LP is white (NCS S0502-G).
The GOLD has built-in control equipment that can be operated from the hand-held micro terminal with plain-text touch screen display or via com-munication. The electrical and control system is completely integrated into the air handling unit. The microprocessor-based equipment controls and regulates temperatures, airflows and other functions. A large number of functions are built into the system and are simple to activate.
If additional functional sections such as dampers and air coolers are required, they can be installed in the ductwork (uninsulated duct acces-sories) or can be docked directly to the air handling unit (insulated duct accessories).
ApplicationThe GOLD units are designed for use in comfort ventilation applica-tions. Depending on the variant selected, GOLD units can be utilised in buildings such as office buildings, schools, day nurseries, public buildings, shops, residential buildings, etc.
GOLD units equipped with plate/coil heat exchanger (PX/CX) and separate supply air and extract air handling units (SD) can also be used for the ventilation of moderately humid buildings; however not where the humidity is continuously high, such as in indoor water parks.
The separate GOLD supply air and extract air handling units (SD) are de-signed for applications in which the supply air and extract air flows need to be completely separated from one another or where, due to limited available space, separate units for supply air and/or extract air are needed.
The GOLD RX/PX/CX/SD units can be installed outdoors and then must be equipped with the following accessories: roof, air intake section and exhaust air hood. The GOLD is designed and tested for temperatures, in the surroundings and the air stream, from -40°C to +40°C.
CertificationSwegon AB has a certified Quality Assurance System that conforms to ISO 9001 Standard and a certified Environmental Management System to ISO 14001. The GOLD air handling system is also certificated by Eurovent. 12 sizes of GOLD RX for air flows up to 2.5 m3/s (9,000 m3/h) have also received Passive House certification.
General Points - GOLD
www.eurovent-certification.com www.certiflash.com
N° 06.06.319. Range: GOLD
Technical Description
GOLD CX
GOLD SD
GOLD RX
GOLD PX
GOLD LP
6
Outdoor air hood
Exhaust air hood
Dual-purpose hood
• Outdoor air hood, sizes 04-40.
• Exhaust air hood, sizes 04-40.
• Dual-purpose hood, sizes 04-08.
• Exterior wall hood, sizes 04-08.
Hoods, GOLD
Exterior wall hood
The GOLD RX/PX/CX/SD units can be installed outdoors with the following accessories: roof, air intake section and exhaust air hood.
The roof is supplied in kit form, complete with the necessary assembly parts and sealing strips. Visible parts are made of sheet steel, painted in a beige colour tone, NCS S2005-Y30R.
Roofs cannot be used on air handling units with top air con-nection spigots.
Outdoor installation, GOLD
GOLD air handling units with roof and insulated duct accessories
Duct accessories, GOLDDuct accessories are available for a complete installation, such asdampers, air heaters for pre- and post- heating, air coolers, prefilters and sound attenuators.
As alternatives, most of the duct acces-sories are provided for connection with full cross sectional area, i.e. Full face. This reduces pressure losses, which saves electric power supplied to the fans. The accessories for Full face are integrated into an insulated casing, which reduces the installation costs and facilitates installation outdoors.
Examples of insulated duct accessories
Examples of uninsulated duct accessories and Full face connection
Complements and accessories
7
Cooling unit COOL DX/COOL DX Top The COOL DX/COOL DX Top are internally fully wired, charged with refrigerant and the unit is trial run.
The cooling unit can be docked to the GOLD or it can be installed as a stand-alone unit. Only one electric power sup-ply and one communication cable (with quick-fit connector) between the COOL DX/COOL DX Top and the GOLD are required. All control is performed via GOLD.
CELEST+ in version LE/HP is a highly efficient chiller for small installations and is available in six sizes up to 30 kW cooling capacity. It is possible to connect several chillers to the same GOLD unit and in doing so dimension the capacity from 9 kW and above. The speed regulated compressors are controlled exactly according to the cooling requirement via SMART Link DX.
DX cooling units
Best energy classSwegon has a complete program of chillers and heat pumps for the production of cold or hot water.
The units are energy efficient and conform to the best energy class. They are certified by Eurovent.
They are available in several different ver-sions and in various sizes and are designed for in- or outdoor installation.
Chillers and heat pumps
Air/Water chillers
Air/Water multifunctional unitsWater/Water chillers and heat pumps
Air/Water heat pumps
Cooling units for minor applications
Complements and accessories
COOL DX
COOL DX Top
GOLD RX Top
GOLD
8
Length
Width
Height(including junction hood and base beams)
Overview – Airflows, GOLDAll the sizing data specified in this brochure are meant for use as an overview. Exact sizing can be carried out in the web-based ProUnit air handling unit selection software.
Contact your nearest Swegon representative for data calculations or use the program yourself at www.swegon.com.
Outdoor air Supply air Extract air Exhaust air
Arrows for airflows in this brochure
Dimensions specified in this brochure
All the air handling units as from size 11 can be divided into sections for transport within the building site.
The length of the longest section is given in the dimension tables.
Division at the building site
Supplied with or without end wall panelThe air handling unit can be ordered without end connec-tion panel for the required direction of airflow and with insulated duct ac-cessories that are designed for Full face connection.
Without end wall panel
With end wall panel
1)Applies for airflow regulation. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). 2) Whenever applicable, the value specified for capacity variant 1 applies.3) Full face
Sizing
GOLDRX
Min. 1) SFPv ≤ 2.0 at 200 Pa 2) Max. Max. Ecodesign 2) 3)
m3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h04 0.08 290 0.42 1510 0.45 1620 0.45 162005 0.08 290 0.42 1510 0.65 2340 0.65 234007 0.08 290 0.69 2480 0.75 2700 0.75 270008 0.20 720 0.77 2770 1.00 3600 1.00 360011 0.20 720 1.00 3600 1.10 3960 1.10 396012 0.20 720 1.14 4100 1.40 5040 1.40 504014 0.20 720 1.65 5940 1.65 5940 1.65 594020 0.30 1080 1.80 6480 2.10 7560 2.10 756025 0.30 1080 2.25 8100 2.50 9000 2.50 900030 0.50 1800 2.35 8460 3.20 11520 2.81 1012035 0.50 1800 3.50 12600 3.90 14040 3.90 1404040 0.75 2700 3.80 13680 5.00 18000 3.90 1404050 0.60 2160 4.75 17100 5.00 18000 5.00 1800060 1.00 3600 5.00 18000 6.50 23400 6.00 2160070 1.00 3600 6.60 23760 7.50 27000 7.50 2700080 1.50 5400 6.85 24660 9.50 34200 8.31 29920
100 1.50 5400 10.00 36000 11.00 39600 11.00 39600120 2.50 9000 10.30 37080 14.00 50400 13.04 46940
GOLDPX
Min. 1) SFPv ≤ 2.0 at 200 Pa 2) Max. Max. Ecodesign 2) 3)
m3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h04 0.08 290 0.45 1620 0.45 1620 0.45 162005 0.08 290 0.47 1690 0.65 2340 0.53 191007 0.08 290 0.71 2560 0.75 2700 0.75 270008 0.20 720 0.79 2840 1.00 3600 0.83 293011 0.20 720 1.01 3640 1.10 3960 1.05 378012 0.20 720 1.14 4100 1.40 5040 1.20 432014 0.20 720 1.65 5940 1.65 5940 1.65 594020 0.30 1080 2.00 7200 2.10 7560 1.85 666025 0.30 1080 2.45 8820 2.50 9000 2.40 864030 0.50 1800 2.55 9180 3.20 11520 2.32 11520
GOLDCX
Min. 1) SFPv ≤ 2.0 at 200 Pa 2) Max. Max. Ecodesign 2) 3)
m3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h35 0.50 1800 3.78 13610 3.90 14040 3.88 1397040 0.75 2700 3.90 14040 3.90 14040 3.90 1404050 1.00 3600 5.00 18000 5.00 18000 5.00 1800060 1.00 3600 5.95 21420 6.50 23400 6.02 2167070 1.50 5400 7.30 26280 7.50 27000 7.48 2693080 1.50 5400 8.00 28800 9.50 34200 7.86 28300100 1.50 5400 11.00 39600 11.00 39600 11.00 39600120 2.50 9000 11.70 42120 14.00 50400 12.68 45650
GOLDSD
Min. 1) SFPv ≤ 1.0 at 200 Pa 2) Max. Max. Ecodesign 2) 3)
m3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/hFan+Filter
04 0.08 290 0.60 2160 0.60 2160 0.60 216005 0.08 290 0.80 2880 0.80 2880 0.66 2380
07 0.08 290 0.80 2880 0.80 2880 0.80 288008 0.20 720 1.19 4280 1.20 4320 1.07 3850
Fan+Filter+Coil h. exch. SFPv ≤ 2.0 at 200 Pa 2)
11 0.20 720 1.05 3780 1.20 4320 1.20 432012 0.20 720 1.20 4320 1.80 6480 1.41 508014 0.20 720 1.65 5940 1.80 6480 1.80 648020 0.30 1080 2.10 7560 2.80 10080 2.25 810025 0.30 1080 2.50 9000 2.80 10080 2.80 1008030 0.50 1800 3.19 11480 4.00 14400 3.47 1249035 0.50 1800 3.90 14040 4.00 14400 4.00 1440040 0.75 2700 4.00 14400 5.00 18000 4.92 1771050 0.60 2160 5.00 18000 5.60 20160 5.60 2016060 1.00 3600 6.50 23400 8.00 28800 6.99 2516070 1.00 3600 7.30 26280 8.00 28800 7.79 2804080 1.50 5400 8.00 28800 12.00 43200 7.86 28300
100 1.50 5400 11.00 39600 12.00 43200 11.48 41330120 2.50 9000 11.70 42120 18.00 64800 12.69 45680
GOLDLP
Min. 1) SFPv ≤ 2.0 at 200 Pa Max. Max. Ecodesignm3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h
05 0.08 290 0.41 1470 0.53 1900 0.50 180008 0.08 290 0.62 2230 0.74 2600 0.74 2600
9
GOLD RX sizes 04/05, 07/08
Right-hand version
Left-hand version
Duct connection options A: Specify left-hand or right-hand version when placing orders. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site via the handheld terminal.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: The air handling unit can be installed upended.
Bottom beam/Base frame/BaseIf the air handling unit is installed horizontally, it must be mounted on a bottom beam (option), stand (accessory) or some other form of base support, so that its inspection doors can be opened.
GOLDRXsize
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
04 1500 825 1011 214-243 Ø 315 0.08 0.42 0.45 0.45 1x230V, 10A or3x400V, 10A
05 1500 825 1011 214-243 Ø 315 0.08 0.42 0.65 0.65 1x230V, 101)/162)A or3x400V, 10A
07 1600 995 1176 262-301 Ø 400 0.08 0.69 0.75 0.75 x230V, 101)/162)A or3x400V, 10A
08 1600 995 1176 270-309 Ø 400 0.20 0.77 1.00 1.00 1x230V, 16A1) or3x400V, 10A1)2)
GOLD RX Top, sizes 04/05, 07/08
GOLDRX Top
size
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
04 1500 825 1011 247 Ø 315 0.08 0.38 0.45 0.45 1x230V, 10A or3x400V, 10A
05 1500 825 1011 247 Ø 315 0.08 0.38 0.65 0.57 1x230V, 10A or3x400V, 10A
07 1600 995 1176 306 Ø 400 0.08 0.65 0.75 0.75 1x230V, 10A or3x400V, 10A
08 1600 995 1176 310 Ø 400 0.20 0.711) 1.00 0.92 1x230V, 16A or3x400V, 10A
1) 0.71 m3/s refers to air handling units in the right-hand version. For air handling units in the left-hand version, the value is 0.77 m3/s.
Right-hand versionLeft-hand version
1) Capacity variant 1. 2) Capacity variant 2.
Duct connection options A: The GOLD is supplied in a right-hand version. The unit can be changed to the left-hand version at the building site via the handheld terminal.
Bottom beam/Base frame/BaseIf the air handling unit is installed horizontally, it must be mounted on a bottom beam (option), stand (accessory) or some other form of base support, so that its inspection doors can be opened.
Sizing
10
GOLD RX, sizes 11/12Duct connection optionsA: Specify left-hand or right-hand version when placing orders. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site via the handheld terminal.
B: Specify with or without end wall panel for each airflow direc-tion when placing orders.
C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Right-hand version
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 1 Fan arrangement 2
GOLDRXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
11 1860 655 1199 1486 444-496 Ø 500 0.20 1.00 1.10 1.10 1x230V, 16A1) or3x400V, 10A1)2)
12 1860 655 1199 1486 466-518 Ø 500 0.20 1.14 1.40 1.40 3x400V, 10A
GOLD RX Top, sizes 11/12Duct connection optionsA: The GOLD is supplied in a right-hand version. The unit can be changed to the left-hand version at the building site via the handheld terminal.
Right-hand versionLeft-hand version
GOLDRX Top
size
Lengthmm
The longest sec-tion when sectio-
nalizingmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
11 1860 655 1199 1486 488 Ø 500 0.20 0.94 1.10 1.10 1x230V, 16A or3x400V, 10A
12 1860 655 1199 1486 504 Ø 500 0.20 1.041) 1.40 1.25 3x400V, 10A
1) 1.04 m3/s refers to air handling units in the right-hand version. For air handling units in the left-hand version, the value is 1.08 m3/s.
Sizing
1) Capacity variant 1. 2) Capacity variant 2.
11
Duct connection optionsA: Specify left-hand or right-hand version when placing orders. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site via the handheld terminal.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when plac-ing orders.
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
E: Specify air intake from above for outdoor air or extract air when placing orders (sizes 14-30, not for outdoor units).
Right-hand version
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 1 Fan arrangement 2
GOLD RX sizes 14/20, 25/30, 35/40
GOLDRXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
14 2080 765 1400 1586 521-589 1000x400 0.20 1.65 1.65 1.65 3x400V, 10A
20 2080 765 1400 1586 557-625 1000x400 0.30 1.80 2.10 2.10 3x400V, 101)/162)A
25 2220 835 1600 1786 666-746 1200x500 0.30 2.25 2.50 2.50 3x400V, 101)/162)A
30 2220 835 1600 1786 706-786 1200x500 0.50 2.35 3.20 2.81 3x400V, 20A
35 2446 948 1990 2085 956-1070 1400x600 0.50 3.50 3.90 3.90 3x400V, 20A
40 2446 948 1990 2085 1006-1120 1400x600 0.75 3.80 3.901/5.002 3,90 3x400V, 201)/252)A
1) Capacity variant 1. 2) Capacity variant 2.
* *
* *
* Sizes 14-30
Sizing
12
GOLD RX, sizes 100/120
GOLDRXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm
Heightmm
Weightkg
Ductconnection3)
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
100 3322 1126 3340 3440 3540-3900 2400x1200 1.50 10.00 11.00 11.00 3x400V, 501)/802)A
120 3322 1126 3340 3440 3746-4168 2400x1200 2.50 10.30 14.00 13.04 3x400V, 801)/1252)A
Capacity variant 1. 2) Capacity variant 2. 3) Duct connection 2500 x 800 mm on the units with a fan outlet for upward air discharge.
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.B: Specify with or without end wall panel for each airflow direction when placing orders. C: The arrangement of the functional sections can be vertically re-versed. Specify this by selecting fan arrangement 1 or 2 when placing orders.D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
DeliveryThe GOLD RX 100/120 air handling units are delivered in five separate subunits: two fan sections, two filter sections and one heat exchanger section. The heat exchanger section can also be supplied split into two casing sections and rotor, in which case the rotor is supplied tilted in a transport cradle (transport height = 2930 mm). After assembling the heat exchanger section, install the five units at the building site.
GOLD RX, sizes 50/60 and 70/80Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when plac-ing orders.
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
DeliveryThe GOLD RX 70/80 units are supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is located in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level.
Right-hand version
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 1 Fan arrangement 2
GOLDRXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
50 2670 1050 2318 2353 1294-1418 1600x800 0.60 4.75 5.00 5.00 3x400V, 201)/322)A
60 2670 1050 2318 2353 1374-1498 1600x800 1.00 5.00 6.50 6.50 3x400V, 321)/502)A
70 3120 1275 2637 2740 2059-2211 1800x1000 1.00 6.60 7.50 7.50 3x400V, 321)/502)A
80 3120 1275 2637 2740 2159-2435 1800x1000 1.50 6.85 9.50 8.31 3x400V, 501)/802)A
1) Capacity variant 1. 2) Capacity variant 2.
Sizing
Right-hand version
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 1 Fan arrangement 2
13
GOLD PX, sizes 04/05, 07/08
GOLD PX, sizes 11/12
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: Specify air intake from above for supply air and/or extract air when placing orders (not for outdoor units).
GOLD PX, sizes 14/20 and 25/30
Right-hand versionLeft-hand version
Right-hand versionLeft-hand version
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
Right-hand versionLeft-hand version
GOLDPX
size
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
04 2000 905 1191 291-337 Ø 315 0.08 0.45 0.45 0.45 1x230V, 10A or3x400V, 10A
05 2000 905 1191 291-337 Ø 315 0.08 0.47 0.65 0.53 1x230V, 101)/162)A or3x400V, 10A
07 2230 1075 1356 360-419 Ø 400 0.08 0.71 0.75 0.75 1x230V, 101)/162)A or3x400V, 10A
08 2230 1075 1356 369-428 Ø 400 0.20 0.79 1.00 0.83 1x230V, 16A1) or3x400V, 10A1)2)
GOLDPX
size
Lengthmm
The longest sec-tion when sectio-
nalizingmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
14 2830 1300 1480 1586 667-773 1000x400 0.20 1.65 1.65 1.65 3x400V, 10A
20 2830 1300 1480 1586 703-809 1000x400 0.30 2.00 2.10 1.85 3x400V, 101)/162)A
25 3220 1550 1680 1786 905-1058 1200x500 0.30 2.45 2.50 2.40 3x400V, 101)/162)A
30 3220 1550 1680 1786 945-1098 1200x500 0.50 2.55 3.20 2.32 3x400V, 161)/202)A
GOLDPX
size
Lengthmm
The longest sec-tion when sectio-
nalizingmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
11 2510 1200 1279 1486 552-646 Ø 500 0.20 1.01 1.10 1.05 1x230V, 16A1) or3x400V, 10A1)2)
12 2510 1200 1279 1486 574-668 Ø 500 0.20 1.14 1.40 1.20 3x400V, 10A
1) Capacity variant 1. 2) Capacity variant 2.
1) Capacity variant 1. 2) Capacity variant 2.
1) Capacity variant 1. 2) Capacity variant 2.
Sizing
14
Right-hand version
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 1 Fan arrangement 2
GOLD CX, size 35/40
GOLDCXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm3)
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
35 2719 948 2961 2085 1635-1749 1400x600 0.50 3.78 3.90 3.88 3x400V, 201)/252)A
40 2719 948 2961 2085 1685-1799 1400x600 0.75 3.90 3.901/5.002 3.90 3x400V, 201)/322)A
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when plac-ing orders.
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: The arrangement of the functional sections can be vertically re-versed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
DeliveryThe GOLD CX 50/60 units are supplied as two units, 70/80 as three units.
GOLDCXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm3)
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
50 2956 1050 3305 2353 2170-2294 1600x800 1.00 5.00 5.00 5.00 3x400V, 251)/322)A
60 2956 1050 3305 2353 2250-2374 1600x800 1.00 5.95 6.50 6.02 3x400V, 401)/502)A
70 3454 1275 3650 2740 3156-3308 1800x1000 1.50 7.30 7.50 7.48 3x400V, 401)/632)A
80 3454 1275 3650 2740 3256-3532 1800x1000 1.50 8.00 9.50 7.86 3x400V, 631)/802)A
GOLD CX, sizes 50/60 and 70/80
Right-hand version
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 1 Fan arrangement 2
1) Capacity variant 1. 2) Capacity variant 2. 3) Including pipework package
1) Capacity variant 1. 2) Capacity variant 2. 3) Including pipework package
Sizing
15
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify with or without end wall panel for each airflow direction when placing orders.
C: The arrangement of the functional sections can vary. Specify this by selecting fan arrangement 1, 2, 4 or 5 when placing orders. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level.
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
DeliveryThe GOLD RX 100/120 air handling units are delivered in six separate subunits: two fan sections, two filter sections and two heat exchanger sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are supplied in unassembled condition for wall or floor mounting.
GOLD CX, size 100/120
GOLDCXsize
Lengthmm
The longest section when sectionalizing
mm
Widthmm
Heightmm
Weightkg
Ductconnection
mm4)
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
100 3396 1144 3677 3440 4374-4734 2400x1200 1.50 11.00 11.00 11.00 3x400V, 631)/802)A
120 3396 1144 3677 3440 4580-5002 2400x1200 2.50 11.70 14.00 12.68 3x400V, 801)/1252)A
1) Capacity variant 1. 2) Capacity variant 2. 4) The dimensions of the duct connection on the units with a fan outlet for upward air discharge are 2500 x 800 mm.
Right-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 5, sup-ply air – upper level
Fan arrangement 5, supply air - lower level
Left-hand version
Fan arrangement 1 Fan arrangement 2
Fan arrangement 4, supply air – upper level
Fan arrangement 4, supply air - lower level
Sizing
16
Installation/duct connection optionsA: The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward.
B: Specify: with or without end connection panel when placing orders.
Bottom beam/Base frame/BaseIf the air handling unit is installed horizontally, it must be mounted on a bottom beam (option), stand (accessory) or some other form of base support, so that its inspection doors can be opened.
GOLD SD, size 04/05, 07/08
GOLDSD
size
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connectionMin SFPv ≤ 1.0 at 200 Pa Max Max
EcodesignFan + Filter
04 1099 825 490 105-119 Ø 315 0.08 0.60 0.60 0.60 1x230V, 10A
05 1099 825 490 105-119 Ø 315 0.08 0.80 0.80 0.66 1x230V, 10A
07 1174 995 575 113-133 Ø 400 0.08 0.80 0.80 0.80 1x230V, 10A
08 1174 995 575 117-137 Ø 400 0.20 1.19 1.20 1.07 1x230V, 10A1)
3x400V, 10A2)
GOLD SD, size 11/12
Fan with filter, if re-quired.
Right-hand versionLeft-hand version
Fan with filter, if required + Coil heat exchanger in extract
air. Droplet eliminator is optional.
Fan with filter, if required + Coil heat exchanger in supply
air.
Duct connection optionsA: Specify left-hand or right-hand version when ordering.
B: Specify: with or without end connection panel when placing orders.
GOLDSD
size
Lengthmm
The longest sec-tion when sectio-
nalizingmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connectionMin SFPv ≤ 2.0
at 200 PaMax Max
Ecodesign
Fan + Filter + Coil heat exchanger
11 2092 1404 11993) 748 321-347 Ø 500 0.20 1.05 1.20 1.201x230V, 10A1)
3x400V, 10A2)
12 2092 1404 11993) 748 332-358 Ø 500 0.20 1.20 1.80 1.41 3x400V, 10A
1) Capacity variant 1. 2) Capacity variant 2.
Sizing
1) Capacity variant 1. 2) Capacity variant 2. 3) Coil Heat Exchanger width + 200 mm
17
Duct connection optionsA: Specify left-hand or right-hand version when placing orders.
B: Specify: with or without end connection panel when placing orders.
C: Specify fan outlet for upward air discharge when placing orders (not applicable to outdoor units).
DeliveryThe size 70/80 GOLD SD units are always supplied as one unit if they each consist of a fan or fan + filter. If it consists of fan + filter + coil heat exchanger, it is supplied as two units.
The GOLD SD 100/120 units are supplied as separate units for fan + filter + coil heat exchanger.
Units in the other sizes are always supplied as one unit.
Fan
Fan + Filter
Fan + Filter + Coil heat exchanger in extract air. The droplet collector is
an accessory.
Fan + Filter + Coil heat exchanger in
supply air
Right-hand versionLeft-hand version
GOLD SD, sizes 14/20,25/30,35/40,50/60,70/80, 100/120
GOLDSD
size
Lengthmm
The longest section when sectionalizing
mm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connectionMin SFPv ≤ 2.0
at 200 PaMax Max
Ecodesign
Fan + Filter + Coil heat exchanger14 2615 988 14004) 906 480-518 1000x400 0.20 1.65 1.80 1.80 3x400V, 10A
20 2615 988 14004) 906 498-536 1000x400 0.30 2.10 2.80 2.25 3x400V, 10A
25 2720 1093 16004) 1126 626-678 1200x500 0.30 2.50 2.80 2.80 3x400V, 10A
30 2720 1093 16004) 1126 646-698 1200x500 0.50 3.19 4.00 3.47 3x400V, 10A
35 2720 1093 19904) 1226 793-861 1400x600 0.50 3.90 4.00 4.00 3x400V, 10A
40 2720 1093 19904) 1226 818-886 1400x600 0.75 4.001)/4.602) 5.001)/6.002) 4.92 3x400V, 101)/162)A
50 2687 1050 23184) 1420 1093-1155 1600x800 0.60 5.00 5.60 5.60 3x400V, 101)/162)A
60 2687 1050 23184) 1420 1133-1195 1600x800 1.00 6.50 8.00 6.99 3x400V, 161)/252)A
70 3452 1327 26374) 1420 1563-1639 1800x1000 1.00 7.30 8.00 7.79 3x400V, 161)/252)A
80 3452 1327 26374) 1420 1613-1689 1800x1000 1.50 8.00 12.00 7.86 3x400V, 251)/402)A
100 3396 1144 33404) 1720 2187-2367 2400x12003) 1.50 11.00 12.00 11.48 3x400V, 251)/402)A
120 3396 1144 33404) 1720 2290-2501 2400x12003) 2.50 11.70 18.00 12.69 3x400V, 401)/632)A
1) Capacity variant. 2) Capacity variant. 3) The dimensions of the duct connection on the units with a fan outlet for upward air discharge are 2500 x 800 mm. 4) Coil Heat Exchanger width + 200 mm
Sizing
18
GOLD LP, sizes 05, 08Right-hand version
Left-hand version
Installation/duct connection optionsA: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by making a simple adjustment in the control equipment.
InstallationThanks to its low installation height, the GOLD LP can be installed in false ceiling voids, horizontally in an attic space or in other confined spaces. In order to save floor space, the GOLD LP can also be mounted by a wall (a floor stand is available as an accessory) as an alternative to a conventional unit arrangement. If the unit is mounted on a wall, the electric equipment cubicle must always be located upwards.
GOLDLP
size
Lengthmm
Width1 1)
mmWidth 2
mmHeight
mmWeight
kgDuct
connection mm
Airflow m3/s Power connectionMin SFPv ≤ 2.0
at 200 PaMax Max
Ecodesign05 2172 507 560 1171 247 454x400 0.08 0.41 0.53 0.50 1x230V, 10A
08 2370 582 635 1329 301 533x475 0.08 0.62 0.74 0.74 3x400V, 10A
1)Refers to the width with the slide rails for the inspection doors removed.
Visible on the ceiling In a corridor
In a closet
Installation Examples
In suspended ceilings
Sizing
19
The COMPACT units are a complete air handling units with direct-driven supply air and extract air fans, supply air and extract air filters, and rotary heat exchanger.
The exterior colour of the visible sheet metal surfaces is white, (NCS S0502-G).
The COMPACT has built-in control equipment that can be oper-ated from the hand-held micro terminal with plain-text display. The electrical and control system is completely integrated into the air handling unit. The microprocessor-based equipment controls and regulates temperatures, airflows and other functions. A large num-ber of functions, including communication, are built into the system and are simple to activate.
If supplementary functional sections such as dampers and air cool-ers are required, they must be installed in the ductwork.
ApplicationThe COMPACT Unit and COMPACT Top units are designed for comfort ventilation and can be used in small premises such as offices, schools, day nurseries, public premises, shops, residential buildings, etc.The space available in smaller buildings is usually restricted. The COMPACT Unit and COMPACT Top make a very compact installation possible. The COMPACT Unit AHUs have duct connection spigots on their end panels, the traditional way, whereas the COMPACT Top units have them at the top.
The COMPACT Air and COMPACT Heat units are designed for comfort ventilation and can be used in classrooms, day nurseries, conference halls, smaller offices, workrooms, shops, restaurants and similar public premises. The COMPACT Air and COMPACT Heat can be installed directly in the room to be ventilated. COMPACT Heat operates in normal applications like COMPACT Air but it can also be used for heating the room with BOOSTER function.
The COMPACT units should be installed indoors.
The COMPACT units are designed and tested for ambient tempera-tures of from -25°C to +40°C, and air stream temperatures of from -40°C to +40°C.
CertificationSwegon AB has a certified Quality Assurance System that conforms to ISO 9001 Standard and a certified Environmental Management System to ISO 14001. The COMPACT air handling system Unit & Top are also certificated by Eurovent.
General Points - COMPACT
Technical Description
COMPACT Unit
COMPACT Top
COMPACT Air COMPACT Heatwww.eurovent-certification.com www.certiflash.com
N° 09.05.426. Range: COMPACT
20
Duct accessories, COMPACT
Outdoor air hood
Exhaust air hood
Dual-purpose hood
• Outdoor air hood (Unit/Top)
• Exhaust air hood (Unit/Top)
• Dual-purpose hood (Unit/Top)
• Exterior wall hood
Hoods, COMPACT
Exterior wall hood
COMPACT control componentsIf necessary, the built-in control equipment can be supple-mented with components e.g. the following:
• Air quality sensor
• Presence detector
• Room sensor
Duct accessories are available for a complete installation, e.g. the following:
• Damper
• Electric or hot water air heater
• Air cooler for water or direct expansion
• Sound attenuator
Air handling unit accessories, COMPACTAccessories are available for the various air handling models, e.g. the following:
• Stand (Unit)
• Door fastener (Unit)
• Extract air connection (Air/Heat)
• Cover plate between air handling unit and roof (Air/Heat)
• Louvre damper (Air, included as standard in the Heat model)
Air heater and air cooler
Damper
Electric air heater
Support stand
Extract air connec-tion piece
Air quality sensor Presence detector
Louvre damper
Complements and accessories
21
Length
Width
Height(including junction hood)
Overview – Airflows, COMPACTAll the sizing data specified in this brochure are meant for use as an overview. Exact sizing can be carried out in the web-based ProUnit air han-dling unit selection software.
Contact your nearest Swegon representative for data cal-culations or use the program yourself at www.swegon.com.
Outdoor air Supply air Extract air Exhaust air
Arrows for airflows in this brochure
Dimensions specified in this brochure
1) The sound pressure level with consideration given to a room effect of -12 dB. 2) Does not apply to operation in the BOOSTER mode.
Length
Width
Height(including base beams)
Length
Width
Height(including base beams)
Length
Width
Height(including base beams, air recircula-tion section and louvre damper)
COMPACTAir
Min. Max./SFPV Max. Ecodesign Sound level ≤ 30 dB(A) at airflow
m3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h02 0.08 290 0.23/1.1 830/1.1 0.23 830 0.231) 8301)
03 0.08 290 0.33/1.8 1190/1.8 0.36 1300 0.251) 9001)
COMPACTHeat
Min. Max./SFPV Max. Ecodesign Sound level ≤ 30 dB(A) at airflow
m3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h02 0.08 290 0.23/1.3 830/1.3 0.23 830 0.231)2) 8301)2)
03 0.08 290 0.305/2.0 1100/2.0 0.36 1300 0.231)2) 8301)2)
Sizing
COMPACTUnit
Min. SFPV ≤ 2.0 at 200 Pa Max. Max. Ecodesignm3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h
02 0.08 290 0.2 720 0.23 830 0.23 83003 0.08 290 0.25 900 0.36 1300 0.36 1300
COMPACTTop
Min. SFPV ≤ 2.0 at 200 Pa Max. Max. Ecodesignm3/s m3/h m3/s m3/h m3/s m3/h m3/s m3/h
02 0.08 290 0.2 720 0.23 830 0.23 83003 0.08 290 0.23 830 0.36 1300 0.36 1300
22
Right-hand version
Left-hand version
COMPACT Unit, sizes 02, 03Duct connection options A: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by making a simple adjustment in the control equipment.
B: The air handling unit can be installed upended.
Base frame/BaseIf the air handling unit is installed horizontally, it must be mounted on a stand (accessory) or some other form of base support, so that its inspection doors can be opened.
COMPACTUnitsize
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
02 1214 788 872 160 Ø 250 0.08 0.2 0.23 0.23 1x230V, 10A
03 1214 788 872 160 Ø 250 0.08 0.25 0.36 0.36 1x230V, 10A
COMPACT Top, sizes 02, 03Duct connection options A: The air handling unit is produced in one variant in which all the components are arranged at their given physical locations inside the unit. All the duct connections are arranged from the top of the air handling unit.
Base frame/BaseThe unit is equipped with base beams.
COMPACTTopsize
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Power connection
Min SFPv ≤ 2.0 at 200 Pa
Max Max Ecodesign
02 1103 788 1302 200 Ø 250 0.08 0.2 0.23 0.23 1x230V, 10A
03 1103 788 1302 200 Ø 250 0.08 0.23 0.36 0.36 1x230V, 10A
Sizing
23
COMPACT Air, sizes 02, 03Duct connection options A: The air handling unit is produced in one variant in which all the components are arranged at their given physical locations inside the unit. All the duct connections are arranged from the top of the air handling unit.
InstallationThe air diffuser section can be separated from the main unit section for transport within the building site.
The unit should be installed in the room to be ventilated and its electric plug should be connected to an earthed mains electric socket. The ducts for outdoor air and exhaust air should be connected to the top of the unit and should be arranged to lead out through the wall.
COMPACTAirsize
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Available pressure for outdoor air/exhaust air
at max. airflowPa
Sound level
≤ 30 dB(A) at m3/s
Power connectionMin Max/SFPv Max
Ecodesign
02 1102 788 2114 331 Ø 250 0.08 0.23/1.1 0.23 20 0.231) 1x230V, 10A
03 1102 788 2114 331 Ø 250 0.08 0.33/1.8 0.36 20 0.251) 1x230V, 10A
1) The sound pressure level with consideration given to a room effect of -12 dB.
COMPACT Heat, sizes 02, 03Duct connection options A: The air handling unit is produced in one variant in which all the components are arranged at their given physical locations inside the unit. All the duct connections are arranged from the top of the air handling unit.
InstallationThe air diffuser section can be separated from the main unit section for transport within the building site.
The unit should be installed in the room to be ventilated and should be connected to the mains power supply via a type Perilex electric plug to an appropriate power outlet. The ducts for outdoor air and exhaust air should be connected to the top of the unit and should be arranged to lead out through the wall.
COMPACTHeatsize
Lengthmm
Widthmm
Heightmm
Weightkg
Ductconnection
mm
Airflow m3/s Available pressure for outdoor air/exhaust air
at max. airflowPa
Sound level
≤ 30 dB(A) at m3/s
Power connectionMin Max/SFPv Max
Ecodesign
02 1102 788 2414 345 Ø 250 0.08 0.23/1.3 0.23 20 0.231)2) 3x400V, 16A
03 1102 788 2414 345 Ø 250 0.08 0.305/2.0 0.36 20 0.231) 2) 3x400V, 16A
1) The sound pressure level with consideration given to a room effect of -12 dB. 2) Does not apply to operation in the BOOSTER mode.
Sizing
EN-G
OLD
& C
OM
PAC
T ov
ervi
ew 2
016-
01-2
5