User’s Manual LG Programmable Logic Controller G3F – AT4A G4F – AT3A GLOFA LG Industrial Systems

Upload: buihuong

Post on 15-Feb-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

User’s Manual

LG Programmable Logic Controller

G3F – AT4AG4F – AT3AGLOFA

LG Industrial Systems

◎ CONTENTS ◎

Chapter 1. INTRODUCTION

1.1 Features···················································································································································1-1

Chapter 2. SYSTEM CONFIGURATION

2.1 Example of System Configuration ···································································································2-1

Chapter 3. SPECIFICATIONS

3.1 General Specifications ····················································································································3-1

3.2 Performance Specifications ················································································································3-2

3.3 Names of Parts and Functions ·············································································································3-3

3.3.1 G3F-AT4A ·······································································································································3-3 3.3.2 G4F-AT3A ·······································································································································3-4

3.3.3 Names of Parts and Functions········································································································3-5

3.4 Setting Procedure for Each Function··································································································3-7

3.4.1 Setting the Setting Range Selection Switch···················································································3-7

3.4.2 Adjusting the Volume ······················································································································3-8

Chapter 4. INSTALLATION

4.1 Installation ········································································································································4-1

4.1.1 Installation Ambience ················································································································· 4-1

4.1.2 Handling precautions ··················································································································· 4-1

Chapter 5. GM PROGRAMMING

5.1 Function Block ·································································································································5-1

5.1.1 Timer Starting ·······························································································································5-1

5.2 Program for Comparing and Outputting the Setting Times of Analog Timers································5-2

5.2.1 System Configuration······················································································································5-2

5.2.2 Initial Settings ································································································································5-2

5.2.3 Program Description····················································································································· 5-2

5.2.4 Program ··········································································································································5-3

Chapter 6. GK PROGRAMMING

6.1 I/O Signals ············································································································································6-1

6.1.1 G3F-AT4A ·······································································································································6-1

6.1.2 G4F-AT3A ·······································································································································6-1

6.1.3 Example for Executing the Anal og Timer T00 by Program····························································6-2

6.2 Program for Comparing and Outputting the Setting Times of Analog Timers································6-3

6.2.1 System Configuration······················································································································6-3

6.2.2 Initial Settings ································································································································6-3

6.2.3 Program Description····················································································································· 6-3 6.2.4 Program ··········································································································································6-4

Chapter 7. TROUBLESHOOTING

7.1 Error Code·············································································································································7-1

7.2 Troubleshooting P rocedure ·········································································································7-2

7.2.1 RUN LED off ···································································································································7-2

7.2.2 The Contact Indication LED for the Timer Operation does not Turn on When the Timer Starts its Operation ·············································································································7-3

7.2.3 The Operation Contact does not Turn on Though the Setting Time has Passed after the Start of the Timer ····················································································································7-4

Chapter 8. TEST RUN

8.1 Run Procedure ···································································································································8-1

Chapter 9. DIMENSIONS

9.1 Dimensions ·············································································································································9-1

9.1.1 G3F-AT4A ·······································································································································9-1

9.1.2 G4F-AT3A ·······································································································································9-2

Chapter 1. INTRODUCTION

1 - 1

Chapter 1. INTRODUCTION

These modules are combined and used with the CPU of the GLOFA PLC GM 1/2/3/4 series and MASTER-

K1000S/300S. The G3F – AT4A is used in the GM 1/2/3 series and MASTER-K1000S series. The G4F – AT3A is

used in the GM4 series and MASTE R-K1000S series. Hereafter, they are commonly called Analog Timer Module

(A/T module). The A/T module performs On Delay operation for a setting time.

1.1 Features

▶ The A/T module has the following features.

1) Up to 16-point (G3F – AT4A) and 8-point (G4F – AT3A) analog timers are applicable.

2) The range of setting time is very wide. (0.1 to 600 sec)

3) Time adjustment is easy.

4) A LED is used to indicate the timer operation status.

5) The backup function for setting time is available.

Chapter 2. SYSTEM CONFIGURATION

2 - 1

Chapter 2. SYSTEM CONFIGURATION

2.1 Example of System Configuration

The following shows the system configuration of the GLOFA GM3 series where the A/T module is mounted.

Battery RS-232C Cable Diskettes(GMWIN) General purpose PC

Memory Module

CPU Module

Main Base (GM3-B0_IM)

Expansion Cable

Expansion Base (GM3-B0_IE) G3F-AT4A

Chapter 3. SPECIFICATIONS

3 - 1

Chapter 3. SPECIFICATIONS

3.1 General Specifications

Table 2.1 shows general specifications of the GLOFA GM series and MASTER-K series.

No Item s Specifications Standard

1 Operating ambient temperature

0 ~ 55℃

2 Storage ambient temperature

-25 ~ 75℃

3 Operating ambient humidity

5 ~ 95%RH, non-condensing

4 Storage ambient humidity

5 ~ 95%RH, non-condensing

Occasional vibration Frequency Acceleration Amplitude Sweep count

10≤f∠57 Hz - 0.075 mm 57 ≤f≤150 Hz 9.8 ㎨ {1G} -

Continuos vibration Frequency Acceleration Amplitude

10≤f∠57 Hz - 0.035 mm

5 Vibration

57≤ f≤150 Hz 4.9 ㎨ {0.5G} -

10 times in each direction for X, Y, Z

IEC 61131-2

6 Shocks *Maximum shock acceleration: 147 ㎨ {15G} *Duration time :11 ms *Pulse wave: half sine wave pulse( 3 times in each of X, Y and Z directions )

IEC 61131-2

Square wave impulse noise ±1,500 V LGIS

Standard

Electrostatic discharge Voltage :4 kV(contact discharge) IEC 61131-2

IEC1000-4-2

Radiated electromagnetic field

27 ~ 500 MHz, 10 V/m IEC 61131-2

IEC 1000-4-3

Severity Level

All power modules

Digital I/Os ( Ue ≥

24 V)

Digital I/Os (Ue < 24 V) Analog I/Os communication

I/Os

7 Noise immunity

Fast transient burst noise

Voltage 2 kV 1 kV 0.25 kV

IEC 61131-2

IEC1000-4-4

8 Operating atmosphere

Free from corrosive gases and excessive dust

9 Altitude for use Up to 2,000m

10 Pollution degree 2 or lower 11 Cooling method Self-cooling

[Table 2.1 ] General specifications

REMARK

1) IEC(International Electrotechnical Commission) : The international civilian organization which produces standards for electrical and electronics industry.

2) Pollution degree : It indicates a standard of operating ambient pollution level. The pollution degree 2 means the condition in which normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected.

Chapter 3. SPECIFICATIONS

3 - 2

3.2 Performance Specifications

Table 3.2 shows the performance specifications of the A/T module.

Specifications Items

G3F – AT4A G4F – AT3A

Timer point 16 points 8 points

Timer setting value range

0.1 to 1.0 sec 1 to 10 sec

10 to 60 sec 60 to 600 sec

Setting can be done for each individual point

Backup Method For backup, set the operation mode selection switch to the TEST side.

Setting Method Setting by the adjustment volume.

Timer Accuracy ± 2.0% (For maximum value)

Timer Operation indication LED : 16 pts Timer Operation indication LED : 8 pts

Operating Indicator

Timer Contact indication LED : 16 pts Timer Contact indication LED : 8 pts

Current consumption 0.3 A (5 VDC) 0.2 A (5VDC)

[Table 3.3] Performance specifications

Chapter 3. SPECIFICATIONS

3 - 3

3.3 Names of Parts and Functions

The following gives the names of parts of the A/T module.

3.3.1 G3F – AT4A

[Side] [Front]

Chapter 3. SPECIFICATIONS

3 - 4

3.3.2 G4F – AT3A

⑤ ⑥

[Side] [Front]

Chapter 3. SPECIFICATIONS

3 - 5

3.3.3 Names of Parts and Functions

The following gives names and function of parts of the A/T module.

No. Name Descriptions

Indicates the On/Off state of the contact of Analog timers (T00 to T15) (On state : turn on, Off state : turn off)

LED Contents LED Contents

00 Contact of the Analog Timer T00 08 Contact of the Analog Timer T08

01 Contact of the Analog Timer T01 09 Contact of the Analog Timer T09

02 Contact of the Analog Timer T02 10 Contact of the Analog Timer T10

03 Contact of the Analog Timer T03 11 Contact of the Analog Timer T11

04 Contact of the Analog Timer T04 12 Contact of the Analog Timer T12

05 Contact of the Analog Timer T05 13 Contact of the Analog Timer T13

06 Contact of the Analog Timer T06 14 Contact of the Analog Timer T14

① Timer contact indication LED

07 Contact of the Analog Timer T07 15 Contact of the Analog Timer T15

Indicates the On/Off state of the contact of Analog timers (T00 to T15) (On state : turn on, Off state : turn off)

LED Contents LED Contents

16 Coil of the Analog Timer T00 24 Coil of the Analog Timer T08

17 Coil of the Analog Timer T01 25 Coil of the Analog Timer T09

18 Coil of the Analog Timer T02 26 Coil of the Analog Timer T10

19 Coil of the Analog Timer T03 27 Coil of the Analog Timer T11

20 Coil of the Analog Timer T04 28 Coil of the Analog Timer T12

21 Coil of the Analog Timer T05 29 Coil of the Analog Timer T13

22 Coil of the Analog Timer T06 30 Coil of the Analog Timer T14

② Timer operation indication LED

23 Coil of the Analog Timer T07 31 Coil of the Analog Timer T15

Chapter 3. SPECIFICATIONS

3 - 6

No. Name Descriptions

Used to select an analog timer (T00 to T15) whose time will be adjusted.

Timer No.

Selected Timer Timer No.

Selected Timer

0 T00 8 T08

1 T01 9 T09

2 T02 A T10

3 T03 B T11

4 T04 C T12

5 T05 D T13

6 T06 E T14

③ Timer number selection switch

7 T07 F T15

④ Operation mode selection switch

Used to adjust and backup the timer value, check the adjusted value and select the operation mode for each timer. . RUN :Position for normal operation . SET :Position for adjustment of the timer value of the timer selected by③. . TEST : Position for manual check and backup of the adjusted timer value.

⑤ Adjustment

Volume Used to adjust the timer value of an analog timer.

⑥ Setting range

selection switch Used to select the setting range for each analog timer.

⑦ RUN LED Indicates the operation status of the A/T module. iOn : Normal operation iOff : 5 VDC line disconnection or A/T module defect.

REMARK Only T00 to T07 are available in the G4F – AT3A. T08 to T15 are not processed.

Chapter 3. SPECIFICATIONS

3 - 7

3.4 Setting Procedure for Each Function

3.4.1 Setting the Setting Range Selection Switch

1) Setting Range Selection Switch

2) Setting Range Selection

Set the time range for each analog timer (T00 to T15) by the setting range selection switch

0.1 to 1.0 sec 1 to 10 sec 10 to 60 sec 60 to 600 sec

Txx 1 Off On Off On

Txx 2 Off Off On On

xx : Means the number of an analog timer (00 to 15)

[Example] When setting the time range of the analog timer T03 to “1 to 10 sec”

3) Factory Setting is “0.1 to 1.0 sec“ for All Analog Timers.

(1) G3F – AT4A

(2) G4F – AT3A

Switch name

Time range

(Set this switch to On) (Set this switch to Off)

Chapter 3. SPECIFICATIONS

3 - 8

3.4.2 Adjusting the Volume

1) Apply the power after the CPU module and the A/T module are set to the following conditions.

. Set the key switch of the CPU module to ‘STOP’.

. Set the operation mode selection switch of the A/T module to ‘SET’.

2) Select the numbers of the analog timers (T00 toT15) whose timer time will be adjusted by the timer

number selection switch.

[Example] When selecting the analog timer T03

REMARK

If set the timer number selection switch of the G4F – AT3A to ‘8 to F’, nothing will be processed.

3) Set the adjustment volume to the timer time, which will be used as a goal, within the timer time range set

in the selection 3.4.1.

4) Set the operation mode selection switch to “TEST’ and check the time from turning-on of the timer

operation indication LED to turn-on of the timer contact indication LED.

5) After checking the on time of the timer contact indication LED, set the operation mode selection switch to

‘SET’.

6) To micro-adjust the timer time to the goal time, repeat 3) to 5).

7) Set the timer time for each analog timer as the procedure shown by 2) to 6).

8) After every timer time for every analog timer has been set, Set the operation mode selection switch to

‘RUN’ and execute the user program.

9) To backup the timer time set, set the operation mode selection switch to ‘TEST’. Then, the setting time

will be stored to the memory.

REMARK

If an analog timer has been adjusted during the RUN state of the CPU module, the analog timer starts its operation by the prior one of the start signals by the operation mode selection switch of the A/T module and by the user program.

Set the timer number selection switch to 3

Short Long

Adjustment Volume

Chapter 4. INSTALLATION

4- 1

Chapter 4. INSTALLATION 4.1 Installation

4.1.1 Installation Ambience

This module has high reliability regardless of its installation ambience. But be sure to check the

following for system in higher reliability and stability.

1) Ambience Requirements

Avoid installing this module in locations, which are subjected or exposed to:

- Water leakage and dust a large amount of dust, powder and other conductive power, oil mist,

salt, of organic solvent exists.

- Mechanical vibrations of impacts are transmitted directly to the module body.

- Direct sunlight. - Dew condensation due to sudden temperature change.

- High or low temperatures (outside the range of 0-55℃)

2) Installing and Wiring

- During wiring or other work, do not allow any wire scraps to enter into it.

- Install it on locations that are convenient for operation. - Make sure that it is not located near high voltage equipment on the same panel.

- Make sure that the distance from the walls of duct and external equipment be 50 mm or more.

- Be sure to be grounded to locations that have good noise immunity.

4.1.2 Handling Precautions

From unpacking to installation, be sure to check the following:

1) Do not drop it off, and make sure that strong impacts should not be applied.

2) Do not dismount printed circuit boards from the case. It can cause malfunctions.

3) During wiring, be sure to check any foreign matter like wire scraps should not enter into the upper side of the PLC, and in the event that foreign matter entered into it, always eliminate it.

Chapter 5. PROGRAMMING

5 - 1

Chapter 5. PROGRAMMING

5.1 Function Block

5.1.1 Timer Starting (G3F-AT4A : AT4TON, G4F-AT3A: AT3TON)

Function block I/O Variable Data type Descriptions

IN BOOL

Request area for function block execution - Used to request an execution of the operating

function block. - Used to set the starting condition for the function

block. [Level ( ) or edge ( ) ]

BASE USINT

Base location No. - Used to write the base No. on which the A/T

module is mounted. - Setting range : GM1 series(0 to 31)., GM2 series

(0 to 7), GM3/4 series (0 to 3)

SLOT USINT

Slot location No. - Used to write the slot No. on which the A/T

module is loaded. - Setting range : 0 to 7

I

TMR USINT

Used timer specification area - Use to specify the used timers. - Setting range : AT4TON(0 to 15), AT3TON(0 to

7)

Q BOOL

Function block finished execution state - If the operating function block has finished its

operations without error after the input variable IN was turned on, “1” is output to this variable. The “1” is retained until the “0” is input to the variable IN. Then, “0” will be output to this variable and operation stops.

G3F-AT4A

O

STAT USINT

Error status indication area - If an error occurs during ex ecution of the

operating function block, the error code will be output to this variable.

- For error contents, refer to Section 7.1.

G4F-AT3A

Chapter 5. PROGRAMMING

5 - 2

5.2 Program for Comparing and Outputting the Setting Times of Analog Timers.

5.2.1 System Configuration

5.2.2 Initial Settings

1) Time setting range : 0.1 to 1.0 sec

2) Used timer : T00

5.2.3 Program Description

The setting times can be adjusted by the adjustment volume of the A/T module without changes of the program even in the RUN state of the PLC CPU.

(1) The starting contact _T10S of the timer T00 repeats off and on with 10 sec cycle. (2) When the _T10S turns on, the timer T00 starts its operation. Q0 turns on after the setting time

has passed. (3) When the Q0 turns on, if the setting time is more than 980 msec, the MAX_TIME, the %QX0.1.0

is set to ON. If less than 900 msec, the MIN_TIME, the %QX0.1.1 is set to ON.

GM4-

PA1A

GM4-

CPUA

G4F-

AT3A

G4Q-

RY2A

Slot 1 Slot 0

1 2

T00

(Set the switch to OFF)

(Set the switch to OFF)

_T10S

Q0

<Timing Chart> 5 sec

Setting time

5 sec

Chapter 5. PROGRAMMING

5 - 3

5.2.4 Program

10 sec cycle start contact

(A 10 sec timer is used to operate

the T00)

(Setting time of the analog timer T00)

Chapter 6. GK PROGRAMMING

6 - 1

Chapter 6. GK PROGRAMMING

6.1 I/O Signals

The followings explain the I/O signals for the A/T module used in the MASTER-K series.

The G3F-AT4A occupies 32 I/O points and the G4F-AT3A occupies 16 I/O points.

6.1.1 G3F-AT4A ( N means the I/O Word No. of the A/T module)

Input Signal Contents Output

Signal Contents

P(N)0 Contact of the analog timer T00 P(N+1)0 Coil of the analog timer T00

P(N)1 Contact of the analog timer T01 P(N+1)1 Coil of the analog timer T01

P(N)2 Contact of the analog timer T02 P(N+1)2 Coil of the analog timer T02

P(N)3 Contact of the analog timer T03 P(N+1)3 Coil of the analog timer T03

P(N)4 Contact of the analog timer T04 P(N+1)4 Coil of the analog timer T04

P(N)5 Contact of the analog timer T05 P(N+1)5 Coil of the analog timer T05

P(N)6 Contact of the analog timer T06 P(N+1)6 Coil of the analog timer T06

P(N)7 Contact of the analog timer T07 P(N+1)7 Coil of the analog timer T07

P(N)8 Contact of the analog timer T08 P(N+1)8 Coil of the analog timer T08

P(N)9 Contact of the analog timer T09 P(N+1)9 Coil of the analog timer T09

P(N)A Contact of the analog timer T10 P(N+1)A Coil of the analog timer T10

P(N)B Contact of the analog timer T11 P(N+1)B Coil of the analog timer T11

P(N)C Contact of the analog timer T12 P(N+1)C Coil of the analog timer T12

P(N)D Contact of the analog timer T13 P(N+1)D Coil of the analog timer T13

P(N)E Contact of the analog timer T14 P(N+1)E Coil of the analog timer T14

P(N)F Contact of the analog timer T15 P(N+1)F Coil of the analog timer T15

Chapter 6. GK PROGRAMMING

6 - 2

6.1.2 G4F-AT3A ( N means the I/O Word No. of the A/T module)

Input Signal Contents

Output Signal Contents

P(N)0 Contact of the analog timer T00 P(N)8 Coil of the analog timer T00

P(N)1 Contact of the analog timer T01 P(N)9 Coil of the analog timer T01

P(N)2 Contact of the analog timer T02 P(N)A Coil of the analog timer T02

P(N)3 Contact of the analog timer T03 P(N)B Coil of the analog timer T03

P(N)4 Contact of the analog timer T04 P(N)C Coil of the analog timer T04

P(N)5 Contact of the analog timer T05 P(N)D Coil of the analog timer T05

P(N)6 Contact of the analog timer T06 P(N)E Coil of the analog timer T06

P(N)7 Contact of the analog timer T07 P(N)F Coil of the analog timer T07

6.1.3 Example for Executing the Analog Timer T00 by Program. (The A/T Module is

mounted onto the Slot 0)

1) If the output P0010 is turned On, the coil of the analog timer T00 turns On and it starts its operation.

2) After one second from the turning-on of the output P0010, the contact of the analog timer T00 will turns

On and the input contact turns On.

Analog timer T00 execution command P0010

P0000

The inside of the G3F-AT4A

Setting time : 1 sec

T00

Contact of T00

P0040 ( )

Chapter 6. GK PROGRAMMING

6 - 3

6.2 Program for Comparing and Outputting the Setting Times of Analog Timers.

6.2.1 System Configuration

6.2.2 Initial Settings

1) Time setting range : 0.1 to 1.0 sec

2) Used timer : T00

6.2.3 Program Description

The setting times can be adjusted by the adjustment volume of the A/T module without changes of the program even in the RUN state of the CPU Module. (1) The coil of the timer T00 turns off and on with 10 sec cycle. (P0008)

(2) When the F0095 turns on, the CPU Module timer T200 starts its operation. When the signal of contact P0000 turns on after setting time, the current time of the T200 is stored to the D0000.

(3) If the T200 is more than 980 msec the P0010 is set to On. If less, the P0011 is set to On. (4) If the T200 is set to On, the M0021 will be reset in order that the T200 starts a new operation.

GM4-

PA1A

K4P-

15AS G4F-

AT3A

G4Q-

TR2A

Slot 1 Slot 0

1 2

T00

(Set the switch to OFF)

(Set the switch to OFF)

<Timing Chart>

5 sec

Setting time

5 sec

P0008

P0000

F0095

Chapter 6. GK PROGRAMMING

6 - 4

6.2.4 Program

(A 10 sec timer is used to operate

the T00)

10 sec cycle start contact

The M0020 is turned on for 1

scan

Turning on the

operation signal of the T00

Turning on the

operation signal of the T00

The 1.5 sec timer T200 is

used to operate the T00

The M030 is

turned on for 1 scan

Storing the T00 setting time to

the D0000

If the setting time is more than 980 ms,

the P0010 is set to ON

Turning the operation

junction T00 Off.

Resetting the M0021 so that the T00 start a new operation

T00 junction signal

<

Chapter 7. TROUBLESHOOTING

7- 1

Chapter 7. TROUBLESHOOTING The followings explain errors and corrective action when operating the A/T module. For the problems relating to the CPU module, refer to the CPU module User’s Manual. 7.1 Error Code Errors in the function block when using the A/T module in the GM series are given below.

Error code Error Content

0 Normal operation

1 Base location No. outside the setting range(0 to 3)

2 Base hardware defect 3 Slot location No. outside the setting range(0 to 7)

4 The corresponding slot has no mounted module.

5 Other module than the A/T module is mounted.

6 Timer No. outside the setting range (G3F-AT4A: 0 to 15, G4F-AT3A : 0 to 7)

7 The module is not in the READY state.

10 The module is in the TEST mode.

Chapter 7. TROUBLESHOOTING

7- 2

7.2 Troubleshooting Procedure 7.2.1 RUN LED off .

RUN LED off

The A/T module is correctly mounted on the base board.

No

Yes

The capacity of the power supply module is sufficient.

No

Yes

The RUN LED is turned on after the CPU module has been replaced and reset.

Yes

No

Base board hardware defect. Contact the service station.

Mount correctly the A/T module on the base board.

Re-examine system configuration with calculating the current consumption of each

module.

CPU module hardware defect. Contact the service station.

The RUN LED is turned on after the A/T module has been replaced and the CPU module has been reset. .

Yes

No

A/T module hardware defect. Contact the service station.

Chapter 7. TROUBLESHOOTING

7- 3

7.2.2 The Contact Indication LED for the Timer Operation does not Turn on When the Timer Starts

its Operation.

See Section 7.2.1

Set the selection switch of the operation mode to ‘RUN’.

The contact indication LED for the timer operation does not turn on when the timer starts its operation.

RUN LED of AT module is turned on.

No

Yes

The selection switch for operation mode is set to ‘RUN’.

No

Yes

The RUN LED is turned on after the CPU module has been replaced and reset.

Yes

No

A/T module hardware defect. Contact the service station.

CPU module hardware defect. Contact the service station.

Chapter 7. TROUBLESHOOTING

7- 4

7.2.3 The Operation Junction does not Turn on Though the Setting Time has Passed after the Start of the Timer

]

The operation junction does not turn on though the setting time has passed after the start of the timer

The operation mode selection switch of the A/T module is set to ‘RUN’.

The setting value is within the setting range.

No

Yes

No

Yes

The setting value is outside the setting range. Refer to Section 3.4.1 and correctly set the setting value.

The junction LED of the A/T module is turned ON.

Yes

No

A/T module hardware defect. Contact the nearest service station.

The junction LED is turned ON, after the CPU module has been replaced and reset .

Yes

No

The junction LED is turned ON, after the A/T module has been replaced and the CPU module has been reset..

Yes

No

CPU module hardware defect. Contact the nearest service station.

Base unit hardware defect.

Contact the nearest service station.

Incorrect setting of the operation mode selection switch. Refer to Section 3.4.2 and correctly set the switch.

CPU module defect. Contact the nearest service station.

Chapter 8. TEST RUN

8- 1

Chapter 8. TEST RUN 8.1 Run Procedure

The following shows the run procedure for the A/T module.

Start

Set the operation mode switch to ‘SET’.

Adjust the timer number selection switch.

Set the time by the adjustment volume.

Set the timer range by the selection switch. (See Section 3.4.1)

Mount the A/T module onto the base unit.

Apply the power to the A/T module.

Down-load the analog timer operating program on the CPU module.

Operation

Set the selection switch for operation mode to ‘RUN’.

(See Section 3.4.2)

Chapter 9. DIMENSIONS

9 - 1

Chapter 9. DIMENSIONS 9.1 Dimensions

8.1.1 G3F-AT4A

Unit : mm

G3F-AT4A

9.1.1

Chapter 9. DIMENSIONS

9 - 2

9.1.2 G4F-AT3A

G4F-AT3A

Be sure to read carefully the safety precautions given in data sheet and user’s manual before operating the module and follow them.

The precautions explained here only apply to the G3F-AT4A and G4F-AT3A.

For safety precautions on the PLC system, see the GLOFA GM3/4 User’s Manuals or the MASTER-K 1000S/300S User’s Manuals. A precaution is given with a hazard alert triangular symbol to call your attention, and precautions are represented as

follows according to the degree of hazard.

However, a precaution followed with can also result in serious conditions.

Both of two symbols indicate that an important content is mentioned, therefore, be sure to observe it. Keep this manual handy for your quick reference in necessary.

SAFETY PRECAUTIONS

WARNING ! I If not provided with proper prevention, it can cause death or fatal injury or considerable loss of property.

CAUTION ! I If not properly observed, it can cause a hazard situation to result in severe or slight injury or a loss of property.

CAUTION !

CAUTION !

Installation Precautions

▶ Operate the PLC in the environment conditions given in the general specifications.

▶ If operated in other environment not specified in the general specifications, it can cause an electric shock, a fire, malfunction or damage or degradation of the module

▶ Make sure the module fixing projections is inserted into the module fixing hole and fixed.

▶ Improper installation of the module can cause malfunction, disorder or falling.

Test Run and Maintenance Precautions

CAUTION !

▶ Do not separate the module from the printed circuit board(PCB), or do not remodel the mod-ule.

They can cause disorder, malfunction, damage of the module or a fire.

When mounting or dismounting the module, perform them after the power has been turned

off.

▶ Do not perform works while the power is applied, which can cause disorder or malfunction.

CAUTION !

Waste Disposal Precautions

▶ When disposing the module, do it as an industrial waste.