Global Harmonization of Data Center Energy Efficiency Metrics

Submitted by: Nomura Research Institute

Green ICT SeminarBandar Seri Begawan, Brunei Darussalam

3 August 2010

Page 2: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Global Harmonization of Datacenter Energy Efficiency Metrics

August 3rd, 2010Takao Shiino, Ph.D.

Nomura Research Institute

Page 3: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 20102

DataCenter

2

Page 4: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Future Energy Consumption of DataCenters(Japan)

Estimated Energy Consumption of DataCenter

Source : Green IT promotion council 20093

Page 5: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Future Energy Consumption of DataCenters (World)

Estimated Energy Consumption of DataCenter

Source : Green IT promotion council 20094

Page 6: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Datacenter Energy Flow and Boundary of Metrics

5

Power Plant

Solar. Wind. CHP. etc

Local Power

Grid PowerData Center Infrastructure

Air conditioner.

Power Supply.

Lightings etc.

Hardware

ITEEPUE ITEUGEC

Data Center

Efficiency of Energy Procurement Efficiency of FacilityEfficiency ofHardware

Efficiency ofSoftware and Operation

Software

and

Operation

IT Equipment

DPPE

Page 7: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

6All Rights Reserved, Copyright © GIPC 2010

DPPE

ITequipment work rate

IT equipment work capacity

×DC energy

IT equipmentenergy

×DC energy

DC energy-Green energyIT equipmentenergy

Note) DC energy: Total power consumption of Data Center

Datacenter Work

DC energy – Green energy

New Metrics, & its 4 sub metrics

The concept of DPPE is based on the following formula:

×

=

=

DC energy – Green energy

IT equipment work rate

IT equipment work Capacity×

=

“ITEU” “ITEE” “PUE” “GEC”

Page 8: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Necessity of new metrics for entire Datacenter

It is necessary to create a usable and agreeable Metrics to express energy efficiency of the entire data center with both “IT equipments” and “Data Center infrastructure”.

“PUE” metric, TGG created, is widely used and accepted throughout the world.PUE is understood as a metric which has a focus on the Data Center Infrastructure.

PUETotal Energy by Data Center

Energy by IT equipments=

Infrastructure(Power, A/C etc)

IT Equipment(Server, Storage,

NW)

Category Change in “PUE” number

Improvement on Energy Consumption will change PUE

Effort of Energy Consumption will not appear on PUE

– i.e. Highly Efficient IT Equipment will not necessary yield good PUE number.

7

Page 9: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Development of “DPPE” in JapanDPPE is developed by the Green IT Promotion Council (GIPC) of Japan.

Datacenter Sub Working Group

– Members: • NTT Data, Intel, Nomura

Research Institute, Daiwa Institute of Research, IBM Japan, NEC, Fujitsu and others.

– MOU with The Green Grid for joint Collaboration

Year Activities

Defined initial DPPE metricsSurveyed Japanese Data Centers1st Work Shop with EU & US

2008

Refined DPPE metricsContinuous discussion with TGG2nd Work Shop with EU & US

2009

Developing measurement guideline

Conducting measurementdiscussion with EU & US

2010

8

Page 10: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Discussion on metrics of DC energy efficiency・2 Feb 2010, in San Jose, Calif. U.S.・Members:

Japan: METI, GIPC, JEITAUS: DOE, EPA, TGGEurope: EC

Global Harmonization of New Metrics

In Feb. 2010, the 2nd International workshop of EU, U.S., and Japan was held. At the workshop all parties agreed to continue the work on establishing a method to measure the entire Data Center efficiency.

2nd workshop on metrics of DC energy efficiency Agreement

All agreed that IT Equipment inclusive of entire Data Center based metric is needed.

Source: http://www.greenit-pc.jp/topics/release/pdf/dppe_e_20100416.pdf 9

Page 11: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Usefulness of the DPPE By the separate application of DPPE’s 4 sub metrics for each line of responsibilities, the entire effort for the Energy Efficiency of the Data Center could be divided into 4 different responsibilities.

Entire Data Center Efficiency must be doubled! So, we need to double the

DPPE number.

CIO

We need to make

ITEE 40%

better

We need to make

ITEU 20% better

We need to make

PUE 20%

better

We need to make GEC x

1.1

CIO CIO CIO CIO

Operations Dept. Purchasing Dept. Facility Dept. Facility Dept.

We could buy Equipments

with 20% improvements.

We could improve

Operations by ……..

We could improve

AC efficiency by xx %

We could use xx KW

of PV

1. CIO determines total goal of DPPE

2. CIO decides goals of sub-metrics and tells them to managers

3. Managers determine plans to achieve each goal.

1.2 x 1.4 x 1.2 x 1.1=2.2 > 2

10

Page 12: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Schedule of Metrics Standardization

Trial of DPPE in Asia,US,EU

Global Harmonization Meeting of Japan,US,EU

2010 20122011

11

Trial of DPPE measurementin Japan and Singapore

Discussion with Standardization Body

Discussion on Data Center Energy Efficiency Metrics

Page 13: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

DPPE Measurement Trial in Japan

Outline Purpose

DPPE Measurement Trial within 2010 in Japan.

Schedule

Subjects

Jul-Sept: 1st phase of the measurement trial. Sept: Analyze the 1st

phase.

Target subject Data Centers will be 20 in Japan.- Mainly, GIPC, JDCC, JISA, ASPIC and others’ member Data Centers.

By measuring DPPE at actual DCs, find problems of DPPE, and verify the effectiveness of the metrics.

Note: Japan Data Center Council (JDCC), Japan Information Technology Service Industry Association (JISA), ASP・SaaS Industry Consortium (ASPIC)

Measurement at actual Data Center

Identify all issues Validate all issues

Revise definition and guideline

12

Page 14: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Green ofEquipment

Effective Green IT with all participants

Green of Use

Improve Utilization

Capacity

Activity×

Energy

Capacity×CO2 = Activity ×

Energy

CO2

Green ofEnergy Source

13

Improve Energy

Productivity

Improve Energy

Mix

Page 15: Global Harmonization of Data Center Energy Efficiency Metricsmddb.apec.org/documents/2010/TEL/TEL42-DSG-WKSP2/10_tel42_d… · Note) DC energy: Total power consumption of Data Center

All Rights Reserved, Copyright © GIPC 2010

Ways to improve energy efficiency of Data Center

Target Environment friendly , sustainable Data Center operation .

MetricsITEE

IT EquipmentEnergy Efficiency

ITEUIT Equipment

Utilization

II IIPUE

Power UsageEffectiveness

GECGreen Energy

Coefficient

IIII

Reduce % of energySpend on facilitiesversus total energyconsumption

Replacegrid electricitywith Green energy

Realizationmethod

Install IT equipments with less energy consumption

Use introduced IT equipment withoptimal efficiency

Reduce energy consumptionof facilities in DataCenter

Reduce energy consumption ofIT equipments in DataCenter

14