geoembalses, manual de instalacion, geomembranas
DESCRIPTION
Geoembalses, manual de instalacion, geomembranasTRANSCRIPT
POWERED BY
INTEREXSA
Internet ww.geoembalses .com
E-mail info@geoembalses .com
Phone +34 610755237
Below mentioned application instruc tions do not replace the projec t documentation and are only of supportive nature.
Juta policy of constant product improvement may mean, that data mentioned in this manual can be changed without prior approval.
TECHNOLOGICAL STANDARD
Summary:
General description of the product ................................................................................................ 2 Welding and tests of HDPE geomembranes ................................................................................... 5
Preparation of an installation....................................................................................................... 10 An installation............................................................................................................................. 13
Use of geomembrane for waste landfill sealing ............................................................................ 21 Other possibilities of geomembrane use ...................................................................................... 26
A list of used literature................................................................................................................ 27
Basic description
The geomembrane GEOEMBALSES BY INTEREXSA (high density polyethylene) is made
from high quality raw material - granulate by
extrusion technology. Material is resistant to chemicals, alkaline, acid and salt solutions.
2
However, various combinations of chemical agents with different concentration and
temperature can appear and that is why we suggest to contact us to consult individual cases.
Material resists to mildew, microorganisms and to
roots penetrating. The geomembrane is safe to health, it also does not affect drinking water. The
geomembrane is UV stabilized. Compared to other polymers, the geomembrane
is characterized by high resistance to chemicals (an aggressive environment of waste landfills),
excellent mechanical properties (high strength,
tensile), long lifetime.
The HDPE geomembrane GEOEMBALSES is
produced in the standard: - width of sheet: 5,10 or 8,0 m
- thickness: 0,60; 0,75; 1,00; 1,50; 2,00; 2,50 mm
- type: smooth/smooth; smooth/textured;
textured/textured - length of roll: according to the type and
thickness An advantage of a wide sheet is a significant
reduction of a number of welds that are generally the most sensitive point of the sealing system. At
the same time the width of the sheet enables
relatively easy handling with individual rolls.
Each roll is marked with a self-adhesive label containing specifications of the product. The
labels help with the product identification. An ispection certificate is issued for each roll. Those
steps are a part of an internal control system.
The sealing geomembrane GEOEMBALSES meets the Government Regulation No. 178/97 Sb.
from 25 June, 1997 that determines technical requirements for building industry products and
meets requirements of these regulations and standards:
The law about waste No. 125/1997 Sb., the notice MŽP about waste disposal No. 338/1997
Sb., ČSN 838032, ČSN 838035, ČSN P 730606, ČSN P 730610, ČSN 730601, ČSN 730602 and
others.
Juta a.s. issued a written statement about the product conformity with technical regulations and
about adhering to the determined procedure of the conformity review on the bases of
explorational tests carried out by an authorized institute ITC Zlín and the certificate No. 991177
V/AO, No. 991178 V/AO, No. 991179 V/AO from
20/12/1999, an authorized institute TZÚS Praha and the certificate No. 01-5461 from 14/6/2000
and the certificate No. 01-5997 from 21.2.2001.
Recommendation for use of the GEOEMBALSES-HDPE geomembrane
GEOEMBALSES th. (mm)
Application 0,6 0,75 1 1,5 2,0 2,5
Insulation against radon x x x x x x
Insulation against dampness x x x x x x
Hydro-insulation of buildings x x x x x
Reservoirs sealing x x x x
Sealing of fuel supplies and supplies of chemicals
x x x x
Landfills sealing S II x x x
Landfills sealing S III x x x
Landfills sealing S IV x x
Landfills capping x x x x
Sealing of water constructions - ponds and rivers
x x x x x
Most of the information stated in the following chapters applies to waste landfills insulation and to insulation against pressure water. A use of the GEOEMBALSES
geomembrane for insulation against dampness, radon and for hydro-insulation of buildings follows different principles.
Warranties and guarantiees
Quality guarantee An internal Geomembrane manufacturing quality
assurance system was designed to specifically control the quality of the product. The principles
of the systematic regular quality assurance
3
control is the BAM Berlin method. All tests on the geomembrane are in accordance with this
procedure, including the frequency of testing.The supervision of the geomembrane quality is a
subject to testing at independent institutes - TGM
WIEN, MPA DARMSTADT and ITC Zlín. The
geomembrane is certified for use in many countries throughout the world. The
geomembrane is manufactured in accordance with the company ISO 9002 quality system
procedures.
4
Welding Welding can be carried out only at temperatures
above +5°C and at relative humidity of air 85% max. It is necessary to carry out special steps in
special cases. Before welding begins, it is
necessary to carry out test welding with material intended for the process while relevant welding
parameters (temperature, speed, pressure) are set (or determined) on the welding machine. Test
welding should be carried out 1x/day at least, or with each change of welding conditions. Data
regarding the test welding and welding samples
should be recorded in a protocol. There is no standard in the Czech Republic that
would regulate ways of welding and tests of geomembrane sealing. We follow German and
Austrian standards for application and tests.
If the geomembrane is being joined, separate
sheets have to overlap each other longitudinaly and transversaly.
Ways od welding a) welding by hot wedge - welding without
welding additives
b) welding by hot air - welding without welding additives
c) extrusion welding - welding with a welding additive, i.e. extrudate
- a raw material of the extrudate and the geomembrane has to be identical
Types of welds
a) overlapped welds without a trial canal (simple joint)
b) overlapped welds with a trial canal (double joint)
c) deposit welds (extrusion joint)
bp = width of trial canal ü = total lapping
do = thickness of top sheet ü1 = front total lapping du = thickness of bottom sheet ü2 = back total lapping
dN = thickness of seam bN = total width of seam dN1 = thickness of front partialseam bN1 = width of front partial seam
dN2 = thickness of back partialseam bN2 = width of back partial seam
5
It can be proved that dimensions of the weld meet regulations in regard to the material and to
the use, or requirements in regard to a project: » back loose lapping should be at least 40 mm,
also because of a trial-technical reason. Front
loose lapping should be max. 5x the thickness of the sheet. Locally terminated deviations do not
affect the quality of the seam. » a width of seams and canals concluded in a
contract, or written in regulations for a specific use, must be kept;
» thicknesses of seams should be regular along
the width and length and should be limited by the sort of thickness and by working process.
Conclusive definitive standards for thicknesses of seams
fNA = a factor of seam thickness for an applied
weld = dN/(do + du) da = a joining track (a change of thickness) for a
lapped seam = (do + du) - dN Lapped seams without additional material
Sheets made of partly crystallic materials, for example HD-PE 0,2<da<0,8
Sheets made of unformed materials 0<da<0,6
Lapped welds 1,25<fNA<1,75
6
Inspection of welds quality a) visual check
Skilled rewiev of external condition requires special professional knowledge and experience.
Conclusions about tightness and strength of a
weld can be deduced generally only. b) a check of seam dimensions
This test finds out characteristic dimensions of a seam on strip trial bodies from a weld, or on the
weld itself. Measured values should meet dimensions stated
in the chapter 5.1.2. (seam types)
c) seam tests - tests can be destructive and undestructive.
c.1. destructive
To find out strength of a joint properly,
destructive Peel Test in Traction (peeling tests) are carried out on random samples.
As trial pieces, samples taken upright to the weld are taken the way so that they have a sufficient
length of a fix. The peeling test is carried out on each weld
during the insulating system assembly directly at
a waste landfill by a mobile tearing device, one test per each 100 m of the weld at least.
The peeling test is considered successful if a
sealing sheet has been prolonged next to the weld (so-called a plastic deformation) and then the
geomembrane sheet has been torn outside the weld.
c.2. undestructive tests
During parallel testing of welds for tightness it is
necessary to adjust the testing process to a particular form of the weld. According to that, the
following processes are used: Lapped seams without a trial canal
A test by a high voltage
A test by vacuum Lapped seams with a trial canal
A test by compressed air Deposit welds
A test by a high voltage A test by vacuum
A test by compressed air A test by compressed air tests a tightness of
lapped welds with a trial canal (double-weld) at a defined mechanic stress.
Testing conditions, as a trial pressure and
duration of the test, have to be adjusted to a sheet material, a sheet thickness, to trial canal
dimensions and to temperature. The test can be carried out 1 hour after the
joining soonest. Temperature of the sealing sheet can be max. 60°C.
At one end, a device for supply of compressed air
with a manometer or a pressure register is installed, it closes the trial canal hermetically.
Here the compressed air is brought and then clearness of the seam is tested. The other end of
the weld is closed hermetically, for example by
welding with hot gas or by a clamp device. A trial pressure itself is adjusted not until one
minute of preliminary stress so that initial deformations are conditioned. The preliminary
stress is set to same values of the final test pressure.
A trial time for testing by compressed air is 10
minutes. When the trial time is out, a canal at the opposite end has to be opened. Air must escape
at once. Welds that cannot be tested parallely are tested
section by section. If there are some mistakes
that cannot be determined instantly we have to appoint suitable shorter trial sections to limit the
problem sections.
7
A seam is considered tight if the pressure in the trial canal does not fall more than 10% of the
initial value during a specified trial time.
The trial pressure follows the geomembrane
thickness. Values are stated in the following chart:
geomembrane
thickness (mm)
pressure (bar)
1,0 1,5 - 2
1,5 2,3 - 3
2,0 3 - 4
2,5 3,5 - 4,5
A vacuum test A vacuum test can be used to control tightness
either lapped seams, or deposit welds. The test proceeds by means of a see-through trial cover
(bell) connecetd to a vacuum pump. The cover
has a pressing sealing ring on its rim to close the tested area hermeticaly.
During the test, a vacuum (depression), that needs to be adjusted to the material and
thickness of sheets and to dimension of the trial
cover, is ran into the cover. Non-destructive tightness tests of of lapped
seams with joined (closed) front edges and of deposit welds can be done by the vacuum test
section by section. Relevant shaped trial covers are used for corners,
edges and angles.
A minimum of 1 hour should pass between joining and testing to create a time space for
conditioning. A tested seam area is smeared, or sprinkled, by a liquid creating bubbles, for
example a soap solution. (It has to be insured
that this liquid, in given conditions, does not affect unfavourably a longtime seams behaviour.)
The trial cover is applied and compressed the way so that the tested seam lies approximately
centrally to the axis of the trial cover. During removing of the cover, it is necessary - due to
longer tested sections - to keep the overlap of the
tested areas = 10 cm. Sheets are tested under the pressure of 0,4 bar. These trial pressures
(depressions) have to be constant for at least 10 sec.
The vacuum is indicated by manometer. Bubbles
appear if the seam is not tight. These locations are marked.
The seam is considered tight if the vacuum is increased fluently, stays constant during the trial
time and no bubbles appear in the seam. Due to a big time absorption for testing of long
seams, the vacuum test is usually limited to short
seams and partial areas as corners, connectors, T-joints and so on. The vacuum test can be an
additional test for other testing methods.
A test by a high voltage This testing process is based on a principle of
discharge in gas, an application of a high voltage
on a discharging track. Testing device composes of a voltage source and
a brush electrode. The process expects an opposite electrode made
from conductive material at the back side of the seam.
Basically we can test tightness of all kinds of
seams by this process. The test is used mostly for deposit welds, i.e. for welds which do not have a
trial canal. The seam area has to be dry and clean; dirt
particles can create an insulating layer and
influence the test this way. A trial voltage has to be adjusted to the material
and thickness of the sheet and also to the weld width (the trial voltage is 15 - 40 kV).
For example, for PE-HD sheets 2,0 mm thick and more is 40 kV an acceptable trial voltage. If the
trial voltage is 40 kV, a width of discharge is more
than 15 mm in dry air. That is why, for example, cca 30 mm wide deposit welds can be tested if the
electrode lies in the middle of the weld, non-tightness is parallel and runs approximately
upright the weld. The moister the air is the bigger
the widths of discharge are. A brush electrode is run over the weld at speed
10 m/min. It has to be ensured that the power creating flashover of the sparkle can be created.
Flashover of sparkles between electrodes that can be seen and heard happens at non-tightnesses
parallel with the whole length (a half of the weld
width). The weld is considered tight if there is no sparkle
discharge. It is possible to prove only no-tightnesses which
are parallel and they run upright the weld. The
distance of the brush from the weld has to be adjusted the discharge width in the air.
8
Test protocols
Results of tests at the building site are stated in the
test protocols.
9
An installation plan Geomembrane sealing is laid in accordance with
an ahead prepared istallation plan which determines dimensions and mutual position of
separate sheets of the geomembrane laid to the
sealing. On the slopes of the waste landfill the geomembrane should be laid the way so that it
could be unrolled down the hill. Lay-out of the geomembrane sheets at horizontal parts is
adapted to this requirement. Lay-out of separate sheets has to be placed so that the joints will not
cross at a single spot.
Joining of separate geomembrane sheets is done by welding. The way of welding has to meet the
geomembrane producer s requirements. In order to join separate parts of the geomembrane after
they had been put down, they have to overlap
each other sufficiently at longitudinal and transversal direction (see part 5 - welds).
Before installation works begin it is necessary that the supplier proposes a plan of the installation
with marked welding seams to the inspection body. It is necessary to remember that cross
joints should not appear in the plan and also there was as few extruded welded joints as possible.
Deviations during the installation works are acceptable with an agreement of the inspection
body. A plan base for the installation plan has to
be provided by a planner in time.
The installation plan should include the following points at least:
- the weld position - uniform marking of all welds
- a position of special constructions (for example -
ends of pipes, connecting with present constructions)
- according to their types (see the chapter 5.1.2.) - a conventional width of used plastic sealing
sheets
- a registered name of the product according to RN S 2073
Possible ways of geomembrane sheets modification at the corners of the waste landfill
are shown on the following pictures.
A) a tree with an inserted sheet.The method is a
classic solution of the waste landfill corner.
10
B1) a tree - a waste landfill - This method is used
on short slopes in the waste landfill corners.
B2) a tree - overlapping - This method is mostly
used for waste landill capping
C) a slope - Corners - This method is used mostly for
shorter slopes to cap waste landfills or for fractional slopes of oblong waste landfill shapes.
POWERED BY
INTEREXSA
Internet ww.geoembalses .com
E-mail info@geoembalses .com
Phone +34 610755237
11
Ending of the geomembrane sheet laid on the slope must not be done at the bottom of the
slope. A minimal distance from the bottom is 1,5 m. A minimal distance of two (T) joints from each
other should be 0,5 m.
Handling, transport and stocking In order not to damage the matrial during the
transport and handling, it is necessary to adhere to the following policies:
The transport has to be done by suitable clean vehicles with sufficient load carrying capacity. A
special attention has to be paid to loading and
unloading of the geomembrane, to ensure that it will not be damaged mechanically. A common
transport is in three layers. 4 rolls at the bottom layer, 3 rolls at the middle layer and 2 rolls at the
top layer. Rolls must be secured against
movement by wedges and belts. A suitable vehicle has to be used for unloading - a crane or a
forklift truck. We suggest using textile belts with a sufficient carrying capacity.
It is necessary to put rolls on a flat surface, free of sharp objects (stones, branches etc.) at the
construction site. To protect the geomembrane, a
base layer of geotextile can be used, NETEX S 1200 for example (joists or europallets). It is
possible to store the rolls in three layers this way. Rolls must be secured against movement.
Whole manipulation with sealing materials must be carried out the way so that they will not be
damaged or degraded. If that happens, they must
not be used in the sealing system. A base for geomembrane sealing
Establishing of subgrade conditions should be done in sections by geotechnical supervision, a
base layers supplier and by an installation company. A report needs to be made and it will
be passed to the installation company as an
agreement with starting of installation works. The installer carries out a visual control of the surface
and marks it in the inspection protocol before the sealing sheets are unrolled. It is necessary to
ensure determined values of requirements
regarding the sealing area before the sealing sheets are laid.
The geomembrane can be laid only on a firm, level and smooth surface of the base without
sharp objects. If it is necessary to lay the geomembrane on a coarse-grained material
subgrade, it is necessary to underlay the
geomembrane with more suitable material or with geotextile of corresponding parameters.
12
Climatic conditions Surrounding conditions can have an essential
influence on the way of joining and thereby on the quality of the joint. It is necessary to keep the
following:
» welding is not allowed without safety arrangements if it rains (a local covering etc.)
» welding should not be carried out if the temperature is lower than +5°C; in exceptional
cases it is necessary to do special arrangements (a tent) and to pre-heat geomembrane sheets
» a continuous weighting of geomembrane
sheets has to be ensured if it is windy » with welding machines working on a principle
of geomembrane heating during welding with a hot air it is necessary to ensure a protection of
the welding machine against a direct influence of
the wind on the hot air flow. The same arrangements stand for an extrusion welding - a
danger of cooling and “blowing away, overheat”
An installation and securing of geomembrane sheets
Laying down a sealing sheet can start only if there
cannot appear any permanent changes of conditions regarding the subgrade during the
installation. It is necessary to remember the protection against wind. A thermical expansion
(“waving”) conditioned by heat is permissible, it
follows material properties (a heat expansivity) and it cannot be prevented practically. That is
why a technological process must count on it, however folding of "waves" must not happen. A
coefficient of a plastic sealing sheet thermal expansion should be used the way so that pouring
of protection drainage layers takes place when
"waving" of geomembrane sheets is minimal. We recommend a presence of an external supervision
during this process. The geomembrane is protected against possible
damage by wind by an adequate weighting of the
surface (for example tyres, sacks with sand etc.) and by anchoring to anchoring grooves (notches)
immediately after its installation. All control steps need to be done before covering the
geomembrane to ensure a quality of the geomembrane coat.
For each geomembrane sealing we recommend an
installation of equipment for geomembrane integrity control which will be carried out when
drainage or covering layers have been laid down.
A testing weld Before the welding works begin, it is necessary to
carry out - 1x a day at least or before each
change of welding conditions - test welding with the material determined for process while there
have to be set, or determined, relevant welding parameters on the welding machine. Then it is
necessary to take sample every 100 lm of the
weld, the same with bigger temperature changes, wind power or air dampness, and also if the
process of welding has been interrupted and if there have been detected defects on the used
welding machine. The welding test is considered positive if there is an extention (a plastic
deformation) along the weld during the peeling
test by the weld.
Welding and tests Procedures during welding and geomembrane
tests are described in detail in the chapter 5.
Details
Design of details around penetrating bodies If some waste landfill device (for example shafts,
pipes) penetrates the sealing, the sealing system must be connected to this device safely and
waterproof so that the sealing cannot be affected
by influence of various vertical and horizontal deformation of adjoining structures.
Joining of the sealing geomembrane to other waste landfill structures and sealing penetrations
must be taken care of in details of the sealing
system project. Some of possible penetrations and joining to concrete constructions follow.
13
A) Pipe penetration through sealing by means of PEHD plate
B) Pipe penetration through sealing with use of more sealing layers
14
C) If some material other than geomembrane penetrates, it is possible to use a penetration by
means of a sleeve (cuff) from GEOEMBALSES geomembrane
A pipe is fastened to the geomembrane sleeve by
a pulling collar (the pull) and by sealing material. We recommend to use two pulling collars.
15
D) Other was of joining pipes from other material than the geomembrane is made of is joining by means of a firm and a loose flange.
Ways of anchoring to concrete constructions: Against descending water
(anchoring of insulations at top parts of shafts, reservoirs etc.; at which the anchoring will not be
strained by pressure water for even a short time).
For those applications, a ledge made from Pz, Cu or Al plate with a corresponding mastic is a
sufficient anchoring element, distance of anchoring elements (rivets, anchoring dowels,
anchors etc.) is 100 - 200 mm.
16
Against pressure water or short-time strain by pressure water
To join the GEOEMBALSES geomembrane to a concrete construction, it is possible to use a plate
that is anchored in the concrete by screws and anchoring dowels. Distance of separate screws
depends on a solidity of the ledge and on the type of anchoring.
Anchoring of the geomembrane to concrete by a
stainless steel ledge
Distance of screws depends on a solidity of an
anchoring ledge, or of an anchoring profile (for
steel amchoring plate 10 mm thick the distance should not be bigger than 150 mm).
It is also possible to anchor the GEOEMBALSES
geomembrane to concrete by a PEHD anchoring
element. This anchoring element is installed
already during concreting itself and the GEOEMBALSES geomembrane is anchored to it by
an extrusion weld.
Anchoring of the geomembrane with a HDPE
anchoring element
17
Anchoring on slopes Geomembrane sealing and protective geotextile
have to be anchored on slopes. Anchoring ditchs (notches) are usually used for this purpose. This
anchoring should ensure not only reliable
anchoring of the sealing to its surroundings and its ending but also to support its stability on the
slope. A rim of the geomembrane sheet in the anchoring
groove is overlapped so far that it covers the whole bottom of the ditch. The ditch dimensions
depend on the length and the slant of the slope,
on the kind of the used geomembrane and on the kind of separate sheets of the sealing system.
Minimal recommended values for the slope slant
up to 1 : 2,5 are stated in the chart
length of slope length in m
length of slope a b c
<10 m 0,5 0,5 0,5
10 - 30 0,8 0,6 0,6
>30 m 1 0,8 0,8
We recommend to use bench on long slopes. Sealing
can here be fixed by terrestrial inter-ditch.
An important factor is to ensure a temporary
stability of the geomembrane for the time when the anchoring ditch is not finished (properly
earth-filled and firmed). The geomembrane can be partly pulled out from the notch because of
temperatures influence and that way its influence
on the geomembrane stability can be reduced. We recommend to anchor the geomembrane by steel
hooks or by a similar way to the bottom part of the terrestrial ditch.
18
A stability of a sealing system on slopes A stability of separate elements of sealing and
drainage system and of protective and capping layers on the slopes of a waste landfill subgrade
or on waste landfill slopes during its closing have
to be proved in the waste landfill design. Data about physical-mechanical characteristics of
separate materials, obtained from their producers, and by carrying out relevant tests in a
range of project and geotechnical and research works, are used for this purpose. In this solution
of stability, especially protection against mutual
displacement of sealing system separate layers and its movement on the subsoil surface have to
be proved. Friction rates between the GEOEMBALSES
geomembrane and various soil materials and
between the GEOEMBALSES geomembrane and the top protective or filter layer have a crucial role
to determine a static safety on slopes. The safety is ensured if a sum total of sliding forces is
smaller than a sum total of frictional forces. To increase transmission of forces in a filter layer
above an insulating sheet, textured sheets can be
used. Strain deformations between separate terrestrial layers affect friction rates above and
under the geomembrane.
The JUTA company a.s. Dvůr Králové produces, apart from the HDPE geomembrane with a
smooth surface, also a geomembrane textured on one side or on both sides.
A project designer can use the GEOEMBALSES
geomembrane with a structured surface where it is needed to increase a safety coefficient and the
slope slant. The use of structured geomembranes has an influence on improvement of all kinds of
factors for various applications. The geomembranes with the textured surface are
specific with smooth trims cca 15 cm wide. It
means that common procedures of smooth geomembrane joining can also be used for
textured geomembranes. The welding technology does not require any change for direct joints. For
sheets where we have to weld the sanded part it
is necessary to remove the sand (grinding machine, scrape), or to re-set parameters of the
welding machine. Advantages of textured geomembranes in contact
with soils or geosynthetic materials are: - high friction coefficient with soil
- high friction coefficient with geosynthetic base
- high angle of inner friction with the top protective geotextile
A chart of friction angles of the GEOEMBALSES geomembrane with various materials
Material Textured PEHD geomembranes
Friction angle (in grades)
Smooth PEHD geomembranes
Friction angle (in grades)
Sanded clay 35 18
Fine-grained clay 32 16
Nonwoven geotextile (Netex) 33 11
Bentonite mat 33 11
Sand 35 20
Concrete 42 22
Above stated values are of informative character only. The producer recommends to carry out
shear tests of relevant geosythetic materials and
natural components creating an insulating system for a particular application.
Protective and covering layers
When the sealing sheets have been welded and the tests done, or after they have been assumed,
it is immediately necessary that the installer puts down the geotextile protective layer if it is
specified by a project designer.
The sealing system in whole and its separate parts must be protected against damage during
building works, during the operation and after the closing of the waste landfill.
The protection of the sealing system elements has
to be included already in the design of the sealing system constructional lay-out and in the specified
work processes for establishing of its separate
parts. If some construction is damaged anyway, it
has to be recorder and the defect removed immediately.
No vehicles or machines can wheel directly on the geomembrane sealing surface. A movement of
belt machines is allowed only after a sufficiently
thick (0,30 m at least) protective or drainage layer has been laid or when inner temporary
communications have been built of pannels, hurdles etc.
Documentation of realization The installer should adapt the installation plan in
accordance with an actual situation, i.e. a
19
realisation documentation (a record about relevant changes of installation, a record about
the places where test samples were taken) should be disposed.
Procedure for an initiation of an installation Heaping up of the first layer should be done by a
front pouring of the layer at least 1 m thick so that the machines or trucks move only on this
layer (in the case of wheeling directly on gravel drainage layer there is a danger of “earthing of
the machines” or trucks and the following damage of the geomembrane sealing). Before it is laid, a
protective geotextile has to be laid if it is specified
by a design. The first layer of waste should be created by loose material free of bigger parts
which could damage the geomembrane (metal, concrete etc.).
20
The waste landfill sealing is designed in regard to the general lay-out of the waste landfill, sorts of
waste which will be deposited in it, a class of its leaches and to natural conditions of the waste
landfill locality. Requirements for the waste
landfill sealing system for the given conditions in the subgrade and for the class of a water leach of
the deposited waste are stated in ČSN 83 8030. The sealing system for sealing of the waste landfill
is designed in regard to the kind of deposited waste and its characteristics, to a constructional
lay-out of the waste landfill and to the way of
capping of its surface. Requirements for the structure of the waste landfill sealing system in
regard to the class of the deposited waste leach are stated in ČSN 83 8030 and ČSN 83 8035.
The waste landfill sealing system has to be
designed from materials and the way so that its integrity and function cannot affect settlement of
the waste landfill and its subgrade, effects of internal and external water and climatic
conditions, or results of activity of people, animals and plants on the waste landfill and its
surroundings. Separate layers of the sealing
system, its subgrade, covering layers and the system as a complex has to be stable.
If a system with more sealing layers is being designed (multiple sealing), it is recommended to
use, for separate sealing layers, various sealing
materials whose favourable characteristics complement each other and do not eliminate each
other in an unfavourable kind of way.
Waste landfill sealing Waste landfills are differed according to the way
of technical security and operating to four groups:
Group S I is specified for the waste of a category other waste whose water leach does not exceed
limit values of the leach class No. I. Group S II is specified for the waste of a
category other waste whose water leach does not
exceed limit values of the leach class No. II. Group S III is specified for the waste of a
category other waste which cannot be specified on the bases of the water leach and for the waste
whose water leach does not exceed limit values of
the leach class No. III. Group S IV is specified for the waste of a
category dangerous waste and also for the waste whose water leach exceed limit values of the
leach class No. III.
A sealing system is a system of sealing materials layers (natural or artificial) completed by other
layers for their mechanical protection. A sealing layer is a layer of a sealing material that
creates a simple sealing barrier. It meets requirements of ČSN 83 8030.
A multiple (combined) sealing is a sealing system
including more layers, generally from various sealing materials.
For simple sealing it is possible to use any of sealing materials. For multiple (combined)
sealings, a suitable combination of sealing
materials is used the way so that the less favourable conditions of some materials are
eliminated for the given conditions. That way a terrestrial sealing is prefered to one sealing layer.
Waste landfills group S I Waste landfills from the group S I do not require
any technical barrier. A subgrade of those waste
landfills has to be free of a vegetative coverage and of a humus layer. Waste in accordance with
the leach class No. I/II. can be deposited also to non-sealed waste landfills with an access of
groundwater.
Waste landfills group S II Waste landfills from the group S II have to have
one barrier - natural or technical. As a natural geological barrier can be considered a subgrade
with a thickness at least 5 m of minerals with a coefficient of filtration k
1.10-8m.s-1
10 m of minerals with a coefficient of filtration k 1.10-7m.s-1
In case that the subgrade does not have a natural geological barrier it is necessary to build a
technical barrier. One of the mostly used options
is a geomembrane sealing. In case that a basic seam is made by surrounding minerals or by
rough material it is necessary to design a sufficiently thick and firm layer from fine-grained
soil under the sealing.
21
Waste landfills group S III Waste landfills from the group S III have to have
at least two barriers. A simple sealing is enough if the waste landfill
subgrade is created by anatural geological barrier
- at least 3 m thick with a permeability characterized by a coefficient of filtration
k 1.10-8m.s-1 - at least 30 m thick with a permeability
characterized by a coefficient of filtration k 1.10-7m.s-1
The sealing has to be established on the whole
area where the waste landfillbody meets a terrain.
In case that the subgrade of the waste landfill does not have a natural geological barrier it is
necessary to build a multiple sealing. The mostly
used option is a combination of a mineral sealing and a sealing geomembrane.
Other from possible sealing systems for waste
landfills from the group S III is a combination of a
bentonite mat (and similar materials) and a
sealing geomembrane.
It is possible to use two sealing geomembranes in
the sealing system at special cases. The ČSN 83 8032 The Waste Landfills Sealings Standard does
not forbid this option but it does not recommend
it either. In the case of use of this option it is
necessary to give reasons for use of sealing layers.
A structure of a layer on the waste landfill bottom:
22
A structure of a layer on the waste landfillslope:
Waste landfills group S IV
Waste landfill for waste from the group S IV are designed individually in regard to a character and
possible interactions of the deposited waste and its danger for various parts of an environment.
Those waste landfills can be built in localities
where the subgrade is characterized by a coefficient of filtration K 1.10-8 m.s-1 for a layer
at least 5 m thick. On the whole area where the waste landfill body meets a terrain, a combined
sealing has to be established, created by a
mineral with a coefficient of filtration K 1.10-
9m.s-1 whose final thickness (in firm condition)
has to be at least 1 m. A terrestrial sealing is added by a geomembrane of a reasonable
thickness, 2,0 mm at least, which resists
corrosion effects of leaking water. A need of other protective barriers or a use of other sealing
elements that it is stated has to be reviewed individually for each waste landfill.
Capping of waste landfills
Sealing layers of the waste landfill are usually created by a leveling layer, sealing layers and a
protective layer. Characteristics of the leveling
layer, especially its thickness and permeability, are designed in regard to the general lay-out of
the sealing layers. A protective layer protects the sealing layers against damage, especially
mechanical. It is usually created by a suitable geotextile or a suitable soil. A drainage layer is
designed from a permeable material at least 0,3
m thick with a coefficient of filtration k 1.10-
4m.s-1. A capping layer above the waste landfill
sealing has to be thick enough to ensure the protection of the top waste landfill sealing against
damage, especially by climatic and biological
effects. The recommended thickness of this layer is at least 1,0 m. To seal waste landfills, the
smallest thickness of the geomembrane is not
specified, however, its functionality has to be ensured for particular conditions of the waste
landfill for at least 30 year. The thickness of the
geomembrane has to be reasoned in all cases. In regard to the weld quality we recommend a
minimal geomembrane thickness 1,0 mm. A surface arrangement of the geomembrane - a
smooth surface, one-sided or both-sided sanded surface - is chosen in regard to its positioning. A
smooth surface is used on a level or a slightly
sloping areas, roughed on slopes, especially to ensure the stability (see the chapter 7.7.). The
waste landfill surface does not have to be watertightly sealed, however it is necessary to
consider a necessity to save a functional drainage
system of the waste landfill during the whole time of its influence on the surroundings.
POWERED BY
INTEREXSA
Internet ww.geoembalses .com
E-mail info@geoembalses .com
Phone +34 610755237
23
Waste landfills group S III
For waste landfills from the group S III a simple
sealing is designed. Geosynthetic materials with corresponding characteristics can also be used for
a drainage layer. JUTA a.s. Dvůr Králové produces
the Petexdren geosynthetic drainage system which can be used instead of the drainage layer.
24
Waste landfills group S IV For waste landfills from the group S IV a two-layer
sealing is designed
Use of geomembrane for waste landfill
sealing - comment
In the previous chapters 8.1. and 8.2. there are desribed sealing systems of waste landfills in
accordance with the Czech regulations ČSN 83 8030 and ČSN 83 8035. If you design sealing
systems of waste landfills in various countries it is
necessary to follow legal regulations of the
particular country. For example, Austrian
regulations ÖNORM S - 2073 and S - 2076 specify HDPE geomembrane min. 2,5 mm thick as an
entirely acceptable material for a basic sealing of waste landfills
.
25
Apart from the bottom sealing of waste landfills and their capping it is possible to use the
GEOEMBALSES geomembrane also in the following areas:
» a sealing of reservoirs and tanks
» sealing elements of supporting constructions (including object reconstructions)
» a surface sealing of pipes with big diameter, of drifts, tunnels etc.
» insulation of reservoirs and tanks foundations
» insulation of carparks, petrol stations,
chemicals stocks to prevent contamination of groundwater
» a sealing of irrigation and gutter drains » insulation of bridges, viaducts etc.
» insulation of constructions
The way of geomembrane installation for those applications depends on many factors and it is
necessary to choose them according to a particular situation.
The geomembrane installation can be generally
characterized this way. The geomembrane is laid on a base layer. A suitable base can be a firm
fine-grained soil, a gravel layer or a geotextile of corresponding parameters. It can be a concrete,
an asphalt-concrete etc in specific cases. When
permeability tests have been carried out, the geomembrane is usually covered by a protective
layer. The protective layer is again chosen in accordance with a particular situation.
A question of the geomembrane protection in case of its application on a surface of a supporting
construction is somehow contradictory. With
regard to the use of the GEOEMBALSES geomembrane characteristics, i.e. resistance
aginst insolation and resistance against other effects, efforts for the geomembrane sealing
concept without any cover is being enforced.
However, an increased danger of the sealing damage, intentional or untentional, appears here,
that is why it is more suitable to lay the geomembrane between well ordered base and
protective layers.
A general way of the GEOEMBALSES geomembrane installation
A possible way of the GEOEMBALSES geomembrane installation for terrestrial dikes sealing
Possible ways of installation for sealing of cannals, reservois etc.
26
- ČSN 83 8030 - Basic Conditions for Designing and Building of Waste Landfills - ČSN 83 8032 - Sealing of Waste Landfills
- ČSN 83 8035 - Capping of Waste Landfills - The German Standard DVS 2225
- The Austrian Standard ÖNORM S 2076
- Materials JUTA a.s. Dvůr Králové
Representatives of the JUTA joint-stock company are ready to answer all questions connected with the
design and the realization of the HDPE geomembrane GEOEMBALSES.
Elaborated by: Petr Kohoutek Ing. Jaroslav Tuček