gen.protections

Upload: ramesh-cherukuri

Post on 03-Apr-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Gen.protections

    1/74

  • 7/28/2019 Gen.protections

    2/74

    GENERATOR

    Generating units are the source of the power

    system and their security against anyadverse conditions is most important in the

    system.

    The GENERATOR protection must ensure afast and selective detection of any fault in

    order to minimize their dangerous effects.

  • 7/28/2019 Gen.protections

    3/74

    Generator is accompanied by excitation system,

    prime mover, voltage regulator, cooling system

    etc. Hence it is not a single equipment. Theprotection of generator should be co-ordinated

    with associated equipment.

    Protection of passive elements like transmissionline and transformers is relatively simple which

    involves isolation of faulty element from the

    system , whereas protection of generators

    involves tripping of generator field breaker,

    generator breaker and turbine.

  • 7/28/2019 Gen.protections

    4/74

    GENERATOR PROTECTION SCHEME

  • 7/28/2019 Gen.protections

    5/74

    GENERATOR AND GENERATOR

    TRANSFORMER AS A UNIT

    Station Transformer: 11/6.6 kv transformer

    with LV grounded through high resistance,

    feeds the station auxiliary load.

    Unit auxiliary transformer: 11/6.6 kv

    transformer with LV grounded through high

    resistance feeds the unit auxiliary loads

  • 7/28/2019 Gen.protections

    6/74

    Any earth fault on the 6.6 kv system cannot beseen by any E/L relay (since the 6.6 kv system

    is high resistance grounded ) However 3-O/Lrelays are provided on the 6.6kv side of thestation transformers and unit auxiliarytransformers. An open delta voltage of the 6.6

    kv bus PT is connected to an over voltage relaywith a very low setting. Any earth fault on the6.6 kv system will cause the presence of theopen-delta voltage and make the voltage relay

    operate which is connected to give alarm. Thefaulty 6.6kv feeder can be identified by trippingthe 6.6kv outlets one after the other.

  • 7/28/2019 Gen.protections

    7/74

  • 7/28/2019 Gen.protections

    8/74

    GENERATOR HAS THREE

    PARTS

    1. STATOR

    2. ROTOR

    3. EXCITATION SYSTEM

  • 7/28/2019 Gen.protections

    9/74

    FAULTS IN GENERATOR

    EXTERNAL FAULTS

    INTERNAL FAULTS

    FAULTS RELATED SYSTEM

  • 7/28/2019 Gen.protections

    10/74

    EXTERNAL FAULTS

    OVER LOADING

    UNBALANCE LOADING

    SHORT CIRCUIT EARTH FAULT

  • 7/28/2019 Gen.protections

    11/74

    INTERNAL FAULTS

    PHASE TO PHASE FAULTS IN WINDINGS

    PHASE TO EARTH FAULTS

    INTER TURN FAULTS

  • 7/28/2019 Gen.protections

    12/74

    FAULTS RELATED SYSTEM

    UNDER VOLTAGE

    OVER VOLTAGE

    UNDER FREQUENCY OVER FREQUENCY

    REVERSE POWER

    LOSS OF EXCITATION LOW-FORWARD POWER

  • 7/28/2019 Gen.protections

    13/74

    GENERATOR PROTECTIONS ARE BROADLY

    CLASSIFIED INTO THREE TYPES

    CLASS-A: (UNIT SHUT DOWN ) This covers all

    electrical protections for faults within the generating

    unit in which GENERATOR FIELD BRK.,

    GENERATOR BREAKER, UAT LV BRK. and TURBINE

    should be tripped

  • 7/28/2019 Gen.protections

    14/74

    CLASS-B: ( INTERLOCKED TRIPPING) This

    covers all MECHANICAL protections of the

    turbine in which TURBINE will be tripped

    first and following this generator will trip

    on REVERSE/LOW FORWARD POWER

    protection(GT/UAT/FIELD brks.)

  • 7/28/2019 Gen.protections

    15/74

    CLASS-C: This covers electrical protection

    for faults in the system in which generator

    will be unloaded by tripping of generator

    breaker only. The unit will come to house

    load operation and the UAT will be in

    service.

  • 7/28/2019 Gen.protections

    16/74

    SOME OF CLASS-C PROTECTIONS ARE

    1. Gen. T/F HV side breaker pole discrepancy

    2. Gen. Neg. Ph. Sequence

    3. Gen. T/F over current

    4. Reverse power protection without turbine

    trip

  • 7/28/2019 Gen.protections

    17/74

    GENERATOR PROTECTIONS

    1. Stator E/F (64)

    95% stator E/F protection (64G1)

    100% stator E/F protection (64G2)

    2. Rotor E/F (64)

    First rotor E/F protection (64R1)

    Second rotor E/F protection (64R2)

  • 7/28/2019 Gen.protections

    18/74

    3. Inter turn fault

    4. Negative phase sequence (46G)

    5. Loss of excitation protection(loss of field) (40G)

    6. Minimum Impedance (Mho backup

    impedance) (21G)

    7. Differential ( 87G)

    8. Overall differential (87 O )

    9. Power protection

    Low forward power (37G)

    Reverse power (32G)

  • 7/28/2019 Gen.protections

    19/74

    10.Frequency protection ( 8 1 )

    Under frequency ( 8 1U)

    Over frequency ( 8 1O)

    11.Thermal overload (51G)

    12.Voltage protection

    Over voltage (59)

    Under voltage (27)

    13.Out of step (pole slipping ) (78G)

    14.Voltage restrained over current (51/27G)

    15.Standby earth fault (51N)

    16.Inadvertent Energization

  • 7/28/2019 Gen.protections

    20/74

    1. STATO E/F PROTECTION

    The most common practice is the neutral point of thegenerator is usually earthed to enable detection of

    earth faults associated with the stator winding andassociated systems and also to limit the transient overvoltages during faults or switching. The commonlyadopted earthing methods for industrial generators.

    High impedance Earthing:

    In this method the neutral of the generator is earthedthrough the primary winding of a groundingtransformer having a loading resistor across itssecondary. This method of earthing of is called highimpedance earthing. In this arrangement , the primaryearth fault current will be limited to between 3 to 25amps depending upon the size of the machine andphase to ground capacitance of the Stator.

  • 7/28/2019 Gen.protections

    21/74

    High impedance grounding is generally usedin case of unit connected Generators where

    the generators is connected to the systemthrough a delta/star step up transformerwith control breaker on the HV (star) side.The neutral of the HV star winding is solidly

    grounded. A neutral displacement relay ( voltage

    operated) connected across secondary of thedistribution transformer. The relay is IDMTtype with typical setting range of 5-20 voltsand is tuned to supply frequency.

  • 7/28/2019 Gen.protections

    22/74

    Short circuits between the stator winding in

    the slots and the stator core are the most

    common electrical fault in Generators. Interturn faults, which normally are difficult to

    detect, will quickly develop into a ground

    fault and will be tripped by the statorground fault protection.

  • 7/28/2019 Gen.protections

    23/74

    95% STATOR E/F PROTECTION

    The relay is normally set to operate at 5% of maximumneutral voltage with a time delay of 0.3 0.5 seconds. Withthis voltage setting , it protects approximately 95% of thestator winding.

    RESULTS IN VOLTAGE SHIFT OF GEN NEUTRAL W.R.T

    GROUND DETECTED BY OVER VOLTAGE RELAY CONNECTED

    ACROSS GROUNDING RESISTOR

    PROTECT APPROX 95% OF STATOR WDG

    It also covers the generator bus, the low voltage winding ofthe unit transformer and the high voltage winding of theunit auxiliary transformer.

  • 7/28/2019 Gen.protections

    24/74

    100% STATOR E/F PROTECTION

    THIRD HARMONIC PRINCIPLE

    For Single line to Ground fault near the neutralend of winding , there will be proportionately lessvoltage available to drive the current through theground, resulting in a lower fault current and lower

    neutral bus voltage.If an earth fault occurs and remains undetected

    because of its location (near the neutral end).A 100 % Stator earth fault protection is designed

    to detect earth faults occurring in the regions ofMachine winding close to the neutral end.

  • 7/28/2019 Gen.protections

    25/74

    Principle: This works on the principle involving monitoring of the

    neutral side and line side components of the third harmonic

    voltages produced by the AC generators.

    AC Generators in service produce a certain magnitude of third

    harmonic voltages in their windings. Under the healthy conditions of

    working the third harmonic voltage developed by the machine is

    shared between the phase to ground capacitive impedance at the

    machine terminal and the neutral to ground impedance at the

    machine neutral.

  • 7/28/2019 Gen.protections

    26/74

    The 100% stator E/F relay includes 95%

    unit which covers the stator winding from

    5% of the neutral and a 3rd harmonicvoltage measuring unit -2 which protects

    the rest of the stator winding.

    The voltage check unit is included to

    prevent faulty operation of the relay at

    generator standstill or during the machinerunning up or running down period.

  • 7/28/2019 Gen.protections

    27/74

  • 7/28/2019 Gen.protections

    28/74

  • 7/28/2019 Gen.protections

    29/74

    ROTOR E/F PROTECTION

    The field circuit of a generator has nointentional earthing and hence a single earthfault occurring in the field system poses noimmediate threat. However, the presence of

    the first ground increases the risk of a secondearth fault developing due to increasedinsulation stresses between the field systemand earth. The resulting double earth fault will

    cause part of the filed winding short circuitedthere by producing an unbalance in themagnetic field and consequent vibrations andmechanical damage.

  • 7/28/2019 Gen.protections

    30/74

    METHODS OF DETECTION

    Potentiometer method

    A.C injection method

    D.C injection method

  • 7/28/2019 Gen.protections

    31/74

    MODERN ROTOR EARTH FAULT PROTECTIONRELAY OPERATES ON THE PRINCIPLE OF LOWFREQUENCY INJECTION INTO THE FIELD

    WINDING VIA CAPACITORS.

    IF AN EARTH FAULT OCCURS, THECORRESPONDING CURRENT OR RESISTANCE ISDETECTED

    In general

    ALARM 25 K OHM TIME = 1.0 SEC

    TRIP 5 K OHM TIME = 0.5 SEC

  • 7/28/2019 Gen.protections

    32/74

    POTENTION METHER METHOD

    In this scheme, a centre tapped resistor is

    connected in parallel with the main field

    winding. The centre point of the resistor is

    connected to earth through a voltage relay.An earth fault on the field winding will

    produce a voltage across the relay. The

    maximum voltage occurring for faults at theends of the winding.

  • 7/28/2019 Gen.protections

    33/74

  • 7/28/2019 Gen.protections

    34/74

    AC INJECTION METHOD

    It comprises of an auxiliary supply transformer, thesecondary of which is connected between earth andone side of the field circuit through an interposedcapacitor and a relay coil.

    The field circuit is subjected to an alternatingpotential at the same level through out, so that anearth fault anywhere in the field system will give riseto a current which is detected by the relay. Thecapacitor limits the magnitude of the current and

    blocks the normal field voltage, preventing thedischarge of a large direct current through thetransformer.

  • 7/28/2019 Gen.protections

    35/74

  • 7/28/2019 Gen.protections

    36/74

    D.C Injection Method

    The capacitance current objection to the a.c

    injection scheme is overcome by rectifying

    the injection voltage. The d.c out put of a

    transformer rectifier power unit is arrangedto bias the positive side of the field circuit to

    a negative voltage relative to earth. The

    current is limited by including a highresistance in the circuit and a sensitive relay

    is used to detect the current.

  • 7/28/2019 Gen.protections

    37/74

  • 7/28/2019 Gen.protections

    38/74

    INTER TURN FAULT

    PROTECTION

    Inter turn faults have commonly been

    disregarded on the basis that if they occur

    they will quickly develop into earth faults.

    This is probably true if the fault is in the slotportion is never attractive and may be

    entirely unjustified. There is a possibility of

    the machine being very seriously damagedbefore the fault evolves to a condition that

    can be detected by the longitudinal system.

  • 7/28/2019 Gen.protections

    39/74

    It is generally considered difficult to obtain

    a reliable protection against short-circuiting

    of one turn if the stator winding has a largenumber of turn per phase.

    For generators with split neutrals, the

    conventional inter turn fault protectivescheme comprises a time delayed low set

    over current relay which senses the current

    flowing in the connection between the

    neutrals of the stator winding.

  • 7/28/2019 Gen.protections

    40/74

    zero sequence voltage measurement

    Short circuit of one or more turns will

    cause the Generated E M F to containzero Sequence component

    Earth faults will also produce a zero

    sequence voltage. Most of the voltagewill be expended on Earthing Resistor

    Hence, drop across the winding should be

    measured

  • 7/28/2019 Gen.protections

    41/74

    NEG.PH.SEQUENCE PORTECTION

    When the generator is connected to a balanced load,

    the phase currents are equal in magnitude anddisplaced electrically by 120 deg. The ampere turnwave produced by the stator currents rotatesynchronously with the rotor and no eddy currentsare induced in the rotor parts.

    Unbalance loading gives rise to a negative sequencecomponent in the stator current. The negativesequence current produces an additional ampereturn wave which rotates backwards, hence it moves

    relatively to the rotor at twice the synchronousspeed. The double frequency eddy currents inducedin the rotor may cause excessive heating, primarilyin the surface of cylindrical rotors and in the damperwinding of rotors with salient poles.

  • 7/28/2019 Gen.protections

    42/74

  • 7/28/2019 Gen.protections

    43/74

    LOSS OF EXCITATION

    Loss of excitation may occur under normalrunning conditions due to followingreasons:

    1. Failure of Brush gear of the pilot or shuntexciter

    2. Accidental opening of the field breaker

    3. Failure of the regulation system4. An open circuit or a short circuit of the

    main field

  • 7/28/2019 Gen.protections

    44/74

    The condition is particularly detrimental when

    the generator is operating in paralleled with

    other generators or with the utility system.When the generator looses its field on load , it

    runs as an induction generator, operating at

    super synchronous speed. The defaulting

    machine absorbs VARs from the system tosupport excitation and continues generating

    action. Slip frequency currents are induced in

    the field system which, it allowed to persist forlong, cause over heating of the field winding

    /rotor iron.

  • 7/28/2019 Gen.protections

    45/74

    The maximum active power that can be

    generated without loss of synchronism

    when the generator losses its excitationdepends on the difference between the

    direct axis and quadrature axis synchronous

    reactance. For generators with salientpoles, the difference is normally sufficiently

    large to keep the machine running

    synchronously, even with an active load of

    15-25% or rated load.

  • 7/28/2019 Gen.protections

    46/74

    For cylindrical turbo generators, the direct

    and quardrature axis reactance are

    practically equal, and the machine fails outof synchronism even with a very small

    active lode, The slip speed increases with

    the active load. The stator end regions and

    parts of the rotor will be overheated, it the

    machine is permitted to run for a long time

    at higher slip speeds.

  • 7/28/2019 Gen.protections

    47/74

  • 7/28/2019 Gen.protections

    48/74

  • 7/28/2019 Gen.protections

    49/74

    BACKUP IMPEDANCE

    The generator minimum impedance

    protection(impedance backup protection) is

    primarily provided to protect the generator

    against uncleared external short circuits onthe lines emanating from the station bus

    bars. The relay has an impedance or offset

    MHO characteristic and is et to cover theimpedance of the longest line.

    I f t th h th i iti l h t

  • 7/28/2019 Gen.protections

    50/74

    In case of generator, though the initial shortcircuit current may be high during the subtransient/transient periods, the steady

    state short circuit current may be less thanthe full load current, due to the effect ofarmature reaction. Since the initial short

    circuit current is high and almost whollyreactive the armature reaction flux is indirect opposition to the field flux. Thiswould reduce the field flux, which in turn

    reduces the induced EMF and hence theshort circuit current. The AVR tends tocompensate the reduction by forcing thefield in case of system faults.

    f l f l h

  • 7/28/2019 Gen.protections

    51/74

    However, for close up faults, the AVRcompensation may not be enough to boostthe voltage and hence the fault current.Conventional over current relays may not,therefore, be suitable for generatorapplication. Voltage controlled or voltage

    restrained over current relays arecommonly adopted in such situations.These relays are designed to become moresensitive with generator voltage reduction

    and hence operate positively, even if thesustained short circuit current fails belowthe full load current.

  • 7/28/2019 Gen.protections

    52/74

    DIFFERENTIAL PROTECTION

    Differential protection is commonly applied

    to generators above 1 MVA rating. This is a

    unit protection, which covers both phase,

    and earth faults within the machine. Thezone of protection is defined by current

    transformers at neutral side and line side of

    the stator winding.

  • 7/28/2019 Gen.protections

    53/74

    Current transformer at each end of the

    protected zone are interconnected by an

    auxiliary pilot circuit. Current transmittedthrough the zone causes secondary current to

    circulate round the pilot circuit without

    producing any current in the relay. A fault

    within the protected zone will cause secondarycurrents of opposite relative phase as

    compared with the through fault condition.

    The summated value of these currents will flowin the relay, thus energizes the relay. The

    voltage setting is decided from the secondary

    load drop by the following formula.

  • 7/28/2019 Gen.protections

    54/74

    The differential relay is usually high

    impedance relay. The current transformers

    on the generator neutral and the line sideshall have identical turns ration and similar

    magnetizing characteristics. Hence under

    normal service conditions and external

    faults, with unsaturated current

    transformers, the voltage across the relay is

    negligible.

  • 7/28/2019 Gen.protections

    55/74

    GEN OVERALL DIFFERENTIAL

  • 7/28/2019 Gen.protections

    56/74

    GEN.OVERALL DIFFERENTIAL

    PROTECTION

    This protection is used to protect the completebus of generator, generator transformer andhigh voltage bus side of unit auxiliarytransformer.

    The special features of the relay are:

    1. Through current restraint for external faults

    2. Magnetizing inrush restraint

    3. Over excitation restraint to counteractoperation at abnormal magnetizing currentscaused by high voltage/low frequency

    Th ti i t i t i i d t

  • 7/28/2019 Gen.protections

    57/74

    The magnetizing restraint is required to

    keep the relay stable when a nearby fault on

    an adjacent feeder is cleared. During the time of fault, the terminal voltage

    of the main transformer is practically zero

    and after fault clearance i.e when the circuit

    breaker of the faulty feeder opens, the

    transformer terminal voltage quickly rises.

    This may cause severe recovery inrush

    currents. The inrush restraint is alsorequired when the unit transformer is

    energized for the H.V bus.

    The o er e citation restraint is important

  • 7/28/2019 Gen.protections

    58/74

    The over excitation restraint is important

    since there is a possibility of over voltage

    when load is suddenly disconnected inwhich the differential relay may trip the

    generator and the voltage remains high until

    the automatic voltage regulator (AVR)

    brought it back to the normal valve.

  • 7/28/2019 Gen.protections

    59/74

  • 7/28/2019 Gen.protections

    60/74

  • 7/28/2019 Gen.protections

    61/74

    POWER PROTECTION

    1. LOW FORWARD POWER:In thermal machines, when the steam flow

    through turbine is interrupted by closing theESVs or the governor valves, the remaining

    steam in the turbine generates (low) powerand the machine enters to motoringconditions drawing power from the system.This protection detects low forward power

    conditions of the generator and tripsgenerator breaker after a time delay, avoidingmotoring of generator.

    The low forward power relay will be

  • 7/28/2019 Gen.protections

    62/74

    The low forward power relay will beprovided with TURBINE TRIP interlock inthermal machines. A setting of 0.5% of rated

    active power of generator with a time delay of2.0 sec. Shall be adopted.

    2. REVERSE POWER:

    Reverse power protection shall be used for

    all types of generators. When the input to theturbine is interrupted the machine enters intomotoring condition drawing power from thesystem. Reverse power relay protects thegenerators from motoring condition. In

    thermal machines, reverse power conditionappears subsequent to low forward powercondition.

    F l tti f

  • 7/28/2019 Gen.protections

    63/74

    For reverse power relay, a setting of

    0.5% of rated active power of generator

    with 2 stage timer as1. Stage-1: with turbine trip interlock, a time

    delay of 2 sec. shall be adopted.

    2. Stage-2: Without turbine trip interlock atime delay of about 20 sec. can be adopted

    to avoid unnecessary tripping of unit

    during system disturbance causing sudden

    rise in frequency or power swing

    conditions.

  • 7/28/2019 Gen.protections

    64/74

    FREQUENCY PROTECTION

    1. UNDER FREQUENCY

    2. OVER FREQUENCY

    The generators are designed to give

    rated output at rated terminal voltage andrated frequency. Hence an operation abovecertain limit i.e +5% and -5% of ratedfrequency is avoided to protect variousapparatus in a network and also thegenerator and turbine.

    OVER LAOD PROTECTION

  • 7/28/2019 Gen.protections

    65/74

    OVER LAOD PROTECTION A generator operating on a large system under

    continuous supervision is not in much danger of

    accidental overloading. The power r that can begenerated is limited by the steam production andhence can not rise un noticed or maintained for anyappreciable period above the programmed level.Overloads in terms of current or MVA as distinctfrom megawatts are possible. Depending on thevoltage regulator setting and type of control relativeto the rest of the system, a given generator may takea disproportionate share of the MVAR load on thesystem. Overloads up to 1.4 times the rated currentare not normally detected by the impedance or overcurrent protection. Sustained loads within this rangeare usually supervised by temperature monitors(RTD/or thermocouples)

    OVER VOLTAGE PROTECTION

  • 7/28/2019 Gen.protections

    66/74

    OVER VOLTAGE PROTECTION

    During the starting up of a generator, prior

    to synchronization, the generator terminalvoltage is obtained by the proper operationof the automatic voltage regulator (AVR).

    After synchronization, the terminal voltageof the machine will be dictated by its ownAVR and also by the voltage level of thesystem and the AVRs of nearby machines. It

    is not possible for one machine to cause anyappreciable rise in the terminal voltage aslong as it is connected to the system.

    Increasing the field excitation, owing to a fault

  • 7/28/2019 Gen.protections

    67/74

    g , gin the AVR, merely increases the reactive MVARoutput, which may ultimately lead to tripping

    of the impedance relay or the V/Hz relay.Maximum excitation limit prevents the rotorfield current and the reactive output powerfrom exceeding the design limits.

    This protection is used for the insulation levelof the generator stator windings. Severeovervoltage will occur, if the generator circuitbreaker is tripped while the machine is

    running at full load and rated power factor, thesubsequent increase in terminal voltage willnormally be limited by a quick acting AVR

    However, if the AVR faulty or at this particular

  • 7/28/2019 Gen.protections

    68/74

    , y ptime switched over to manual control, over voltagewill occur. This voltage rise will be further increasedif simultaneous over speeding should occur, owing

    to a slow acting turbine governor.Modern unit transformers with high magnetic

    qualities have a relatively sharp and well definedsaturation level, with a knee point voltage between1.2 and 1.25 times the rated voltage (Un). A suitablesetting of the over voltage relay is, therefore,between 1.15 and 1.2 times Un and with a definitedelay of 1 to 3 sec.

    An instantaneous high set voltage rely can be

    included to trip the generator quickly in case ofexcessive over voltage following a sudden loss ofload and generator over speeding.

    OUT OF STEP (POLE SLIPPING)

  • 7/28/2019 Gen.protections

    69/74

    OUT OF STEP (POLE SLIPPING) An generator may lose synchronism with the

    power system, without failure of the excitationsystem, because of severe system faultdisturbance operation at a high load with aleading power factor and hence a relatively

    weak field, In this condition, which is quitedifferent from the failure of field system, themachine is subject to violent oscillations oftorque, with wide various in current, powerand power factor. Synchronism can be

    regained if the load is sufficiently reduced butif this does not occur within a few seconds it isnecessary to isolate the generator and thenresynchronize.

    The impedance of the generator measure at the

  • 7/28/2019 Gen.protections

    70/74

    The impedance of the generator measure at thestator terminals changes mostly whensynchronism is lost by the machine. The

    terminal voltage will begin to decrease and thecurrent to increase, resulting in a decrease ofimpedance and also a change in power factor.A pole slipping protection comprising of two

    ohm relays is used to detect out of stepoperation. The relay monitors the loadimpedance at the machine terminals andoperates when the terminal impedance locussequentially crosses both ohm relay

    characteristics which corresponds to one poleslip between the defaulting machine and thesystem

    VOLTAGE RESTRAINED

  • 7/28/2019 Gen.protections

    71/74

    VOLTAGE RESTRAINED

    OVER CURRENT

    This will operate when the fault currentfrom the generator terminal becomes low

    due to excitation system characteristic with

    under voltage criteria. It operates as abackup protection for system faults with

    suitable time delay.

  • 7/28/2019 Gen.protections

    72/74

    STANDBY EARTH FAULT

    This relay monitors the current in the

    generator transformer neutral. It can detect

    earth faults in the transformer HV side or in

    the adjacent network.

    INADVERTENT ENERGIZATION

  • 7/28/2019 Gen.protections

    73/74

    INADVERTENT ENERGIZATION

    Many instances of inadvertent energization1. Closing the generator breaker with the

    machine at standstill

    2. Closing a unit service breaker with themachine at standstill

    3. High voltage breaker flashover near

    synchronism4. Closing of generator disconnect with unit

    breaker closed

    F ll lt i ti f hi t

  • 7/28/2019 Gen.protections

    74/74

    Full voltage energization of a machine at

    standstill does not produce an enormous

    magnitude of current, but it does supply anextreme impact of torque and mechanical

    damage to the shaft or bearings may occur.

    The resulting current is of sufficient

    magnitude that fast removal is necessary if

    thermal damage to the generator is to be

    avoided.