gen.protections
TRANSCRIPT
-
7/28/2019 Gen.protections
1/74
-
7/28/2019 Gen.protections
2/74
GENERATOR
Generating units are the source of the power
system and their security against anyadverse conditions is most important in the
system.
The GENERATOR protection must ensure afast and selective detection of any fault in
order to minimize their dangerous effects.
-
7/28/2019 Gen.protections
3/74
Generator is accompanied by excitation system,
prime mover, voltage regulator, cooling system
etc. Hence it is not a single equipment. Theprotection of generator should be co-ordinated
with associated equipment.
Protection of passive elements like transmissionline and transformers is relatively simple which
involves isolation of faulty element from the
system , whereas protection of generators
involves tripping of generator field breaker,
generator breaker and turbine.
-
7/28/2019 Gen.protections
4/74
GENERATOR PROTECTION SCHEME
-
7/28/2019 Gen.protections
5/74
GENERATOR AND GENERATOR
TRANSFORMER AS A UNIT
Station Transformer: 11/6.6 kv transformer
with LV grounded through high resistance,
feeds the station auxiliary load.
Unit auxiliary transformer: 11/6.6 kv
transformer with LV grounded through high
resistance feeds the unit auxiliary loads
-
7/28/2019 Gen.protections
6/74
Any earth fault on the 6.6 kv system cannot beseen by any E/L relay (since the 6.6 kv system
is high resistance grounded ) However 3-O/Lrelays are provided on the 6.6kv side of thestation transformers and unit auxiliarytransformers. An open delta voltage of the 6.6
kv bus PT is connected to an over voltage relaywith a very low setting. Any earth fault on the6.6 kv system will cause the presence of theopen-delta voltage and make the voltage relay
operate which is connected to give alarm. Thefaulty 6.6kv feeder can be identified by trippingthe 6.6kv outlets one after the other.
-
7/28/2019 Gen.protections
7/74
-
7/28/2019 Gen.protections
8/74
GENERATOR HAS THREE
PARTS
1. STATOR
2. ROTOR
3. EXCITATION SYSTEM
-
7/28/2019 Gen.protections
9/74
FAULTS IN GENERATOR
EXTERNAL FAULTS
INTERNAL FAULTS
FAULTS RELATED SYSTEM
-
7/28/2019 Gen.protections
10/74
EXTERNAL FAULTS
OVER LOADING
UNBALANCE LOADING
SHORT CIRCUIT EARTH FAULT
-
7/28/2019 Gen.protections
11/74
INTERNAL FAULTS
PHASE TO PHASE FAULTS IN WINDINGS
PHASE TO EARTH FAULTS
INTER TURN FAULTS
-
7/28/2019 Gen.protections
12/74
FAULTS RELATED SYSTEM
UNDER VOLTAGE
OVER VOLTAGE
UNDER FREQUENCY OVER FREQUENCY
REVERSE POWER
LOSS OF EXCITATION LOW-FORWARD POWER
-
7/28/2019 Gen.protections
13/74
GENERATOR PROTECTIONS ARE BROADLY
CLASSIFIED INTO THREE TYPES
CLASS-A: (UNIT SHUT DOWN ) This covers all
electrical protections for faults within the generating
unit in which GENERATOR FIELD BRK.,
GENERATOR BREAKER, UAT LV BRK. and TURBINE
should be tripped
-
7/28/2019 Gen.protections
14/74
CLASS-B: ( INTERLOCKED TRIPPING) This
covers all MECHANICAL protections of the
turbine in which TURBINE will be tripped
first and following this generator will trip
on REVERSE/LOW FORWARD POWER
protection(GT/UAT/FIELD brks.)
-
7/28/2019 Gen.protections
15/74
CLASS-C: This covers electrical protection
for faults in the system in which generator
will be unloaded by tripping of generator
breaker only. The unit will come to house
load operation and the UAT will be in
service.
-
7/28/2019 Gen.protections
16/74
SOME OF CLASS-C PROTECTIONS ARE
1. Gen. T/F HV side breaker pole discrepancy
2. Gen. Neg. Ph. Sequence
3. Gen. T/F over current
4. Reverse power protection without turbine
trip
-
7/28/2019 Gen.protections
17/74
GENERATOR PROTECTIONS
1. Stator E/F (64)
95% stator E/F protection (64G1)
100% stator E/F protection (64G2)
2. Rotor E/F (64)
First rotor E/F protection (64R1)
Second rotor E/F protection (64R2)
-
7/28/2019 Gen.protections
18/74
3. Inter turn fault
4. Negative phase sequence (46G)
5. Loss of excitation protection(loss of field) (40G)
6. Minimum Impedance (Mho backup
impedance) (21G)
7. Differential ( 87G)
8. Overall differential (87 O )
9. Power protection
Low forward power (37G)
Reverse power (32G)
-
7/28/2019 Gen.protections
19/74
10.Frequency protection ( 8 1 )
Under frequency ( 8 1U)
Over frequency ( 8 1O)
11.Thermal overload (51G)
12.Voltage protection
Over voltage (59)
Under voltage (27)
13.Out of step (pole slipping ) (78G)
14.Voltage restrained over current (51/27G)
15.Standby earth fault (51N)
16.Inadvertent Energization
-
7/28/2019 Gen.protections
20/74
1. STATO E/F PROTECTION
The most common practice is the neutral point of thegenerator is usually earthed to enable detection of
earth faults associated with the stator winding andassociated systems and also to limit the transient overvoltages during faults or switching. The commonlyadopted earthing methods for industrial generators.
High impedance Earthing:
In this method the neutral of the generator is earthedthrough the primary winding of a groundingtransformer having a loading resistor across itssecondary. This method of earthing of is called highimpedance earthing. In this arrangement , the primaryearth fault current will be limited to between 3 to 25amps depending upon the size of the machine andphase to ground capacitance of the Stator.
-
7/28/2019 Gen.protections
21/74
High impedance grounding is generally usedin case of unit connected Generators where
the generators is connected to the systemthrough a delta/star step up transformerwith control breaker on the HV (star) side.The neutral of the HV star winding is solidly
grounded. A neutral displacement relay ( voltage
operated) connected across secondary of thedistribution transformer. The relay is IDMTtype with typical setting range of 5-20 voltsand is tuned to supply frequency.
-
7/28/2019 Gen.protections
22/74
Short circuits between the stator winding in
the slots and the stator core are the most
common electrical fault in Generators. Interturn faults, which normally are difficult to
detect, will quickly develop into a ground
fault and will be tripped by the statorground fault protection.
-
7/28/2019 Gen.protections
23/74
95% STATOR E/F PROTECTION
The relay is normally set to operate at 5% of maximumneutral voltage with a time delay of 0.3 0.5 seconds. Withthis voltage setting , it protects approximately 95% of thestator winding.
RESULTS IN VOLTAGE SHIFT OF GEN NEUTRAL W.R.T
GROUND DETECTED BY OVER VOLTAGE RELAY CONNECTED
ACROSS GROUNDING RESISTOR
PROTECT APPROX 95% OF STATOR WDG
It also covers the generator bus, the low voltage winding ofthe unit transformer and the high voltage winding of theunit auxiliary transformer.
-
7/28/2019 Gen.protections
24/74
100% STATOR E/F PROTECTION
THIRD HARMONIC PRINCIPLE
For Single line to Ground fault near the neutralend of winding , there will be proportionately lessvoltage available to drive the current through theground, resulting in a lower fault current and lower
neutral bus voltage.If an earth fault occurs and remains undetected
because of its location (near the neutral end).A 100 % Stator earth fault protection is designed
to detect earth faults occurring in the regions ofMachine winding close to the neutral end.
-
7/28/2019 Gen.protections
25/74
Principle: This works on the principle involving monitoring of the
neutral side and line side components of the third harmonic
voltages produced by the AC generators.
AC Generators in service produce a certain magnitude of third
harmonic voltages in their windings. Under the healthy conditions of
working the third harmonic voltage developed by the machine is
shared between the phase to ground capacitive impedance at the
machine terminal and the neutral to ground impedance at the
machine neutral.
-
7/28/2019 Gen.protections
26/74
The 100% stator E/F relay includes 95%
unit which covers the stator winding from
5% of the neutral and a 3rd harmonicvoltage measuring unit -2 which protects
the rest of the stator winding.
The voltage check unit is included to
prevent faulty operation of the relay at
generator standstill or during the machinerunning up or running down period.
-
7/28/2019 Gen.protections
27/74
-
7/28/2019 Gen.protections
28/74
-
7/28/2019 Gen.protections
29/74
ROTOR E/F PROTECTION
The field circuit of a generator has nointentional earthing and hence a single earthfault occurring in the field system poses noimmediate threat. However, the presence of
the first ground increases the risk of a secondearth fault developing due to increasedinsulation stresses between the field systemand earth. The resulting double earth fault will
cause part of the filed winding short circuitedthere by producing an unbalance in themagnetic field and consequent vibrations andmechanical damage.
-
7/28/2019 Gen.protections
30/74
METHODS OF DETECTION
Potentiometer method
A.C injection method
D.C injection method
-
7/28/2019 Gen.protections
31/74
MODERN ROTOR EARTH FAULT PROTECTIONRELAY OPERATES ON THE PRINCIPLE OF LOWFREQUENCY INJECTION INTO THE FIELD
WINDING VIA CAPACITORS.
IF AN EARTH FAULT OCCURS, THECORRESPONDING CURRENT OR RESISTANCE ISDETECTED
In general
ALARM 25 K OHM TIME = 1.0 SEC
TRIP 5 K OHM TIME = 0.5 SEC
-
7/28/2019 Gen.protections
32/74
POTENTION METHER METHOD
In this scheme, a centre tapped resistor is
connected in parallel with the main field
winding. The centre point of the resistor is
connected to earth through a voltage relay.An earth fault on the field winding will
produce a voltage across the relay. The
maximum voltage occurring for faults at theends of the winding.
-
7/28/2019 Gen.protections
33/74
-
7/28/2019 Gen.protections
34/74
AC INJECTION METHOD
It comprises of an auxiliary supply transformer, thesecondary of which is connected between earth andone side of the field circuit through an interposedcapacitor and a relay coil.
The field circuit is subjected to an alternatingpotential at the same level through out, so that anearth fault anywhere in the field system will give riseto a current which is detected by the relay. Thecapacitor limits the magnitude of the current and
blocks the normal field voltage, preventing thedischarge of a large direct current through thetransformer.
-
7/28/2019 Gen.protections
35/74
-
7/28/2019 Gen.protections
36/74
D.C Injection Method
The capacitance current objection to the a.c
injection scheme is overcome by rectifying
the injection voltage. The d.c out put of a
transformer rectifier power unit is arrangedto bias the positive side of the field circuit to
a negative voltage relative to earth. The
current is limited by including a highresistance in the circuit and a sensitive relay
is used to detect the current.
-
7/28/2019 Gen.protections
37/74
-
7/28/2019 Gen.protections
38/74
INTER TURN FAULT
PROTECTION
Inter turn faults have commonly been
disregarded on the basis that if they occur
they will quickly develop into earth faults.
This is probably true if the fault is in the slotportion is never attractive and may be
entirely unjustified. There is a possibility of
the machine being very seriously damagedbefore the fault evolves to a condition that
can be detected by the longitudinal system.
-
7/28/2019 Gen.protections
39/74
It is generally considered difficult to obtain
a reliable protection against short-circuiting
of one turn if the stator winding has a largenumber of turn per phase.
For generators with split neutrals, the
conventional inter turn fault protectivescheme comprises a time delayed low set
over current relay which senses the current
flowing in the connection between the
neutrals of the stator winding.
-
7/28/2019 Gen.protections
40/74
zero sequence voltage measurement
Short circuit of one or more turns will
cause the Generated E M F to containzero Sequence component
Earth faults will also produce a zero
sequence voltage. Most of the voltagewill be expended on Earthing Resistor
Hence, drop across the winding should be
measured
-
7/28/2019 Gen.protections
41/74
NEG.PH.SEQUENCE PORTECTION
When the generator is connected to a balanced load,
the phase currents are equal in magnitude anddisplaced electrically by 120 deg. The ampere turnwave produced by the stator currents rotatesynchronously with the rotor and no eddy currentsare induced in the rotor parts.
Unbalance loading gives rise to a negative sequencecomponent in the stator current. The negativesequence current produces an additional ampereturn wave which rotates backwards, hence it moves
relatively to the rotor at twice the synchronousspeed. The double frequency eddy currents inducedin the rotor may cause excessive heating, primarilyin the surface of cylindrical rotors and in the damperwinding of rotors with salient poles.
-
7/28/2019 Gen.protections
42/74
-
7/28/2019 Gen.protections
43/74
LOSS OF EXCITATION
Loss of excitation may occur under normalrunning conditions due to followingreasons:
1. Failure of Brush gear of the pilot or shuntexciter
2. Accidental opening of the field breaker
3. Failure of the regulation system4. An open circuit or a short circuit of the
main field
-
7/28/2019 Gen.protections
44/74
The condition is particularly detrimental when
the generator is operating in paralleled with
other generators or with the utility system.When the generator looses its field on load , it
runs as an induction generator, operating at
super synchronous speed. The defaulting
machine absorbs VARs from the system tosupport excitation and continues generating
action. Slip frequency currents are induced in
the field system which, it allowed to persist forlong, cause over heating of the field winding
/rotor iron.
-
7/28/2019 Gen.protections
45/74
The maximum active power that can be
generated without loss of synchronism
when the generator losses its excitationdepends on the difference between the
direct axis and quadrature axis synchronous
reactance. For generators with salientpoles, the difference is normally sufficiently
large to keep the machine running
synchronously, even with an active load of
15-25% or rated load.
-
7/28/2019 Gen.protections
46/74
For cylindrical turbo generators, the direct
and quardrature axis reactance are
practically equal, and the machine fails outof synchronism even with a very small
active lode, The slip speed increases with
the active load. The stator end regions and
parts of the rotor will be overheated, it the
machine is permitted to run for a long time
at higher slip speeds.
-
7/28/2019 Gen.protections
47/74
-
7/28/2019 Gen.protections
48/74
-
7/28/2019 Gen.protections
49/74
BACKUP IMPEDANCE
The generator minimum impedance
protection(impedance backup protection) is
primarily provided to protect the generator
against uncleared external short circuits onthe lines emanating from the station bus
bars. The relay has an impedance or offset
MHO characteristic and is et to cover theimpedance of the longest line.
I f t th h th i iti l h t
-
7/28/2019 Gen.protections
50/74
In case of generator, though the initial shortcircuit current may be high during the subtransient/transient periods, the steady
state short circuit current may be less thanthe full load current, due to the effect ofarmature reaction. Since the initial short
circuit current is high and almost whollyreactive the armature reaction flux is indirect opposition to the field flux. Thiswould reduce the field flux, which in turn
reduces the induced EMF and hence theshort circuit current. The AVR tends tocompensate the reduction by forcing thefield in case of system faults.
f l f l h
-
7/28/2019 Gen.protections
51/74
However, for close up faults, the AVRcompensation may not be enough to boostthe voltage and hence the fault current.Conventional over current relays may not,therefore, be suitable for generatorapplication. Voltage controlled or voltage
restrained over current relays arecommonly adopted in such situations.These relays are designed to become moresensitive with generator voltage reduction
and hence operate positively, even if thesustained short circuit current fails belowthe full load current.
-
7/28/2019 Gen.protections
52/74
DIFFERENTIAL PROTECTION
Differential protection is commonly applied
to generators above 1 MVA rating. This is a
unit protection, which covers both phase,
and earth faults within the machine. Thezone of protection is defined by current
transformers at neutral side and line side of
the stator winding.
-
7/28/2019 Gen.protections
53/74
Current transformer at each end of the
protected zone are interconnected by an
auxiliary pilot circuit. Current transmittedthrough the zone causes secondary current to
circulate round the pilot circuit without
producing any current in the relay. A fault
within the protected zone will cause secondarycurrents of opposite relative phase as
compared with the through fault condition.
The summated value of these currents will flowin the relay, thus energizes the relay. The
voltage setting is decided from the secondary
load drop by the following formula.
-
7/28/2019 Gen.protections
54/74
The differential relay is usually high
impedance relay. The current transformers
on the generator neutral and the line sideshall have identical turns ration and similar
magnetizing characteristics. Hence under
normal service conditions and external
faults, with unsaturated current
transformers, the voltage across the relay is
negligible.
-
7/28/2019 Gen.protections
55/74
GEN OVERALL DIFFERENTIAL
-
7/28/2019 Gen.protections
56/74
GEN.OVERALL DIFFERENTIAL
PROTECTION
This protection is used to protect the completebus of generator, generator transformer andhigh voltage bus side of unit auxiliarytransformer.
The special features of the relay are:
1. Through current restraint for external faults
2. Magnetizing inrush restraint
3. Over excitation restraint to counteractoperation at abnormal magnetizing currentscaused by high voltage/low frequency
Th ti i t i t i i d t
-
7/28/2019 Gen.protections
57/74
The magnetizing restraint is required to
keep the relay stable when a nearby fault on
an adjacent feeder is cleared. During the time of fault, the terminal voltage
of the main transformer is practically zero
and after fault clearance i.e when the circuit
breaker of the faulty feeder opens, the
transformer terminal voltage quickly rises.
This may cause severe recovery inrush
currents. The inrush restraint is alsorequired when the unit transformer is
energized for the H.V bus.
The o er e citation restraint is important
-
7/28/2019 Gen.protections
58/74
The over excitation restraint is important
since there is a possibility of over voltage
when load is suddenly disconnected inwhich the differential relay may trip the
generator and the voltage remains high until
the automatic voltage regulator (AVR)
brought it back to the normal valve.
-
7/28/2019 Gen.protections
59/74
-
7/28/2019 Gen.protections
60/74
-
7/28/2019 Gen.protections
61/74
POWER PROTECTION
1. LOW FORWARD POWER:In thermal machines, when the steam flow
through turbine is interrupted by closing theESVs or the governor valves, the remaining
steam in the turbine generates (low) powerand the machine enters to motoringconditions drawing power from the system.This protection detects low forward power
conditions of the generator and tripsgenerator breaker after a time delay, avoidingmotoring of generator.
The low forward power relay will be
-
7/28/2019 Gen.protections
62/74
The low forward power relay will beprovided with TURBINE TRIP interlock inthermal machines. A setting of 0.5% of rated
active power of generator with a time delay of2.0 sec. Shall be adopted.
2. REVERSE POWER:
Reverse power protection shall be used for
all types of generators. When the input to theturbine is interrupted the machine enters intomotoring condition drawing power from thesystem. Reverse power relay protects thegenerators from motoring condition. In
thermal machines, reverse power conditionappears subsequent to low forward powercondition.
F l tti f
-
7/28/2019 Gen.protections
63/74
For reverse power relay, a setting of
0.5% of rated active power of generator
with 2 stage timer as1. Stage-1: with turbine trip interlock, a time
delay of 2 sec. shall be adopted.
2. Stage-2: Without turbine trip interlock atime delay of about 20 sec. can be adopted
to avoid unnecessary tripping of unit
during system disturbance causing sudden
rise in frequency or power swing
conditions.
-
7/28/2019 Gen.protections
64/74
FREQUENCY PROTECTION
1. UNDER FREQUENCY
2. OVER FREQUENCY
The generators are designed to give
rated output at rated terminal voltage andrated frequency. Hence an operation abovecertain limit i.e +5% and -5% of ratedfrequency is avoided to protect variousapparatus in a network and also thegenerator and turbine.
OVER LAOD PROTECTION
-
7/28/2019 Gen.protections
65/74
OVER LAOD PROTECTION A generator operating on a large system under
continuous supervision is not in much danger of
accidental overloading. The power r that can begenerated is limited by the steam production andhence can not rise un noticed or maintained for anyappreciable period above the programmed level.Overloads in terms of current or MVA as distinctfrom megawatts are possible. Depending on thevoltage regulator setting and type of control relativeto the rest of the system, a given generator may takea disproportionate share of the MVAR load on thesystem. Overloads up to 1.4 times the rated currentare not normally detected by the impedance or overcurrent protection. Sustained loads within this rangeare usually supervised by temperature monitors(RTD/or thermocouples)
OVER VOLTAGE PROTECTION
-
7/28/2019 Gen.protections
66/74
OVER VOLTAGE PROTECTION
During the starting up of a generator, prior
to synchronization, the generator terminalvoltage is obtained by the proper operationof the automatic voltage regulator (AVR).
After synchronization, the terminal voltageof the machine will be dictated by its ownAVR and also by the voltage level of thesystem and the AVRs of nearby machines. It
is not possible for one machine to cause anyappreciable rise in the terminal voltage aslong as it is connected to the system.
Increasing the field excitation, owing to a fault
-
7/28/2019 Gen.protections
67/74
g , gin the AVR, merely increases the reactive MVARoutput, which may ultimately lead to tripping
of the impedance relay or the V/Hz relay.Maximum excitation limit prevents the rotorfield current and the reactive output powerfrom exceeding the design limits.
This protection is used for the insulation levelof the generator stator windings. Severeovervoltage will occur, if the generator circuitbreaker is tripped while the machine is
running at full load and rated power factor, thesubsequent increase in terminal voltage willnormally be limited by a quick acting AVR
However, if the AVR faulty or at this particular
-
7/28/2019 Gen.protections
68/74
, y ptime switched over to manual control, over voltagewill occur. This voltage rise will be further increasedif simultaneous over speeding should occur, owing
to a slow acting turbine governor.Modern unit transformers with high magnetic
qualities have a relatively sharp and well definedsaturation level, with a knee point voltage between1.2 and 1.25 times the rated voltage (Un). A suitablesetting of the over voltage relay is, therefore,between 1.15 and 1.2 times Un and with a definitedelay of 1 to 3 sec.
An instantaneous high set voltage rely can be
included to trip the generator quickly in case ofexcessive over voltage following a sudden loss ofload and generator over speeding.
OUT OF STEP (POLE SLIPPING)
-
7/28/2019 Gen.protections
69/74
OUT OF STEP (POLE SLIPPING) An generator may lose synchronism with the
power system, without failure of the excitationsystem, because of severe system faultdisturbance operation at a high load with aleading power factor and hence a relatively
weak field, In this condition, which is quitedifferent from the failure of field system, themachine is subject to violent oscillations oftorque, with wide various in current, powerand power factor. Synchronism can be
regained if the load is sufficiently reduced butif this does not occur within a few seconds it isnecessary to isolate the generator and thenresynchronize.
The impedance of the generator measure at the
-
7/28/2019 Gen.protections
70/74
The impedance of the generator measure at thestator terminals changes mostly whensynchronism is lost by the machine. The
terminal voltage will begin to decrease and thecurrent to increase, resulting in a decrease ofimpedance and also a change in power factor.A pole slipping protection comprising of two
ohm relays is used to detect out of stepoperation. The relay monitors the loadimpedance at the machine terminals andoperates when the terminal impedance locussequentially crosses both ohm relay
characteristics which corresponds to one poleslip between the defaulting machine and thesystem
VOLTAGE RESTRAINED
-
7/28/2019 Gen.protections
71/74
VOLTAGE RESTRAINED
OVER CURRENT
This will operate when the fault currentfrom the generator terminal becomes low
due to excitation system characteristic with
under voltage criteria. It operates as abackup protection for system faults with
suitable time delay.
-
7/28/2019 Gen.protections
72/74
STANDBY EARTH FAULT
This relay monitors the current in the
generator transformer neutral. It can detect
earth faults in the transformer HV side or in
the adjacent network.
INADVERTENT ENERGIZATION
-
7/28/2019 Gen.protections
73/74
INADVERTENT ENERGIZATION
Many instances of inadvertent energization1. Closing the generator breaker with the
machine at standstill
2. Closing a unit service breaker with themachine at standstill
3. High voltage breaker flashover near
synchronism4. Closing of generator disconnect with unit
breaker closed
F ll lt i ti f hi t
-
7/28/2019 Gen.protections
74/74
Full voltage energization of a machine at
standstill does not produce an enormous
magnitude of current, but it does supply anextreme impact of torque and mechanical
damage to the shaft or bearings may occur.
The resulting current is of sufficient
magnitude that fast removal is necessary if
thermal damage to the generator is to be
avoided.