generator protection reg670 operator's manual...disclaimer the data, examples and diagrams in this...

128
Relion ® 670 series Generator protection REG670 Operator's manual

Upload: others

Post on 26-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • Relion® 670 series

    Generator protection REG670Operator's manual

  • Document ID: 1MRK502028-UENIssued: February 2015

    Revision: CProduct version: 1.2

    © Copyright 2012 ABB. All rights reserved

  • CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

    The software and hardware described in this document is furnished under a licenseand may be used or disclosed only in accordance with the terms of such license.

    TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

    WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    ABB AB

    Substation Automation Products

    SE-721 59 Västerås

    Sweden

    Telephone: +46 (0) 21 32 50 00

    Facsimile: +46 (0) 21 14 69 18

    http://www.abb.com/substationautomation

    HTTP://WWW.ABB.COM/SUBSTATIONAUTOMATION

  • DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.

    This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

  • ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.

  • Table of contents

    Section 1 Introduction.....................................................................11Introduction to the operator’s manual...............................................11

    About the complete set of manuals for an IED............................11About the operator’s manual.......................................................12Intended audience.......................................................................13Related documents......................................................................13Revision notes.............................................................................14

    Section 2 Safety information..........................................................15Warnings..........................................................................................15

    Section 3 Overview........................................................................17Operator overview............................................................................17Identify the IED.................................................................................17

    Section 4 Understand the IED local human-machineinterface..........................................................................21Overview...........................................................................................21Keypad.............................................................................................22Key activated screens......................................................................23

    The Help screen..........................................................................23The Reset screen........................................................................24

    LCD..................................................................................................24Small............................................................................................24Medium........................................................................................24

    LED...................................................................................................25Introduction..................................................................................25Status indication LEDs................................................................25Indication LEDs...........................................................................25

    Local HMI setup ...............................................................................26How to navigate................................................................................26

    Read............................................................................................26Change .......................................................................................26Control.........................................................................................27

    Section 5 Understand the injection unit local human-machineinterface..........................................................................29Injection unit REX060.......................................................................29REX060 start up sequence...............................................................29REX060 Front panel controls...........................................................30Display..............................................................................................31

    Table of contents

    1Operator's manual

  • How to set frequency and voltage and current gain factors.............33Setting system frequency............................................................33Setting stator and rotor injection frequency.................................33Selecting rotor gain......................................................................33Selecting stator gain....................................................................34Resetting overvoltage..................................................................34

    Section 6 Understand the HMI tree................................................37Overview...........................................................................................37

    Menu-tree for REG670................................................................37

    Section 7 Read measured values..................................................39Overview...........................................................................................39View analog primary values..............................................................40

    Overview......................................................................................40View analog secondary values.........................................................40

    Overview......................................................................................40View analog mean values.................................................................41

    Overview......................................................................................41mA input module MIM............................................................41Signal matrix for mA inputs SMMI..........................................41

    View monitoring values.....................................................................41Service values CVMMXN............................................................41Current phasors CMMXU............................................................42Voltage phasors VMMXU/VNMMXU...........................................42Current sequence component CMSQI........................................42Voltage sequence component VMSQI........................................42

    View metering values.......................................................................42Pulse counter logic PCGGIO.......................................................42Function for energy calculation and demand handlingETPMMTR...................................................................................43

    Section 8 Event list.........................................................................45View events......................................................................................45

    Overview......................................................................................45

    Section 9 Handle disturbances.......................................................47Identify a disturbance.......................................................................47View disturbance record details........................................................47

    View general information.............................................................47View disturbance indications.......................................................47View event recordings.................................................................47View trip values...........................................................................48

    Trigger a disturbance report manually..............................................48

    Table of contents

    2Operator's manual

  • Section 10 Read and change settings.............................................49System time and synchronization.....................................................49

    System time.................................................................................49Time synchronization...................................................................49

    Overview................................................................................49TimeSynch.............................................................................49TIMESYNCHBIN....................................................................50DSTBEGIN.............................................................................50DSTEND.................................................................................50SYNCHIRIG-B........................................................................50SYNCHSNTP.........................................................................50TIMEZONE.............................................................................50

    General settings...............................................................................51Power system..............................................................................51

    Overview................................................................................51Identifiers................................................................................51Primary values........................................................................51

    Communication............................................................................51Overview................................................................................51Remote communication..........................................................51SPA, LON and IEC 60870–5–103 settings.............................52Station communication...........................................................53Ethernet configuration............................................................54

    Analog and I/O modules..............................................................55Overview................................................................................55Analog modules......................................................................55I/O modules............................................................................56

    HMI..............................................................................................56Overview................................................................................56LEDs.......................................................................................56Screen ...................................................................................57Functions................................................................................57Change lock ..........................................................................57

    Differential protection...................................................................57Overview................................................................................57Generator differential protection GENPDIF ...........................57Transformer differential protection, two windingT2WPDIF................................................................................57Transformer differential protection, three windingT3WPDIF................................................................................58

    Impedance protection..................................................................58Sensitive rotor earth fault protection, injection basedROTIPHIZ ..............................................................................58

    Table of contents

    3Operator's manual

  • 100% stator earth fault protection STTIPHIZ ........................58Control.........................................................................................58

    Apparatus control...................................................................58Control commands.................................................................59Synchrocheck and energizing check SESRSYN ...................60

    Monitoring....................................................................................60Overview................................................................................60Service values CVMMXN.......................................................60Current phasors CMMXU.......................................................61Voltage phasors VMMXU/VNMMXU......................................61Current sequence components CMSQI ................................61Voltage sequence components VMSQI ................................61Disturbance report DRPRDRE...............................................62Generic measured value MVGGIO........................................62Event function ........................................................................62Logical signal status report BINSTATREP.............................62IEC 60870–5–103 ..................................................................63

    Metering.......................................................................................63Overview................................................................................63Pulse counter logic PCGGIO..................................................63Function for energy calculation and demand handlingETPMMTR .............................................................................63

    Setting group N.................................................................................64Overview......................................................................................64Differential protection...................................................................64

    Overview................................................................................64Generator differential protection GENPDIF ...........................64Transformer differential protection, two windingT2WPDIF ...............................................................................64Transformer differential protection, three windingT3WPDIF ...............................................................................64Restricted earth fault protection REFPDIF ............................65High impedance differential protection HZPDIF ....................65

    Impedance protection..................................................................65Overview................................................................................65Full-scheme distance protection, mho characteristicZMHPDIS ..............................................................................65Directional impedance element for mho characteristicsZDMRDIR ..............................................................................65Pole slip protection PSPPPAM ..............................................66Sensitive rotor earth fault protection, injection basedROTIPHIZ ..............................................................................66100% stator earth fault protection STTIPHIZ ........................66Loss of excitation ...................................................................66

    Table of contents

    4Operator's manual

  • Current protection........................................................................66Overview................................................................................66Accidental energizing protection for synchronousgenerator AEGGAPC.............................................................66Breaker failure protection CCRBRF ......................................67Directional over-power protection GOPPDOP ......................67Directional under-power protection GUPPDUP .....................67Instantaneous phase overcurrent protection PHPIOC ..........67Instantaneous residual overcurrent protection EFPIOC ........67Negativ sequence time overcurrent protection formachines NS2PTOC..............................................................67Four step directional negative phase sequenceovercurrent protection NS4PTOC..........................................68Four step phase overcurrent protection OC4PTOC ..............68Pole discordance protection CCRPLD...................................68Four step residual overcurrent protection EF4PTOC ............68Sensitive directional residual over current and powerprotection SDEPSDE ............................................................68Thermal overload protection, two time constantsTRPTTR ................................................................................68

    Voltage protection........................................................................69Overview................................................................................69Overexcitation protection OEXPVPH ....................................69Two step overvoltage protection OV2PTOV .........................69Two step residual overvoltage protection ROV2PTOV .........69100% stator earth fault protection, 3rd harmonic basedSTEFPHIZ .............................................................................69Two step undervoltage protection UV2PTUV ........................70Voltage differential protection VDCPTOV .............................70

    Frequency protection...................................................................70Overview................................................................................70Overfrequency protection SAPTOF .......................................70Rate-of-change frequency protection SAPFRC ....................70Underfrequency protection SAPTUF .....................................70

    Multipurpose protection...............................................................71Overview................................................................................71General current and voltage protection CVGAPC..................71

    Secondary system supervision....................................................71Overview................................................................................71Current circuit supervision CCSRDIF ....................................71Fuse failure supervision SDDRFUF.......................................71

    Control.........................................................................................72Overview................................................................................72Synchrocheck and energizing check SESRSYN ...................72

    Table of contents

    5Operator's manual

  • Monitoring....................................................................................72Overview................................................................................72Event counter CNTGGIO.......................................................72

    Logic............................................................................................72Overview................................................................................72Tripping logic SMPPTRC ......................................................72Trip matrix logic TMAGGIO....................................................73LogicGate...............................................................................73LogicRSMemory.....................................................................73LogicSRMemory.....................................................................73LogicTimerSet........................................................................73

    Activate setting group.......................................................................73Language..........................................................................................73

    Section 11 Diagnose IED status.......................................................75Read internal events.........................................................................75Find available functions....................................................................75

    Section 12 Test the IED...................................................................77Overview...........................................................................................77IED test mode...................................................................................78View binary input values...................................................................78

    Overview......................................................................................78Binary Input Module BIM........................................................78

    View binary output values.................................................................79Overview......................................................................................79

    Binary Output Module BOM...................................................79Function test modes.........................................................................79

    Overview......................................................................................79Differential protection ..................................................................79Impedance protection..................................................................79Current protection........................................................................79Voltage protection .......................................................................80Frequency protection...................................................................80Multipurpose protection ..............................................................80Secondary system protection .....................................................80Control ........................................................................................80Monitoring....................................................................................80Logic............................................................................................80

    Function status.................................................................................81Overview......................................................................................81Differential protection...................................................................81

    Generator differential protection GENPDIF............................81

    Table of contents

    6Operator's manual

  • Transformer differential protection, two windingT2WPDIF ...............................................................................81Transformer differential protection, three windingT3WPDIF ...............................................................................81Restricted earth fault protection, low impedanceREFPDIF ...............................................................................81High impedance differential protection HZPDIF ....................82

    Impedance protection..................................................................82Full-scheme distance protection, mho characteristicZMHPDIS...............................................................................82Directional impedance element for mho characteristicZDMRDIR...............................................................................82Pole slip protection PSPPPAM ..............................................82Sensitive rotor earth fault protection, injection basedROTIPHIZ ..............................................................................82100% stator earth fault protection STTIPHIZ ........................83Loss of excitation LEXPDIS ..................................................83

    Current protection........................................................................83Accidental energizing protection for synchronousgenerator AEGGAPC.............................................................83Breaker failure protection CCRBRF.......................................83Directional over-power protection GOPPDOP.......................83Directional under-power protection GUPPDUP......................83Instantaneous phase overcurrent protection PHPIOC...........84Instantaneous residual overcurrent protection EFPIOC.........84Negative sequence time overcurrent protection formachines NS2PTOC..............................................................84Four step directional negative phase sequenceovercurrent protection NS4PTOC..........................................84Four step phase overcurrent protection OC4PTOC...............84Pole discordance protection CCRPLD...................................84Four step residual overcurrent protection EF4PTOC.............85Sensitive directional residual over current and powerprotection SDEPSDE.............................................................85Thermal overload protection, two time constantsTRPTTR.................................................................................85

    Voltage protection........................................................................85Overexcitation protection OEXPVPH.....................................85Two step overvoltage protection OV2PTOV..........................85Two step residual overvoltage protection ROV2PTOV..........86100% Stator earth fault protection, 3rd harmonic basedSTEFPHIZ .............................................................................86Two step undervoltage protection UV2PTUV.........................86Voltage differential protection VDCPTOV..............................86

    Frequency protection...................................................................86

    Table of contents

    7Operator's manual

  • Overfrequency protection SAPTOF........................................86Rate-of-change frequency protection SAPFRC.....................87Underfrequency protection SAPTUF......................................87

    Multipurpose protection...............................................................87General current and voltage protection CVGAPC..................87

    Secondary system supervision....................................................87Current circuit supervision CCSRDIF.....................................87Fuse failure supervision SDDRFUF.......................................88

    Control.........................................................................................88Apparatus control...................................................................88Commands.............................................................................92IEC61850 generic communication I/O functionsDPGGIO.................................................................................92Synchrocheck and energizing check SESRSYN ...................93

    Monitoring....................................................................................93Logical signal status report BINSTATREP.............................93Disturbance report DRPRDRE...............................................93Event counter CNTGGIO.......................................................93Generic measured value MVGGIO........................................94Global positioning system......................................................94IEC61850 generic communication I/O functions 16inputs SP16GGIO...................................................................94LEDs.......................................................................................94Measured value expander block RANGE_XP........................94IEC61850 generic communication I/O functionsSPGGIO.................................................................................94

    Logic............................................................................................95Boolean 16 to Integer conversion B16IFCVI, B16I.................95Integer to Boolean 16 conversion IB16FCVB, IB16...............95Tripping logic SMPPTRC ......................................................95Trip matrix logic TMAGGIO....................................................95Logic gate...............................................................................95Logic SR/RS memory.............................................................96Logic timer set........................................................................96

    Communication............................................................................96Remote communication..........................................................96Station communication...........................................................96

    Setting groups.............................................................................97Test .............................................................................................97Authorization................................................................................97

    LED Test ..........................................................................................97Line differential test..........................................................................98

    Section 13 Control and supervise the bay........................................99

    Table of contents

    8Operator's manual

  • Overview...........................................................................................99Read measured values and check apparatus status...................99Locating and using the single line diagram.................................99Control screen messages..........................................................101

    Section 14 Reset............................................................................103Reset guide for IED........................................................................103

    Reset counters..........................................................................103Circuit breaker SXCBR.........................................................103Circuit switch SXSWI............................................................103Reset event counter CNTGGIO...........................................103Reset pulse counter PCGGIO..............................................103LDCM clear counters............................................................103Function for energy calculation and demand handlingETPMMTR............................................................................104

    Reset disturbances and event list DRPRDRE...........................104Reset LEDs...............................................................................104

    Start and trip LEDs...............................................................104All indication LEDs...............................................................104

    Reset lockout SMPPTRC .........................................................104Reset process eventlist.............................................................105Reset temperature functions.....................................................105

    Reset guide for REX060.................................................................105Resetting overvoltage................................................................105

    Section 15 Authorization................................................................107Overview.........................................................................................107Principle of operation......................................................................107LogOn or logOff..............................................................................109Authorization handling in the IED...................................................109Internet Protocol ports security guideline.......................................110

    Section 16 Glossary.......................................................................113

    Table of contents

    9Operator's manual

  • 10

  • Section 1 Introduction

    About this chapterThis chapter is an introduction to the operator’s manual, its purpose and usage.

    1.1 Introduction to the operator’s manual

    1.1.1 About the complete set of manuals for an IEDThe user’s manual (UM) is a complete set of five different manuals:

    IEC09000744-1-en.vsd

    Pla

    nnin

    g &

    pur

    chas

    e

    disp

    osal

    Eng

    inee

    ring

    Inst

    allin

    g

    Com

    mis

    sion

    ing

    Ope

    ratio

    n

    Mai

    nten

    ance

    Dec

    omm

    issi

    onin

    gde

    inst

    allin

    g&

    Application manual

    Operator’s manual

    Installation and

    Engineeringmanual

    Commissioning manual

    manualTechnical reference

    IEC09000744 V1 EN

    The Application Manual (AM) contains application descriptions, settingguidelines and setting parameters sorted per function. The application manualshould be used to find out when and for what purpose a typical protection functioncould be used. The manual should also be used when calculating settings.

    The Technical Reference Manual (TRM) contains application and functionalitydescriptions and it lists function blocks, logic diagrams, input and output signals,setting parameters and technical data sorted per function. The technical reference

    1MRK502028-UEN C Section 1Introduction

    11Operator's manual

  • manual should be used as a technical reference during the engineering phase,installation and commissioning phase, and during normal service.

    The Installation and Commissioning Manual (ICM) contains instructions onhow to install and commission the protection IED. The manual can also be used asa reference during periodic testing. The manual covers procedures for mechanicaland electrical installation, energizing and checking of external circuitry, setting andconfiguration as well as verifying settings and performing directional tests. Thechapters are organized in the chronological order (indicated by chapter/sectionnumbers) in which the protection IED should be installed and commissioned.

    The Operator’s Manual (OM) contains instructions on how to operate theprotection IED during normal service once it has been commissioned. Theoperator’s manual can be used to find out how to handle disturbances or how toview calculated and measured network data in order to determine the cause of a fault.

    The Engineering Manual (EM) contains instructions on how to engineer the IEDsusing the different tools in PCM600. The manual provides instructions on how toset up a PCM600 project and insert IEDs to the project structure. The manual alsorecommends a sequence for engineering of protection and control functions, LHMIfunctions as well as communication engineering for IEC 61850 and DNP3.

    1.1.2 About the operator’s manualUse the operator’s manual for instruction on how to perform common tasks duringnormal service.

    The operator’s manual contains the following chapters:

    • The chapter “Safety information” presents warnings and notices, which theuser should pay attention to.

    • The chapter “Overview” describes operations an operator may perform on adaily basis or when the need arises.

    • The chapter “Understand the local human-machine interface” describes howto use the human-machine interface.

    • The chapter “Understand the HMI tree” describes the different menu trees.• The chapter “Read measured values” describes how to locate and identify

    available measurement data.• The chapter “Event list” describes the location and nature of recorded events.• The chapter “Handle disturbances” describes how to retrieve disturbance

    information and reset alarms.• The chapter “Read and change settings” describes how to locate, and change

    settings and parameters.• The chapter “Diagnose IED status” describes the location and use of available

    diagnostic tools.• The chapter “Test the IED” describes the tests applicable to the IED.• The chapter “Control and supervise the bay” describes how to use the Single

    Line Diagram to open and close primary apparatuses.

    Section 1 1MRK502028-UEN CIntroduction

    12Operator's manual

  • • The chapter “Reset” describes resetting procedures.• The chapter “Authorization”describes user categories and password procedures.• The chapter “Glossary” describes words and acronyms used in the literature

    describing the IED.

    This manual does not contain any instructions for commissioning or testing.

    1.1.3 Intended audience

    GeneralThe operator’s manual addresses the operator, who operates the IED on a daily basis.

    RequirementThe operator must be trained in and have a basic knowledge of how to operateprotection equipment. The manual contains terms and expressions commonly usedto describe this kind of equipment.

    1.1.4 Related documentsDocuments related to REG670 Identity numberOperator’s manual 1MRK 502 028-UEN

    Installation and commissioning manual 1MRK 502 029-UEN

    Technical reference manual 1MRK 502 027-UEN

    Application manual 1MRK 502 030-UEN

    Product guide customized 1MRK 502 031-BEN

    Product guide pre-configured 1MRK 502 032-BEN

    Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670 1MRG001910

    Connection and Installation components 1MRK 513 003-BEN

    Test system, COMBITEST 1MRK 512 001-BEN

    Accessories for 670 series IEDs 1MRK 514 012-BEN

    670 series SPA and signal list 1MRK 500 092-WEN

    IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN

    Engineering manual 670 series 1MRK 511 240-UEN

    Buyer’s guide REG 216 1MRB520004-BEN

    Communication set-up for Relion 670 series 1MRK 505 260-UEN

    More information can be found on www.abb.com/substationautomation.

    1MRK502028-UEN C Section 1Introduction

    13Operator's manual

    HTTP://WWW.ABB.COM/SUBSTATIONAUTOMATION

  • 1.1.5 Revision notesRevision Description- First issue for 670 series version 1.2

    A Minor corrections made

    B Maintenance updates, PR corrections

    C Maintenance updates, PR corrections

    Section 1 1MRK502028-UEN CIntroduction

    14Operator's manual

  • Section 2 Safety information

    About this chapterThis chapter lists warnings and cautions that must be followed when handling theIED.

    2.1 Warnings

    Do not touch circuitry during operation. Potentially lethal voltagesand currents are present.

    Always connect the IED to protective earth, regardless of theoperating conditions. This also applies to special occasions such asbench testing, demonstrations and off-site configuration. Operatingthe IED without proper earthing may damage both IED andmeasuring circuitry and may cause injuries in the event of an accident.

    Never remove any screw from a powered IED or from a IEDconnected to powered circuitry. Potentially lethal voltages andcurrents are present.

    Always avoid touching the circuitry when the cover is removed.The product contains electronic circuitries which can be damaged ifexposed to static electricity (ESD). The electronic circuitries alsocontain high voltage which is lethal to humans.

    1MRK502028-UEN C Section 2Safety information

    15Operator's manual

  • 16

  • Section 3 Overview

    About this chapterThis chapter presents a general overview of the Operator's manual.

    3.1 Operator overview

    The Local human-machine interface (LHMI) on the IED provides an idealmechanism for the day to day operation and even advanced use of the IED. Thekeypad, LCD and LEDs on the front of the IED are what constitute the LHMI.Troubleshooting, apparatus control, monitoring, setting and configuring are allpossible via this interface. Through the screens and menu elements available, aswell as the keypad, the user is able to navigate throughout the menu structure andmove from screen to screen. This document is, to a great extent, arranged in thesame way as the IED software is structured and describes all aspects of operationvia the LHMI.

    The operator can document disturbances so that their causes can be analyzed andevaluated for future reference. For example, the fault currents and voltages at thetime of the fault can be documented. The operator can also retrieve data aboutprotected objects, providing further information for fault analysis. This impliesviewing the mean value of current, voltage, power and frequency or primary andsecondary measured phasors. The operator can check the IED status at any time.

    In some cases the operator may need to change the way the IED operates. Thismight include changing the active setting group or a parameter value. This mustalways be done strictly according to applicable regulations because un-authorizedchanges may lead to severe damage of the protected object especially if a fault isnot properly disconnected.

    3.2 Identify the IED

    To identify the IED, open the diagnostics menu. The identity of the IED along withother data is found under:

    Main menu/Diagnostics/IED status/Product Identifiers

    When the Product identifiers submenu is opened, the user sees the following screen:

    1MRK502028-UEN C Section 3Overview

    17Operator's manual

  • IEC10000336-1-en.vsd

    IED10000336 V1 EN

    Figure 1: Typical example of product identifier screen on local HMI

    IEDProdType is the Relion 670 series product type (REB,REC, RED, REG, REL, RET and so on)

    ProductDef specifies the version of the product, in thefollowing order: major version. minor version.major revision. minor revision (1.2.2.0 forexample)

    Both IEDProdType and ProductDef are visible in the PCM600 tool, under Properties:

    Section 3 1MRK502028-UEN COverview

    18Operator's manual

  • IEC10000337-1-en.vsdIEC10000337 V1 EN

    Figure 2: Typical example of IED product type and version properties inPCM600

    FirmwareVer Specifies the version of the product firmware

    IEDMainFunType Specifies the main IED functionality, inaccordance to IEC60870-5-103 numbering:

    • REL - 128, compatible range• REC - 242, private range• RED - 192, compatible range• RET - 176, compatible range• REB - 207, private range• REG - 150, private range• REQ – 245, private range

    SerialNo

    OrderingNo Are production identifiers

    ProductionDate

    1MRK502028-UEN C Section 3Overview

    19Operator's manual

  • 20

  • Section 4 Understand the IED local human-machine interface

    About this chapterThis chapter describes the display, its keys (buttons) and LEDs that make up thelocal HMI on the IED. How the keys are used to navigate the HMI, how tointerpret the graphic information on the LCD and, what the LEDs indicate isexplained in the sections that follow.

    4.1 Overview

    The human machine interface is used to monitor and to some extent control theway the IED operates. The configuration designer can add functions that alert toevents requiring the attention of the operator.

    IEC08000098 V1 EN

    Figure 3: 1/2 x 19” case with small LCD

    1MRK502028-UEN C Section 4Understand the IED local human-machine interface

    21Operator's manual

  • IEC08000084 V1 EN

    Figure 4: 1/1 x 19” case with medium LCD

    4.2 Keypad

    The keypad is used to monitor and operate the IED. The keypad has the same lookand feel in all IEDs. LCD screens and other details may differ but the way the keysfunction is identical.

    IEC05000153 V1 EN

    Figure 5: The HMI keypad.

    Table 1 describes the HMI keys that are used to operate the IED.

    Section 4 1MRK502028-UEN CUnderstand the IED local human-machine interface

    22Operator's manual

  • Table 1: HMI keys on the front of the IED

    Key Function

    IEC05000101 V1 EN

    Press to close or energize a breaker or disconnector.

    IEC05000102 V1 EN

    Press to open a breaker or disconnector.

    IEC05000103 V1 EN

    Press to open two sub menus: Key operation and IED information.

    IEC05000104 V1 EN

    Press to clear entries, cancel commands or edit.

    IEC05000105 V1 EN

    Press to open the main menu and to move to the default screen.

    IEC05000106 V1 EN

    Press to set the IED in local or remote control mode.

    IEC05000107 V1 EN

    Press to open the reset screen.

    IEC05000108 V1 EN

    Press to start the editing mode and confirm setting changes, when in editing mode.

    IEC05000109 V1 EN

    Press to navigate forward between screens and move right in editing mode.

    IEC05000110 V1 EN

    Press to navigate backwards between screens and move left in editing mode.

    IEC05000111 V1 EN

    Press to move up in the single line diagram and in the menu tree.

    IEC05000112 V1 EN

    Press to move down in the single line diagram and in the menu tree.

    4.3 Key activated screens

    4.3.1 The Help screenThe help screen is activated by pressing the Help key on the front panel of the IED.It includes the submenu listed below:

    • General operation

    The General Operation submenu provides information about the IED keypad.

    1MRK502028-UEN C Section 4Understand the IED local human-machine interface

    23Operator's manual

  • The I and O keys are used to open (OFF) and close (ON) breakers anddisconnectors when using the Single Line Diagram (SLD) in direct control situations.

    4.3.2 The Reset screenThe reset screen is activated by the Reset key on the front panel of the IED or viathe main menu. The reset screen includes the submenus listed below:

    • Reset LEDs• Reset lockout• Reset counters• Reset temperature functions

    The Reset LEDs submenu consists of two lower level menus which are the “Startand trip LEDs” and “All indication LEDs” submenus. To reset a counter, the actualcounter must first be selected. The submenus and their structures are discussed inthe “Reset” chapter of this document.

    4.4 LCD

    4.4.1 SmallThe small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on thesmall HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters perline. The first line displays the product name and the last line displays date andtime. The remaining 5 lines are dynamic. This LCD has no graphic display potential.

    4.4.2 MediumThe following case sizes can be equipped with the medium size LCD:

    • 1/2 x 19”• 3/4 x 19”• 1/1 x 19”

    This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28lines with up to 40 characters per line. To display the single line diagram, this LCDis required.

    Section 4 1MRK502028-UEN CUnderstand the IED local human-machine interface

    24Operator's manual

  • 4.5 LED

    4.5.1 IntroductionThe LED module is a unidirectional means of communicating. This means thatevents may occur that activate a LED in order to draw the operators attention tosomething that has occurred and needs some sort of action.

    4.5.2 Status indication LEDsThe three LEDs above the LCD provide information as shown in the table below.

    LED Indication InformationGreen:

    Steady In service

    Flashing Internal failure

    Dark No power supply

    Yellow:

    Steady Dist. rep. triggered

    Flashing Terminal in test mode

    Red:

    Steady Trip command issued

    4.5.3 Indication LEDsThe LED indication module comprising 15 LEDs is standard in 670 series. Its mainpurpose is to present an immediate visual information for protection indications oralarm signals.

    Alarm indication LEDs and hardware associated LEDs are located on the righthand side of the front panel. Alarm LEDs are located on the right of the LCDscreen and show steady or flashing light.

    • Steady light indicates normal operation.• Flashing light indicates alarm.

    Alarm LEDs can be configured in PCM600 and depend on the binary logic.Therefore they can not be configured on the local HMI.

    Typical examples of alarm LEDs

    • Bay controller failure• CB close blocked• Interlocking bypassed• Differential protection trip• SF6 Gas refill

    1MRK502028-UEN C Section 4Understand the IED local human-machine interface

    25Operator's manual

  • • Position error• CB spring charge alarm• Oil temperature alarm• Thermal overload trip• Bucholtz trip

    The RJ45 port has a yellow LED indicating that communication has beenestablished between the IED and a computer.

    The Local/Remote key on the front panel has two LEDs indicating whether local orremote control of the IED is active.

    4.6 Local HMI setup

    The contrast and other settings of the LCD can be adjusted from the local HMImenu tree. The contrast and other factory settings for the local HMI can beadjusted as follows:

    Settings/General settings/HMI/Screen

    4.7 How to navigate

    4.7.1 ReadTo read values and access information about the objects being monitored theoperator must navigate the menu tree using the arrow keys. The active submenu orvalue is highlighted.

    Navigation is as follows:

    • Press the right arrow key to move to the main menu.• Press the down arrow key to move from the Single line diagram to the desired

    submenu.• Use the right arrow key to move downwards in the HMI tree until the desired

    parameter is displayed.• Press C and the down arrow key simultaneously to see the next page in the

    parameter screen.• Press C and the up arrow key simultaneously to return to the previous

    parameter screen.• Use the left arrow key to navigate back up the menu tree.

    4.7.2 ChangeTo change a parameter setting the following steps should be followed:

    Section 4 1MRK502028-UEN CUnderstand the IED local human-machine interface

    26Operator's manual

  • 1. Navigate to the desired parameter or quantity using the arrow keys.2. Press the E key when the parameter to be changed is highlighted.3. Move between digits or letters using the left and right arrow keys.4. Use the up and down arrow keys to change the digit or letter concerned.5. Press the E key once the desired changes have been made.6. Press the left arrow key to move up a level in the HMI tree.7. You will be prompted to confirm the changes, use the left and right arrow keys

    to toggle between yes and no in the pop up window and press the E key toconfirm your choice.

    8. Press the left arrow key to move up to the next level in the HMI tree.

    4.7.3 ControlThe HMI offers the operator the opportunity to exercise direct local control overbreakers and other apparatuses in the bay using the graphic display and designatedkeys on the front panel of the IED.

    By pressing the L/R key until the uppermost of the two LEDs next to the key lightsup, local operator control can be exercised from the HMI.

    An apparatus is selected using the up and down arrow keys. The active apparatus ishighlighted in the display.

    The Open or Close commands are issued by pressing the O or I keys;

    The user is requested to confirm the command in a pop-up window.

    E confirms a command; C cancels it.

    Interlocking or synchrocheck conditions may cause other query windows to pop-up.

    1MRK502028-UEN C Section 4Understand the IED local human-machine interface

    27Operator's manual

  • 28

  • Section 5 Understand the injection unit local human-machine interface

    5.1 Injection unit REX060

    The injection unit REX060 is used to inject voltage and current signals to thegenerator or motor stator and rotor circuits. REX060 generates two square wavesignals with different frequencies for injection into the stator and rotor circuitsrespectively. The response from the injected voltage and currents are thenmeasured by the REX060 unit and amplified to a level suitable for the analogvoltage inputs of IED.

    For local operation, the REX060 unit is provided with a control panel on the front.

    Local operation shall only be performed according to the operationregulations set up by the relevant operation authority of the plant.

    5.2 REX060 start up sequence

    When the injection unit REX060 is energized, the ABB logotype is shownfollowed by current REX060 revision status. When the start up sequence iscompleted, the main menu (normal display content) is shown. The duration of thestart up sequence is a few seconds.

    1MRK502028-UEN C Section 5Understand the injection unit local human-machine interface

    29Operator's manual

  • 5.3 REX060 Front panel controls

    IEC11000053-1-en.vsd

    IEC11000053 V1 EN

    Figure 6: REX060 front panel

    Section 5 1MRK502028-UEN CUnderstand the injection unit local human-machine interface

    30Operator's manual

  • Table 2: HMI keys on the front of the injection unit REX060

    Key FunctionThe Injection switch enables injection at rotor and stator 2s after switching on. A LED indicates that the injectionswitch is set to enable injection. The injection switch canbe padlocked in off position in order to cut-off bothinjection signals.

    The Key-lock button enables/disables the keypad.Hold the Key-lock button for a period of 1.2 s to 4 s to lockor unlock the keys. A key-lock LED indicates when thekeypad is unlocked.

    • Moves the cursor in the direction of the arrows• With the cursor is in value change state, pressing

    the up button increases the value and pressing thedown button decreases the value.

    Pressing the clear button cancels changes that have notbeen stored.

    Pressing the enter button stores the changed value. If thevalue is outside range, the limit value is stored.

    5.4 Display

    On the front of the enclosure there is a backlit LCD.

    • 6 x 12 pixel characters• Graphical LCD 128 x 64 pixels

    In figure 7 the content of the display is shown for a REX060 with one SIM and oneRIM module. Row 1 contains mains frequency information. Row 2-3 containsstator information and row 4-5 rotor information. Column 1 (empty) gives status,column 2 and 3 are informative and column 4 contains variables, settable by thekeypad.

    1MRK502028-UEN C Section 5Understand the injection unit local human-machine interface

    31Operator's manual

  • System

    STATOR

    UmaxEFROTOR

    Gainf [Hz] :

    [V] :

    f [Hz] :

    f [Hz] : 50

    087

    120

    113

    4

    IEC10000334-1-en.vsd

    Column 1 2 3 4Row

    1

    2

    3

    4

    5

    IEC10000334 V1 EN

    Figure 7: Display content in normal operation

    Column 1 (status column) symbolsTable 3: Status symbols and their description

    Status symbol Description of the status Priority

    IEC10000329 V1 EN

    Over voltage occurred, injection is blocked. This can occur onboth X61/62 and X81/82 (Stator & Rotor) simultaneously or oneither of them. The symbol is displayed in the status column(column 1) in row 2 for X61/62 and in row 4 for X81/82. Theinjection is blocked until a manual reset of the blocking occurs.

    1

    IEC10000330 V1 EN

    Injection blocked by the injection switch. The symbol is displayedin the status column (column 1) and is always shown in both row2 and 4.

    2Over voltage

    blocked statusoverrides

    displaying ofthis status

    Ø

    Injection blocked by binary input. Blocked injection will be shownin the status column (column 1) depending on binary in status.This can occur on both X61/62 then shown in row 2 and X81/82then shown in row 4 (Stator & Rotor) simultaneously or on etherof them.

    3Injection

    switch andover voltage

    blockedoverrides

    displaying ofthis status

    IEC10000332 V1 EN

    Analog output saturation. This status is set when the analogsignal, current and or voltage, to REG670 IED is too high andmay thereby be incorrect due to saturation in amplifier stage.Saturation status will be shown in the status column (column 1)in row 3 or 5 depending on the saturation occurrence

    Not applicable

    Backlight is on for 30 seconds after pressing any button. Backlight activation bypressing any button does not cause any other action than turning on the backlight.

    Section 5 1MRK502028-UEN CUnderstand the injection unit local human-machine interface

    32Operator's manual

  • 5.5 How to set frequency and voltage and current gainfactors

    Frequency, current and voltage gain for the stator and/or rotor can be set and storedfrom the injection unit HMI. If a value is out of range, the limit value is stored. Thedisplay shows the latest stored settings.

    The settings are stored in non-volatile memory, which means that they remainstored in case IED is powered off.

    5.5.1 Setting system frequencyFrequency can be set to either 50 or 60 Hz.

    1. Use the Up and Down button to select frequency.2. Store the new frequency by pressing the Enter button, or clear the last stored

    frequency by pressing the Clear button.

    5.5.2 Setting stator and rotor injection frequencyFrequency can be set as integer in range 50 to 250 Hz for a stator and 75 to 250 Hzfor a rotor.

    1. Use the keypad to navigate to stator or rotor frequency (row 2 or 4)2. Press E to enter value change state3. Use the Up and Down button to select frequency4. Store the new frequency by pressing the E (Enter) button, or clear the chosen

    frequency by pressing the C (Clear) button

    5.5.3 Selecting rotor gainDefault (gain factor 3) is the recommended level, where a defined effect of worstcase single fault at exciter circuit is allowed. A higher gain factor (4) may causesaturation in case of single fault in exciter circuit. A lower gain factor may beneeded if the degree of disturbance is high. Change from default value only ifrequested by ICT tool during calibration procedure.

    Select rotor gain factor according to the table below.

    1MRK502028-UEN C Section 5Understand the injection unit local human-machine interface

    33Operator's manual

  • Table 4: Rotor gain

    Gain factor Note1 Extreme

    2 Enhanced

    3 Default

    4 Reduced

    5.5.4 Selecting stator gainStator gain factor for both voltage and current depends on the highest voltage thatmay occur at the injection point of VT or DT. That voltage depends on the VT/DTratio and the stator rated primary voltage.

    Select gain factor in accordance with highest voltage that may occur at theinjection point. See Technical reference manual for exact formulas depending onparticular injection arrangement.

    Table 5: Stator gain

    UmaxEF [V] Note240

    200

    160 Default value

    up to 120

    5.5.5 Resetting overvoltageStator and rotor injection output is protected against voltages exceeding maximumoperating range (10% of rated VT/DT) by a relay blocking the injection circuit.This blocking is controlled by measuring the stator and/or rotor voltage, andremains blocked until manually reset. The blocking remains in the non-volatilememory when the IED is powered off.

    Overvoltage blocking is indicated by a symbol shown in Table 3.

    Resetting procedure:

    1. Power off the REX060.2. Press and hold the C and Key-lock buttons.3. Power on the REX060 and wait until the status indication Over-voltage

    (symbol) disappears from the display.4. Release the C and Key-lock buttons.

    Section 5 1MRK502028-UEN CUnderstand the injection unit local human-machine interface

    34Operator's manual

  • REX060 stator and rotor overvoltage protection of injection circuit

    Both rotor and stator have two levels of protection, injection circuit interruptioncontrolled by the voltage sense input and a fuse for over-current protection. Thevoltage controlled interruption, overvoltage, will normally occur prior tointerruption by fuse and the reset sequence is described above. A blown fuserequires module disassembling to replace the fuse (F 4 A 250 V for stator and F160 mA 250 V for rotor). However, if this occurs it is recommended to identify thereason for the over-current and take necessary actions to reduce the current beforerestarting the unit. The problem must be outside the injection unit since this unitcannot provide enough energy to blow the fuse.

    REX062 input protection

    REX062 limits overvoltage by a varistor at the injection output to stator.Normally , REX060 will interrupt the injection circuit in case of excessive over-current in the injection chain. Fuse within REX062 is an additional protection incase of failure within REX062 during over-voltage condition.

    A blown REX062 fuse requires a module disassembling to replace the fuse (F 6.3A 250 V). However, if this occurs it is recommended to identify the reason for theover-current and do needed actions to reduce the current.

    1MRK502028-UEN C Section 5Understand the injection unit local human-machine interface

    35Operator's manual

  • 36

  • Section 6 Understand the HMI tree

    About this chapterThis chapter describes the structure of the HMI. The main menu includessubmenus such as Measurements, Events, Disturbance Report, Settings,Diagnostics, Test and Reset. These branch out into a typical tree structure.

    6.1 Overview

    The local HMI has the following main menu:

    • Control• Measurements• Events• Disturbance records• Settings• Diagnostics• Test• Reset• Authorization• Language

    Each main menu item can have several other submenus.

    6.1.1 Menu-tree for REG670Main menu Sub menu Sub-sub menuControl Single line diagram

    Commands

    Measurements Analog primary valuesAnalog secondary valuesAnalog mean valuesMonitoringMetering

    Events

    Disturbance records Manual trig

    Settings Time

    Table continues on next page

    1MRK502028-UEN C Section 6Understand the HMI tree

    37Operator's manual

  • Main menu Sub menu Sub-sub menu General settings Power system

    CommunicationAnalog modulesI/O modulesHMIDifferential protectionImpedance protectionCurrent protectionVoltage protectionControlMonitoringMetering

    Setting group N Differential protectionImpedance protectionCurrent protectionVoltage protectionFrequency protectionMultipurpose protectionScheme communicationSecondary systemsupervisionControlMonitoringLogic

    Activate setting group

    Diagnostics Internal eventsIED status

    Test IED test modeBinary input valuesBinary output valuesFunction test modesFunction statusLED testLine differential test

    Reset Reset countersReset internal eventlistReset LEDsReset lockoutReset temperature

    Authorization

    Language

    Section 6 1MRK502028-UEN CUnderstand the HMI tree

    38Operator's manual

  • Section 7 Read measured values

    About this chapterThis chapter describes measurement categories and how to locate them using theHMI. Each measurement category has a section of its own that includes a generaldescription of the type of quantity being measured and the path in the local HMI tothe measurement.

    7.1 Overview

    The measurement menu contains primarily analog measurement data. Externalsignals can also be viewed as they are or as they appear in the Signal Matrix Tool(SMT). These signals are a virtual representation of the hard wired signals on thevarious inputs and outputs. SMT is only accessible via PCM600 and is intended tosimplify the configuration of the IED. It allows hardware changes to be madewithout having to reconfigure the internal logic. Signals that can be used in SMTare indicated with the Suffix SMT.

    The functions available under measurements are outlined below.

    1. Analog primary values are the quantities measured on the primary side of thecurrent and voltage transformers (CTs and VTs).

    2. Analog secondary values are the quantities measured on the secondary side ofthe current and voltage transformers. These are the quantities measured on theTransformer module (TRM) inputs.

    3. Analog mean values are the quantities measured at the inputs of themilliampere module (MIM).

    4. Under Monitoring a number of submenus are available. These include Servicevalues, Current phasors, Voltage phasors, Current sequence components andVoltage sequence components.

    5. Metering displays the pulse counter and energy calculation and demandhandling functions. The measurements available for pulse counter show pulsecounter status data.

    All measurement descriptions in this document reflect the maximum number ofhardware units possible in any application. In reality the hardware in the IED willbe chosen according to a particular application. For example, it is possible to equipa 1/1 x 19” case IED with 14 I/O modules. In reality fewer I/O modules may beinstalled. In the measurements menu the operator will only see data from thehardware and software installed.

    1MRK502028-UEN C Section 7Read measured values

    39Operator's manual

  • Measurement for voltage channels used for injection protection (i.e.connected to REX060) will not display correct values becauseinjection frequency differs from the rated power system frequency.To monitor these values use service values under respectiveprotection function.

    7.2 View analog primary values

    7.2.1 OverviewThe analog primary values are analog quantities measured on the primary side ofthe TRM and reflect the actual current or voltage on the primary side of the VTsand CTs. The ratio is adjusted under settings and also depends on the rating of theTRM. 24 primary values and phase angles are displayed in this view.

    The analog primary values are values on the input (primaryequipment side) of the merging unit (MU) when IEC 61850-9-2LEprocess bus communication is used. These values are scaledaccording to a fixed "universal" scaling of 1 mA per LSB and 10mV per LSB and transmitted to the IED via IEC 61850-9-2LEprotocol.

    Main menu/Measurements/Analog primary values

    Displays the quantities measured by the transformer module (TRM) or received viaIEC 61850-9-2 LE process bus. For each channel used the amplitude of the voltageor current and its phase angle is shown. If the amplitude is to low for calculation,the angle will be indicated with "- - -". The status of the module is always shownand channels not in use are indicated with "- - " . Data from TRMs and LDCMs aswell as Merging Units can be viewed. All currents and voltages are given in RMSvalues.

    7.3 View analog secondary values

    7.3.1 Overview

    Analog secondary values shows secondary CT currents and VT voltages. These arethe actual current and voltage values at the TRM inputs.

    Section 7 1MRK502028-UEN CRead measured values

    40Operator's manual

  • For analog values received from Merging Units, no analog secondary values areshown.

    Main menu/Measurements/Analog secondary values

    Displays up to 24 channels with secondary CT and VT data. RMS values are shown.

    7.4 View analog mean values

    7.4.1 OverviewMeasurements from the Milliampere Input Module (MIM) are found in this part ofthe measurements menu. Data from either the hard wired mA module or SignalMatrix Tool mA modules are shown here.

    7.4.1.1 mA input module MIM

    Main menu/Measurements/Analog mean values/mA modules/MIM:x

    Displays input data from the milli-ampere module which has six inputs. Each inputhas a range of +/- 20 mA. The value displayed on the screen is however dependanton the settings for the Milli-ampere Module. In the menu for settings, the range anda transformation factor can be adjusted to suit the application. This means that aninput 3 mA may be displayed as temperature of 45 degrees. The output valuesshown are without units.

    7.4.1.2 Signal matrix for mA inputs SMMI

    Main menu/Measurements/Analog mean values/SMT mA modules/Instance:x

    Displays the input signals coming into the Milli-ampere Module. Each module hassix physical inputs with an input tolerance of +/- 20mA. The value displayeddepends on the settings applied to this board which may for example cause an inputof 3mA to show a value 30. The SMT mA modules are the virtual representation ofMIMs in Signal Matrix Tool.

    7.5 View monitoring values

    7.5.1 Service values CVMMXNMain menu/Measurement/Monitoring/ServiceValues(MMXN)/CVMMXN:x

    Displays up to three instances of CVMMXN with measured values for S, P, Q, PF,U, I, ILead, ILag and F.

    1MRK502028-UEN C Section 7Read measured values

    41Operator's manual

  • 7.5.2 Current phasors CMMXUMain menu/Measurement/Monitoring/CurrentPhasors(MMXU)/CMMXU:x

    All three phase currents and their phase angles are displayed here.

    7.5.3 Voltage phasors VMMXU/VNMMXU

    Main menu/Measurements/Monitoring/VoltagePhasors(MMXU)/Phase -Phase/VMMXU:x

    Phase to phase voltages and phase angles are displayed here.

    Main menu/Measurement/Monitoring/VoltagePhasors(MMXU)/Phase - Earth/VNMMXU:x

    Phase to earth voltages and phase angles are displayed here.

    7.5.4 Current sequence component CMSQIMain menu/Measurements/Monitoring/CurrentSequenceComponents(MSQI)/CMSQI:x

    The current sequence component under monitoring displays the positive (I1),negative (I2) and zero sequence (I0) current values for a three phase line, bothmagnitude and phase angle for each component are displayed. These indicate howwell balanced a system is. In an ideal balanced system the zero sequence currentshould be zero, the positive sequence current should be equal to the current of eachphase with the same phase angle (relative to GPS) as the L1 phase signal and thenegative sequence current should be zero.

    7.5.5 Voltage sequence component VMSQIMain menu/Measurements/Monitoring/VoltageSequenceComponents(MSQI)/VMSQI:x

    The Voltage sequence component displays the positive (U1), negative (U2) andzero (U0) sequence components in the system, and includes the magnitude andphase angle of each component.

    7.6 View metering values

    7.6.1 Pulse counter logic PCGGIOMain menu/Measurements/Metering/PulseCounter(PCGGIO)/PCGGIO:x

    Section 7 1MRK502028-UEN CRead measured values

    42Operator's manual

  • The output data generated from the pulse counter function include data about thestatus of the counter and counter values.

    7.6.2 Function for energy calculation and demand handlingETPMMTRMain menu/Measurements/Metering/ThreePhEnergMeas(MMTR)/ETPMMTR:x

    The output data generated from the energy measuring function includes activeforward/reverse energy and reactive forward/reverse energy.

    1MRK502028-UEN C Section 7Read measured values

    43Operator's manual

  • 44

  • Section 8 Event list

    About this chapterThis chapter describes how to find and read the event list.

    8.1 View events

    8.1.1 OverviewEvents displays recorded events such as trips and breaker opened or closed.

    Main menu/Events

    Displays a list of events in chronological order and where each event has a timestamp. The latest event is at the top of the list.

    1MRK502028-UEN C Section 8Event list

    45Operator's manual

  • 46

  • Section 9 Handle disturbances

    About this chapterThis chapter describes disturbance detection and handling. This includes resettingLED alarms, triggering disturbance reports and the viewing of several fault indicators.

    9.1 Identify a disturbance

    A disturbance record can be generated manually by using the Manual Trigfunctionality in the HMI menu. Other disturbance records are generatedautomatically in the system dependant on the settings made. Disturbance reportsgenerate a disturbance sequence number and are time tagged. The fault locationand fault loop are among the data generated in a fault record. Under each faultreport there are five categories of information available. These are described in thesections that follow.

    9.2 View disturbance record details

    9.2.1 View general information

    By choosing General information after selecting a disturbance record in the list ofdisturbance records the screen generated displays information about thedisturbance such as its sequence number, time of occurrence, trig-signal, faultlocation and fault loop. The path in the HMI is shown below.

    Main menu/Disturbance records/Manual trig

    9.2.2 View disturbance indications

    The Indications section of a disturbance record displays the recording number and,the time and date of the disturbance. The path in the HMI is shown below.

    Main menu/Disturbance records/Record xx/Indications

    9.2.3 View event recordingsThe Event recording section in the Disturbance report shows the recording number.The path in the HMI is shown below.

    1MRK502028-UEN C Section 9Handle disturbances

    47Operator's manual

  • Main menu/Disturbance records/Record xx/Event recording

    9.2.4 View trip valuesIn the Trip values section of a disturbance recording both the pre-fault and the faultvalues for current, voltage and phase angle can be viewed. The recording numberand Trig time are also displayed. The path in the HMI is shown below.

    Main menu/Disturbance records/Record xx/Trip Values

    9.3 Trigger a disturbance report manually

    Using the manual trigger generates an instant disturbance report. Use this functionto get a snapshot of the monitored line. Follow the path below and answer yes inthe Execute manual trig dialog box.

    Main menu/Disturbance records/Manual trig

    Section 9 1MRK502028-UEN CHandle disturbances

    48Operator's manual

  • Section 10 Read and change settings

    About this chapterThis chapter describes how to find and change settings and parameters. The chapteris divided into two sections which match the way the two categories of settings aredivided up in the HMI. The General settings group consists of those parametersthat cause an automatic restart of the IED. The Setting group N consists of sixgroups of settings with default values for all parameters. These do not require orcause a restart once they have been changed. Time, synchronization and theactivation of setting groups are also dealt with here.

    It takes a minimum of three minutes for the IED to save the newsettings, during this time the DC supply must not be turned off.

    Do not perform a setting change at the same time as a hardwarereconfiguration. Doing so might cause the IED to malfunction.

    10.1 System time and synchronization

    10.1.1 System timeMain menu/Settings/Time/System time

    Under System time, the system clock date and time are set. If there is a need tochange the time settings in the LHMI the changes will take effect immediately. Toconfirm the new settings, press E. To remove the changes, press C.

    10.1.2 Time synchronization

    10.1.2.1 Overview

    The synchronization settings are divided into categories Time synch, Time synchBIN, Time synch SNTP, Time synch DST Begin, Time synch DST End, Timesynch time zone and Time synch IRIG-B. The settable parameters are found undereach category.

    10.1.2.2 TimeSynch

    Main menu/Settings/Time/Synchronization/TIMESYNCHGEN:x/General

    1MRK502028-UEN C Section 10Read and change settings

    49Operator's manual

  • Here the parameters FineSyncSource, CourseSyncSrc and SyncMaster areswitched on or off.

    Main menu/Settings/Time/Synchronization/TIMESYNCHGEN:x/IEC61850-9-2

    The synchronization parameters for IEC 61850-9-2LE process bus communicationare set here.

    IEC 61850-9-2LE process bus communication is not supported inREG670.

    10.1.2.3 TIMESYNCHBIN

    Main menu/Settings/Time/Synchronization/SYNCHBIN:x

    Binary input synchronization settings available here are the position of the of themodule, the number of the binary input and the detection mode.

    10.1.2.4 DSTBEGIN

    Main menu/Settings/Time/Synchronization/DSTBEGIN:x

    The starting point for Daylight Savings Time is set here.

    10.1.2.5 DSTEND

    Main menu/Setttings/Time/Synchronization/DSTEND:x

    The end point of Daylight Savings Time is set here.

    10.1.2.6 SYNCHIRIG-B

    Main menu/Settings/Time/Synchronization/SYNCHIRIG-B:x

    The type of input, time domain, type of encoding and time zone for IRIG-B are sethere.

    10.1.2.7 SYNCHSNTP

    Main menu/Settings/Time/Synchronization/SYNCHSNTP:x

    Here the IP addresses for the Simple Network Time Protocol servers are set.

    10.1.2.8 TIMEZONE

    Main menu/Settings/Time/Synchronization/TIMEZONE:x

    Section 10 1MRK502028-UEN CRead and change settings

    50Operator's manual

  • The time zone according to Coordinated Universal Time (UTC) is set here.

    10.2 General settings

    Parameters under General settings that are changed will cause the IED to restart.This occurs automatically and requires no manual intervention.

    The IED must be in setting group 1 before changing settings inGeneral settings

    10.2.1 Power system

    10.2.1.1 Overview

    Under Power system in General settings there are four parameter categories. Theseare Identifiers, Primary values, three phase analog group and three phase analogsum group.

    10.2.1.2 Identifiers

    Main menu/Settings/General settings/Power system/Identifiers

    Displays list with Station Name, Station Number, Object Name, Object Number,Unit Name and Unit Number.

    10.2.1.3 Primary values

    Main menu/Settings/General settings/Power system/Primary values

    Displays the system frequency.

    10.2.2 Communication

    10.2.2.1 Overview

    The parameter settings for communications are found under General Settings\Communications. Communication settings cover network interfaces, protocol,remote communication and reception of interlocking information.

    10.2.2.2 Remote communication

    Main menu/Settings/General settings/Communication/LDCM configuration/LDCMX

    1MRK502028-UEN C Section 10Read and change settings

    51Operator's manual

  • Displays settings for Remote Binary Communication (CRB) and for Remote MultiCommunication (CRM). The multi communication block can send both binary andanalog data whereas the binary can only send binary data.

    Each instance of CRB has several settable parameters where the channel mode canbe set on or off, terminal numbers can be entered, synchronization can be set tomaster or slave and opto power can be set high or low.

    Each instance of CRM has several settable parameters. These include those aboveand others such as transmission delay and transmission current.

    10.2.2.3 SPA, LON and IEC 60870–5–103 settings

    Rear optical LON port

    The menu for the rear optical LON port has five submenus for various settingsaffecting LON parameters. The HMI paths to these submenus and their contentsare described below.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical LON port/General

    In the General submenu there are three settings. These are for the Subnet address,the Node address and the NeuronID.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical LON port/ServicePinMessage

    In this submenu a Service pin message can be generated. This is similar to a “ping”in traditional networks. This sends a signal to another node in the system which isthen made aware of the Neuron ID of LON port and can respond to that port.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical LON port/ADE

    The Application Data Event (ADE) menu is where operation of LON is set on oroff and where the data exchange speed can be set. If LON is used primarily to sendevent data then the appropriate setting is slow. Should LON be used, for example,as a channel for TRIP signals then the setting fast would be appropriate.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical LON port/SPA

    Settings for SPA over LON are made here. The operation setting is used to switchthe function on or off and the slave address setting is where the slave address isentered.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical LON port/Horizontal communication

    This setting is used to activate or deactivate horizontal communication.

    Section 10 1MRK502028-UEN CRead and change settings

    52Operator's manual

  • Rear optical SPA-IEC-DNP port

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical SPA-IEC-DNP port

    In this submenu SPA or IEC is chosen and the necessary settings for the respectivecommunication protocols are made.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical SPA-IEC-DNP port/Protocol selection

    SPA and IEC cannot run at the same time and in this submenu one of the options ischosen.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical SPA-IEC-DNP port/SPA

    When SPA is chosen the baud rate and slave address are set here.

    Main menu/Settings/General settings/Communication/SLM configuration/Rear optical SPA-IEC-DNP port/IEC60870–5–103

    When IEC 60870–5–103 is used the settings Slave address, Baud rate, RevPolarityand CycMeasRepTime are done here.

    10.2.2.4 Station communication

    DNP3.0 for TCP/IP and EIA-485 communication protocol

    Main menu/Settings/General settings/Communication/Station communication/DNP3.0

    The DNP 3.0 related parameters are found here.

    GOOSE Binary receive

    Main menu/Settings/General settings/Communication/Station communication/GOOSEBinReceive/GOOSEBINRCV:x

    Includes available instances of GOOSE binary receive (GOOSEBINRCV) wheresetting Operation can be set On or Off.

    IEC61850–8–1

    Main menu/Settings/General settings/Communication/Station communication/IEC61850–8–1

    Includes settings for the IED name,Operation (On/Off) and GOOSE.

    Multicommand send

    1MRK502028-UEN C Section 10Read and change settings

    53Operator's manual

  • Main menu/Settings/General settings/Communication/Station communication/MultiCommandSend/MULTICMDSND:x

    Includes available instances of Multicommand send settings allowing the user toadjust the maximum and minimum cycle time.

    Multicommand receive

    Main menu/Settings/General settings/Communication/Station communication/MultiCommandReceive/MULTICMDRCV:x

    Includes available instances of Multicommand receive settings allowing the user toadjust the maximum and minimum cycle time, the pulse duration and mode ofoperation. The mode of operation is either steady or pulsed.

    Horizontal communication via GOOSE for interlocking

    Main menu/Settings/General settings/Communication/Station communication/ReceivingInterlInfo/GOOSEINTLKRCV:x

    Includes available instances of GOOSEINTLKRCV for horizontal communicationvia GOOSE. Each instance or set can be switched On or Off via the Operation Onand Off parameter.

    10.2.2.5 Ethernet configuration

    IEC 61850-9-2LE process bus communication is not supported inREG670.

    Main menu/Settings/General settings/Communication/Ethernet configuration/Front port

    The IP Address and IP mask for the ethernet port on the front panel of the IED areset here. These are generally used when connecting a PC directly to the IED.Remember that this is a static IP address and that the appropriate network settingsmust also be made in the PC.

    Main menu/Settings/General settings/Communication/Ethernet configuration/Rear OEM-Port AB

    The IP address, IP mask and Mode for the IEC 61850-8-1 communication using theOptical Ethernet Module (OEM) at the rear of the IED are set here.

    Main menu/Settings/General settings/Communication/Ethernet configuration/Rear OEM-Port CD

    The IP address (with different IP address when a second channel is used), IP maskand Mode for the Optical Ethernet Module (OEM) at the rear of the IED are sethere. The CD port is used for IEC 61850-9-2LE communication.

    Section 10 1MRK502028-UEN CRead and change settings

    54Operator's manual

  • Main menu/Settings/General settings/Communication/Ethernet configuration/Rear OEM - Redundant PRP

    Redundant station bus communication IEC61850-8-1 are set here.

    Main menu/Settings/General settings/Communication/Ethernet configuration/Gateway

    If a gateway is used to access the system the address to that gateway is entered here.

    10.2.3 Analog and I/O modules

    10.2.3.1 Overview

    Under Analog modules in the General settings menu there are settings for Analoginputs and I/O modules. Within each instance of analog input there are settings forall 12 channels that include the name of the channel, star point of the CT circuit,the primary and secondary values from the measuring transformers (CTs and VTs).The channel type and ratings are shown but cannot be changed.

    The settings for binary inputs and outputs even include the milliampere inputmodules. A mix of up to 14 instances of BIM, BOM and IOM is possibledepending on the physical configuration of the IED. Operation ON or OFF can beset for all of these and for the BIMs oscillation release and oscillation blocksettings are available. These settings are on board level and apply to all binaryinputs or outputs on a board.

    10.2.3.2 Analog modules

    Main menu/Settings/General Settings/Analog modules/AnalogInputs

    Displays all variations of analog input modules with parameters. The analog inputmodules have different combinations of current and voltage inputs. Each channelhas parameters where the type of channel is set, the primary and secondary valuesfrom VTs and CTs and for Current Transformers the star point location (line sideor busbar side) is set.

    Main menu/Settings/General Settings/Analog modules/MergingUnit

    Displays parameters for the merging units. For the MU channels, no primary orsecondary values need to be set, due to the fixed standardized scaling of 1 mA/10mV per LSB

    Main menu/Settings/General Settings/Analog modules/3PhaseAnalogGroup/SMAIX:Y

    Here, settings for the Fourier filters, the minimum system voltage required tomeasure frequency, the item designation of CTs or VTs, and the system voltage are

    1MRK502028-UEN C Section 10Read and change settings

    55Operator's manual

  • set. These settings are required by the preprocessing blocks and are usually onlyadjusted during the initial engineering phase.