Electrical Protection
![Page 2: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/2.jpg)
![Page 3: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/3.jpg)
Electrical Faults
� Phase to phase� Phase to ground� Phase to phase to phase� Phase to phase to phase to ground
![Page 4: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/4.jpg)
Purpose of Protection System
� Minimize damage� Leave unaffected equipment in-service� Maintain equipment operating limits� Maintain electrical system stability
![Page 5: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/5.jpg)
Requirements of a Protection System
� Speed� Reliability� Security� Sensitivity
![Page 6: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/6.jpg)
Some terms
� Over-current� Overload� Inverse time
![Page 7: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/7.jpg)
Protection Zones
![Page 8: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/8.jpg)
Simple Zone
![Page 9: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/9.jpg)
![Page 10: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/10.jpg)
Double Protection
"A" Bus Protection
"B" Bus Protection
CircuitBreaker
X
Bus
CircuitBreaker
Y
CT2
CT3
CT3
CT1
Bus Zone
CT4
CT2
CT4
CT1
![Page 11: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/11.jpg)
ProtectionZones
xBusH2
Y
Bus Zone H2
Bus H1
Bus Zone H1
Bus Zone H3
BusH3
TransformerT1
ZoneT1
ZoneG1G1
TransformerSST1
ZoneSST1
SST1LV Bus
Bus Zone L1Bus L1
![Page 12: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/12.jpg)
Breaker Failure
� Minimizes the amount of equipment removed from service in event of a failure
� Failure Determination� Not started opening in a certain time� Not open in a certain time� Current not broken in a certain time
![Page 13: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/13.jpg)
Duplicate Protection Schemes
A Protection B Protection
Breaker X Breaker Y Device ZAction Q
Initiate InitiateTrip TripClose Close
PT
CT2
CT1 Electrical bus Electrical
System
ProtectionLogic
ProtectionOutput
ElectricalDevices
SystemInput
![Page 14: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/14.jpg)
Bus Protection
![Page 15: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/15.jpg)
Bus Protection
� Over-current� Differential � Back-up� Under voltage
![Page 16: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/16.jpg)
Over-current Relay
I 1P
I 1S
CT 2000/5 A
![Page 17: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/17.jpg)
Differential Protection
I 1P
I 1S
CT1 2000/5 A
I 2P
I 2S
CT2 2000/5 ABusH1
X Y
I = I1S = I2S
I = I1S = I2S
I = I1P = I2P
I 2SI 1S
![Page 18: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/18.jpg)
Fault Conditions
I 1P
I 1S
CT1 2000/5 A
I 2P
I 2S
CT2 2000/5 ABusH1
X Y
I 1SI 2S
Fault
![Page 19: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/19.jpg)
I 1P
CT 2000/5 A
I 2P
CT 2000/5 ABusH1
X Y
I 1S I 2S
I 1S
I 3S CT 2000/5 A
I 3P
T1
I 2S
I3S
![Page 20: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/20.jpg)
Bus Protection Scheme
X
YLoadL2
LoadL1
T1
S Bus
Bus Differential Backup
Zone L1
Zone L2
![Page 21: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/21.jpg)
Back-up relay
X
YLoad
L2
LoadL1
T1
S Bus
Over CurrentBackup Relay Differential
Relay
![Page 22: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/22.jpg)
Bus Under Voltage Protection
Armature shown in the non-energized (trip) position
NormallyOpenContacts
To PotentialTransformer
![Page 23: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/23.jpg)
![Page 24: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/24.jpg)
![Page 25: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/25.jpg)
Bus Protection
� Over-current� Differential � Back-up� Under voltage
![Page 26: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/26.jpg)
Transformer Protection
![Page 27: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/27.jpg)
Transformer Protection
� Instantaneous� Differential� Gas� Thermal Overload� Ground
![Page 28: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/28.jpg)
Transformer Characteristics
� High magnetizing inrush currents� Ratio mismatch with CTs aggravated by
tap-changers� Phase shifts� Transformers are affected by over-fluxing� Affected by over-temperature
![Page 29: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/29.jpg)
Transformer Zone
T1
CT2
CT3
CT4
CT1
T1 Zone
CT3
CT1
CT4
CT2
"A" Transformer Protection
"B" Transformer Protection
![Page 30: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/30.jpg)
Differential
I 1P
I 1S
CT1
I 2P
I 2S
CT2
I = I1S = I2S
T1
Operate Coil
Restraint Coil
Restraint Coil
I 1S I 2S
![Page 31: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/31.jpg)
![Page 32: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/32.jpg)
![Page 33: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/33.jpg)
![Page 34: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/34.jpg)
![Page 35: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/35.jpg)
Gas Relay
![Page 36: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/36.jpg)
Winding Temperature
![Page 37: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/37.jpg)
Ground Fault Protection
CT1
T1
GroundBackup
DifferentialRelay
CT2
TransformerStar Point
GroundCT
IN
IN
CT3IF
![Page 38: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/38.jpg)
Transformer Protection
� Instantaneous� Differential� Gas� Thermal Overload� Ground
![Page 39: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/39.jpg)
Motor Protection
![Page 40: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/40.jpg)
Service Factor
� Continuous allowable overload� Many motors some with a power rating and a
service factor� A 10 HP motor with a service factor of 1.15
has a maximum continuous output of 11.5 HP
![Page 41: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/41.jpg)
Motor Protection Summary
� Instantaneous Over-current� Stall� Thermal Overload� Phase Unbalance� Ground
![Page 42: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/42.jpg)
Inverse Time Relay
![Page 43: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/43.jpg)
![Page 44: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/44.jpg)
Overload
![Page 45: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/45.jpg)
Ground Fault Protection
![Page 46: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/46.jpg)
Single Phase to Ground Protection
![Page 47: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/47.jpg)
Stalls
![Page 48: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/48.jpg)
Thermal Overload & Phase Unbalance
![Page 49: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/49.jpg)
Diagram of the Unit
Rotation as Ele me nts He at/Co ol
Phase Unbalance Contac tsLoad Indicating Po inte r
Adjus table Ove rload Contac t
Ove rloadSettingPo inte r
Shaft
He ater(e le c trical
c onnec tio ns no ts ho wn)
Ac tuating Bime tal
Ambie nt Co mpensating Bime tal
He at Shie ld
![Page 50: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/50.jpg)
![Page 51: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/51.jpg)
![Page 52: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/52.jpg)
![Page 53: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/53.jpg)
![Page 54: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/54.jpg)
![Page 55: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/55.jpg)
![Page 56: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/56.jpg)
![Page 57: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/57.jpg)
Motor Protection Summary
� Instantaneous Over-current� Stall� Thermal Overload� Phase Unbalance� Ground
![Page 58: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/58.jpg)
Generator Protection
![Page 59: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/59.jpg)
Classes of TG trips
� Class A� Trip generator breaker, field breaker and
turbine� Electrical trips before the output breakers
� Class B� Trip generator output but leave it supplying
station service� Electrical faults in the switchyard
![Page 60: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/60.jpg)
Classes of TG trips
� Class C� Over excitation high V/Hz� Only used when generator is isolated from grid
� Class D� Trip turbine � Trip Generator after motoring is detected� Mechanical type turbine trips high condenser pressure
![Page 61: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/61.jpg)
Generator Protection
� Over-current� Overload� Differential � Split phase differential � Ground� Rotor ground� Phase Unbalance� Low field� Under frequency� Out of Step� Reverse power
![Page 62: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/62.jpg)
R
Prote ctionZo ne s
W B
Diffe re ntialRelay
Ne utral Co nne c tionto Gro und
a) He althy Phas e b) Faulted Phas e c ) Ope n Circ uit in the Phas e
Ge ne rator Terminals
![Page 63: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/63.jpg)
Differential
G1
Operate Coil
Restraint Coil
Restraint Coil
I 1S I 2S
I 2P
I 2S
CT2
I 1S
CT1I 1P
GeneratorStar Point
Is = I1S = I2S
IP = I1P = I2P
To MainTransformer
![Page 64: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/64.jpg)
Ground Fault Protection
T1
G1
GT1
Stator GroundRelay
IF
![Page 65: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/65.jpg)
Rotor Ground Fault
![Page 66: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/66.jpg)
Other Protections
� Phase Unbalance� Loss of field� Under frequency� Out of Step
![Page 67: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/67.jpg)
Reverse Power
G
Re ve rsePowe rRe aly
V.T.
![Page 68: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/68.jpg)
Generator Protection
� Over-current� Overload� Differential � Split phase differential � Ground� Rotor ground� Phase Unbalance� Low field� Under frequency� Out of Step� Reverse power
![Page 69: Generator Protection](https://reader035.vdocuments.us/reader035/viewer/2022081716/5473abe1b4af9ff34e8b461b/html5/thumbnails/69.jpg)
For You To Do