generator operation and protection

Upload: mujeebtalib

Post on 14-Oct-2015

90 views

Category:

Documents


8 download

DESCRIPTION

Generator Operation and Protection

TRANSCRIPT

  • 7/13/2019 Generator Operation and Protection

    1/52

    GENERATOR OPERATION, PROTECTION

    & PROTECTION SYSTEMIOCL, PARADIP REFINERY

  • 7/13/2019 Generator Operation and Protection

    2/52

    Topics covered

    Generator details

    Checks during normal operation

    Different capability curves of generator

    Control & Monitoring Architecture

    Overview of Generation & Distribution busControl philosophy of GIS

    Brief about DAVR

    Overview of Generator & Generator Transformer

    ProtectionProtection chart of Generator & Generator Transformer

    WHY & HOW of each type of protection

    Generator CO2 system

  • 7/13/2019 Generator Operation and Protection

    3/52

    GENERATOR MODULES

    Air Cooled Turbogenerator : TARIHydrogen Cooled Turbogenerator : THRI

    Hydrogen/Water Cooled TG : THDF

    MODULE NOMENCLATURE (EXAMPLE)

    TARI 108/46 Paradip Refinery : TARI 1080-36P for GTGTHRI 108/44 TARI 800-20P for STG

    THDF 115/59

    MW CAPACITY RANGE OF TURBOGENERATOR

    Air Cooled Turbogenerator : 80MW 240MWHydrogen Cooled Turbogenerator : 100MW 350MW

    Hydrogen and Water Cooled Turbogenerator : 450MW 1000MW

    GENERATOR DETAILS

  • 7/13/2019 Generator Operation and Protection

    4/52

  • 7/13/2019 Generator Operation and Protection

    5/52

    PARAMETERS OPERATION VALUES ALARMS

    Stator teeth temp. 50-100 deg. C 120 deg.C

    Generator winding temp. 50-100 deg. C 120 deg. C

    Stator core temp.

    50-100 deg. C

    120 deg. C

    Cold air temp. < 55 deg. C

    Hot air temp.

  • 7/13/2019 Generator Operation and Protection

    6/52

    PARAMETER OPERATING VALUE ALARM TRIP

    Bearing vib < 10 mm/sec 12.5 mm/sec. 25 mm/sec (peak)

    Bearing temp < 85 deg. C 100 deg. C 120 deg. C

    Load Limits : As per the capability curve

    Rate of loading : Permissible rate of loading depends on the condition of the winding

    Insulation

    Space Heater : when generator is not running space heater should be ON

    Monitoring:

    a) Temperature monitoring of components (through temp scanner)

    b) Generator hot air temp

    c) Shaft grounding brushd) Rotor vibration

    e) Fuse of brushless exciter with the help of stroboscope

    Generator IR value : Min. IR value = (KV rating +1) M Ohm @ 40 deg C with 5 KV IR tester

    Action required if IR value is less than min : Identification of low IR section , if found in winding

    drying out to be adopted.

    CHECKS ON GENERATOR DURING NORMAL OPERATION :

  • 7/13/2019 Generator Operation and Protection

    7/52

  • 7/13/2019 Generator Operation and Protection

    8/52

  • 7/13/2019 Generator Operation and Protection

    9/52

  • 7/13/2019 Generator Operation and Protection

    10/52

    PERMISSIBLE SYNCHRONISING CRITERIA

  • 7/13/2019 Generator Operation and Protection

    11/52

    PMG

    Main Exciter

    Rotor winding

    Rectifier Wheel

    Ring for rotor earth

    fault

    EXCITER ROTOR

  • 7/13/2019 Generator Operation and Protection

    12/52

    BRUSHLESS EXCITATION SYSTEM

  • 7/13/2019 Generator Operation and Protection

    13/52

    ECS panel

    in CPP

    C/R

    I/O

    panel

    SCAP

    Toshiba GIS

    I/O

    panel

    ECS panelsin GIS

    building

    Operator

    work

    station

    EEP panel

    Control & Monitoring Architecture

    FOcable

  • 7/13/2019 Generator Operation and Protection

    14/52

    66KV BUS 1

    66KV GIS SLD CPP Generation Bus & S/S-303 Distribution Bus

    66KV BUS 3

    66KV BUS 4

    11 /66 KV

    10 MVA

    (ONAN)

    YnYn0,Z=12%

    66KV BUS 2

    To Transformers at downstream distribution sub-stations

    X

    118.3 MW

    GTG 1 GTG 2

    X

    X

    X

    11 /69 KV

    148/118 MVA

    (ONAF/ONAN)

    OCTC

    YNd11,Z=14.8%

    STG 2

    X

    X

    STG 1

    X

    X

    GTG 3

    X

    X X

    X

    X

    X

    3150 A 40 KA ,1 SEC 3150 A

    11 /69 KV

    37.5 MVA

    (ONAN)

    OCTC

    YNd11,Z=11.2%

    118.3 MW 118.3 MW 30 MW 30 MW

    BS 1

    BS 2

    X

    x xx

    66KV BUS 2X X

    x

    x66KV BUS 1

    SS 303 GIS -66kV,3150 A,40kA for 3 sec3150 A 3150 A

    X X X X XX X XX

    O

    /

    gF

    D

    R

    O

    /

    g

    F

    D

    R

    O

    /

    g

    F

    D

    R

    O

    /

    g

    F

    D

    R

    O

    /

    g

    F

    D

    R

    O

    /

    g

    F

    D

    R

    O

    /

    g

    F

    D

    R

    O

    /

    gF

    D

    R

    O

    /g

    F

    D

    R

    O

    /

    g

    F

    D

    R

    Generation Bus

    Distribution Bus

    X

    x

    BC 1

    X

    x

    BC 2

  • 7/13/2019 Generator Operation and Protection

    15/52

    GIS control philosophy

    Synchronisation facility is provided to generators, sectionalisers, bus couplers and Tie-

    transformer breakers

    Synchronisation can be performed from SCAP as well as ECS in Auto as well as in manual

    mode.

    SCAP /ECS/OFF selection switch provided on SCAP

    All breakers can be controlled from SCAP as well as ECS with Remote in LCC

    All isolators can be controlled from SCAP as well ECS with Remote in LCC

    All earthing switch can be controlled from LCC only with Local selection in LCC

    All breakers can be controlled from LCC in maintenance mode (line & breaker side earthswitch connected) with Local selection in LCC

    All isolators can be controlled from LCC with Local selection in LCC

  • 7/13/2019 Generator Operation and Protection

    16/52

    A section of 66kV TOSHIBA GIS Generation Sub-Stations Bays Local Control Panels

  • 7/13/2019 Generator Operation and Protection

    17/52

    CPP Synchronisation Control & Annunciation Panel (SCAP)

  • 7/13/2019 Generator Operation and Protection

    18/52

    Block Diagram of DAVR with Dual Auto (inbuilt Manual) Channels & Dual PLC

  • 7/13/2019 Generator Operation and Protection

    19/52

    21G,27G,32G,37G,40G,46G,50GDM,51G,59G,60G,64G(95%),64G(100%),64F,78G,81G,87G & 99GT

    Y

    G

    x

    P345 P345

    P127

    P633

    P633

    P141

    P127

    66 Kv GIS Bus

    87GT

    51GT/ 64RGT

    870A/ 51NGT

    P345

    51VG 51VG

    3 nos VTs for AVR Ch1, Ch2,

    Met & Prot

    To rotor E/F protection

    GENERATOR & GENERATOR TRANSFORMER PROTECTION OVERVIEW

    66/11 KV transformer

  • 7/13/2019 Generator Operation and Protection

    20/52

    Integrated Numerical generator protection relay

    Areva Make Model P345 (two independent relay GR1 & GR2)

    Protection code Description21G: Generator backup impedance protection

    27G: Under voltage protection

    32G: Reverse power protection

    37G: Low forward power protection

    40G: Field failure protection46G: Negative sequence current protection

    50GDM: Dead machine protection

    51G: Definite time overload protection

    59G: Overvoltage protection

    60G: Voltage balance relay (fuse failure)

    64G(95%): Stator earth fault protection(95% winding)64G(100%): Stator earth fault protection(100% winding)

    64F: Rotor earth fault protection

    78G: Out of step(pole slipping) protection

    81G: Under/Over frequency protection

    87G: Differential protection

    99GT: Gen & Gen Transformer Overfluxing protection

    PROTECTION RELAYS

  • 7/13/2019 Generator Operation and Protection

    21/52

    Protection Relay Protection

    Code

    Description of protection

    Areva Make P127 Numerical

    protection relay(two

    independent relay)

    51VG Generator voltage restrained over

    current protection

    Areva Make P141 Numerical

    protection relay

    51GT/64RGT Generator Transformer HV side over

    current & restricted earth fault

    protectionAreva Make P633 Numerical

    protection relay (1strelay)

    870A/51NGT

    Overall differential & Generator

    transformer backup earth fault

    protection

    Areva Make P633 Numerical

    protection relay (2nd

    relay)

    87GT Generator Transformer differential

    protection

    Areva Make VAEM21 relay 64F1A 1strotor earth fault relay

    Areva Make CAEM33 relay 64F2 2ndrotor earth fault relay

    PROTECTION RELAYS

  • 7/13/2019 Generator Operation and Protection

    22/52

    Important Accessories for

    protection relays

    Code Description of code

    Areva Make P931 RGR2 low frequency square wave generator

    for rotor E/F

    Areva Make PR5104 REP Repeater for rotor E/F protection signal

    Siemens Make 7XT3300 G20Hz 20Hz generator for 100% stator E/F

    Siemens Make 7XT3400 FGR2 Band pass filter with built in voltage

    divider for 100% stator E/F protection

    PROTECTION RELAYS

    OVERVIEW OF GENERATOR PROTECTION

  • 7/13/2019 Generator Operation and Protection

    23/52

    OVERVIEW OF GENERATOR PROTECTION

  • 7/13/2019 Generator Operation and Protection

    24/52

    GENERATOR PROTECTION

    Electrical protection provided - To quickly detect & initiate shut down for

    major electrical faults associated with the generating plant.Abnormalelectrical conditions arise as a result of some failure with the generatingplant itself,but can also be externally imposed on the generator. Commoncategories of faults and abnormal conditions to be detected are:

    1. Internal Faults

    Phase and /or ground faults in the stator and associated protection zone

    Ground faults in the rotor (field winding)

    2. Abnormal Operating Conditions.

    a. Loss of field.

    b. Overload.

    c. Overvoltage.

    d. Under and over frequency

    e. Unbalanced Operation e.g. single phasing.

    f. Loss motoring i.e. loss of prime mover.

    g. Loss of synchronization (out of step).

    h. Subsynchronous oscillation.

  • 7/13/2019 Generator Operation and Protection

    25/52

    GENERATOR DIFFERENTIAL (87G)

    WHY

    For protection of the stator windings against internal faults- to detect stator

    winding multi phase and earth faults . Normally involves high fault current ,

    so fast clearing required.

    HOW Based on the principle of circulating currents. The difference of two currents

    of the two sets of CTs (one set on the neutral side & other set on line side of

    generator) flow through the relay.

    Operates only with in the protected zone for internal faults.

    Stability to be ensured for stability against out of zone fault

    GENERATOR DIFFERENTIAL (87G)

  • 7/13/2019 Generator Operation and Protection

    26/52

    GENERATOR DIFFERENTIAL (87G)

  • 7/13/2019 Generator Operation and Protection

    27/52

    VOLTAGE DEPENDENT OVERCURRENT (51VG)

    WHY

    A fault close to the generator will result in a fault current decrement since

    the armature reaction of the generator significantly reduces the fault current.

    Provides back up protection for uncleared downstream faults with time

    delay.

    HOW

    Voltage restrained over current relay. When voltage is low, relay will operate

    on low current

  • 7/13/2019 Generator Operation and Protection

    28/52

    STATOR EARTH FAULT PROTECTION (64G)

    WHY

    Most faults in a generator are a consequence of insulation failure. They may

    lead to turntoturn faults and ground faults. Required for the earth fault ingenerator stator windings, potential transformers, lightning arrestors, surgecapacitors & neutral bus duct. Fault current must be low as it may damage thecore , which is very costly affaire. Hence ground fault protection is veryessential for generators.

    HOW Maximum resistive fault current limited to 7.8 Amp (under field forcing) by

    neutral grounding transformer & secondary loading resistor.

    95% of stator winding is protected by sensing voltage (overvoltage) acrosssecondary loading resistor.

    100% of stator winding is protected by low frequency injection method.

    100% stator earth fault protection can be provided by injecting an external lowfrequency alternating voltage into the starpoint or the terminals of themachine. Under normal healthy conditions only a very small current flows viathe stator earth capacitance due to the high impedance of this path at lowfrequencies (Xc = 1/2fc). In the event of an earth fault the measured currentincreases due to the smaller impedance of the earth fault path.

  • 7/13/2019 Generator Operation and Protection

    29/52

    STATOR EARTH FAULT PROTECTION (64G)

  • 7/13/2019 Generator Operation and Protection

    30/52

    ROTOR EARTH FAULT PROTECTION (64F)

    WHY

    An earth fault in the rotor winding does not cause immediate damage;

    however, if a second earth fault occurs it constitutes a winding short-circuit of

    the excitation circuit. The resulting magnetic unbalances can cause extreme

    mechanical forces which may cause damage to the machine.

    HOW

    The rotor earth fault protection injects a DC voltage into the rotor circuit; the

    polarity of the voltage is reversed at low frequencies and the frequency is

    selectable by the user through a link selection.

    Every time the DC voltage is reversed in polarity, a charging current is applied

    due to the capacitance of the rotor windings to earth. Under no fault

    conditions, the charging current should be discharged to zero.

    When a rotor earth fault occurs, the steady state current will no longer be zero,

    the magnitude of which can then be used to calculate the fault resistance.

    Other method: -ve biased voltage injection(VAEM) for 1strotor earth fault and

    potentiometer method(CAEM) for 2ndrotor earth fault.

  • 7/13/2019 Generator Operation and Protection

    31/52

    ROTOR EARTH FAULT PROTECTION (64F)

  • 7/13/2019 Generator Operation and Protection

    32/52

    REVERSE POWER PROTECTION (32G)

    WHY

    In the event of prime mover failure, a generator connected in parallel with a

    power system - will begin to run as Motor . The active power is drawn fromthe power system to cover alternator & failed prime mover mechanical losses.

    HOW

    A time delay provided to reverse power protection tripping - to prevent false

    tripping during some system fault conditions & power system swings.

    A typical setting for reverse power protection - with 0.2% to 0.5% of the rated

    power of the generator.

    A time delay provided for operation without turbine trip.

  • 7/13/2019 Generator Operation and Protection

    33/52

    LOW FORWARD POWER PROTECTION(37G)

    WHY

    To avoid over speed damage to Large turbo alternators, with slender, low

    inertia rotor designs like that of steam turbines - do not have high over speedtolerance , non urgent tripping of the generator breaker & the excitation

    system can be interlocked with a low forward power function.

    HOW

    Measurement of the low power - done similar to that of reverse power

    function

    A typical under power setting : 0.5% of rated power.

    A time delay provided for operation without turbine trip.

    In gas turbine driven generators - Low forward power protection not required.

    NEGATIVE PHASE SEQUENCE PROTECTION(46G)

  • 7/13/2019 Generator Operation and Protection

    34/52

    NEGATIVE PHASE SEQUENCE PROTECTION(46G)

    WHY

    Negative sequence currents create an mmf wave in opposite direction to thedirection of rotation of rotor. This cuts the rotor at twice the rotational speed,

    and induces a 100 Hz eddy current flows in the outside skin of the rotor body, onthe wedges & in the top winding conductors and cause heating which can causesevere over heating and ultimately, the melting of the wedges in the air gap.

    HOW

    Negative sequence current is measured by the relay. An inverse-time overcurrent

    relay excited by negative sequence current can be used for this protection. Themachine designer establishes constant k. It can be in the range of 550.

    8% continuous negative sequence current can tolerated.

    UNBALANCED LOAD TIME CURVE

  • 7/13/2019 Generator Operation and Protection

    35/52

    UNBALANCED LOAD-TIME CURVE

    FIELD FAILURE PROTECTION (40G)

  • 7/13/2019 Generator Operation and Protection

    36/52

    FIELD FAILURE PROTECTION (40G)

    WHY

    When the excitation of a generator fails - its internal e.m.f. will decay. Thisresults in fall of active power output (accelerate to super synchronous speed)

    & increasing level of reactive power being drawn from the system. In the lagging power factor-operating region, limits are determined either by

    rotor field heating limit or by stator armature heating limit. During the leadingpower factor-operating region, it is the iron end region-heating limit due toeddy currents that is detrimental to the machine. Turbo-alternators may nothave adequate reactive power absorption capability. Hence, they are seldomoperated with leading power factor.

    HOW

    This protection function - measures the impedance at the terminals of agenerator to detect failure of the generators excitation.

    During loss of excitation - the terminal impedance of the generator undergoesa transition from the first quadrant to the fourth quadrant.

    Offset Mho relay Xa= 0.5 Xd , Xb= Xd

    Time delay used. But in case of U/V no time delay.

  • 7/13/2019 Generator Operation and Protection

    37/52

    X

    R-Xa

    Xb

    Load Point

    Machine terminal

    loss of fieldlocus

    Field Failure protection function characteristic with typical machine impedance

    TRIP

    NO TRIP

  • 7/13/2019 Generator Operation and Protection

    38/52

    UNDER VOLTAGE PROTECTION (27G)

    WHY

    Under voltage - can be used to detect abnormal operating conditions, AVR failureor an un-cleared power system fault by other generator protection.

    It can be interlocked with the field failure protection - to prevent its operation

    during stable power swings.

    Under voltage protection - not a commonly specified requirement for generator

    protection.

    HOW

    Operates when the three phase voltages fall below the common set point. An

    adjustable timer is available .

    Under voltage threshold ( V< ) setting - set below the steady state phase-phase

    voltage seen by the relay for a three-phase fault at the remote end of any feeder

    connected to the generator bus.

    70% of normal voltage.

  • 7/13/2019 Generator Operation and Protection

    39/52

    OVER VOLTAGE PROTECTION (59G)

    WHY

    Over voltage protection - set to prevent possible damage to generator insulation,prolonged over fluxing of the generating plant or damage to isolated power system

    loads.

    HOW

    Over voltage operates when the three phase voltages are above their commonthreshold setting.

    At 105% voltage , alarm with 2 sec delay

    At 140% voltage, Trip without delay

  • 7/13/2019 Generator Operation and Protection

    40/52

    UNDER FREQUENCY PROTECTION (81GUF)

    WHY

    Under frequency operation of a generator - occurs when the power system

    load exceeds the prime mover capability of the generator.

    Under frequency running at nominal voltage - will result in over fluxing of the

    generator.

    Unsafe for turbine

    HOW

    The under frequency protection function of the relay - utilises the AC voltage

    input signals as the frequency measurand.

    Two independent time-delayed stages of under frequency protections.

    First stage48.5 Hz, Alarm with 2.5 Sec delay

    Second stage47.5 Hz, Trip with 2 sec delay.

  • 7/13/2019 Generator Operation and Protection

    41/52

    OVER FREQUENCY PROTECTION (81GOF)

    WHY

    Over frequency running of a generating set arises when the mechanicalpower in put to the generator is in excess of the electrical load & mechanical

    losses.

    Over frequency protection - a back up protection function to cater governor

    or throttle control failure following loss of load & prevent over speeding.

    HOW

    Over frequency protection function of the relay - utilises the AC input signals

    as the frequency measurand.

    A single time delayed stage of over frequency protection , with an over

    frequency threshold setting ( F> ) and a time delay setting ( t ). 51.5 Hz, Alarm with 2 sec delay.

  • 7/13/2019 Generator Operation and Protection

    42/52

    VOLTAGE BALANCE FUNCTION (60G)

    WHY

    Voltage balance function - provided to detect PT fuse failure so that an alarm

    can be raised & unwanted generator shut down by the voltage sensitive

    protection function can be prevented.

    HOW

    The voltage balance protection function - operates from signal derived fromthe relays two main PT secondary inputs and signals derived from an

    additional pair of reference PT secondary inputs.

    The level of voltage difference is determined between each of the two main &

    reference voltage inputs.

    When a voltage difference in excess of an adjustable threshold ( Vs ) isdetected - an alarm is raised.

    ( )

  • 7/13/2019 Generator Operation and Protection

    43/52

    GENERATOR BACKUP IMPEDANCE PROTECTION(21G)

    WHY

    Back-up protection must be applied at the generator so that faults are cleared

    in the event of downstream protection/circuit breakers failing to operate. Also

    current will come down with time.

    HOW

    Under impedance protection. This element is set to monitor the system

    impedance at the terminals of the machine. If the impedance measured fallsbelow a set threshold then the element will operate.

    System back-up protection must operate quickly during a fault and must not

    operate for load conditions.

    ( )

  • 7/13/2019 Generator Operation and Protection

    44/52

    GENERATOR DEAD MACHINE PROTECTION(50GDM)

    WHY

    To provide fast protection for accidental energization of a generator when the

    machine is not running condition.

    HOW

    Instantaneous overcurrent element that is gated with a three-phase

    undervoltage detector and is blocked by the VT supervision element.

    GENERATOR OUT OF STEP PROTECTION(78G)

  • 7/13/2019 Generator Operation and Protection

    45/52

    GENERATOR OUT OF STEP PROTECTION(78G)

    WHY

    A generator might pole slip, or fall out-of-step with other power system

    sources, in the even of failed or abnormally weak excitation or as a result of

    delayed system fault clearance.

    HOW

    To detect this condition, distance relay looking into the generator (or into the

    transformer-generator unit) should be installed. Even a distance relay used forloss-of-field protection will pick-up on such power swing.

    If the swing moves out of the relay characteristic, before the timer runs down,

    then, no trip action will be initiated. However, if the swing persists for

    sufficient time, the loss-of-excitation distance relay will operate on power

    swing.

    GENERATOR DEFINITE TIME OVERLOAD PROTECTION(51G)

  • 7/13/2019 Generator Operation and Protection

    46/52

    GENERATOR DEFINITE TIME OVERLOAD PROTECTION(51G)

    WHY

    To protect the generator from going out of the capability and safe operation

    limit.

    HOW

    Thermal modeling of the generator as per the given data and

    recommendation of supplier.

    GENERATOR & GENERATOR TRANSFORMER OVERFLUXING

  • 7/13/2019 Generator Operation and Protection

    47/52

    PROTECTION PROTECTION (99GT)

    WHY

    High voltage or low frequency, causing a rise in the V/Hz ratio, will produce high

    flux densities in the magnetic core of the machine or transformer. This could

    cause the core of the generator or transformer to saturate and stray flux to be

    induced in un-laminated components that have not been designed to carry flux.

    The resulting eddy currents in solid components (e.g. core bolts & clamps) and

    end of core laminations can cause rapid overheating and damage.

    HOW

    V/f element of the relay set as per the overfluxing withstand capability of the

    generator & generator transformer.

    Time delayed Alarm is used to take action

    Inverse characteristics is used for trip

    GENERATOR STATOR FRAME OVERTEMPERATURE PROTECTION

  • 7/13/2019 Generator Operation and Protection

    48/52

    (CO2 SYSTEM)

    WHY

    To provide protection against fire/ hot spots inside generator enclosure.

    HOW

    80 deg C & 100 deg C fire detectors installed at equal distance along the

    periphery of generator frame /enclosure (Turbine end & Exciter End).

    Logic formed to avoid mal-operation of detector for release CO2 in thegenerator enclosure and class A tripping.

    CO2 is also released in case of actuation of generator differential protection.

  • 7/13/2019 Generator Operation and Protection

    49/52

    Fire Detector arrangement inside generator enclosure(Turbine side)

  • 7/13/2019 Generator Operation and Protection

    50/52

    Fire Detector arrangement inside generator enclosure (Exciter side)

    GENERATOR CLASS A PROTECTION TABLE

  • 7/13/2019 Generator Operation and Protection

    51/52

    GENERATOR CLASS-A PROTECTION TABLE

    ORlogic for class

    A trip

    GEN WINDING DIFFERENTIAL 87G

    GEN TR DIFFERENTIAL 87GT

    STATOR EARTH FAULT 64G

    GEN TR REF 64RGT

    OVERALL DIFFERENTIAL 870A

    GEN FRAME TEMPERATURE 100 DEG

    CELSIUS

    ROTOR E/F 64F

    Tripping of both generator breaker and turbine occurs for any of the following conditions

    EMERGENCY PUSH BUTTON

  • 7/13/2019 Generator Operation and Protection

    52/52

    THANK YOU