generali-111 finish plan overall - first floor i-112 finish plan overall - second floor i-401...
TRANSCRIPT
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
G-001SET NUMBER:
LAS CRUCES ACADEMIC CAMPUS
HOUSING RENOVATIONSNEW MEXICO STATE UNIVERSITY
SHEET INDEX
GENERAL
G-001COVER SHEET, INDEX & GENERAL CONSTRUCTION INFORMATION
G-002SYMBOLS, LEGENDS & ABBREVIATIONS
G-003 ACCESSIBILITY STANDARDS
79, 80,
185
RHODES GARRETT HAMIEL HALL
A-101 WORK PLAN - FIRST FLOOR
A-102 WORK PLAN - SECOND FLOOR
A-103 ROOF WORK PLAN
A-104 REFLECTED CEILING PLAN - FIRST FLOOR
A-105 REFLECTED CEILING PLAN - SECOND FLOOR
A-510 ROOF DETAILS
A-601 SCHEDULES
INTERIOR FINISHES
I-001 INTERIOR ABBREVIATIONS & FINISH LEGEND
I-111 FINISH PLAN OVERALL - FIRST FLOOR
I-112 FINISH PLAN OVERALL - SECOND FLOOR
I-401 ENLARGED FINISH PLANS
LAS CRUCES, NEW MEXICO 88003
PACKAGE 2 (95% Construction Docs)
GENERAL CONSTRUCTION INFORMATION
BUILDING IBC 2018
PLUMBING UPC 2015
MECHANICAL UMC 2015
ELECTRICAL NEC 2014
FIRE IFC 2018
ENERGY 2009 IECC
ACCESSIBILITYIBC 2015, CH. 11; ICC/ANSI A117.1-2009
APPLICABLE CODES
ALTERNATE NO. 1
PROVIDE KEETONE ETHYLENE ESTER (KEE)
ROOFING SYSTEM IN LIEU OF BASE BID
SPECIFIED EPDM ROOFING SYSTEM
ALTERNATE NO.2
PROVIDE NEW CARPET, LVT AND BASE IN
COMMONS AREAS AS SCHEDULED. WORK
REQUIRES HAZARDOUS MATERIALS REMOVAL OF
EXISTING FLOOR COVERINGS
ALTERNATE NO. 3
RETROFIT EXISTING FIRE SUPPRESSION SYSTEM
FOR CONCEALED FIRE SPRINKLER HEADS IN
CORRIDOR AREAS SCOPED FOR NEW CEILING
REPLACEMENT.
ALTERNATE NO. 5
PROVIDE MINERAL WOOL FIBER INSULATION
BOARD AND PLYWOOD PROTECTION BOARD AT
ATTIC ROOF AREAS OVER CONCRETE ROOF
DECK
ALTERNATE NO. 6
REPLACE EXISTING GLAZED CERAMIC TILE WITH
QUARRY TILE AT LOCATIONS INDICATED
ALTERNATES LIST
FOR
RHODES GARRETT HAMIEL HALL (79, 80,185)
PROJECT LOCATION
SITE MAPAREA MAP
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
G-002
AA00
CL
99.6
99.6
X X
320.10 TC
319.60 G
319.60
+TC
+G
+FL
WP
A
x
3
1
9
.
6
0
DS
FD
RD
OD
CJ
S
MCJ
GENERAL DRAWING LEGEND FLOOR PLAN LEGENDSITE PLAN LEGEND ROOF PLAN LEGEND RCP LEGEND DETAIL LEGENDABBREVIATIONS
SD
SHEET TYPE DESIGNATORS
AANNNSHEET IDENTIFICATION FORMAT
0 GENERAL (COVER SHEETS, INDEX, SYMBOLS LEGEND, NOTES, ETC.)
1 PLANS (HORIZONTAL VIEWS)
2 ELEVATIONS (VERTICAL VIEWS)
3 SECTIONS (SECTIONAL VIEWS)
4 LARGE SCALE VIEWS (ENLARGED PLANS, ELEVATIONS, OR SECTIONS
THAT ARE NOT DETAILS)
5 DETAILS
6 SCHEDULES AND DIAGRAMS
7 USER DEFINED (FOR TYPES THAT DO NOT FALL IN OTHER CATEGORIES
OR STANDARD DETAILS)
8 USER DEFINED (FOR TYPES THAT DO NOT FALL IN OTHER CATEGORIES)
9 3D REPRESENTATIONS (ISOMETRICS, PERSPECTIVES, PHOTOGRAPHS)
SHEET TYPE
DESIGNATOR
(SEE BELOW)
DISCIPLINE
DESIGNATOR
SHEET SEQUENCE
NUMBER
ROOM NAME
ROOM NUMBER
DOOR NUMBER
WINDOW MARK
EQUIPMENT
LOUVER MARK
HOLLOW METAL FRAME
MARK
ALUMINUM FRAME MARK
KEY NOTE
KEY NOTE-DEMOLITION
PARTITION TYPE
DISPLAY BOARD
REVISION
STRUCTURAL COLUMN
LINE
DATUM ELEVATION
(EXISTING)
DATUM ELEVATION
(NEW)
BREAK LINE
CENTER LINE
SHEET NUMBER WHERE REFERENCED
REFERENCE NUMBER
DRAWING BLOCK TITLE
PLAN DETAIL MARK
SECTION MARK
ELEVATION MARK
NORTH ARROW
NORTH ARROW FOR
SITE PLANS
EXISTING DOOR
NEW DOOR
MATCH/DIVIDE LINE
PROPERTY LINE
EXISTING
CONSTRUCTION TO
REMAIN
EXISTING
CONSTRUCTION TO BE
REMOVED
PROPERTY LINE
FENCE
NEW ASPHALT PAVING
NEW CONCRETE
WALK/PAVING
NEW CONTROL JOINT
NEW EXPANSION JOINT
NEW CONTOUR LINES
EXISTING CONTOUR
LINES TO REMAIN
NEW SPOT ELEVATION
EXISTING SPOT
ELEVATION
TOP OF CURB
GUTTER
FLOW LINE
WORKING POINT
ACCESSIBLE PARKING
SIGN
PARKING SIGN
LIGHT POLE
TREE
SLOPE
FLOOR DRAIN
DOWN SPOUT
FURNITURE/EQUIPMENT
NIC
FIRE EXTINGUISHER AND
BRACKET
FIRE EXTINGUISHER AND
CABINET
HANDRAIL
WALL GUARD
END WALL GUARD
CORNER GUARD
WIRE MESH OR FABRIC
PARTITION
GLAZING SYSTEM
NEW PARTIAL HEIGHT
WALLS
NEW METAL STUD
WALLS
EXISTING
CONSTRUCTION TO BE
REMOVED
EXISTING
CONSTRUCTION TO
REMAIN
MASONRY CONTROL
JOINT
CMU WALL
FACE BRICK
CONCRETE WALL ROOF DRAIN
OVERFLOW DRAIN
SLOPE
MECHANICAL
EQUIPMENT
VENT THROUGH ROOF
(VTR)
SKYLIGHT
ROOF HATCH
SMOKE DETECTOR
ACCESS PANEL
SPEAKER
CONTROL JOINT
CEILING TRACK
SKYLIGHT
LIGHT FIXTURES
EXIT LIGHTS
RETURN AIR OR
EXHAUST GRILLE
SUPPLY AIR GRILLE
LAY-IN CEILING PANEL
LAY-IN CEILING PANEL
SUSPENDED METAL
LATH AND PLASTER
CEILING
GYP BD CEILING COMPACTED SOIL
UNDISTURBED SOIL
STONE/MARBLE
PLASTER OR STUCCO
ON METAL LATH
STEEL
CONCRETE IN SECTION
BRICK
CMU
BATT INSULATION
ACOUSTICAL TILE
RIGID INSULATION
WOOD CONTINUOUS
WOOD DISCONTINUOUS
PLASTER, SAND OR
CEMENT GROUT
POUROUS FILL, GRAVEL
(CAPILLARY WATER
BARRIER PAVEMENT BASE)
TERRAZZO (IN SECTION)
ROOM NAME
000
000
00
00
LV00
HM00
AL00
00
00
00
0
NORTH
N
A1/G-001
A1/G-001
A1/G-001
/
A1
TITLE
1/8"=1'-0"
FEB
FEC
A
ACC ACCESSIBLE
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJUSTABLE
ADDM ADDENDUM
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
ARCH ARCHITECT
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY OF TESTING MATERIALS
AUTO AUTOMATIC
AVG AVERAGE
AWG AMERICAN WIRE GAGE
AWS AMERICAN WELDING SOCIETY
A/C AIR CONDITIONING
B
BAL BALANCE
BC BACK OF CURB
BIA BRICK INSTITUTE OF AMERICA
BITUM BITUMINOUS
BL BUILDING LINE
BLDG BUILDING
BM BENCH MARK
BOCA BUILDING OFFICIALS AND CODE ADMINISTRATORS
INTERNATIONAL, INC
BOS BOTTOM OF STEEL
BOT BOTTOM (BOTTOM FACE, LAYER, SIDE)
B PL BASE PLATE
BRDG BRIDGING
BRG BEARING
BTWN BETWEEN
BUR BUILT-UP ROOFING
C
C AMERICAN STANDARD CHANNEL (STRUCTURAL
SHAPE)
CU FT CUBIC FOOT
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CG CORNER GUARD
CI CAST IRON
CIR CIRCLE
CIRC CIRCULAR
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
cm CENTIMETER
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECT
CONSTR CONSTRUCTION
CONT CONTINUE
CONTR CONTRACTOR
CRCMF CIRCUMFERENCE
CSK COUNTER SUNK
CSI CONSTRUCTION SPECIFICATIONS INSTITUTE
CTR CENTER
CU YD CUBIC YARD
D
D DEPTH
DAT DATUM
DBL DOUBLE
DDS DOUBLE DISPLAY STRIP
DEG DEGREE
DEMO DEMOLISH
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIV DIVIDE
DL DEAD LOAD
DS DOWNSPOUT
DWG DRAWING
E
E EAST, MODULUS OF ELASTICITY
EA EACH
EF EACH FACE, EXTERIOR FINISH
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXP BT EXPANSION BOLT
EXT EXTERIOR
F
FD FLOOR DRAIN
FDTN FOUNDATION
FEB FIRE EXTINGUISHER & BRACKET
FEC FIRE EXTINGUISHER & CABINET
FF EL FINISH FLOOR ELEVATION
FIN FLR FINISH FLOOR
FIN FINISH(ED)
FOC FACE OF CONCRETE, FACE OF CURB
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FS FAR SIDE (FACE, LAYER)
FT FOOT
FTG FOOTING
FURG FURRING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GOVT GOVERNMENT
GYP BD GYPSUM BOARD
GYP GYPSUM
H
HDBD HARDBOARD
HDWD HARDWOOD
HDW HARDWARE
HEX HEXAGON(AL)
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HEAT PUMP
HS HIGH STRENGTH
HT HEIGHT
HVAC HEATING VENTILATION AND AIR CONDITIONING
I
I MOMENT OF INERTIA
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IF INSIDE FACE
INCL INCLUDE(D)(ING)(SIVE)
INS INSULATION
INT INTERIOR
INV INVERT(ED)
J
JAN JANITOR
L
l LITER
L ANGLE (STRUCTURAL SHAPE)
LB POUND
LH LEFT HAND
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LT WT LIGHT WEIGHT
M
MAU MAKE UP AIR UNIT(S)
m METER(S)
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MCJ MASONRY CONTROL JOINT
MECH MECHANIC(AL)
MFG MANUFACTURING
MFR MANUFACTURER
MIL STD MILITARY STANDARD
MIN MINIMUM
MISC MISCELLANEOUS
mm MILLIMETER
MO MASONRY OPENING
MOD MODIFY
MT METAL THRESHOLD
MTL METAL
MLWK MILLWORK
N
N NORTH
NA NOT APPLICABLE
NAT NATURAL
NBS NATIONAL BUREAU OF STANDARDS
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NS NEAR SIDE (FACE)
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVER FLOW DRAIN
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/OWNER INSTALLED
OH DR OVERHEAD DOOR
OPNG OPENING
OPH OPPOSITE HAND
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
Oz OUNCE
P
PAR PARALLEL
PCA PORTLAND CEMENT ASSOCIATION
PCF POUNDS PER CUBIC FOOT
PCI PRESTRESSED CONCRETE INSTITUTE
PERF PERFORATE(D)
PERP PERPENDICULAR
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAL FOOT
PR PAIR
PREFAB PREFABRICATE
PREFIN PREFINISH
PRELIM PRELIMINARY
PROJ PROJECT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PBD PARTICLE BOARD
PTD PAPER TOWEL DISPENSER
PTDWR PAPER TOWEL DISPENSER & WASTE RECEPTACLE
PVC POLYVINYL CHLORIDE
PLYWD PLYWOOD
PVG PAVING
Q
QC QUALITY CONTROL
QTY QUANTITY
R
R RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REFL REFLECT
REINF REINFORCE
REQD REQUIRED
REV REVISION
RH RIGHT HAND(ED)
RO ROUGH OPENING
ROW RIGHT OF WAY
RTU ROOF TOP UNIT
S
S SOUTH
SBCCI SOUTHERN BUILDING CODE CONGRESS
INTERNATIONAL
SCHED SCHEDULE
SD SOAP DISPENSER
SDI STEEL DOOR INSTITUTE
SECT SECTION
SHT SHEET
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SPEC SPECIFICATION
SP SOLID PLASTIC
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPENDED
SYMM SYMMETRICAL
T
THD TREAD
TAN TANGENT
TEMP TEMPORARY
TFF TOP OF FINISH FLOOR
THK THICKNESS
TLT TOILET
TMH TOP OF MANHOLE
TOB TOP OF BEAM
TOC TOP OF CURB
TOF TOP OF FOOTING
TOG TOP OF GRADE
TOJ TOP OF JOIST
TOL TOLERANCE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TRANS TRANSPARENT
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
T&G TONGUE AND GROOVE
U
UBC UNIFORM BUILDING CODE
UL UNDERWRITERS LABORATORIES, INC.
ULT ULTIMATE
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
V
VAR VARIES
VERT VERTICAL
W
W WEST
WLD WELDED
WP WORK POINT
WWF WELDED WIRE FABRIC
W/ WITH
W/O WITHOUT
W/W WALL TO WALL
X
XFMR TRANSFORMER
DB00
A0
PLAN NORTH ARROW
PLAN NORTH
TRUE NORTH
FURNISHINGS
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
G-003
1/4
1
2
1/2
60" MIN
60 M
IN
30
MIN
24
MIN
12
MIN
30
MIN
12
MIN
60 MIN
48 MIN
30
MIN
FORWARD
PARALLEL
48 M
IN
30 MIN
30 M
IN
48 MIN
36 MIN
X >
24
60 MIN
X >
15
ELEVATION
TOE CLEARANCE
PLAN
CENTERED
30 M
IN
6 MAX
17-25
ELEVATION
KNEE CLEARANCE
8 MIN
9"
MIN
11 MIN
27 M
IN
4 MAX
X ≥ 80
X >
27
X <
80"
27"
MA
X
48 M
AX
15
MIN
20
MAX
48 M
AX
44 M
AX
2O-25
MAX
10 MAX
48 M
AX
15
MIN
34 M
AX
10 MAX
48 M
AX
34 M
AX
>10-24
MAX
46 M
AX
24
MAX 48 MIN
24
MAX
32 M
IN
36 M
IN
32 M
IN
36 M
IN
Y
48 M
IN
X
42 MIN
X
42 MIN
X<48
CLEAR FLOOR AREA/ACCESSIBLE ROUTE
ALCOVE
FORWARD
ALCOVE
PARALLEL
180 DEG
TURN AROUND
NARROW
PASSAGE
SINGLE
WHEELCHAIR
T-SHAPE
TURN AROUND
CIRCLE
TURN AROUND
BEVELED TRANSITION
VERTICAL TRANSITION
PROTRUDING
OBJECT
UNDER STAIRS
FORWARD REACH RANGES SIDE REACH RANGES
PROTRUDING OBJECT PROTECTION/REACH RANGES
5 M
AX
15 M
IN
BACK WALL
BACK WALL
LENGTH
30 M
IN
30 M
IN
12 MIN
CO
NT
RO
L
EN
D W
ALL
24 M
IN
12 MAX 24 MAX24 MIN
12 M
IN
24 M
IN
12 MAX
15 MAX
12 MAX15 MAX12 MAX
24 MAX24 MIN
REMOVABLE SEAT CONTROLS LOCATION FIXED SEAT
REMOVABLE SEAT FIXED SEAT
CO
NT
RO
L
WA
LL
BACK
SE
AT
WA
LL
36
36
36 M
IN
48 MIN
SE
AT
60 MIN
30 M
IN
30 M
IN
36
36 MIN
60 MIN60 MIN
30 M
IN
30 M
IN
6 M
AX
6 MAX6 MAX
6 M
AX
6 MAX
6 MAX
6 M
AX
6 M
AX
6 MAX
TRANSFER SHOWER ROLL-IN SHOWER ROLL-IN SHOWER
W/ SEAT ROLL-IN SHOWER
W/ SEAT
ALTERNATE
38 M
IN
48 M
AX
15 MAX
BACK
WALL
CONTROL WALL
WITHOUT SEAT
CONTROL WALL
WITH SEAT
48 M
AX
27 MAX
48 M
AX
SHOWERS
8-10
17-19
8-10
17-19
17-19
SHOWER SEAT
48 M
IN
33 MIN 33 MIN
60 M
IN
33 MIN 33 MIN
BENCH SEATING
THEATER SEATING
30 M
IN
24 M
IN
BENCH SEATING
THEATER SEATING
ASSEMBLY SEATING
LINE OF SIGHT
LINE OF SIGHT
SPORTS ARENA
THEATER/PLAYHOUSE
AUDITORIUM/CONCERT HALL
LECTURE HALLS
MEETING ROOMS
OF TUB
CO
NT
RO
L E
ND
W
ALL
HE
AD
E
ND
W
ALL
LENGTH
OF TUB
WA
LL/P
OS
T M
TD
CA
NT
ILE
VE
RE
D
UN
IT
FORWARD APPROACH
ACCESSIBLE UNIT
56 M
IN
59 M
IN
60 MIN60 MIN
4 MAX
42 M
IN
6 M
IN
6 MIN
42 M
IN
60 M
IN
35-37
ANY AMOUNT
X ≥ 80
X <
27
PROTRUDING
OBJECT
URINALS
NOTE:
WIDE SIDE
LEVER ON
36 MIN
TYPICAL WATER CLOSETS
33-36
250 LBS AND BE CONTINUOUS
GRAB BARS MUST SUPPORT
EWC/DRINKING FOUNTAINS
DOWN TO 27" AFF MIN
APRON THAT EXTENDS
HIGH UNIT SHOULD HAVE
15 MIN
CL
BRACKET MOUNTED
FIRE EXTINGUISHER
48
48
* CHALKBOARD MOUNTING
* MARKERBOARD MOUNTING
36 M
AX
9
ROOM
FIRE ALARM
AUDIBLE &
ACCESSIBLE
COAT HOOKS
VISUAL SIGNAL
60 M
AX
OUTLET
15 M
IN
80-96
48 M
AX
2 FROM
DOOR FRAME
48 M
AX
* TACKBOARD MOUNTING
CABINET
FIRE EXTINGUISHER
TOWELS
48 M
AX
MISC MOUNTING (DIMENSIONS SHOWN ARE TO THE HIGHEST OPERABLE PART)
STANDARD ACCESSIBLE MOUNTING HEIGHTS
TELEPHONE
THERMOSTAT
TOWELS
SWITCH
OUTLET
CUPS
SOAP
TO
P O
F E
XT
IN
GU
IS
HE
R
IN
SID
E O
F C
AB
IN
ET
TO
P O
F T
RA
Y
6
FIN CLG
IF CEILING IS BELOW 90"
MOUNT TOP OF SIGNAL DEVICE
6" BELOW FINISHED CEILING
NOTE:
17 MIN
EQUIPMENT PERMITTED
IN OUTLINED AREA
36 M
AX
28-34
38 M
AX
2 M
AX
WASHING MACHINE
TOP LOAD
CONVEYOR
GROCERY
SLIDE
TRAYACCESSIBLE
COAT HOOKS
AMBULATORY ACCESSIBLE TOE CLEARANCE SIDE APPROACH WALL HUNG WATER CLOSET FLOOR MTD WATER CLOSET
TYPICAL TOILET STALLS
CL
HE
AD
E
ND
(REQUIRED) (REQUIRED)
WA
LL
TUBS
CL
PUSH SIDE
48 M
IN
NOTE:
PULL SIDE
18 MIN
60 M
IN
X
FRONT APPROACHES SWINGING DOORS
HAS BOTH A CLOSER AND A LATCH
X = 12" MIN (305mm) IF DOOR
PUSH SIDE
Y
42 M
IN
PUSH SIDE
NOTE:
A CLOSER
PULL SIDE
A CLOSER
Y = 54" MIN (1370mm) IF DOOR HAS
NOTE:
PULL SIDE
NOTE: X = 36" MIN IF Y = 60";
X = 42" MIN IF Y = 54"
X
Y
Y
42 M
IN
HINGE SIDE APPROACHES SWINGING DOORS
LATCH SIDE APPROACHES SWINGING DOORS
Y = 48" MIN (1220mm) IF DOOR
22 MIN
HAS BOTH A CLOSER AND A LATCH
Y = 48" MIN IF DOOR HAS
Y
48 M
IN
24 MIN24 MIN
NOTE:
VESTIBULE DOORS
TWO HINGED DOORS IN SERIES
NOTE:
THE CLEARANCES FOR FRONT APPROACHES
ALL DOORS IN ALCOVES SHALL COMPLY WITH
TYPICAL DOOR CLEARANCES
48 MIN
4
8
M
I
N
VESTIBULE DOORS
32 MIN
CLEAR
43 M
AX
34 M
IN
60 M
IN
18 MIN
X>
8
48 M
IN
12 MIN
X>
8
48 M
IN
RECESSED DOOR
DOOR HARDWARE DOOR LITE
CLOSER & LATCH PROVIDED
WALL
CL
GENERAL NOTES
ACCESSIBILITY GUIDELINE SHEETS ARE BASED ON
THE APPLICABLE ACCESSIBILITY STANDARDS
ADOPTED BY THE STATE OF NEW MEXICO; 2003 ICC
ANSI A117.1
ACCESSIBILITY GUIDELINE SHEETS ARE FOR
INFORMATIONAL PURPOSES ONLY. AND INTENDED
TO SERVE AS A GUIDE FOR CONSTRUCTION
PROFESSIONALS AND OWNERS.
SOME OF THE INFORMATION AND PICTOGRAPHS
SHOWN MAY NOT BE APPLICABLE TO THIS PROJECT.
REFER TO PLUMBING SHEETS FOR PLUMBING
FIXTURE MOUNTING HEIGHTS.
GRAPHICS SHOWN ARE FOR ADULTS.
48 M
AX
27 MAX
17-19
CL
16-18
CL
16-18
CL
16-18
CL
16-18
CL
60 MIN
CLEARANCE AT WATER CLOSET
16-18
CL
56 M
IN
LAVATORY, URINAL
OR TOILET ACCESSORIES
NOT IN A STALL
12
MIN
24 MIN
15 MIN
CL
36
36
TO
S
HO
ULD
ER
IF Y=60 MIN, X=36 MIN
33-36
LINE OF SIGHT OVER HEADS
CL
FRONT LOAD
15-36
IF A WALL HUNG OR FLOOR
MOUNTED FLUSH VALVE
WATER CLOSET IS SPECIFIED,
ENSURE ALL DIMENSIONS
SHOWN ARE MET.
EXAMPLE SIGNAGE - SEE STANDARD ACCESSIBLE MOUNTING HEIGHT
LETTERS & BRAILLE
GRAPHIC SYMBOLS
6x8 PICTOGRAM
6 M
IN
MEN
6x8 PICTOGRAM
GRAPHIC SYMBOLS
LETTERS & BRAILLE
6 M
IN
WOMEN
& BRAILLE
ROOM NUMBER
8x6 ROOM NAME
6 M
IN
129
SUPERVISOR
MAINTENANCE
& BRAILLE
10x3 ROOM NAME
ADMINISTRATION
6x6 DIRECTIONAL
GRAPHIC SYMBOL
ONLY ONLY
GRAPHIC SYMBOL
6x6 DIRECTIONAL
6 M
IN
& BRAILLE
6x6 CHANGEABLE
MESSAGE W/ PERMANENT
ROOM NAME, NUMBER,
ITHJOHN S
OFFICE
169
REFER TO SIGNAGE PACKAGE OR DETAILS FOR ACTUAL SIGNAGE SPECIFIED
6x8 PICTOGRAM
GRAPHIC SYMBOLS
LETTERS & BRAILLE
6 M
IN
STAIR 1
6x8 PICTOGRAM
GRAPHIC SYMBOLS
LETTERS & BRAILLE
6 M
IN
STAIR 1
48 M
IN
60 M
AX
60 M
AX
48 M
IN
6 M
IN
60 M
AX
48 M
IN
60 M
AX
48 M
IN
CL
DISPENSERS
36 MAX
12
MAX
54 MIN
42 MIN
33-36
TO
P O
F G
RIP
PIN
G
SU
RF
AC
E
7-9
48 M
AX
15 M
IN
100
48 M
IN
15
MIN
CL
30
MIN
X
36
MIN
IF X>24
15
MIN
CL
36
MIN
IF X>24
X
CL
LAVATORIES
36
MIN
IF X>24
X
REFER TO KNEE AND
TOE CLEARANCE GRAPHICS
CL
36 MIN
30
IF X ≤ 24
X
15
MIN
CL
NOT ASSOCIATED
24 MIN
9"
MIN
15
MIN
CL
WITH A WATER CLOSET
ONLY TOILET
ASSOCIATED WITH
WATER CLOSETS ARE
ALLOWED WITHIN
FLOOR AREA
ACCESSORIES
CHANGES IN LEVELNOTE: REFER TO "CHANGES IN LEVEL" DETAILS FOR SHOWER THRESHOLDS
THRESHOLD
SEAT
SEAT
THRESHOLD THRESHOLD
1
2
1/4
VERTICAL/BEVELED
1/4
TRANSITION
43 M
AX
43 M
AX
48 M
AX
LIT
E
OP
EN
IN
G
SURFACE OF MIRROR
TOP OF REFLECTIVE
74 M
IN
BOTTOM OF
MIRROR
SURFACE OF
REFLECTIVE
40 M
AX
REFLECTIVE SURFACE
NORTH
A1
RHODES HALL - 1ST FLOOR
1/8"=1'-0" -
A2
HAMIEL HALL - 1ST FLOOR
1/8"=1'-0" -
A4
GARRETT HALL - 1ST FLOOR
1/8"=1'-0" -
NORTH NORTH
8' 16'0 4' 8' 16'0 4' 8' 16'0 4'
B
B
B
B
B
A
B
C
B
A
B
C
B A
B A
B C
B C
03
08
ROOM
102
ROOM
101
ROOM
103
ROOM
104
ROOM
106
ROOM
105
ROOM
108
LOUNGE
107
SHOWER
150
RESTROOM
148
SHOWER / BATH
126
SHOWER
171
RESTROOM
173
LOUNGE
109
ROOM
110
ROOM
113
ROOM
114
CLASSROOM
113
ROOM
116
ROOM
115
ROOM
117
ROOM
118
ROOM
120
ROOM
119
ROOM
184
ROOM
182
ROOM
180
ROOM
178
ROOM
176
ROOM
174
ROOM
172
ROOM
166
ROOM
164
ROOM
162
ROOM
160
ROOM
158
ROOM
156
ROOM
168
STAIRS
04
ROOM
181
ROOM
179
ROOM
177
ROOM
175
ROOM
165
ROOM
163
ROOM
161
ROOM
159
ROOM
157
ROOM
155
ROOM
167
ROOM
169
STAIRS
03
ROOM
121
ROOM
123
ROOM
125
ROOM
127
ROOM
129
ROOM
131
LOUNGE
135
LOUNGE
137
ROOM
133
STAIRS
02
ROOM
128
ROOM
134
ROOM
136
ROOM
134A
ROOM
134B
ROOM
130
LOUNGE
139
LAUNDRY
141A
KITCHEN
141B
ROOM
143
ROOM
145
ROOM
149
ROOM
151
ROOM
153
ROOM
147
ROOM
142
ROOM
144
ROOM
146
ROOM
138
ROOM
140
STAIRS
01
B
B
B
B
02
02
02
01
01
03
04
04
04
05
05
05
04
RA
MP
DO
WN
RA
MP
DO
WN
UP
UP
UP
UP
01
01
01
01
01
01
01
01
01
01
02
102
DEMOLITION NOTES
REMOVE EXISTING CONSTRUCTION AS INDICATED BY:00
1. REMOVE EXISTING 1X4 RECESSED LIGHT FIXTURES, EXIT SIGNS,
ACOUSTICAL LAY-IN TILE AND SUSPENDED GRID SYSTEM.
PERIMETER ANGLE MOLD SHALL REMAIN. TYPICAL THROUGHOUT
THE CORRIDORS. MECHANICAL RETURN GRILLES SHALL BE
RELOCATED IN THE NEW LAY-IN CEILING
2. REMOVE EXISTING SURFACE MOUNTED 1X4 LIGHT FIXTURE,
TYPICAL IN THE STAIRWELLS.
3. REMOVE VINYL STAIR TREAD AND / OR RISERS.
4. REMOVE EXISTING CARPET AND VINYL BASE THIS SPACE INCLUDING
WITHIN THE CLOSETS. PATCH AND REPAIR WALLS WITH APPROVED
MATERIAL NECESSARY TO RECEIVE NEW BASE AS SCHEDULED.
(ROOMS 101 - 106, 108, 110, 113 - 121, 123, 125, 127 - 131, 133, 134,
134A. 134B, 136, 138, 140, 142 - 147, 149, 151, 153, 155 - 169, 172, 174 -
182, 184, 201 - 208, 210, 213 - 221, 223, 225, 227 - 236, 238 - 239, 242,
244, 245 - 251, 253, 255, 257, 259 - 274, 276, 278 - 286 and 288)
5. ALTERNATE No.02 : REMOVE CARPET AND VINYL BASE IN COMMONS
SPACES, STAIRWELLS AND LANDINGS. PATCH AND REPAIR WALLS
WITH APPROVED MATERIAL NECESSARY TO RECEIVE NEW BASE AS
SCHEDULED. EXISTING STAIR TREADS IN STAIRWELLS SHALL
REMAIN.
6. REMOVE EXISTING DOOR, PREPARE FRAME TO RECEIVE NEW DOOR
AS SCHEDULED.
7. REMOVE NON-COMPLIANT DOOR KNOB. PREPARE DOOR TO
RECEIVE NEW DOOR HANDLE.
8. ALTERNATE No.06: REMOVE EXISTING TILE IN STAIRWELLS AND
ENTRY LOBBIES. PREPARE SLAB FOR NEW FINISH AS SCHEDULED
LEGEND
WOOD TRIM / RAILING IN HALLWAY
1X4 LIGHT FIXTURE
GENERAL NOTES
A. DOCUMENTS ARE BASED ON EXISTING FILES PROVIDED BY NMSU
AND ON FIELD OBSERVATIONS. PRIOR TO BEGINNING ANY
DEMOLITION WORK, MAKE A THOROUGH SURVEY OF THE
BUILDING AND NOTIFY THE ARCHITECT IN WRITING OF ALL
OBSERVED DISCREPANCIES BETWEEN THE EXISTING CONDITIONS
AND THOSE SHOWN ON THE DRAWINGS.
B. PROVIDE MEASURES TO PROTECT ALL MATERIAL AND
EQUIPMENT TO REMAIN DURING THE DURATION OF THE PROJECT.
C. DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO THOSE
ITEMS NOTED. OTHER ITEMS OF MINOR NATURE MAY EXIST
WHICH ARE NOT SPECIFICALLY NOTED ON THE DRAWINGS ARE
TO BE REMOVED AS NECESSARY TO PROVIDE ACCESS OR ALLOW
ALTERATIONS FOR THE NEW WORK TO PROCEED.
D. WHERE DEMOLITION EXPOSES SUBSTRATES WHICH WILL
RECEIVE NEW FINISH MATERIALS, PROPERLY REMOVE EXISTING
MATERIALS AS REQUIRED FOR NEW FINISHES.
E. PATCH AND REPAIR EXISTING ADJACENT TO MATCH WHERE
REQUIRED DUE TO DEMOLITION PROCEDURES.
F. OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL
IMPROVEMENTS REPLACED DURING CONSTRUCTION.
COORDINATE WITH OWNER PRIOR TO BEGINNING OF PROJECT
FOR ITEMS TO BE SALVAGED FOR OWNER USE.
G. CONTRACTOR SHALL DISPOSE OF MATERIAL IN A PROPER
MANNER AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION
AND IN ACCORDANCE WITH LOCAL AND STATE CODES AND
ORDINANCES.
NIC - NOT IN CONTRACT, NO WORK IN THIS SPACE
AS INDICATED BY: 00
KEY NOTES
FIRE EXTINGUISHER (BRACKET or CABINET)
RHODES GARRETT HAMIEL GENERAL NOTES
01
01
06
06
06
06
01
01
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
0404
04
04
04
04
04
05
05
05
05
05
05
05
05
0902 07
06
01
01
04
04
04
04
04
04
04
04
04
04
04
04
04
04
05
1. EXISTING TILE FLOOR FINISH TO REMAIN.
2. EXISTING TILED SURFACE TO REMAIN.
3. EXISTING WOOD FLOORING TO REMAIN.
4. EXISTING MECHANICAL UNIT TO REMAIN.
5. EXISTING WATER FOUNTAIN TO REMAIN.
6. EXISTING WOOD RAIL TRIM TO RECEIVE NEW WOOD CAP FINISH,
TYPICAL THROUGHOUT CORRIDOR AND VESTIBULE. REFER TO
DETAIL A1/A-510.
7. PAINT HANDRAIL AND GUARDRAILS THROUGHOUT STAIRWELL,
COLOR AS SCHEDULED. PAINT ROOF ACCESS LADDER SAME
COLOR IF PRESENT IN STAIRWELL.
8. RESTROOM / SHOWERS WILL RECEIVE PAINT AND MIRACLE
METHOD FINISH. REFER TO INTERIOR SHEETS FOR SCHEDULED
FINISHES.
9. ALTERNATE No.06: NEW QUARRY TILE FINISH AS SCHEDULED
10. DISPLAY BOARD. OWNER SHALL REMOVE PRIOR TO
COMMENCING DEMOLITION ACTIVITY.
A. EXISTING LAY-IN CEILING TILES, GRID, EXIT SIGNS AND 1X4 LIGHT FIXTURES IN CORRIDORS SHALL BE REMOVED AND REPLACED WITH NEW FIXTURES AS SPECIFIED.
PERIMETER ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING PLANS FOR NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE SPRINKLER HEADS TO BE CONCEALED WITHIN THE CEILING WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE "MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR AND 4'-0" HIGH WAINSCOT. ALL OTHER
NON-TILE SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE "MIRACLE METHOD" TREATMENT. SURFACES INCLUDE BUT ARE NOT LIMITED TO THE ENTIRE FLOOR, RESTROOM
BASE AND THE SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE "MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT SHOWER
AND CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT FINISHES.
F. ALL EXISTING APPURTENANCES LOCATED ON THE SUSPENDED CEILING SHALL BE TEMPORARILY REMOVED, CHECKED FOR DAMAGE, TESTED, CLEANED AND REINSTALLED IN
THE NEW SUSPENDED CEILING GRID.
06
06
09 0507
04
09 0702 05
06
06
06
06
06
05
05
05
05
05
06
06
06
06
06
06
06
01
01
01
01
01
01
ST
EP
DO
WN
OPEN TO
ABOVE
05
05
06
06
09
07
02
03
03
OPEN TO
ABOVE
06
06
06
06
05
05
05
05
05
05
08
08
08
08
08
EXIT SIGN
ROOM
113A
0404
RESTROOM
RH
RESTROOM
GH
01
07
05
02
0404
06
102 103
08
08
08
08
09
08
09
08
03
03
09
08
C6
GARRETT HALL - BASEMENT
1/8"=1'-0" -
NORTH
8' 16'0 4'
B6
HAMIEL HALL - BASEMENT
1/8"=1'-0" -
NORTH
8' 16'0 4'
090207
05
08
STAIRS
01
02
0902 07 05
08
02
STAIRS
04
UP
UP
06
VENDING ROOM
124
101
10
10
104
105
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
A-101
NORTH
A1
RHODES HALL - 2ND FLOOR
1/8"=1'-0" -
A3
HAMIEL HALL - 2ND FLOOR
1/8"=1'-0" -
A4
GARRETT HALL - 2ND FLOOR
1/8"=1'-0" -
NORTH NORTH
8' 16'0 4' 8' 16'0 4' 8' 16'0 4'
B
A
B
C
B
A
B
C
B A
B A
B C
B C
ROOM
202
ROOM
201
ROOM
203
ROOM
204
ROOM
206
ROOM
205
ROOM
208
ROOM
207
ROOM
210
ROOM
213
ROOM
214
ROOM
113
ROOM
216
ROOM
215
ROOM
217
ROOM
218
ROOM
220
ROOM
219
ROOM
288
ROOM
286
ROOM
284
ROOM
282
ROOM
280
ROOM
278
ROOM
276
ROOM
270
ROOM
268
ROOM
266
ROOM
264
ROOM
262
ROOM
260
ROOM
272
STAIRS
04
ROOM
285
ROOM
283
ROOM
281
ROOM
279
ROOM
269
ROOM
267
ROOM
265
ROOM
263
ROOM
261
ROOM
259
ROOM
271
ROOM
273
ROOM
274
SHOWER
275
RESTROOM
277
ROOM
221
ROOM
223
ROOM
225
ROOM
227
ROOM
229
ROOM
231
ROOM
235
ROOM
233
STAIRS
02
ROOM
228
ROOM
236
ROOM
238
ROOM
234
ROOM
232
ROOM
230
ROOM
239
ROOM
245
ROOM
247
ROOM
249
ROOM
253
ROOM
255
ROOM
257
ROOM
251
ROOM
246
ROOM
248
ROOM
250
ROOM
242
ROOM
244
STAIRS
01
B
B
B
B
B
B
B
B
GENERAL NOTES
A. EXISTING LAY-IN CEILING TILES, GRID, EXIST SIGNS AND 1X4
LIGHT FIXTURES IN CORRIDORS SHALL BE REMOVED AND
REPLACED WITH NEW FIXTURES AS SPECIFIED. PERIMETER
ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING
PLANS FOR NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE
SPRINKLER HEADS TO BE CONCEALED WITHIN THE CEILING
WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR
AND 4'-0" HIGH WAINSCOT. ALL OTHER NON-TILE SURFACES
SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE BUT ARE
NOT LIMITED TO THE ENTIRE FLOOR, RESTROOM BASE AND THE
SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER SURFACES
SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE
FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT SHOWER AND
CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE
NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT
FINISHES.
F. ALL EXISTING APPURTENANCES LOCATED ON THE SUSPENDED
CEILING SHALL BE TEMPORARILY REMOVED, CHECKED FOR
DAMAGE, TESTED, CLEANED AND REINSTALLED IN THE NEW
SUSPENDED CEILING GRID.
G.
ROOM
211
ROOM
240
SHOWER
254
SHOWER
252
01
01
04
01
01
01
01
01
03
04
ST
EP
DO
WN
ST
EP
DO
WN
01
01
01
01
01
DN
DN
DN
DN
03
03
06
06
06
06
06
01
01
02
0202
03
03
03
04
04
04
04
04
04
04
04
04
04
04
04
04
04
05
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
04
0404
04
04
04
04
04
04
04
04
0404
04
04
04
04
04
05
OPEN TO
BELOW
OPEN TO
BELOW
05
04
04
05
05
05
05
05
05
05
05
05
05
05
05
05
05
05
05
02
02
08
08
08
08
08
SHOWER / BATH
226
07
05
04
0205
07
07
0205
06
06
06
06
06
06
06
06
06
06
06
06
06
06
06
06
06
06
06
05
05
LEGEND
WOOD TRIM / RAILING IN HALLWAY
1X4 LIGHT FIXTURE
NIC - NOT IN CONTRACT, NO WORK IN THIS SPACE
AS INDICATED BY: 00
KEY NOTES
FIRE EXTINGUISHER (BRACKET or CABINET)
1. EXISTING TILE FLOOR FINISH TO REMAIN.
2. EXISTING TILED SURFACE TO REMAIN.
3. EXISTING WOOD FLOORING TO REMAIN.
4. EXISTING MECHANICAL UNIT TO REMAIN.
5. EXISTING WATER FOUNTAIN TO REMAIN.
6. EXISTING WOOD RAIL TRIM TO RECEIVE NEW WOOD CAP FINISH,
TYPICAL THROUGHOUT CORRIDOR AND VESTIBULE. REFER TO
DETAIL A1/A-510.
7. PAINT HANDRAIL AND GUARDRAILS THROUGHOUT STAIRWELL,
COLOR AS SCHEDULED. PAINT ROOF ACCESS LADDER SAME
COLOR IF PRESENT IN STAIRWELL.
8. RESTROOM / SHOWERS WILL RECEIVE PAINT AND MIRACLE
METHOD FINISH. REFER TO INTERIOR SHEETS FOR SCHEDULED
FINISHES.
EXIT SIGN
04
05
07
05
05
05
DEMOLITION NOTES
REMOVE EXISTING CONSTRUCTION AS INDICATED BY:00
1. REMOVE EXISTING 1X4 RECESSED LIGHT FIXTURES, EXIT SIGNS,
ACOUSTICAL LAY-IN TILE AND SUSPENDED GRID SYSTEM.
PERIMETER ANGLE MOLD SHALL REMAIN. TYPICAL THROUGHOUT
THE CORRIDORS. MECHANICAL RETURN GRILLES SHALL BE
RELOCATED IN THE NEW LAY-IN CEILING
2. REMOVE EXISTING SURFACE MOUNTED 1X4 LIGHT FIXTURE,
TYPICAL IN THE STAIRWELLS.
3. REMOVE VINYL STAIR TREAD AND / OR RISERS.
4. REMOVE EXISTING CARPET AND VINYL BASE THIS SPACE INCLUDING
WITHIN THE CLOSETS. PATCH AND REPAIR WALLS WITH APPROVED
MATERIAL NECESSARY TO RECEIVE NEW BASE AS SCHEDULED.
(ROOMS 101 - 106, 108, 110, 113 - 121, 123, 125, 127 - 131, 133, 134,
134A. 134B, 136, 138, 140, 142 - 147, 149, 151, 153, 155 - 169, 172, 174 -
182, 184, 201 - 208, 210, 213 - 221, 223, 225, 227 - 236, 238 - 239, 242,
244, 245 - 251, 253, 255, 257, 259 - 274, 276, 278 - 286 and 288)
5. ALTERNATE No.02 : REMOVE CARPET AND VINYL BASE IN COMMONS
SPACES, STAIRWELLS AND LANDINGS. PATCH AND REPAIR WALLS
WITH APPROVED MATERIAL NECESSARY TO RECEIVE NEW BASE AS
SCHEDULED. EXISTING STAIR TREADS IN STAIRWELLS SHALL
REMAIN
6. REMOVE EXISTING DOOR, PREPARE FRAME TO RECEIVE NEW DOOR
AS SCHEDULED.
7. REMOVE NON-COMPLIANT DOOR KNOB. PREPARE DOOR TO
RECEIVE NEW DOOR HANDLE.
RHODES GARRETT HAMIEL GENERAL NOTES
A. EXISTING LAY-IN CEILING TILES, GRID, EXIST SIGNS AND 1X4 LIGHT FIXTURES IN CORRIDORS SHALL BE REMOVED AND REPLACED WITH NEW FIXTURES AS SPECIFIED.
PERIMETER ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING PLANS FOR NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE SPRINKLER HEADS TO BE CONCEALED WITHIN THE CEILING WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE "MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR AND 4'-0" HIGH WAINSCOT. ALL OTHER
NON-TILE SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE "MIRACLE METHOD" TREATMENT. SURFACES INCLUDE BUT ARE NOT LIMITED TO THE ENTIRE FLOOR, RESTROOM
BASE AND THE SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE "MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT SHOWER
AND CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT FINISHES.
F. ALL EXISTING APPURTENANCES LOCATED ON THE SUSPENDED CEILING SHALL BE TEMPORARILY REMOVED, CHECKED FOR DAMAGE, TESTED, CLEANED AND REINSTALLED IN
THE NEW SUSPENDED CEILING GRID.
01
05
01
104 105
04
02
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
A-102
NORTH
8' 16'0 4'
A1
ROOF PLAN
RHODES GARRETT HAMIEL HALL
3/32"=1'-0" -
DEMOLITION NOTES
REMOVE EXISTING CONSTRUCTION AS INDICATED BY:00
1. REMOVE AND DISPOSE OF EXISTING BALLAST, EPDM MEMBRANE AND RIGID
INSULATION DOWN TO THE EXISTING ROOF DECK STRUCTURE. CAREFULLY
REMOVE TERMINATION BARS AVOIDING DAMAGING SUBSTRATE.
2. REMOVE EXISTING ROOF DRAIN BODY, STRAINER AND CLAMPING RING.
3. REMOVE MODIFIED BITUMINOUS ROOF SYSTEM DOWN TO WOOD FRAMING
SYSTEM AND PREPARE TO RECEIVE NEW ROOFING AS SCHEDULED.
4. REMOVE EXISTING METAL FLASHING, WOOD FASCIA AND WOOD LOOKOUTS
ALONG ENTIRE PERIMETER OF HIGH ROOF. REFER TO DETAIL E4/A-510.
5. REMOVE EXISTING PORTION OF PARAPET WALL AND ROOFING MEMBRANE
TO ALLOW A SMOOTH AND CONTINUOUS ROOF PLANE.
6. REMOVE EXISTING ROOF HATCH COVER, HATCH CURB TO REMAIN.
7. REMOVE EXISTING CLAY TILE ROOF; INCLUDING WOOD DECKING.
8. REMOVE EXISTING ACCESS DOOR AND PREPARE AREA TO RECEIVE NEW
ACCESS DOOR.
9. REMOVE PLASTER FINISH DOWN TO THE MASONRY SUBSTRATE FROM TOP
OF CHIMNEY DOWN TO ROOF PLANE.
RGH GENERAL NOTES
A. THIS ROOF PLAN SHOWS OVERALL INTENT OF ROOF SLOPES, MECHANICAL
UNIT LOCATIONS, DIFFERENT ROOFING TYPES AND OTHER VARIOUS
ROOFING RELATED ITEMS. CONTRACTOR SHALL REFER TO ROOFING
SHEETS FOR SPECIFIC INFORMATION ON ROOFING MEMBRANE AND
DETAILS ASSOCIATED WITH THE DIFFERENT ROOFING TYPES.
B. CONTRACTOR SHALL PROVIDE BARRICADES, FALL PROTECTION AND ANY
OTHER MEANS TO PROTECT WORKERS AND THE PUBLIC DURING PROJECT.
C. NOT ALL ROOF PENETRATIONS ARE SHOWN FOR CLARITY. ALL ROOF
PENETRATIONS SHALL BE FLASHED TO A POSITIVE SLOPE AWAY FROM
PENETRATION. COORDINATE WITH ALL TRADES.
D. CONTRACTOR SHALL COMPLY WITH ALL LOCAL, STATE, FEDERAL CODES,
STATUTES, REGULATIONS AND LAWS GOVERNING THIS WORK.
E. CONTRACTOR SHALL COORDINATE THE RE-CONNECTION OF ALL ROOFTOP
EQUIPMENT, VENTS, CURBS, ETC.
F. THE CONTRACTOR SHALL REMOVE ONLY EXISTING ROOFING MATERIALS
THAT CAN BE REPLACED WITH NEW MATERIALS AS THE WEATHER
PERMITS.
G. CONTRACTOR SHALL REPAIR ALL DAMAGED AREAS OF STUCCO AND
MASONRY CONSTRUCTION ON EXISTING ROOF PARAPET PRIOR TO
INSTALLATION OF ROOFING SYSTEM AND FLASHING TO INSURE SOUND
AND SOLID SUBSTRATE.
H. CONTRACTOR SHALL TEST ALL EXISTING ROOF DRAINS TO ENSURE ALL
ARE CLEAR AND FUNCTIONAL. IF DRAINS ARE DAMAGE AND DO NOT
FUNCTION, NOTIFY THE ARCHITECT IN WRITING.
AS INDICATED BY: 00
KEY NOTES
1. EXISTING MECHANICAL UNIT TO REMAIN.
2. EXISTING ROOF HATCH AND SAFETY RAILING SYSTEM TO REMAIN.
3. EXISTING CHIMNEY TO RECEIVE NEW STUCCO FINISH, REFER TO
SPECIFICATIONS.
4. EXISTING ROOF DRAIN, REFER TO RGH GENERAL NOTE H.
5. NEW OPERABLE WOOD ACCESS PANEL, REFER TO DETAIL C1/ A-510
6. NEW CLAY TILE ROOFING OVER NEW DECKING. CLAY TILE COLOR TO
MATCH EXISTING.
7. ADDITIVE ALTERNATE No.05: AT PENTHOUSE SPACES, ADHERE MINERAL
FIBER BOARD, R-15 BUT NO LESS THAN 6" TO EXISTING CONCRETE FLOOR
AND COVERED WITH MECHANICALLY FASTENED 3/4" EXTERIOR GRADE
PLYWOOD SHEATHING.
8. NEW 3'X3' ROOF HATCH AND SAFETY GUARDRAIL. UTILIZE EXISTING CURB
AND SEAL UNDERSIDE OF ROOF HATCH OVERHANG. REFER TO D6/A-510
01
01
01 01 01 01
01
01
01
01
01
01
01
01
02
03
03
03
03
03
03
03
03
03
02
04
04
04
04
04
04
04
04
04
03
03
01
E1
/ A
-5
10
E1
/R
GH
A
-5
10
E1
/ A
-5
10
E1/ A-510
E1/ A-510
E1/ A-510
E1/ A-510
E5
/ A
-5
10
E5
/ A
-5
10
E5
/ A
-5
10
E5
/ A
-5
10
E5/ A-510
E5/ A-510
E5/ A-510
E5/ A-510
E1/ A-510
E5/ A-510
E4/ A-510
E4
/ A
-5
10
E6
/ A
-5
10
04
E6
/ A
-5
10
D2
/ A
-5
10
05
05
D2
/ A
-5
10
D2/ A-510
D3
/ A
-5
10
D3
/ A
-5
10
D3/ A-510
06
04
E4
/ A
-5
10
SLOPE
2:12
SLOPE
2:12
RID
GE
D2/ A-510
D5/ A-510
D5/ A-510
07
08
08
08 08
05
05
05 05
06
04
04
04
04
04
04
1'-6" F.V.
06
07
07
07
08
08
04
04
04
A-103
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
GENERAL NOTES
A. EXISTING APPURTENANCES SHALL BE TEMPORARILY REMOVED, CHECKED FOR
DAMAGE, TESTED, CLEANED AND REINSTALLED IN THE NEW SUSPENDED CEILING
GRID. DAMAGED DEVICES SHALL BE REPLACED.
B. EXISTING PERIMETER GRID ANGLE MOLD SHALL REMAIN. PAINT GRID ANGLE MOLD
WHITE.
C. ADDITIVE ALTERNATE No.03: MODIFY EXISTING SPRINKLER HEADS TO BE
CONCEALED WITHIN THE CEILING WITH ESCUTCHEON FINISH.
D. REMOVE ALL EXISTING LIGHT FIXTURES IN AS SHOWN ON SHEET A-101 AND PROVIDE
NEW LIGHT FIXTURES AS SPECIFIED. RE-USE EXISTING BRANCH CIRCUITS TO THE
FULLEST EXTENT. FIELD VERIFY CAPACITY OF CIRCUIT BEFORE CONNECTING TO
EXISTING CIRCUIT. DO NOT EXCEED NEC MAXIMUM LOADING. PROVIDE NEW WIRE
AND CONDUIT AS NECESSARY AND ADJUST WIRE SIZE TO ACCOMMODATE FOR
VOLTAGE DROP IF REQUIRED PER NEC. CONNECT FIXTURES TO EXISTING LIGHTING
CONTROLS.
E. REPLACE EXISTING SIGNS, CONNECT TO EXISTING BRANCH LIGHTING CIRCUIT
SERVING THE AREA. ALL EMERGENCY AND EGRESS LIGHTING SHALL BE CONNECTED
TO THE SAME BRANCH CIRCUIT SERVING THE LIGHTS AND SHALL BE ON THE LINE
SIDE OF THE RELAYS OR SWITCHING DEVICES. ALL EXIT SIGNS SHALL BE
CONNECTED FOR CONTINUOUS OPERATION.
NORTH
A1
REFLECTED CEILING PLAN
RHODES HALL - 1ST FLOOR
1/8"=1'-0"
A2
REFLECTED CEILING PLAN
HAMIEL HALL - 1ST FLOOR
1/8"=1'-0"
A4
REFLECTED CEILING PLAN
GARRETT HALL - 1ST FLOOR
1/8"=1'-0"
NORTH
NORTH
8' 16'0 4'
8' 16'0 4'
8' 16'0 4'
LEGEND
B
B
B
B
B
A
B
C
B
A
B
C
B A
B A
B C
B C
RECESSED LIGHT FIXTURE (RL-1 AS SPECIFIED)
STAIRS
04
STAIRS
03
STAIRS
02
STAIRS
01
B
B
B
B
RECESSED EMERGENCY LIGHT FIXTURE
E1
SURFACE MOUNT EMERGENCY LIGHT FIXTURE
E2
E2
E2
E2
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E2
E1
E1
E1
2 x 2 ACOUSTICAL LAY-IN CEILING SYSTEM
ATC1 AS SCHEDULED
(RL-1E AS SPECIFIED)
(SM-1E AS SPECIFIED)
D6
REFLECTED CEILING PLAN
GARRETT HALL - BASEMENT
1/8"=1'-0"
E2
E2
C6
REFLECTED CEILING PLAN
HAMIEL HALL - BASEMENT
1/8"=1'-0"
NORTH
8' 16'0 4'
E2
E2
STAIRS
01
STAIRS
04
UP
UP
HVAC GRILLE
7'-6"
CLG. FIN.
7'-6"
CLG. FIN.
7'-6"
CLG. FIN.
7'-0"
CLG. FIN.
AS INDICATED BY: 00
KEY NOTES
1. SOFFIT, PINATED. REFER TO INTERIOR SHEETS FOR FINISH.
2. PROVIDE A RECESSED SLOPE CEILING MOUNTING KIT FOR FIXTURE IN SLOPED
CEILING GRID AS RECOMMENDED BY MANUFACTURER
01
01
01
01
01
01
01
01
E2
EXIT SIGN - COOPER LIGHTING MODEL APX7R
OR APPROVED EQUAL
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
A-104
NORTH
A1
REFLECTED CEILING PLAN
RHODES HALL -- 2ND FLOOR
1/8"=1'-0" -
A3
REFLECTED CEILING PLAN
HAMIEL HALL -- 2ND FLOOR
1/8"=1'-0" -
A4
REFLECTED CEILING PLAN
GARRETT HALL -- 2ND FLOOR
1/8"=1'-0" -
NORTH NORTH
8' 16'0 4' 8' 16'0 4' 8' 16'0 4'
B
A
B
C
B
A
B
C
B A
B A
B C
B C
B
B
B
B
B
B
B
B
GENERAL NOTESLEGEND
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
A. EXISTING APPURTENANCES SHALL BE TEMPORARILY REMOVED, CHECKED FOR
DAMAGE, TESTED, CLEANED AND REINSTALLED IN THE NEW SUSPENDED CEILING
GRID. DAMAGED DEVICES SHALL BE REPLACED.
B. EXISTING PERIMETER GRID ANGLE MOLD SHALL REMAIN. PAINT GRID ANGLE MOLD
WHITE.
C. ADDITIVE ALTERNATE No.03: MODIFY EXISTING SPRINKLER HEADS TO BE
CONCEALED WITHIN THE CEILING WITH ESCUTCHEON FINISH.
D. REMOVE ALL EXISTING LIGHT FIXTURES IN AS SHOWN ON SHEET A-102 AND
PROVIDE NEW LIGHT FIXTURES AS SPECIFIED. RE-USE EXISTING BRANCH
CIRCUITS TO THE FULLEST EXTENT. FIELD VERIFY CAPACITY OF CIRCUIT BEFORE
CONNECTING TO EXISTING CIRCUIT. DO NOT EXCEED NEC MAXIMUM LOADING.
PROVIDE NEW WIRE AND CONDUIT AS NECESSARY AND ADJUST WIRE SIZE TO
ACCOMMODATE FOR VOLTAGE DROP IF REQUIRED PER NEC. CONNECT FIXTURES
TO EXISTING LIGHTING CONTROLS.
E. REPLACE EXISTING EXIT SIGNS, CONNECT TO EXISTING BRANCH LIGHTING
CIRCUIT SERVING THE AREA. ALL EMERGENCY AND EGRESS LIGHTING SHALL BE
CONNECTED TO THE SAME BRANCH CIRCUIT SERVING THE LIGHTS AND SHALL BE
ON THE LINE SIDE OF THE RELAYS OR SWITCHING DEVICES. ALL EXIT SIGNS SHALL
BE CONNECTED FOR CONTINUOUS OPERATION.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-0"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-2"
CLG. FIN.
7'-1"
CLG. FIN.
RECESSED LIGHT FIXTURE (RL-1 AS SPECIFIED)
EXIT SIGN - COOPER LIGHTING MODEL APX7R
RECESSED EMERGENCY LIGHT FIXTURE
E1
SURFACE MOUNT EMERGENCY LIGHT FIXTURE
E2
2 x 2 ACOUSTICAL LAY-IN CEILING SYSTEM
ATC1 AS SCHEDULED
(RL-1E AS SPECIFIED)
(SM-1E AS SPECIFIED)
HVAC GRILLE
AS INDICATED BY: 00
KEY NOTES
1. SOFFIT. REFER TO INTERIOR SHEETS FOR FINISH.
01
01
01
01
01
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E2
E2
E2
E2
E2
E2
OR APPROVED EQUAL
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
A-105
A1
HALLWAY RAIL DETAIL
3"=1'-0"
3/8"
1 1/8"
4 1
/2
"2
"
3/8"
7/8"
1/4"
NEW RAILING
PAINT TO MATCH
WALL COLOR
EXIST WOOD
RAILING (1x6)
PAINT TO MATCH
WALL COLOR
E1
PARAPET DETAIL
1 1/2"=1'-0"
EXISTING STUCCO OVER
EXISTING WALL
CONT SEALANT
EXISTING STRUCTURE
TO REMAIN
E2
VENT FLASH DETAIL
1 1/2"=1'-0"
ROLL DOWN FLASHING
1" MIN DOWN INTO PIPE
PLUMBING VENT
STACK
SEALANT
MODIFIED MEMBRANE
FLASHING
MODIFIED BASE FLASHING
FELT BASE PLIES
ROOFING
MEMBRANE
1/2" FIBER BOARD
4" MIN
12
" M
IN
.
E3
LARGE PIPE VENTILATION DET.
1 1/2"=1'-0"
VENT OR PIPE
SEALANT
DRAWBAND
WATERTIGHT
SHEET METAL
RAIN COLLAR
NON-SHRINK
GROUT
SHEET METAL,
WATERTIGHT
PITCH PAN
MODIFIED
MEMBRANE
FLASHING
BASE FLASHING
FELT BASE PLIES
4" MIN.
E4
CORNICE DETAIL
1 1/2"=1'-0"
CONT CLEAT
EXISTING PLASTER
E5
ROOF DETAIL
1 1/2"=1'-0"
EXISTING STUCCO
POLYISOCYANURATE
INSULATION
EXISTING WOOD
DECK TO REMAIN
BASE PLY
MEMBRANE
ROOFING
FLASHING
MEMBRANE
CONT METAL FLASHING
E6
EXPANSION JOINT
1 1/2"=1'-0"
EXPANSION JOINT
PREMANUFACTURED
COVER
SECURED METAL CAP (WITH FASTENERS
and NEOPRENE WASHERS
CHAMFER EACH
SIDE OF WOOD
CURB TO DRAIN
FLEXIBLE WATER
PROOF MEMBRANE
CLOSURE
COMPRESSIBLE
INSULATION
ROOFING MEMBRANE
BASE FLASHING
BASE PLY
ROOFING
MEMBRANE
D1
NOT USED
3"=1'-0"
D2
DETAIL @ ROOF
1 1/2"=1'-0"
ROOFING
MEMBRANE
1/2" FIBER BOARD
4 1/2" POLYISOCYANURATE
INSULATION
CONT METAL
CAP
CANT STRIP
CONT 2x WOOD
NAILER (BOTH
SIDES)
RUN ROOFING UP
AND OVER PARAPET
CONT SEALANT
CONT COUNTERFLASHING
TERMINATION BAR
ROOFING MEMBRANE
(HEAT WELD)
BASE FLASHING
(HEAT WELD)
D3
DETAIL @ ROOF
1 1/2"=1'-0"
CONT CLEAT
CONT SEALANT
1/2" COVER BOARD
BASE FLASHING
D4
ROOF HATCH
1 1/2"=1'-0"
ROOF HATCH
EXTERIOR LOCK
PROVISION
IN
TE
RIO
R
HA
ND
LE
FASTENER WITH NEOPRENE WASHER
INTEGRAL CAP FLASHING
TERMINATION BAR FASTENED 8" O.C.
60 MIL ROOFING FB MEMBRANE
3" MIN ON FIELD
BASE FLASHING
CANT FASTENED TO NAILER
D5
DETAIL @ ROOF
1 1/2"=1'-0"
ROOFING
MEMBRANE
1/2" FIBER BOARD
4 1/2" POLYISOCYANURATE
INSULATION
CONT METAL CAP
RUN ROOFING UP
AND OVER PARAPET
CANT STRIP
CONT 2x WOOD
NAILER (BOTH
SIDES)
D6
ROOF HATCH OVERHANG
1 1/2"=1'-0"
TERMINATION BAR FASTENED 8" O.C.
60 MIL ROOFING FB MEMBRANE
3" MIN ON FIELD, HEAT WELD
BASE FLASHING
CANT FASTENED TO NAILER
WELD NEW STEEL PLATE AT TOP
LINE OF EXISTING WALL/ OPENING
TO COMPENSATE FOR OVERSIZED HATCH
C1
ACCESS PANEL
3"=1'-0"
2x CONT FRAME
WOOD ACCESS DOOR WITH HINGES
AND MANUAL LATCHING SYSTEM
SHEET METAL SILL FLASHING
EXISTING WALL
RUN ROOFING UP AND OVER CURB
ROOFING MEMBRANE
BASE FLASHING
C2
ELEVATION @ TOWER
NOT TO SCALE
SAND, PRIME AND PAINT
EXISTING GUARDRAL
SAND, PRIME AND PAINT
EXISTING DECORATIVE
WROUGHT IRON. REFER
SAND, PRIME AND PAINT
EXISTING DECORATIVE
WROUGHT IRON
REPAIR AND PAINT
PAINT EXISTING CORNICE
TO MATCH EXISTING
CLAY TILE ROOF WITH NEW
SUBSTRATE/ DECKING
TO 05 03 72 HISTORICAL
DECORATIVE METAL REPAIR
REPAIR AND PAINT
EXISTING CONCRETE
TO MATCH EXISTING
REPAIR AS NECESSARY
REMOVE EXISTING MTL
FLASHING REPLACE W/
PRE-FINISHED MTL
FLASHING
REMOVE AND
REPLACE CONT. 4X4
SAND AND REPAINT
EXISTING 2-2X8 LOOK
OUTS. REPLACE
DAMAGED UNITS
EXISTING 2X6 TO
REMIAN
REMOVE EXISTING ROOFING
SYSTEM AND REPLACE WITH
SPECIFIED SYSTEM
REMOVE EXISTING
ROOFING SYSTEM AND
REPLACE WITH SYSTEM
AS SPECIFIED
PAINT COLOR AS SPECIFIED
TERMINATION BAR
BASE FLASHING
ROOFING
MEMBRANE
1/2" COVER BOARD
POLYISOCYANURATE
INSULATION, TAPERED FOR
POSITIVE DRAINAGE, R-25 MIN.
BONDING ADHESIVE
LAP SEALANT
FASTENER AND PLATE
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
A-510
A
G = SEE GLAZING SCHEDULE (THIS SHEET) FOR TYPE
WEATHER STRIPPING, EXT FIRE STOP
L4 = 90 MIN
M3 = LOUVRE
* = SIMILAR
X=EXISTING
7
6
-
SILL
REMARKS
-
5
-
HEAD
4
FRAME
3
SCTF
CONST
X
SIZE JAMB
DETAILS
2
A
TYPE
1
PR SIZE
DOOR
1
FLR
101
MARK
DOOR SCHEDULE
CONST
FOOTNOTES
H3 = 1 1/2 PR HINGES, PANIC DEVICE, CLOSER, DEADBOLT,
1 1/2 PR HINGES, LEVER, PRIVACY SET, CLOSER, GASKET,=H2
WALL STOP, SILENCER, KICKPLATE
HARDWARE (WHEN NO SPECS)
H1 = 1 1/2 PR HINGES, LEVER, LOCKSET, CLOSER,
HOLLOW METAL TRANSOM TO MATCH DOOR, SIZE AS NOTED=T2
WOOD TRANSOM TO MATCH DOOR, SIZE AS NOTED=T1
TRANSOM
60 MIN=L3
LABEL
L1
L2
=
= 45 MIN
20 MIN
GLAZING
DOOR TRIM TO MATCH EXISTING=M2
= VERIFY ROUGH OPENINGM1
MISCELLANEOUS (GENERAL NOTES)
=
=HM
ALUM
1
HOLLOW METAL FRAME PROFILE & ADDITIONAL INFORMATION.
HMPF= HOLLOW METAL, PAINT FINISH
DOOR SIZE INDICATED IS NOMINAL. REDUCTION SHALL BE MADE FOR
ALUMINUM
OPENING SIZE (INDICATED IN FT-IN, WxH)
THRESHOLD & EDGE CLEARANCES. ALL DOORS ARE 1 3/4" THICK,
REFER TO STANDARD DOOR DETAILS (THIS SHEET) FOR TYPICAL
SIZE INDICATED IS OVERALL FRAME DEPTH.
5 FRAME SIZE (INDICATED IN INCHES)
HMLP= HOLLOW METAL, LAMINATED PLASTIC COVERED
SCLP= SOLID CORE WOOD, LAMINATED PLASTIC COVERED
HM = HOLLOW METAL
SOLID CORE WOOD, TRANSPARENT FINISH
SOLID CORE WOOD, PAINT FINISH=
=
3 CONSTRUCTION/VENEER
SCTF
SCPF
2 DOOR TYPE
REFER TO DOOR TYPE SCHEDULE (THIS SHEET)
FRAME TYPE4
HOLLOW METAL, PAINT FINISH
DETAILS6
EXAMPLE:
DETAIL # A1/A-501 SHEET #
7 REMARKS
WALL STOP, SILENCERS
UNLESS INDICATED OTHERWISE.
2-0x7-0
SEE STANDARD DOOR DETAILS (THIS SHEET) FOR
CASED OPENING FRAME=M6
DOOR DETAILS (THIS SHEET).
DOOR HEAD /TRANSOM PANEL DETAILS
M5 = PROVIDE HOSPITAL STOP ON FRAME. SEE STANDARD
VERIFY FINISH OPENING SIZE=M4
M7 =
00A
DOOR TYPE SCHEDULE
1
1
1
1
102
103
104
105
---
A2-8x7-0
---
---
---
A2-8x7-0
A2-8x7-0
A2-8x7-0
2'-8"
7'-0"
M3
M3
SCTF
SCTF
SCTF
SCTF
X
X
X
X
X
X
X
X
X
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 11,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
RGH A-601
A
ATC ACOUSTICAL TILE CEILING
AWT ACOUSTICAL WALL TREATMENT
B
BG BUMPER GUARD
BNT BULL NOSE TILE
C
CG CORNER GUARD
CHR CHAIR RAIL
CPT CARPET
CT CERAMIC TILE
CUB CUBICAL CURTAIN
CURT CURTAIN (PRIVACY, STAGE)
D
DLS DIMENSIONAL LETTERS
DRS DOUBLE ROLLER SHADE
F
FLS FLUID APPLIED SPORTS FLOORING
FWP FABRIC WRAPPED PANELS
G
GLS ARCHITECTURAL TILE
GLT GLASS TILE
GT GROUT
H
HIC HIGH IMPACT WALL COVERING
HLB HORIZONTAL LOUVER BLINDS
HR HANDRAIL
K
KPL KICKPLATE
L
LINO LINOLEUM
LKR LOCKER
LVT LUXURY VINYL TILE
M
MACC METAL ACCESSORY
MM MIRACLE METHOD
MT METAL THRESHOLD
MTL METAL
MTLB METAL BASE
P
PB PAINTED BASE
PC POLISHED CONCRETE
PLAM PLASTIC LAMINATE
PMTL PAINTED METAL
PT PAINT
Q
QT QUARRY TILE
QTZ QUARTZ SLAB
R
RACC RESILIENT ACCESSORY
RB RESILIENT BASE (VINYL, RUBBER, TP)
RBR RUBBER (TILE AND SHEET)
RES RESIN PANEL
RFS RESILIENT SPORTS FLOORING
RSN PLASTIC RESIN PANEL
S
SCN SEALED CONCRETE
SCB SELF COVE BASE
SGN SIGNAGE
SNC STAINED CONCRETE
SRP SLIP RESISTANT PROTECTIVE FLOORING
SRS SINGLE ROLLER SHADE
SSM SOLID SURFACE MATERIAL
SST STAINLESS STEEL
SWS SPECIAL WALL SURFACES
SV SHEET VINYL
T
TC TOILET COMPARTMENTS
TER TERRAZZO
TKBD TACKBOARD
TPF TRANSPARENT FINISH
TS TRANSITION STRIP
V
VCT VINYL COMPOSITION TILE
VWC VINYL WALL COVERING
ABBREVIATIONS INTERIOR FINISH LEGEND
DESIGNATION DESCRIPTION MANUFACTURER STYLE COLOR REMARKS
SECTION 09 30 13 - CERAMIC TILING
QT1 QUARRY TILE DALTILE QUARRY TILE BLAZE FLASH | 0Q41
SIZE: 6" X 6"
GROUT
CUSTOM BUILDING PRODUCTS #180 SANDSTONE
MACC1 METAL ACCESSORY SCHLUTER SYSTEMS REFER TO SPECIFICATIONS SATIN ANODIZED ALUMINUM
SECTION 09 51 13 - ACOUSTICAL PANEL CEILINGS
ATC1 ACOUSTICAL TILE CEILING USG CEILING SOLUTIONS RADAR, CLIMAPLUS
PERFORMANCE
FLAT WHITE 050
SECTION 09 65 13 - RESILIENT BASE AND ACCESSORIES
RB1 RESILIENT BASE ROPPE 700 SERIES - TYPE TP 123 CHARCOAL
4" COVE WITH TOE; COIL
RACC1 RESILIENT ACCESSORY ROPPE REFER TO SPECIFICATIONS 123 CHARCOAL
SECTION 09 65 19 - RESILIENT TILE FLOORING
LVT1 LUXURY VINYL TILE INTERFACE LEVEL SET | NATURAL
WOODGRAINS
A00209 MAHOGANY INSTALL: ASHLAR PATTERN
SIZE: 25CM X 1M
LVT2 LUXURY VINYL TILE SHAW CONTRACT MINDFUL PLAY | INSPIRE LVT
0884V
ENCOURAGE 84535 INSTALL: ASHLAR PATTERN
SIZE: 12" X 24"
LVT3 LUXURY VINYL TILE SHAW CONTRACT CRETE + JEOGORI | CRETE
0203V
SMOKE 03510 INSTALL: ASHLAR PATTERN
SIZE: 18" X 18"
SECTION 09 91 23 - INTERIOR PAINTING
PT1 PAINT (FIELD) SHERWIN WILLIAMS SW 6064 | RETICENCE
PT2 PAINT SHERWIN WILLIAMS SW 7024 | FUNCTIONAL GRAY
PT3 PAINT SHERWIN WILLIAMS SW 6240 | WINDY BLUE
PT4 PAINT PPG 1011-7 ONYX
SECTION 09 93 00 - STAINING AND TRANSPARENT FINISHING
TPF1 WOOD STAIN BENJAMIN MOORE REFERENCE SPECIFICATIONS STAIN TO MATCH EXISTING
SECTION 09 96 00 - HIGH-PERFORMANCE COATINGS
MM1 SPECIAL WALL COATING MIRACLE METHOD NATURAL ACCENTS ONYX 44136 RESTROOM WALL COATING
MM2 SPECIAL WALL COATING MIRACLE METHOD NATURAL ACCENTS GRAPHITE 57500 RESTROOM FLOOR COATING
END OF LEGEND
RHODES GARRETT HAMIEL GENERAL NOTES
A. CONTRACTOR SHALL VERIFY, CLARIFY, AND COORDINATE DIMENSIONAL
DISCREPANCIES (NEW AND EXISTING) FROM THIS OR ANY PLAN, SECTION OR
ELEVATION WITH THE INTERIOR DESIGNER PRIOR TO CONSTRUCTION.
B. VERIFY WITH THE OWNER THE FINAL DISPOSITION OF ANY MILLWORK, SHELVING,
DOORS, AND EQUIPMENT REMOVED DURING CONSTRUCTION.
C. MATERIALS TO REMAIN SHALL BE PROTECTED FROM DAMAGE DURING
CONSTRUCTION. PATCH AND REPAIR ALL ADJACENT WALLS, CEILINGS, FLOORS,
AND BASE TO MATCH EXISTING WHERE DEMOLITION OR DAMAGE OCCURS. NEW
FINISHES SHALL MATCH THE ADJACENT WALL, CEILING, FLOOR, AND BASE, IN
TEXTURE, PATTERN, AND COLOR. INTERIOR DESIGNER SHALL APPROVE FINAL
WORK.
D. PREPARE SUBSTRATES TO RECEIVE NEW FINISHES WHERE SPECIFIED PER
MANUFACTURE'S WRITTEN GUIDELINES. REFERENCE I-001 FOR FINISH LEGEND
AND FINISH SCHEDULE. NOT ALL FINISHES ARE DEPICTED ON THIS DRAWING.
E. WHERE DAMAGE OCCURS FROM INSTALLATION OF CEILING OR FIRE ALARM,
PATCH AND REPAIR TO MATCH EXISTING.
F. CONTRACTOR SHALL REFERENCE ALL DRAWINGS FOR ADDITIONAL FINISH
LOCATIONS TO INCLUDE WALL FINISH PLANS, FLOOR FINISH PLANS, REFLECTED
CEILING PLANS, RELATED DETAILS AND APPENDIX IN THE PROJECT MANUAL.
GENERAL NOTES
GENERAL FINISH NOTES
** ALL EXISTING FINISHES SHALL REMAIN UNO. DENOTED ON ARCHITECTURAL PLANS.
REFER TO I-001 FOR FINISH LEGEND AND SCHEDULE.
FLOORS:
A. BASE BID: ALL EXISTING FLOORING SHALL REMAIN; ONLY THE FOLLOWING ROOMS
SHALL RECEIVE NEW FLOOR FINISH AS SCHEDULED: 101-106, 108, 110, 113-121, 123,
125, 127-131, 133, 134, 134A, 134B, 136, 138, 140, 142-147, 149, 151, 153, 155-169, 172,
174-182, 184, 201-208, 210, 113, 213-221, 223, 225, 227-236, 238-239, 242, 244-251, 253,
255, 257, 259-274, 276, 278-286 AND 288.
B. ALTERNATE No. 02: ALL SPECIFIED SPACES SHALL RECEIVE NEW FLOOR FINISH AS
SCHEDULED; REFERENCE I-001 FOR FINISH SELECTIONS AND I-401 FOR TYPICAL
FINISH PLANS.
C. ALTERNATE No. 06: ALL SPECIFIED SPACES/AREAS SHALL RECEIVE NEW QUARRY
TILE FLOOR FINISH AS SCHEDULED; REFERENCE I-001 FOR FINISH SELECTIONS AND
I-401 FOR TYPICAL FINISH PLANS.
D. ALL TILED FLOOR SURFACES IN RESTROOMS AND SHOWER ROOMS SHALL RECEIVE
(MM2).
E. ALL TILED FLOOR SURFACES IN WET AREAS THAT HAVE EXISTING GLAZED TILE
THAT IS DAMAGED, CONTRACTOR SHALL REMOVE DAMAGED TILE, CLEAN AREA,
REPLACE WITH TILE THAT IS SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE
METHOD TREATMENT AS SPECIFIED.
F. ALL FLOORS SHALL RECEIVE (LVT2) UNO.
G. REFER TO ENLARGED FINISH PLANS FOR DENOTATIONS AND PATTERN DIRECTIONS;
LENGTH OF PRODUCT IS TO BE INSTALLED AS INDICATED BY DIRECTION OF
ARROWS UNO.
BASE:
A. ALL BASE SHALL BE (RB1).
B. ALL TILED BASE IN RESTROOMS SHALL RECEIVE (MM2) UNO.
WALLS:
A. ALL WALLS SHALL RECEIVE (PT1) UNO.
B. ALL WALLS THAT HAVE WOOD CHAIR RAIL CAP SHALL RECEIVE FINISH AS FOLLOWS:
(RB1) WALL BASE, (PT2) PAINT BELOW CHAIR RAIL CAP, (PT4) WOOD CHAIR RAIL CAP
REFER TO ARCHITECTURE FOR DETAILS, (PT1) PAINT ABOVE CHAIR RAIL CAP.
C. ALL TILED WALL SURFACES IN RESTROOMS AND SHOWER ROOMS SHALL RECEIVE
(MM1).
E. ALL TILED WALL SURFACES IN WET AREAS THAT HAVE EXISTING GLAZED TILE THAT
IS DAMAGED, CONTRACTOR SHALL REMOVE DAMAGED TILE, CLEAN AREA, REPLACE
WITH TILE THAT IS SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE METHOD
TREATMENT AS SPECIFIED.
F. REFER TO ENLARGED FINISH PLANS FOR FINISH TAGS AND TERMINATION POINTS.
CEILINGS:
A. ALL CEILINGS SHALL BE (ATC1) UNO.
B. PAINT ALL VERTICAL AND HORIZONTAL SURFACES OF DRYWALL AND PLASTER
CEILINGS (PT1) UNO.
C. ALL WOODEN BEAMS IN LOUNGE SPACES SHALL RECEIVE NO NEW FINISH AND
SHALL BE PROTECTED PRIOR TO PAINTING.
MILLWORK:
A. ALL EXISTING MILLWORK SHALL RECEIVE NO NEW FINISH.
MISCELLANEOUS:
A. NEW WOOD DOORS SHALL RECEIVE (TPF1).
B. ALL EXISTING INTERIOR PAINTED DOORS SHALL RECEIVE (PT1).
C. ALL PAINTED DOOR TRIM SHALL RECEIVE (PT4).
D. ALL STAIR HANDRAILS AND GUARDRAILS SHALL RECEIVE (PT4).
E. ALL ROOF ACCESS LADDERS AT ENCLOSED STAIRWELLS SHALL RECEIVE (PT4).
F. ALL STAIR RISERS/TREADS SHALL RECEIVE NO NEW FINISH UNO.
A. EXISTING LAY-IN CEILING TILES, GRID, EXIST SIGNS AND 1X4 LIGHT FIXTURES IN
CORRIDORS SHALL BE REMOVED AND REPLACED WITH NEW FIXTURES AS SPECIFIED.
PERIMETER ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING PLANS FOR
NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE SPRINKLER HEADS TO
BE CONCEALED WITHIN THE CEILING WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE "MIRACLE METHOD"
TREATMENT. SURFACES INCLUDE TILE FLOOR AND 4'-0" HIGH WAINSCOT. ALL OTHER
NON-TILE SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE "MIRACLE METHOD"
TREATMENT. SURFACES INCLUDE BUT ARE NOT LIMITED TO THE ENTIRE FLOOR,
RESTROOM BASE AND THE SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER
SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR
SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE "MIRACLE METHOD"
TREATMENT. SURFACES INCLUDE TILE FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT
SHOWER AND CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE NEW
PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT FINISHES.
F. ALL EXISTING APPURTENANCES LOCATED ON THE SUSPENDED CEILING SHALL BE
TEMPORARILY REMOVED, CHECKED FOR DAMAGE, TESTED, CLEANED AND
REINSTALLED IN THE NEW SUSPENDED CEILING GRID.
I-001
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 09,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
NORTH
A1
OVERALL FINISH PLAN
RHODES HALL 1st FLOOR
1/8"=1'-0" -
A2
OVERALL FINISH PLAN
HAMIEL HALL 1st FLOOR
1/8"=1'-0" -
A3
OVERALL FINISH PLAN
GARRETT HALL 1st FLOOR
1/8"=1'-0" -
NORTH NORTH
8' 16'0 4' 8' 16'0 4' 8' 16'0 4'
LEGEND
WOOD TRIM / RAILING IN HALLWAY
B
B
B
B
B
A
B
C
B
A
B
C
B A
B A
B C
B C
GENERAL NOTES
A. CONTRACTOR SHALL VERIFY, CLARIFY, AND COORDINATE
DIMENSIONAL DISCREPANCIES (NEW AND EXISTING) FROM THIS
OR ANY PLAN, SECTION OR ELEVATION WITH THE INTERIOR
DESIGNER PRIOR TO CONSTRUCTION.
B. VERIFY WITH THE OWNER THE FINAL DISPOSITION OF ANY
MILLWORK, SHELVING, DOORS, AND EQUIPMENT REMOVED
DURING CONSTRUCTION.
C. MATERIALS TO REMAIN SHALL BE PROTECTED FROM DAMAGE
DURING CONSTRUCTION. PATCH AND REPAIR ALL ADJACENT
WALLS, CEILINGS, FLOORS, AND BASE TO MATCH EXISTING
WHERE DEMOLITION OR DAMAGE OCCURS. NEW FINISHES SHALL
MATCH THE ADJACENT WALL, CEILING, FLOOR, AND BASE, IN
TEXTURE, PATTERN, AND COLOR. INTERIOR DESIGNER SHALL
APPROVE FINAL WORK.
D. PREPARE SUBSTRATES TO RECEIVE NEW FINISHES WHERE
SPECIFIED PER MANUFACTURE'S WRITTEN GUIDELINES.
REFERENCE I-001 FOR FINISH LEGEND AND FINISH SCHEDULE.
NOT ALL FINISHES ARE DEPICTED ON THIS DRAWING.
E. THE INTERIOR MATERIAL LEGEND LISTS THE COLORS, PATTERNS
AND TEXTURES REQUIRED FOR INTERIOR FINISHES, INCLUDING
BOTH FACTORY APPLIED COLORS THAT ARE EXPOSED TO VIEW IN
THE FINISHED CONSTRUCTION. SPECIFIC LOCATIONS WHERE
VARIOUS MATERIALS ARE REQUIRED ARE INDICATED IN DRAWING.
WHEN COLOR IS NOT DESIGNATED FOR ITEMS, THE CONTRACTOR
SHALL ASK FOR A COLOR SELECTION.
F. A TRANSITION SHALL BE PROVIDED BETWEEN DISSIMILAR
FLOORING TYPES; CONTRACTOR SHALL VERIFY LOCATIONS. THE
TRANSITION SHALL BE THE APPROPRIATE THICKNESS TO
ACCOMMODATE THE SCHEDULED FLOORING AND CREATE AN
ACCESSIBLE TRANSITION BETWEEN FLOORING TYPES. PROVIDE
APPLICABLE TRANSITION BETWEEN NEW MATERIAL AND EXISTING
FLOORING AS NEEDED.
G. WHERE FLOORING TRANSITIONS OCCUR AT DOORS; MATERIAL
CHANGE SHALL OCCUR AT THE DOOR CENTER LINE.
D1/I-401
D3/I-401
D2/I-401
B3/I-401
NIC - NOT IN CONTRACTROOM
102
ROOM
101
ROOM
103
ROOM
104
ROOM
106
ROOM
105
ROOM
108
LOUNGE
107
SHOWER
150
RESTROOM
148
SHOWER / BATH
126
SHOWER
171
RESTROOM
173
LOUNGE
109
ROOM
110
ROOM
113
ROOM
114
CLASSROOM
113
ROOM
116
ROOM
115
ROOM
117
ROOM
118
ROOM
120
ROOM
119
ROOM
184
ROOM
182
ROOM
180
ROOM
178
ROOM
176
ROOM
174
ROOM
172
ROOM
166
ROOM
164
ROOM
162
ROOM
160
ROOM
158
ROOM
156
ROOM
168
STAIRS
04
ROOM
181
ROOM
179
ROOM
177
ROOM
175
ROOM
165
ROOM
163
ROOM
161
ROOM
159
ROOM
157
ROOM
155
ROOM
167
ROOM
169
STAIRS
03
ROOM
121
ROOM
123
ROOM
125
ROOM
127
ROOM
129
ROOM
131
LOUNGE
135
LOUNGE
137
ROOM
133
STAIRS
02
ROOM
128
ROOM
134
ROOM
136
ROOM
134A
ROOM
134B
ROOM
130
ROOM
137
LOUNGE
139
LAUNDRY
141A
KITCHEN
141B
ROOM
143
ROOM
145
ROOM
149
ROOM
151
ROOM
153
ROOM
147
ROOM
142
ROOM
144
ROOM
146
ROOM
138
ROOM
140
STAIRS
01
B
B
B
B
B5/I-401
D4/I-401
E3/I-401
E4/I-401
DO
WN
DO
WN
UP
UP
UP
UP
A1/I-401
E5/I-401
A1/I-401
(SIM)
A1/I-401
(SIM)
RHODES GARRETT HAMIEL
GENERAL NOTES
A. EXISTING LAY-IN CEILING TILES, GRID, EXIST SIGNS AND 1X4
LIGHT FIXTURES IN CORRIDORS SHALL BE REMOVED AND
REPLACED WITH NEW FIXTURES AS SPECIFIED. PERIMETER
ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING
PLANS FOR NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE
SPRINKLER HEADS TO BE CONCEALED WITHIN THE CEILING
WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR
AND 4'-0" HIGH WAINSCOT. ALL OTHER NON-TILE SURFACES
SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE BUT ARE
NOT LIMITED TO THE ENTIRE FLOOR, RESTROOM BASE AND THE
SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER SURFACES
SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE
FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT SHOWER AND
CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE
NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT
FINISHES.
F. ALL EXISTING APPURTENANCES LOCATED ON THE SUSPENDED
CEILING SHALL BE TEMPORARILY REMOVED, CHECKED FOR
DAMAGE, TESTED, CLEANED AND REINSTALLED IN THE NEW
SUSPENDED CEILING GRID
D5/I-401
D5/I-401
(SIM)
D5/I-401
(SIM)
D4/I-401
(SIM)
GENERAL FINISH NOTES
RESTROOM
RH
RESTROOM
GH
E5/I-401
ROOM
113A
A5/I-401
A5/I-401
(SIM)
** ALL EXISTING FINISHES SHALL REMAIN UNO. DENOTED ON
ARCHITECTURAL PLANS. REFER TO I-001 FOR FINISH LEGEND AND
SCHEDULE.
FLOORS:
A. BASE BID: ALL EXISTING FLOORING SHALL REMAIN; ONLY THE
FOLLOWING ROOMS SHALL RECEIVE NEW FLOOR FINISH AS
SCHEDULED: 101-106, 108, 110, 113-121, 123, 125, 127-131, 133, 134,
134A, 134B, 136, 138, 140, 142-147, 149, 151, 153, 155-169, 172,
174-182, 184, 201-208, 210, 113, 213-221, 223, 225, 227-236, 238-239,
242, 244-251, 253, 255, 257, 259-274, 276, 278-286 AND 288.
B. ALTERNATE No. 02: ALL SPECIFIED SPACES SHALL RECEIVE NEW
FLOOR FINISH AS SCHEDULED; REFERENCE I-001 FOR FINISH
SELECTIONS AND I-401 FOR TYPICAL FINISH PLANS.
C. ALTERNATE No. 06: ALL SPECIFIED SPACES/AREAS SHALL
RECEIVE NEW QUARRY TILE FLOOR FINISH AS SCHEDULED;
REFERENCE I-001 FOR FINISH SELECTIONS AND I-401 FOR
TYPICAL FINISH PLANS.
D. ALL TILED FLOOR SURFACES IN RESTROOMS AND SHOWER
ROOMS SHALL RECEIVE (MM2).
E. ALL TILED FLOOR SURFACES IN WET AREAS THAT HAVE EXISTING
GLAZED TILE THAT IS DAMAGED, CONTRACTOR SHALL REMOVE
DAMAGED TILE, CLEAN AREA, REPLACE WITH TILE THAT IS
SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE METHOD
TREATMENT AS SPECIFIED.
F. ALL FLOORS SHALL RECEIVE (LVT2) UNO.
G. REFER TO ENLARGED FINISH PLANS FOR DENOTATIONS AND
PATTERN DIRECTIONS; LENGTH OF PRODUCT IS TO BE INSTALLED
AS INDICATED BY DIRECTION OF ARROWS UNO.
BASE:
A. ALL BASE SHALL BE (RB1).
B. ALL TILED BASE IN RESTROOMS SHALL RECEIVE (MM2) UNO.
WALLS:
A. ALL WALLS SHALL RECEIVE (PT1) UNO.
B. ALL WALLS THAT HAVE WOOD CHAIR RAIL CAP SHALL RECEIVE
FINISH AS FOLLOWS: (RB1) WALL BASE, (PT2) PAINT BELOW CHAIR
RAIL CAP, (PT4) WOOD CHAIR RAIL CAP REFER TO ARCHITECTURE
FOR DETAILS, (PT1) PAINT ABOVE CHAIR RAIL CAP.
C. ALL TILED WALL SURFACES IN RESTROOMS AND SHOWER ROOMS
SHALL RECEIVE (MM1).
E. ALL TILED WALL SURFACES IN WET AREAS THAT HAVE EXISTING
GLAZED TILE THAT IS DAMAGED, CONTRACTOR SHALL REMOVE
DAMAGED TILE, CLEAN AREA, REPLACE WITH TILE THAT IS
SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE METHOD
TREATMENT AS SPECIFIED.
F. REFER TO ENLARGED FINISH PLANS FOR FINISH TAGS AND
TERMINATION POINTS.
CEILINGS:
A. ALL CEILINGS SHALL BE (ATC1) UNO.
B. PAINT ALL VERTICAL AND HORIZONTAL SURFACES OF DRYWALL
AND PLASTER CEILINGS (PT1) UNO.
C. ALL WOODEN BEAMS IN LOUNGE SPACES SHALL RECEIVE NO
NEW FINISH AND SHALL BE PROTECTED PRIOR TO PAINTING.
MILLWORK:
A. ALL EXISTING MILLWORK SHALL RECEIVE NO NEW FINISH.
MISCELLANEOUS:
A. NEW WOOD DOORS SHALL RECEIVE (TPF1).
B. ALL EXISTING INTERIOR PAINTED DOORS SHALL RECEIVE (PT1).
C. ALL PAINTED DOOR TRIM SHALL RECEIVE (PT4).
D. ALL STAIR HANDRAILS AND GUARDRAILS SHALL RECEIVE (PT4).
E. ALL ROOF ACCESS LADDERS AT ENCLOSED STAIRWELLS SHALL
RECEIVE (PT4).
F. ALL STAIR RISERS/TREADS SHALL RECEIVE NO NEW FINISH UNO.
I-111
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 09,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
NORTH
A1
OVERALL FINISH PLAN
RHODES HALL 2nd FLOOR
1/8"=1'-0" -
A2
OVERALL FINISH PLAN
HAMIEL HALL 2nd FLOOR
1/8"=1'-0" -
A3
OVERALL FINISH PLAN
GARRETT HALL 2nd FLOOR
1/8"=1'-0" -
NORTH
NORTH
8' 16'0 4' 8' 16'0 4'
8' 16'0 4'
B
A
B
C
B
A
B
C
B A
B A
B C
B C
ROOM
202
ROOM
201
ROOM
203
ROOM
204
ROOM
206
ROOM
205
ROOM
208
ROOM
207
LOUNGE
209
ROOM
210
ROOM
213
ROOM
214
ROOM
113
ROOM
216
ROOM
215
ROOM
217
ROOM
218
ROOM
220
ROOM
219
ROOM
288
ROOM
286
ROOM
284
ROOM
282
ROOM
280
ROOM
278
ROOM
276
ROOM
270
ROOM
268
ROOM
266
ROOM
264
ROOM
262
ROOM
260
ROOM
272
STAIRS
04
ROOM
285
ROOM
283
ROOM
281
ROOM
279
ROOM
269
ROOM
267
ROOM
265
ROOM
263
ROOM
261
ROOM
259
ROOM
271
ROOM
273
ROOM
274
SHOWER
275
RESTROOM
277
ROOM
221
ROOM
223
ROOM
225
ROOM
227
ROOM
229
ROOM
231
ROOM
235
LOUNGE
137
ROOM
233
STAIRS
02
ROOM
228
ROOM
236
ROOM
238
ROOM
234
ROOM
232
ROOM
230
ROOM
137
ROOM
239
ROOM
245
ROOM
247
ROOM
249
ROOM
253
ROOM
255
ROOM
257
ROOM
251
ROOM
246
ROOM
248
ROOM
250
ROOM
242
ROOM
244
STAIRS
01
B
B
B
B
B
B
B
B
ROOM
211
ROOM
240
SHOWER
254
SHOWER
252
E3/I-401
B5/I-401
D4/I-401
D1/I-401
D3/I-401
D2/I-401
B3/I-401
E4/I-401
DN
DN
DN
DN
DN
DN
B1/I-401
(SIM)
(SIM)
(SIM)
B1/I-401
(SIM)
(SIM)
(SIM)
(SIM)
SHOWER / BATH
226
(SIM)
LEGEND
WOOD TRIM / RAILING IN HALLWAY
GENERAL NOTES
A. CONTRACTOR SHALL VERIFY, CLARIFY, AND COORDINATE
DIMENSIONAL DISCREPANCIES (NEW AND EXISTING) FROM THIS
OR ANY PLAN, SECTION OR ELEVATION WITH THE INTERIOR
DESIGNER PRIOR TO CONSTRUCTION.
B. VERIFY WITH THE OWNER THE FINAL DISPOSITION OF ANY
MILLWORK, SHELVING, DOORS, AND EQUIPMENT REMOVED
DURING CONSTRUCTION.
C. MATERIALS TO REMAIN SHALL BE PROTECTED FROM DAMAGE
DURING CONSTRUCTION. PATCH AND REPAIR ALL ADJACENT
WALLS, CEILINGS, FLOORS, AND BASE TO MATCH EXISTING
WHERE DEMOLITION OR DAMAGE OCCURS. NEW FINISHES SHALL
MATCH THE ADJACENT WALL, CEILING, FLOOR, AND BASE, IN
TEXTURE, PATTERN, AND COLOR. INTERIOR DESIGNER SHALL
APPROVE FINAL WORK.
D. PREPARE SUBSTRATES TO RECEIVE NEW FINISHES WHERE
SPECIFIED PER MANUFACTURE'S WRITTEN GUIDELINES.
REFERENCE I-001 FOR FINISH LEGEND AND FINISH SCHEDULE.
NOT ALL FINISHES ARE DEPICTED ON THIS DRAWING.
E. THE INTERIOR MATERIAL LEGEND LISTS THE COLORS, PATTERNS
AND TEXTURES REQUIRED FOR INTERIOR FINISHES, INCLUDING
BOTH FACTORY APPLIED COLORS THAT ARE EXPOSED TO VIEW IN
THE FINISHED CONSTRUCTION. SPECIFIC LOCATIONS WHERE
VARIOUS MATERIALS ARE REQUIRED ARE INDICATED IN DRAWING.
WHEN COLOR IS NOT DESIGNATED FOR ITEMS, THE CONTRACTOR
SHALL ASK FOR A COLOR SELECTION.
F. A TRANSITION SHALL BE PROVIDED BETWEEN DISSIMILAR
FLOORING TYPES; CONTRACTOR SHALL VERIFY LOCATIONS. THE
TRANSITION SHALL BE THE APPROPRIATE THICKNESS TO
ACCOMMODATE THE SCHEDULED FLOORING AND CREATE AN
ACCESSIBLE TRANSITION BETWEEN FLOORING TYPES. PROVIDE
APPLICABLE TRANSITION BETWEEN NEW MATERIAL AND EXISTING
FLOORING AS NEEDED.
G. WHERE FLOORING TRANSITIONS OCCUR AT DOORS; MATERIAL
CHANGE SHALL OCCUR AT THE DOOR CENTER LINE.
NIC - NOT IN CONTRACT
A. EXISTING LAY-IN CEILING TILES, GRID, EXIST SIGNS AND 1X4
LIGHT FIXTURES IN CORRIDORS SHALL BE REMOVED AND
REPLACED WITH NEW FIXTURES AS SPECIFIED. PERIMETER
ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING
PLANS FOR NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE
SPRINKLER HEADS TO BE CONCEALED WITHIN THE CEILING
WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE FLOOR
AND 4'-0" HIGH WAINSCOT. ALL OTHER NON-TILE SURFACES
SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE BUT ARE
NOT LIMITED TO THE ENTIRE FLOOR, RESTROOM BASE AND THE
SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER SURFACES
SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE
"MIRACLE METHOD" TREATMENT. SURFACES INCLUDE TILE
FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT SHOWER AND
CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE
NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT
FINISHES.
F. ALL EXISTING APPURTENANCES LOCATED ON THE SUSPENDED
CEILING SHALL BE TEMPORARILY REMOVED, CHECKED FOR
DAMAGE, TESTED, CLEANED AND REINSTALLED IN THE NEW
SUSPENDED CEILING GRID
RHODES GARRETT HAMIEL
GENERAL NOTES
D4/I-401
(SIM)
GENERAL FINISH NOTES
OPEN TO
BELOW
OPEN TO
BELOW
(SIM)
** ALL EXISTING FINISHES SHALL REMAIN UNO. DENOTED ON
ARCHITECTURAL PLANS. REFER TO I-001 FOR FINISH LEGEND AND
SCHEDULE.
FLOORS:
A. BASE BID: ALL EXISTING FLOORING SHALL REMAIN; ONLY THE
FOLLOWING ROOMS SHALL RECEIVE NEW FLOOR FINISH AS
SCHEDULED: 101-106, 108, 110, 113-121, 123, 125, 127-131, 133, 134,
134A, 134B, 136, 138, 140, 142-147, 149, 151, 153, 155-169, 172,
174-182, 184, 201-208, 210, 113, 213-221, 223, 225, 227-236, 238-239,
242, 244-251, 253, 255, 257, 259-274, 276, 278-286 AND 288.
B. ALTERNATE No. 02: ALL SPECIFIED SPACES SHALL RECEIVE NEW
FLOOR FINISH AS SCHEDULED; REFERENCE I-001 FOR FINISH
SELECTIONS AND I-401 FOR TYPICAL FINISH PLANS.
C. ALTERNATE No. 06: ALL SPECIFIED SPACES/AREAS SHALL
RECEIVE NEW QUARRY TILE FLOOR FINISH AS SCHEDULED;
REFERENCE I-001 FOR FINISH SELECTIONS AND I-401 FOR
TYPICAL FINISH PLANS.
D. ALL TILED FLOOR SURFACES IN RESTROOMS AND SHOWER
ROOMS SHALL RECEIVE (MM2).
E. ALL TILED FLOOR SURFACES IN WET AREAS THAT HAVE EXISTING
GLAZED TILE THAT IS DAMAGED, CONTRACTOR SHALL REMOVE
DAMAGED TILE, CLEAN AREA, REPLACE WITH TILE THAT IS
SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE METHOD
TREATMENT AS SPECIFIED.
F. ALL FLOORS SHALL RECEIVE (LVT2) UNO.
G. REFER TO ENLARGED FINISH PLANS FOR DENOTATIONS AND
PATTERN DIRECTIONS; LENGTH OF PRODUCT IS TO BE INSTALLED
AS INDICATED BY DIRECTION OF ARROWS UNO.
BASE:
A. ALL BASE SHALL BE (RB1).
B. ALL TILED BASE IN RESTROOMS SHALL RECEIVE (MM2) UNO.
WALLS:
A. ALL WALLS SHALL RECEIVE (PT1) UNO.
B. ALL WALLS THAT HAVE WOOD CHAIR RAIL CAP SHALL RECEIVE
FINISH AS FOLLOWS: (RB1) WALL BASE, (PT2) PAINT BELOW CHAIR
RAIL CAP, (PT4) WOOD CHAIR RAIL CAP REFER TO ARCHITECTURE
FOR DETAILS, (PT1) PAINT ABOVE CHAIR RAIL CAP.
C. ALL TILED WALL SURFACES IN RESTROOMS AND SHOWER ROOMS
SHALL RECEIVE (MM1).
E. ALL TILED WALL SURFACES IN WET AREAS THAT HAVE EXISTING
GLAZED TILE THAT IS DAMAGED, CONTRACTOR SHALL REMOVE
DAMAGED TILE, CLEAN AREA, REPLACE WITH TILE THAT IS
SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE METHOD
TREATMENT AS SPECIFIED.
F. REFER TO ENLARGED FINISH PLANS FOR FINISH TAGS AND
TERMINATION POINTS.
CEILINGS:
A. ALL CEILINGS SHALL BE (ATC1) UNO.
B. PAINT ALL VERTICAL AND HORIZONTAL SURFACES OF DRYWALL
AND PLASTER CEILINGS (PT1) UNO.
C. ALL WOODEN BEAMS IN LOUNGE SPACES SHALL RECEIVE NO
NEW FINISH AND SHALL BE PROTECTED PRIOR TO PAINTING.
MILLWORK:
A. ALL EXISTING MILLWORK SHALL RECEIVE NO NEW FINISH.
MISCELLANEOUS:
A. NEW WOOD DOORS SHALL RECEIVE (TPF1).
B. ALL EXISTING INTERIOR PAINTED DOORS SHALL RECEIVE (PT1).
C. ALL PAINTED DOOR TRIM SHALL RECEIVE (PT4).
D. ALL STAIR HANDRAILS AND GUARDRAILS SHALL RECEIVE (PT4).
E. ALL ROOF ACCESS LADDERS AT ENCLOSED STAIRWELLS SHALL
RECEIVE (PT4).
F. ALL STAIR RISERS/TREADS SHALL RECEIVE NO NEW FINISH UNO.
I-112
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 09,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.
LEGEND
AS INDICATED BY:00
KEY NOTES
D1
ENLARGED FINISH PLAN
SHOWER AND RESTROOM
1/4"=1'-0" -
D3
ENLARGED FINISH PLAN
SHOWER/BATH
1/4"=1'-0" -
4' 8'0 2'
4' 8'0 2'
NO WORK THIS ROOM
RHODES GARRETT HAMIEL GENERAL NOTES
WOOD TRIM / RAILING IN HALLWAY
A. EXISTING LAY-IN CEILING TILES, GRID AND 1X4 LIGHT FIXTURES IN CORRIDOR SHALL
BE REMOVED AND REPLACED WITH NEW LED FIXTURES AS SPECIFIED. PERIMETER
ANGLE TRIM SHALL REMAIN. REFER TO REFLECTED CEILING PLANS FOR NEW WORK.
ADDITIVE ALTERNATE No. 03 - MODIFY EXISTING FIRE SPRINKLER HEADS TO BE
CONCEALED WITHIN THE CEILING WITH ESCUTCHEON FINISH.
B. ALL COMMUNITY RESTROOM TILED SURFACES SHALL RECEIVE "MIRACLE METHOD"
TREATMENT. SURFACES INCLUDE TILE FLOOR AND 4'-0" HIGH WAINSCOT. ALL OTHER
NON-TILE SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO
INTERIOR SHEETS.
C. ALL TILED SURFACES IN SUITE RESTROOMS SHALL RECEIVE "MIRACLE METHOD"
TREATMENT. SURFACES INCLUDE BUT ARE NOT LIMITED TO THE ENTIRE FLOOR,
RESTROOM BASE AND THE SHOWER 7'-0" HIGH WAINSCOT WALLS. ALL OTHER
SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFER TO INTERIOR
SHEETS.
D. ALL COMMUNITY SHOWER TILED SURFACES SHALL RECEIVE "MIRACLE METHOD"
TREATMENT. SURFACES INCLUDE TILE FLOOR, 4'-0" HIGH WAINSCOT, FULL HEIGHT
SHOWER AND CHANGING STALL WALLS. ALL OTHER SURFACES SHALL RECEIVE NEW
PAINT FINISH AS SCHEDULED. REFER TO INTERIOR SHEETS.
E. IN RESTROOMS WHERE THE "MIRACLE METHOD" WILL BE RECEIVED, EXISTING
TOILETS WILL BE REMOVED PRIOR TO WORK AND REINSTALLED AT COMPLETION OF
WORK.
F. EXTERIOR WINDOWS WILL BE REMOVED AND REPLACED WITH NEW ENERGY
EFFICIENT UNITS. REFER TO SHEET A-601 FOR WINDOW TYPES.
G. REFER TO INTERIOR SHEETS FOR ALL MATERIAL AND PAINT FINISHES.
H. ALL EXISTING APPURTENANCES LOCATED IN THE SUSPENDED CEILING SHALL BE
TEMPORARILY REMOVED, CHECKED FOR DAMAGE, TESTED, CLEANED AND
REINSTALLED IN THE NEW SUSPENDED CEILING GRID.
SHOWER
150
RESTROOM
148
SHOWER / BATH
126
4' 8'0 2'
B3
ENLARGED FINISH PLAN
TYPICAL SUITE W/ SHARED RESTROOM
1/4"=1'-0" -
A. CONTRACTOR SHALL VERIFY, CLARIFY, AND COORDINATE DIMENSIONAL
DISCREPANCIES (NEW AND EXISTING) FROM THIS OR ANY PLAN, SECTION OR
ELEVATION WITH THE INTERIOR DESIGNER PRIOR TO CONSTRUCTION.
B. VERIFY WITH THE OWNER THE FINAL DISPOSITION OF ANY MILLWORK, SHELVING,
DOORS, AND EQUIPMENT REMOVED DURING CONSTRUCTION.
C. MATERIALS TO REMAIN SHALL BE PROTECTED FROM DAMAGE DURING
CONSTRUCTION. PATCH AND REPAIR ALL ADJACENT WALLS, CEILINGS, FLOORS,
AND BASE TO MATCH EXISTING WHERE DEMOLITION OR DAMAGE OCCURS. NEW
FINISHES SHALL MATCH THE ADJACENT WALL, CEILING, FLOOR, AND BASE, IN
TEXTURE, PATTERN, AND COLOR. INTERIOR DESIGNER SHALL APPROVE FINAL
WORK.
D. PREPARE SUBSTRATES TO RECEIVE NEW FINISHES WHERE SPECIFIED PER
MANUFACTURE'S WRITTEN GUIDELINES. REFERENCE I-001 FOR FINISH LEGEND
AND FINISH SCHEDULE. NOT ALL FINISHES ARE DEPICTED ON THIS DRAWING.
E. THE INTERIOR MATERIAL LEGEND LISTS THE COLORS, PATTERNS AND TEXTURES
REQUIRED FOR INTERIOR FINISHES, INCLUDING BOTH FACTORY APPLIED COLORS
THAT ARE EXPOSED TO VIEW IN THE FINISHED CONSTRUCTION. SPECIFIC
LOCATIONS WHERE VARIOUS MATERIALS ARE REQUIRED ARE INDICATED IN
DRAWING. WHEN COLOR IS NOT DESIGNATED FOR ITEMS, THE CONTRACTOR
SHALL ASK FOR A COLOR SELECTION.
F. A TRANSITION SHALL BE PROVIDED BETWEEN DISSIMILAR FLOORING TYPES;
CONTRACTOR SHALL VERIFY LOCATIONS. THE TRANSITION SHALL BE THE
APPROPRIATE THICKNESS TO ACCOMMODATE THE SCHEDULED FLOORING AND
CREATE AN ACCESSIBLE TRANSITION BETWEEN FLOORING TYPES. PROVIDE
APPLICABLE TRANSITION BETWEEN NEW MATERIAL AND EXISTING FLOORING AS
NEEDED.
G. WHERE FLOORING TRANSITIONS OCCUR AT DOORS; MATERIAL CHANGE SHALL
OCCUR AT THE DOOR CENTER LINE.
H. UNLESS SPECIFICALLY NOTED OTHERWISE ON AN INDIVIDUAL UNIT, ALL WORK
NOTED ON ENLARGED FINISH PLANS I-401 SHALL APPLY TO ALL RHODES GARRETT
HAMIEL ROOMS UNITS. REFER TO I-001 FOR INTERIOR FINISH LEGEND AND NOTES.
GENERAL NOTES
MM1
4' 8'0 2'
4' 8'0 2'
B5
ENLARGED FINISH PLAN
TYPICAL SUITE W/O RESTROOM
1/4"=1'-0" -
4' 8'0 2'
4' 8'0 2'
4' 8'0 2'
LVT1
4' 8'0 2'
LVT1
03
05
01
MM2
1. EXISTING TILED FLOOR AND WALL SURFACES TO REMAIN; PREPARE SURFACES TO
RECEIVE "MIRACLE METHOD TREATMENT" AS SCHEDULED. SURFACES TO INCLUDE
TILE FLOOR, 4'-0" HIGH WAINSCOT, TILE WALL BASE, FULL HEIGHT SHOWER (IF
APPLICABLE), EXISTING TUB (IF APPLICABLE) AND CHANGING STALL WALLS. ALL
OTHER SURFACES SHALL RECEIVE NEW PAINT FINISH AS SCHEDULED. REFERENCE
INTERIOR FINISH LEGEND.
2. ALTERNATE No. 02: SPACE SHALL RECEIVE NEW FLOOR FINISH AS SCHEDULED;
REFERENCE INTERIOR FINISH LEGEND.
3. ALTERNATE No. 06: SPACE/AREA SHALL RECEIVE NEW QUARRY TILE FLOOR FINISH
AS SCHEDULED; REFERENCE INTERIOR FINISH LEGEND.
4. EXISTING WOOD STAIR TREADS SHALL BE PREPARED TO RECEIVE NEW FINISH AS
SCHEDULED, REFERENCE INTERIOR FINISH LEGEND.
5. EXISTING TILED WALL AND BASE SURFACES TO REMAIN; PREPARE SURFACES TO
RECEIVE "MIRACLE METHOD TREATMENT" AS SCHEDULED. SURFACES TO INCLUDE
TILED WALL BASE, TILED WALL, AND EXISTING TUB.
6. LOUNGE 135 EXISTING WOOD FLOORING SHALL REMAIN, NO WORK. PROTECT
FLOORING PRIOR TO PAINTING.
7. EXISTING TILED SURFACE TO REMAIN, NO WORK.
8. EXISTING STAIR TREADS AND/OR RISERS TO REMAIN, NO WORK.
9. CONTRACTOR SHALL COORDINATE NEW TILE TERMINATION POINTS TO ALIGN WITH
EXISTING CERAMIC TILE. VERIFY EXISTING DIMENSION.
MM1
01
MM2
MM1
01
MM2
LOUNGE
109
CLASSROOM
113
LOUNGE
107
A1
ENLARGED FINISH PLAN
TYPICAL LOUNGE AT FIRST FLOOR
1/4"=1'-0" -
4' 8'0 2'
B1
ENLARGED FINISH PLAN
TYPICAL LOUNGE AT SECOND FLOOR
1/4"=1'-0" -
4' 8'0 2'
LVT3
LVT3
LVT3
PT
3P
T3
PT3 PT3
PT2
PT2 PT2
LVT1
MM1
01
MM2
ROOM
131
ROOM
129
LVT1
MM1
01
MM2
SHOWER
171
MM1
01
MM2
RESTROOM
173
MM1
01
MM2
ROOM
178
D2
ENLARGED FINISH PLAN
SHOWER AND RESTROOM
1/4"=1'-0" -
4' 8'0 2'
A5
ENLARGED FINISH PLAN
SHARED KITCHEN
1/4"=1'-0" -
E5
ENLARGED FINISH PLAN
TYPICAL HALLWAY BATHROOM
1/4"=1'-0" -
E4
ENLARGED FINISH PLAN
TYPICAL STAIRS
1/4"=1'-0" -
PT3 PT3
04
04
PT
3P
T3
STAIRS
04
STAIRS
03
STAIRS
02
PT2
TPF1
TPF1
04
TPF1
04
TPF1
02
02
02
D4
ENLARGED FINISH PLAN
TYPICAL STAIRS
1/4"=1'-0" -
E3
ENLARGED FINISH PLAN
TYPICAL STAIRS
1/4"=1'-0" -
07
07
07
07
07
GENERAL FINISH NOTES
4' 8'0 2'
D5
ENLARGED FINISH PLAN
TYPICAL ENTRY
1/4"=1'-0" -
03
LVT3
02
OPEN TO BELOW
RESTROOM
RH
06
ROOM
113A
LVT1
QT1
QT1
03
QT1
03
QT1
02
02
02
02
02
LVT2
LVT2
LVT2
** ALL EXISTING FINISHES SHALL REMAIN UNO. DENOTED ON ARCHITECTURAL PLANS.
REFER TO I-001 FOR FINISH LEGEND AND SCHEDULE.
FLOORS:
A. BASE BID: ALL EXISTING FLOORING SHALL REMAIN; ONLY THE FOLLOWING ROOMS
SHALL RECEIVE NEW FLOOR FINISH AS SCHEDULED: 101-106, 108, 110, 113-121, 123,
125, 127-131, 133, 134, 134A, 134B, 136, 138, 140, 142-147, 149, 151, 153, 155-169, 172,
174-182, 184, 201-208, 210, 113, 213-221, 223, 225, 227-236, 238-239, 242, 244-251, 253,
255, 257, 259-274, 276, 278-286 AND 288.
B. ALTERNATE No. 02: ALL SPECIFIED SPACES SHALL RECEIVE NEW FLOOR FINISH AS
SCHEDULED; REFERENCE I-001 FOR FINISH SELECTIONS AND I-401 FOR TYPICAL
FINISH PLANS.
C. ALTERNATE No. 06: ALL SPECIFIED SPACES/AREAS SHALL RECEIVE NEW QUARRY
TILE FLOOR FINISH AS SCHEDULED; REFERENCE I-001 FOR FINISH SELECTIONS AND
I-401 FOR TYPICAL FINISH PLANS.
D. ALL TILED FLOOR SURFACES IN RESTROOMS AND SHOWER ROOMS SHALL RECEIVE
(MM2).
E. ALL TILED FLOOR SURFACES IN WET AREAS THAT HAVE EXISTING GLAZED TILE
THAT IS DAMAGED, CONTRACTOR SHALL REMOVE DAMAGED TILE, CLEAN AREA,
REPLACE WITH TILE THAT IS SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE
METHOD TREATMENT AS SPECIFIED.
F. ALL FLOORS SHALL RECEIVE (LVT2) UNO.
G. REFER TO ENLARGED FINISH PLANS FOR DENOTATIONS AND PATTERN DIRECTIONS;
LENGTH OF PRODUCT IS TO BE INSTALLED AS INDICATED BY DIRECTION OF
ARROWS UNO.
BASE:
A. ALL BASE SHALL BE (RB1).
B. ALL TILED BASE IN RESTROOMS SHALL RECEIVE (MM2) UNO.
WALLS:
A. ALL WALLS SHALL RECEIVE (PT1) UNO.
B. ALL WALLS THAT HAVE WOOD CHAIR RAIL CAP SHALL RECEIVE FINISH AS FOLLOWS:
(RB1) WALL BASE, (PT2) PAINT BELOW CHAIR RAIL CAP, (PT4) WOOD CHAIR RAIL CAP
REFER TO ARCHITECTURE FOR DETAILS, (PT1) PAINT ABOVE CHAIR RAIL CAP.
C. ALL TILED WALL SURFACES IN RESTROOMS AND SHOWER ROOMS SHALL RECEIVE
(MM1).
E. ALL TILED WALL SURFACES IN WET AREAS THAT HAVE EXISTING GLAZED TILE THAT
IS DAMAGED, CONTRACTOR SHALL REMOVE DAMAGED TILE, CLEAN AREA, REPLACE
WITH TILE THAT IS SIMILAR TO ADJACENT AND PROCEED WITH MIRACLE METHOD
TREATMENT AS SPECIFIED.
F. REFER TO ENLARGED FINISH PLANS FOR FINISH TAGS AND TERMINATION POINTS.
CEILINGS:
A. ALL CEILINGS SHALL BE (ATC1) UNO.
B. PAINT ALL VERTICAL AND HORIZONTAL SURFACES OF DRYWALL AND PLASTER
CEILINGS (PT1) UNO.
C. ALL WOODEN BEAMS IN LOUNGE SPACES SHALL RECEIVE NO NEW FINISH AND
SHALL BE PROTECTED PRIOR TO PAINTING.
MILLWORK:
A. ALL EXISTING MILLWORK SHALL RECEIVE NO NEW FINISH.
MISCELLANEOUS:
A. NEW WOOD DOORS SHALL RECEIVE (TPF1).
B. ALL EXISTING INTERIOR PAINTED DOORS SHALL RECEIVE (PT1).
C. ALL PAINTED DOOR TRIM SHALL RECEIVE (PT4).
D. ALL STAIR HANDRAILS AND GUARDRAILS SHALL RECEIVE (PT4).
E. ALL ROOF ACCESS LADDERS AT ENCLOSED STAIRWELLS SHALL RECEIVE (PT4).
F. ALL STAIR RISERS/TREADS SHALL RECEIVE NO NEW FINISH UNO.
08
08
08
1'-4 1/2"
09
LOUNGE
209
I-401
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
LAS CRUCES 8918.17
1
THIS DOCUMENT IS RELEASED ON JANUARY 09,
2019 FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF MICHAEL THOMAS
STILLS, R.A., NEW MEXICO LICENSE #5580. IT IS
NOT TO BE USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PURPOSES. PARKHILL, SMITH & COOPER, INC.