genaux
DESCRIPTION
gen auxTRANSCRIPT
BHEL, Hardwar
Generator Bearing
2.1-5001-0015/1
Turbo Generators
Description
BHEL, Hardwar 2.1-5003-0011/1
Measuring of Bearing TemperatureTurbo Generators
Description
BHEL, Hardwar 2.1-5005-0007/1
Generator Bearing Insulation
THDF, THFF Series
Turbo Generators
Description
BHEL, Hardwar
The rotor shaft ends are brought out of the
gastight enclosure through double-flow shaft seals.
With th is type of shaf t seal , the escape of
hydrogen between the rotating shaft and the housing
is prevented by maintaining a cdontinus film of oil
between the shaft and a non-rotating floating seal
ring. To accomplish this, seal oil from two separate
circuits, i.e. the air side and hydrogen side seal oil
circuit, is fed to the seal ring at a pressure slightly
higher than the hydrogen pressure. In addition,
higher pressure air side oil is supplied to the shaft
seal for thrust load compensation of the seal ring.
1 Seal ring carrier
2 Seal ring
Hydrogen side seal oil
Air side seal oil
Ring relief oil
Fig.1 Interchange of Oil in Annular Groove of Shaft
Seal
The double-flow shaft seal is characterized by its
shor t ax ia l length, i ts independence f rom the
respective axial and radial position of the shaft, and
low hydrogen losses due to absorption by the seal
oil.
The two halves of the babbitted seal ring float on
the shaft journal with a small clearance and are
guided in the axial direction by a seal ring carrier
resistant to distortion and bending. The seal ring is
Shaft Seal
2.1-6000-0006/1
relatively free to move in the radial direction, but is
restrained from rotating by use of a pin. The seal ring
carrier, bolted to the end shield, is insulated to prevent
the flow of shaft currents. The oil is supplied to the
shaft seal at three different pressures (air side and
hydrogen side seal oil pressures and higher pressure
oil for ring relief) over pipes and the mounting flange
of the seal ring carrier. The air side and hydrogen
side real oil is admitted into the air side and hydrogen
side annular grooves, respectively, of the seal ring
via passage in the seal ring carrier and seal ring. A
continuous film of oil is maintained between the shaft
and the seal ring. The clearance between shaft and
seal ring is such that friction losses are minimized
and an oil film of sufficient thickness is maintains
without an unnecessarily large oil flow. Temperature
rise of the seal oil is therefore small which contributes
to reliable sealing. The babsitt lining of the seal ring
ensure high reliability even in the event of boundary
friction.
The air side seal oil pump delivers the oil at a
pressure maintained at >1.4 bar above the generator
hydrogen gas pressure at the shaft seal by means of
a differential pressure valve ("A" valve)
On the hydrogen side, the hydrogen-saturated seal
oi l is c i rculated in a c losed circui t . A pressure
equalizing valve maintains the oil pressure on the
hydrogen side slightly blow that on the air side, thus
keeping the interchange of oil between the air and
hydrogen sides to a very small value.
Air side seal oil for ring relief is fed to the annular
groove in the air side seal ring carrier and forced
between the seal ring and the seal ring carrier. In this
way the oil and gas pressure acting on the seal ring
are balanced, and the friction between the seal and
seal ring carrier is reduced. The seal ring is thus free
to adjust its radial position, Which is important during
the starting and shutdown period. The seal ring will
adjust its position according to the shaft position as
dictated by the oil film thickness and the vibratory
condition.
The seal ring need follow the axial displacement
of the generator shaft, which is primarily caused by
turbine expansion. The dishing permits the shaft to
slide through the seal ring without impairing the
sealing effect.
Turbo Generators
Description
BHEL, Hardwar
Shaft Seal
2.1-6001-0004/1
Turbo Generators
Description
Air
Hydrogenb
Air side seal oil
H2 side seal oil
Pressure oil for seal ring relief
BHEL, Hardwar 2.1-7100-0025/1
Seal Oil System
Shaft seals supplied with pressurized seal oil are
provided to prevent hydrogen losses at the shaft and
the ingress of air into the hydrogen-cooled generator.
Details of the shaft seal are given in a separate
description in this manual.
As long as the seal oil pressure in the annular
gap exceeds the gas pressure in the generator, no
hydrogen will escape from the generator housing.
The shaft seal is supplied with seal oil by a separate
system consisting of a hydrogen side seal oil circuit
and an air side seal oil circuit. The oil in the seal oil
system is the same as that used in the turbine-
generator journal shown.
1 Air Side Seal Oil Circuit
During normal operation, the air side ac pump
draws the seal oil from the seal oil storage tank and
feeds it to the shaft seals via coolers and filters. The
seal oil supplied to the shaft seals which drains
towards the air s ide through the annular gaps
between the shaft and seal rings is returned to the
seal oil storage tank.
For the air side seal oil circuit, three seal oil
pumps are provided with one of the three pumps
always in operation. In the event of a failure of the
pump in service due to a mechanical or electrical
failure, the second pump automatically takes over. If
both pumps fail, the seal oil supply is taken over by
the stand-by pump without any interruption.
2 Hydrogen Side Seal Oil Circuit
During normal operation, the hydrogen side pump
draws the seal oil from the seal oil storage tank and
feeds it to the shaft seal via coolers and filters. The
seal oil supplied to the shaft seals which drains
towards the hydrogen side through the annular gaps
between the shaft and the seal rings is first collected
in the generater prechambers and then returned to
the seal oil tank.
By dividing the seal oil system into two separate
circuits, the hydrogen losses at the seals are kept to
a minimum. Since the hydrogen side seal oil comes
into contact with only the hydrogen gas, it is saturated
with hydrogen and contains no air. Vacuum treatment
of the seal oil and the resulting continuous hydrogen
losses are thus avoided. The air side seal oil, which
is only in contact with air, becomes saturated with
air. By separating the two seal oil circuits, entry of air
to the hydrogen compartment is kept to a minimum
thereby maintaining good hydrogen purity.
One seal oil pump is used for oil circulation in the
hydrogen side oil circuit. In the event of a failure of
this pump, the seal oil to the hydrogen side annular
Turbo Generators
Description
2.1-7100-0025/2
gap is derived from the air side oil supply circuit.
When opera t ing i s th is manner , a s low
deterioration of the hydrogen purity in the generator
will take place, since the oil f lowing towards the
hydrogen side will introduce air, which will come out
of the oil in the hydrogen atmoshere due to the change
in pressures. In case of prolonged operation, it may
eventually become necessary to improve the hydrogen
purity by gas scavenging.
3 Seal Oil Prsessure Regulation
The air side and the hydrogen side seal oil circuits
are, hower, in contact in the annular gaps between
the shaft seal. The seal oil pressures at the shaft seal
are set so that the air side seal oil pressure is slightly
higher than the hydrogen side seal oil pressure.
Accordingly, a very small quantity of oil flows from
the air side to the hydrogen side in the annular gap
resulting in a gradual increase in the amount of oil in
the hydrogen side oil circuit. A float valve in seal oil
tank returns the excess oil to the seal oil stroge tank.
The interchange of oil between the two circuit is so
small that the aforementioned advantages of two
separate circuit are not impaired.
Oil pressures which exceed the generator gas
pressure are required to ensure proper sealing of the
generator. With the seal oil pumps in operation, the
seal oil pressure is controlled by differential pressure
valves "A" ("A" valve). The first "A" valve controls the
seal oil pressure after two equal-priority ac air side
seal oil pumps. The pressure after the standby seal
oil pump is separately controlled by the second "A"
valve. Depending on the valve setting and the singnal
o i l p ressure preva i l l ing (sea l o i l p ressure and
hydrogen casing pressure), a larger or smaller amount
of oil is returned to the suction pipe so that the
required seal oil pressures is established at the shaft
seals.
The function of the "A" valves is illustrated in the
attached diagram. Since the gas pressure and the
signal oil pressure act in opposite directions, the valve
stem is moved upwards or downwards when these
pressure become unbalanced. The valve cone is
arranged so that the valve c loses further for a
downward movement of the valve stem (occurs at
rising gas pressure or falling seal oil pressure). This
oil flow throttling results in a rise of the air side seal
oil pressure at the shaft seals. Setting of the desired
differential pressure (set valve) to be maintainde by
the valve is done by a coresponding preloading of the
main bellows. The preloading is adjusted with a
compression spring, the upper end of which is rigidly
connected to the valve yoke, while its lower end is
linked to the valve stem by means of an adjusting nut.
As may be seen on the at tached d iagram,
differentaial pressure valve "C" ("C" valve) serves to
control the seal oil pressure in the hydrogen side seal
oil circuit and operates on the same principle, with
the only difference being that the air side seal oil
pressures are used as singals.
The constant differential pressure between the air
s ide and the hydrogen side oi l is control led by
separate pressure equalizing control valves for each
shaft seal. The function of the pressure equalizing
control valve is illustrated in the attached diagram.
Due to the fact that the air side and hydrogen side
seal oil pressures act in opposite directioins, the valve
stem is moved upwards or downwards when these
pressures are unbalanced. The valve opens further
with a downward movement of the valve stem (occours
at rising air side seal oil pressure), resulting in a reise
of the hydrogen side seal oil pressure. Setting of the
desired differential pressure to be maintained by the
valve is done by a corresponding preloading of the
control piston.
4 Seal Oil Drains
The oil drains from the air side of the shaft seals
discharges to the generator beadring space and is
returnde to the turbine oil tank via the seal oil storage
tank together with the bearign oil.
The oil drained from the hydrogen side of the shaft
seals is discharged into the generator prechambers.
The prechambers reduce the oil flow which permits
the escape of entrained gas bubbles and defoaming
of the oil. Down-stream of the prechambers the oil
flows are combined and returned into the seal oil tank.
Float valves keep the oi l level in the tank at a
predetermined level. If an excessive amount of oil is
supplied to the seal oil tank, a float valve allows some
oil to return to the seal oil storage tank.
The small amount of hydrogen escaping from the
generator together with the oil does not present a
danger to the generator surrounding since the oil
drained on the hydrogen side is returned to the turbine
oil tank only via the seal oil storage tank where the
majority of the entrained hydrogen is removed. The
seal oil storage tank is connected to the bearing vapor
exhaus te rs wh ich a lso ven t the genera to r
prechambers.
5 Seal Ring Relief
To ensure free movement of the seal ringl, the
shaft seals are provide with pressure oil for ring relief.
The oil supply for ring relief is obtainde from the air
side oil circuit. The required pressure setting for each
shaft seal is accomplished separately.
BHEL, Hardwar
BHEL, Hardwar
BHEL, Hardwar 2.1-7104-0001/1
Pressure Equalizing Control ValveTurbo Generators
Description
BHEL, Hardwar 2.1-7101-0002/1
Differential Pressure Valve ATurbo Generators
Description
BHEL, Hardwar 2.1-7103-0002/1
Differential Pressure Valve CTurbo Generators
Description
BHEL, Hardwar 2.1-7111-7379/10197E
Seal Oil DiagramList of Valves For Seal Oil System
Turbo Generators
Description
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
1 MKW 01 Gate Vlave 80 2.5 CS FL Shut off Seal Oil Pumps Pipe LineAA 503
2. MKW 01 Needle Valve 15 2.5 CS SC Shut Off Valve For SOST Pipe LineAA 505 Drain
3. MKW 01 Needle Valve 15 2.5 CS SC Shut Off Valve in U Loop Pipe LineAA 505 Drain
4. MKW 03 Float Valve 50 1.6 CS FL Float Valve For Seal Oil Seal Oil UnitAA 001 Tank Drain
5. MKW 03 Float Valve 50 1.6 CS FL Float Valve For Seal Oil Seal Oil UnitAA 022 Tank, Supply From Air Side
Circuit
6. MKW 03 Gate Valve 50 4.0 CS FL Shut Off Valve in Drain Seal Oil UnitAA 501 Line of Seal Oil Tank Circuit
7. MKW03 Gate Valve 50 4.0 CS FL Shut Off Valve For Seal Seal Oil UnitAA 503 Seal Oil Drain Loop
8. MKW 03 Needle Vlave 15 2.5 CS SC Drain Valve For H2 Side Pipe LineAA 503 Seal Oil Drain Loop
9. MKW 03 Gate Valve 50 4.0 CS FL Shut Off Valve in Drain Seal Oil UnitAA 504 By Pass lIne at Seal Oil
Tank
10. MKW 03 Globe Valve 20 2.5 CS FL Shut Off Valve For Oil Seal Oil UnitAA 505 Level Indicator For Seal
Oil Tank
11. MKW 03 Globe Valve 20 2.5 CS FL Shut Off Valve For Oil Seal Oil UnitAA 506 Level Indicator, Bottom
12 MKW 11 Relief Valve 20 2.5 cs FL Relief Valve For AC Seal Oil Seal Oil UnitAA 001 Pump-1 (Air Side)
13 MKW 11 Diff. Pressure 25 1.6 CS FL For Maintaining Constant Seal Oil UnitAA 002 Regulating Valve Pressure Difference
14 MKW 11 Globe Valve 8 2.5 CS BW Seal Oil Impulse of DPRV Seal Oil UnitAA 507
15 MKW 11 Check Valve 50 4.0 CS FL Check Valve After AC Seal Seal Oil UnitAA 003 Oil Pump-1 (Air Side)
16 MKW 11 Gate Valve 50 4.0 CS FL Shut Off Valve in By Pass Seal Oil UnitAA 508 Line
17 MKW 11 Gate Valve 80 4.0 CS FL Inlet to Seal Oil Pump-1 S.O. Pump UnitAA 501 Air Side
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
18 MKW 11 Gate Vlave 50 4.0 CS BW Shut off Valve inOil Seal Oil UnitAA 505 DPRV
19 MKW 11 Gate Valve 10 2.5 CS BW Shut Off Valve in Oil Seal Oil UnitAA 506 Impule Line of DPRV
20 MKW 11 Shut Off Valve 50 2.5 CS FL Non Return Shut Off Valve Seal Oil UnitAA 004 After Air Side Seal Oil
Pump-1 & 2
21 MKW 11 Gate Valve 50 4.0 CS FL Shut Off Valve Before Seal Oil UnitAA 504 DPRV
22 MKW 13 Relief Valve 20 2.5 CS FL Relief Volve For Seal Seal Oil Pump UnitAA 001 Oil Pump (H2 Side)
23 MKW 13 Diff. Pressure 25 1.6 CS FL For Maintaining Constant Seal Oil UnitAA 002 Regulating Valve Pressure Difference
24 MKW 13 Check Valve 50 4.0 CS FL Check Valve After H2 Side Seal Oil UnitAA 003 Seal Oil Pump
25 MKW 13 Gate Valve 50 4.0 CS FL Shut Off Valve Before H2 Seal Oil UnitAA 501 Side Seal Oil Pump
26 MKw 13 Gate Valve 50 4.0 CS FL Shut Off Valcve For Seal Seal Oil UnitAA 503 Oil Before H2 Side Coolers
27 MKW 13 Globe Balve 10 2.5 CS BW Shut Off Valve in Air Side Seal Oil UnitAA 505 Impulse Line
28 MKW 13 Globe Valve 50 4.0 CS FL Shut Off Valve in H2 Side Seal Oil UnitAA 511 Seal Oil Drain Line
29 MKW 13 Globe Valve 10 2.5 CS BW Equalising Valve in Bypass Seal Oil UnitAA 507 of Impulse Line
30 MKW 13 Needle Valve 8 2.5 CS BW Seal Oil Vent Valve at Seal Oil UnitAA 508 DPRV (Air Side)
31 MKW 13 Globe Valve 8 2.5 CS BW Seal Oil Vent Valve at Seal Oil UnitAA 509 DPRV (H2 Side)
32 MKW 13 Gate Valve 25 4.0 CS FL Shut Off Valve in H2 Side Seal Oil UnitAA 510 DPRV Bypass Line to S.O.T.
33 MKW 13 Globe Valve 10 2.5 CS BW Shut of Vlave in H2 Side Seal Oil UnitAA 506 Impulse LIne
34 MKW 21 Relief Valve 20 0.0 CS FL Relief Valve For Seal Oil S.O. Pump UnitAA 001 Pump-2 (Air Side)
35 MKW 21 Check Valve 50 4.0 CS FL Check Valve After Seal Oil Seal Oil UnitAA 002 Pump-2 (Air Side)
36 MKW 21 Gate Valve 80 4.0 CS FL Inlet to Seal Oil Pump-2 S.O. Pump UnitAA 501 (Air Side)
2.1-7111-7379/20197E
BHEL, Hardwar
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
37 MKW 21 Gate Vlave 50 4.0 CS FL Air Side & H2 Side Oil Seal Oil UnitAA 503 Interconnection
38 MKW 23 Globe Valve 8 25.0 CS SC H2 Implulse to DPRV Seal Oil UnitAA 503
39 MKW 23 Globe Valve 8 25.0 CS SC H2 Impulse to DPRV Seal Oil UnitAA 504
40 MKW 31 Relief Valve 20 2.5 CS FL Relief Valve For Seal Oil S.O. Pump UnitAA 001 Pump-3 (Air Side)
41 MKW 31 Globe Valve 10 2.5 CS BW Shut Off Valve in Oil Seal Oil UnitAA 506 Impulse Line of DPRV
42 MKW 31 Diff. Pressure 25 1.6 CS FL For Mianitaining Constant Seal Oil UnitAA 002 Regulating Valve Pressure Difference
43 MKW 31 Globe Valve 8 2.5 CS BW Seal Oil IMpulse Vent of Seal Oil UnitAA 507 DPRV
44 MKW 31 N.R. Shut Off 50 2.5 CS FL Non Return shut Off Valve Seal Oil UnitAA 004 Valve After Air Side Seal Oil
45 MKW 31 Gate Valve 50 4.0 CS FL Shut Off Valve Before Seal Oil UnitAA 504 DPRV
46 MKW 31 Gate Valve 50 4.0 CS FL Shut Off Valve After DPRV Seal Oil UnitAA 505
47 MKW 31 Check Valve 50 4.0 CS FL Check Valve After Seal Oil Seal Oil UnitAA 003 Puni-3 (Air Side)
48 MKW 31 Gate Valve 80 4.0 CS FL Inlet to Seal Oil Pump-3 S.O. Pump UnitAA 501 (Air Side)
49 MKW 51 Double Change 50 1.6 CS FL Change Over Valve at Seal Oil UnitAA 501 Over Valve Seal Oil Cooler (Air Side)
50 MKW 51 Double Change 50 1.6 CS FL Change Over Valve at Seal Oil UnitAA 502 Over Valve Seal Oil Cooler (Air Side)
51 MKW 51 Globe Valve 8 2.5 CS BW Filler Valve For Air Side Seal Oil UnitAA 503 Seal Oil Cooler
52 MKW 51 Globe Valve 8 2.5 CS BW Seal Oil Drain Valve at Seal Oil UnitAA 504 Air Side Cooler-2
53 MKW 51 Globe Valve 8 2.5 CS BW Seal Oil Drain Valve at Seal Oil UnitAA 505 Air Side Cooler-1
54 MKW 51 Water Valve 8 2.5 CS BW Cooling Water Drain Valve Seal Oil UnitAA 506 at Cooler-2 (Air Side)
55 MKW 51 Double Change 50 1.6 CS FL Change Over Valve For Seal Seal Oil Unit With FiltyerAA 512 Over Valve Oil Filter-1 (Air Side)
2.1-7111-7379/30197E
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
56 MKW 51 Double Change 50 1.6 SC FL Change Over Valve For Seal Seal Oil Unit With FilterAA 513 Over Valve Oil Filter-2 (Air Side)
57 MKW 51 Globe Valve 8 2.5 CS BW Cooling Water Vant Valve Seal Oil UnitAA 508 at Cooler-2 (Air Side)
58 MKW 51 Globe Valve 8 2.5 CS BW Seal Oil Vent Valve From Seal Oil UnitAA 510 at Cooler-2 (Air Side)
59 MKW 51 Globe Valve 8 2.5 CS BW Seal Oil Vent Valve From Seal Oil UnitAA 511 at Cooler-1 (Air Side)
60 MKW 51 Globe Valve 8 2.5 CS BW Cooling Water Drain Valve Seal Oil UnitAA 507 at Cooler-1 (Air Side)
61 MKW 51 Globe Valve 8 2.5 CS BW Cooling Water Vent Valve Seal Oil UnitAA 509 at Cooler-1 (Air Side)
62 MKW 53 Double Change 50 1.6 CS FL Change Over Valve at Seal Oil UnitAA 501 Over Valve Seal Oil Cooler (H2 Side)
63 MKW 53 Globe Valve 8 2.5 CS BW Change Over Valve at Seal Oil UnitAA 502 Over Valve Seal Oil Cooler (H2 Side)
64 MKW 53 Globe Valve 8 2.5 CS BW Filler Valve For H2 Side Seal Oil UnitAA 503 Over Valve Seal Oil Cooler
65 MKW 53 Globe Valve 8 2.5 CS BW Seal Oil Drain Valve at H2 Seal Oil UnitAA 504 Side Cooler-2
66 MKW 53 Globe Valve 8 2.5 CS BW Seal Oil Drain Valve at H2 Seal Oil UnitAA 557 Side Cooler-1
67 MKW 53 Needle Valve 8 2.5 CS BW Cooling Water Drain Valve Seal Oil UnitAA 506 at Cooler-2 (H2 Side)
68 MKW 53 Double Change 50 1.6 CS FL Change Over Valve for Seal Seal Oil Unit With FilterAA 513 Over Valve Oil Filter-2 ( H2 Side)
69 MKW 53 Globe Valve 8 2.5 CS BW Cooling Water Drain Valve Seal Oil UnitAA 507 at Cooler-1 (H2 Side)
70 MKW 53 Globe Valve 8 2.5 CS BW Cooling Water Vent Valve Seal Oil UnitAA 509 at Cooler-1 (H2 Side)
71 MKW 53 Globe Valve 8 2.5 CS BW Seal Oil Vent Valve Seal Oil UnitAA 510 at Cooler-1 (H2 Side)
72 MKW 53 Globe Valve 8 2.5 CS BW Seal Oil Vent Valve Seal Oil UnitAA 511 at Cooler-1 (H2 Side)
73 MKW 53 Double Change 50 1.6 CS FL Change Over Valve for Seal Seal Oil UnitAA 512 Over Valve Oil Filter-1 ( H2 Side)
74 MKW 53 Globe Valve 8 2.5 CS BW Cooling Water Vent Valve Seal Oil UnitAA 508 at Cooler-2 (H2 Side)
2.1-7111-7379/40197E
BHEL, Hardwar
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
75 MKW 71 3-Way Valve 50 1.6 CS FL 3-Way Valve, TE (Air Side) S.O. Valve RackAA 511
76 MKW 71 Gate Valve 50 4.0 CS FL Shut Off Valve For Seal S.O. Valve RackAA 512 Oil, TE (Air Side)
77 MKW 71 Gate Valve 10 2.5 CS BW Shut Off Valve in Seal Oil S.O. Valve RackAA 512 Imppulse Line, TE (Air Side)
78 MKW 71 3-Way Valve 8 2.5 CS BW Vent For Equalising Valve S.O. Valve RackAA 514 TE (Air Side)
79 MKW 71 3-Way Valve 50 1.6 CS FL 3-Way Valve, EE (Air Side) S.O. Valve RackAA 521
80 MKW 71 Gate Valve 50 4.0 CS FL Shut Off Valve For Seal S.O. Valve RackAA 522 Oil, EE (Air Side) Thro’FM
81 MKW 71 Globe Valve 10 2.5 CS BW Sjit Pff Va;ve om Sea; Po; S.O. Valve RackAA 523 Impulse Line EE (Air Side)
82 MKW 71 Globe Valve 8 2.5 CS BW Vent For Equalising Valve S.O. Valve RackAA 524 EE (Air Side)
83 MKW 71 Needle Valve 15 2.5 CS SC First Shut Off Valve For Pipe LineAA 551 Pr. Measurement Before Air
Side Manifold
84 MKW 71 Needle Valve 15 2.5 CS SC First Shut Off Valve For Pipe LineAA 552 Air Side Seal Oil Pressure
Measurement, EE
85 MKW 71 Needle Valve 15 2.5 CS SC First Shut Off Valve For Pipe LineAA 553 Air Side Seal Oil Pressure
Measurement, EE
86 MKW 73 Equalising 50 2.5 CS FL Equalising Valve For Seal S.O. Valve RackAA 011 Valve Oil Pressure, TE (H2 Side)
87 MKW 73 Equalising 50 2.5 CS FL Equalising Valve For Seal S.O. Valve RackAA 021 Valve Oil Pressure, TE (H2 Side)
88 MKW 73 3-Way Valve 50 1.6 CS FL 3-Way Valve, TE (H2 Side) S.O. Valve RackAA 511
89 MKW 73 Gate Valve 50 4.0 CS FL Shut Off Valve For Seal S.O. Valve RackAA 512 Oil, TE (H2 Side)
90 MKW 73 Globe Valve 8 2.5 CS BW Vent For Equalising Valve S.O. Valve RackAA 513 Impulse Line, TE (H2 Side)
91 MKW 73 Globe Valve 8 2.5 CS BW Vent For Equalising Valve S.O. Valve RackAA 514 TE (H2 Side)
92 MKW 73 3-Way Valve 50 1.6 CS FL 3-Way Valve, EE (H2 Side) S.O. Valve RackAA 521
93 MKW 73 Gate Valve 50 4.0 CS FL Shut Off Valve For Seal S.O. Valve RackAA 522 Oil, EE (H2 Side)
2.1-7111-7379/50197E
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
94 MKW 73 Globe Valve 10 2.5 CS BW Shut Off Valve in Seal Oil S.O. Valve RackAA 523 Inpulse Line, EE (H2 Side)
95 MKW 73 Globe Valve 8 2.5 CS BW Vent For Equalising Valve S.O. Valve RackAA 524 EE (H2 Side)
96 MKW 76 3-Way Valve 25 1.6 CS FL Multiway Shut Off Valve S.O. Valve RackAA 511 For R.R. Flow Meters (TE)
97 MKW 76 Gate Valve 25 4.0 CS FL Shut Off Valve After S.O. Valve RackAA 512 R.R. Flow Meter (TE)
98 MKW 76 Regulating 25 4.0 CS FL Regulating Valve For S.O. Valve RackAA 513 Valve Ring Relief Oil, TE
99 MKW 76 3-Way Valve 25 1.6 CS FL Multiway Shut Off Valve S.O. Valve RackAA 521 For R.R. Flow Meters (EE)
100 MKW 76 Gate Valve 25 4.0 CS FL Shut Off Valve After S.O. Valve RackAA 522 R.R. Flow Meter (EE)
101 MKW 76 Regulating 25 4.0 CS FL Regulating Valve For S.O. Valve RackAA 523 Valve Ring Relief Oil, TE
102 PGB 51 3-Way Valve 65 1.6 CS FL 3-Way Valve f=For Cooling Seal Oil UnitAA 501 Water Inlet (H2 Side)
103 PGB 52 Regulating 65 1.6 CS FL Regulating Valve After Seal Oil UnitAA 501 Valve Seal Oil Cooler-1, H2 Side
104 PGB 52 Regulating 65 1.6 CS FL Regulating Valve After Seal Oil UnitAA 502 Valve Seal Oil Cooler-2, H2 Side
105 PGB 61 3-Way Valve 65 1.6 CS FL 3-Way Valve f=For Cooling Seal Oil UnitAA 501 Water Inlet (H2 Side)
106 PGB 62 Regulating 65 1.6 CS FL Regulating Valve After Seal Oil UnitAA 501 Valve Seal Oil Cooler-1, H2 Side
107 PGB 62 Regulating 65 1.6 CS FL Regulating Valve After Seal Oil UnitAA 501 Valve Seal Oil Cooler-2, H2 Side
Legend
FL = FlangedSC = ScrewedCS = Carbon SteelSS = Stainless SteelCA = Cast Stell
2.1-7111-7379/60197E
BHEL, Hardwar 2.1-7120-0004/1
Bearing Vopor Exhauster
The bearing vapour exchauster establishes a
vacuum in the generator bearing compartments
which prevents the escape of oil from the bearing
compartments along the shaft . In addit ion, the
bearing vapour exhausted draws off any hydrogen
gas wh ich may be admi t ted in to the bear ing
compartments in the event of a shaft seal failure.
The bearing vapour exhauster embodies optimum
safeguards permitting it to be used for extracting
hydrogen gas from the bearing compartments.
The exchauser is driven by a three-phase motor
attached perpendicular to the exhauster housing.
Flanged connections are provided for the suction and
delivery pipes.
The fan impeller is directly mounted on the motor
shaft. The shaft is sealed with a double-acting
grease-lubricated axial seal which works via a
packing washer which is forced in the axial direction
against the seal collar. A spring provides for a highly
flexible seal.
1 Drive motor
2 Regressing device
3 Suction branch
4 Delivery branch
Fig.1 Bearing Vapour Exchauster
1 Packing washer
2 Seal collar
3 Motor shaft
4 Motor flange
5 Regressing device
6 Exhauster housing
7 Fan ampler
Fig.2 Bearing Vapour Exhauster
BHEL, Hardwar 2.1-7123-0005/1
Seal Oil Pumps
1 General
Oil lubricated radial seals at the rotor shaft ends
prevent the hydrogen gas from escaping from the
generator to the atmosphere.
Seal oil pumps are used to supply the seal oil to
the shaft seals in a closed circuit.
1 Idler screw
2 Driving rotor
3 Dummy pastor
4 Shaft seal (sliding ring gland)
Fig.1 Screw Pump With Relief Valve
2 Construction and Mode of Operation
The seal oil pumps are three-screw pumps. One
double-thread driving rotor and two driven idler screw
dare closely meshed and run with a close clearance
in the casing insert. The pump casing accommodates
the casing insert and is closed off by covers at the
drive end and nondriver end.
The crew pump is suitable for rigorous service and,
due to the absence of control parts sensitive to dirt,
a l lows for relat ively large var iat ions of seal oi l
viscosity.
High speeds are readily attainable because all
moving parts perform rotary movements only.
The main components of the pump are illustrated
in the sectional view of a screw pump.
By internalising, the helical passages in the rotors
are divided into compartments completely sealed
which, while rotating progress completely uniformly
and without undue stressing from the suction to the
discharge end, thus acting like a piston. Dummy
pistons compensate for the axial thrust on the thread
flank faces at the discharge end. Axial thrust on the
deep-groove ball bearing is thus eliminated.
The idler screw are hydraulically driven due to
suitable screw dimensioning. The thread f lanks
transmit only the torque resulting from fluid friction,
which ensures very quiet running.
The screw pumps are driven by electric motors
through a coupling. The motor speed and rating are
matched to the expected delivery flow and heads.
BHEL, Hardwar 2.1-7130-0003/1
Seal Oil Cooler and Seal Oil Filter
1 Seal Oil Coolers
The air side and hydrogen side oil coolers are
each fu l l - capac i t y coo le rs . One i s a lways in
operation, while the second one serves as a stand-
by. The seal oil flow can be changed over from one
cooler to the other by means of two interlocked three-
way rotary transfer valves.
2 Seal Oil Filters
The seal oil filters are arranged directly after the
seal oil coolers. The filters have a fine mesh screen
which serves to prevent damage to the shaft seals
by foreign particles entrained in the oil. By connecting
two separate filters in series, one if the two filters
can always be maintained in operation, supplying
filtered oil to the shaft seals. The changeover valve
assembly at the filters allows one filter to be out of
service for cleaning without interruption of the oil
flow.
1 Filter housing 5 Valve lever
2 Differential pressure 6 Transfer valve assembly
indicator
3 Valve assembly 7 P r e s s u r e
equalizing valve
4 Oil outlet flange 8 P o s i t i o n
indicator
Fig.1 Seal Oil Filter
BHEL, Hardwar
Seal Oil Filter
2.1-7132-0005/1
1 Position indicator 8 Drain plug2 Eyebolt 9 Changeover valve assembly3 Filter valve 10 Oil outlet flange4 Strainer 11 Valve lever5 Filter houshing 12 Oil inlet flange6 Support 13 Signal line for differential7 Vent plug Pressure
BHEL, Hardwar
1. General
The pressures of the hydrogen side and air side sealoil circuits are applied to dirrerential pressuremeasurement devices. A complete system formeasurement of the seal oil differential pressuresconsists of the following components.
Differential pressure transmission linesEqualizing valve assamblyDufferential pressure gauges
The seal oil pressurs are transmitted to the
Differential Pressure Meter SystemTurbo Generators
Description
2.1-7150-0012/1
diaphragms of the pressure gauges via the transmissionlines and equalizing valve assembly. Vents are providedat the pressure gauges.
2. Dirrerential Pressure Meters for Direct Indication
The two input pressures to be compared act on thediaphragms on bothe sides, With the force set up by thedifferential pressure producing a deflection of the elasticbody. The resulting movement is transmitted to thepointer mechanism for direct indication of the differentialpressure. The point has a deflection of 270 degrees.
BHEL, Hardwar
Gas SystemTurbo Generators
Description
2.1-7200-0027/10999E
1. GeneralThe gas system consists of the following
components :
CO2 bottle rack
H2 bottle rack
N2 bottle rack
Gas dryerGas valve rack
The design of the gas system complies withthe safety regulations according to VDE 0530.Part 3 and with the German pressure vesselcode.
2. Hydrogen SupplyThe hydrogen for the generator is supplied
from a hydrogen bottle rack. The hydrogenshould have a minimum purity of 99.7 %.
2.1 H2 Bottle Rack
The H2 bottles are connected to the manifoldon the bottle rack. Valves on the bottles andvalves on the manfold allow replacement ofindividual bottles during operation. The hydrogenis stored in the steel bottles at a very highpressure. The hydrogen gas available in themanifold at bottle pressure is passed to twoparal lel-connected pressure reducers forexpansion to the required intermediate pressureand is then passed to pressure reducers on thegas valve rack for expansion to the pressurerequired for generator operation. Relief valveson the low-pressure sides of all pressurereducers are connected to an outlet pipe systemthrough which any excess hydrogen is passedto the atmosphere. All pressure reducers are ofidentical design. Single-stage construction of thepressure reducers ensures a constant pressure,even under low or no flow conditions, and allowslarge volume flow quantities of hydrogen to bereduced in pressure during the hydrogen fillingprocedure.
3. Carbon Dioxide SupplyAs a precaution against explosive mixtures,
air must never be directly replaced with hydrogenduring generator filling not the hydrogen replaceddirectly with air during the emptying procedure.In both cases, the generator must be scavengedor purged with an inert gas, carbon dioxide(CO
2)
being used for this purpose.
3.1 CO2 Bottle Rack
The carbon dioxide is supplied in steel bottlesin the liquid state. The bottles should be providedwith risers to ensure complete emptying. Thearrangement of the CO
2 bottle rack corresponds
to that of the H2 bottle rack. The liquid CO
2, which
is stored under pressure, is fed to the gas valverack via a shutoff valve.
3.2 CO2 Flash Evaporator
At the gas valve rack the liquid CO2 is
evaporated and expanded in a CO2 f lash
evaporator. The heat for vaporization is suppliedto the flash evaporator electrically. A temperaturecontrol is provided so that freezing of the flashevaporator is prevented, and the CO
2 is admitted
into the generator at the proper temperature. Onesafety valve each on the high-pressure and low-pressure sides protects the pipe system againstinadmissible high pressure.
4 Compressed air SupplyTo remove the CO
2 from the generator, a
compressed air supply with compressed air filteris connected to the general air system of thepower plant.
Under all operating conditions, except forCO2 purging, the compressed air hose betweenthe filter and the generator pipe system shouldbe disconnected. This visible break is to ensurethat no air can be admitted into a hydrogen-filledgenerator.
5. Gas Valve Rack andGas Monitoring Equipment
5.1 Gas Valve RackTo aid in operation of the gas system, the
gas valve rack is furnished with a mini diagramon the face of the panel.
The valves used in the gas system haverubber/metal-sealed valve seats to ensure gastightness.
5.2 Casing Pressure MeasurementFor measuring and checking the gas pressure
in the generator, the gas rack is provided with apressure transmitter and pressure gauges forlocal measurement. For safety, the pressuretransmitter is of an explosion proof design.
2.1-7200-0027/20999E
5.3 Electrical Purity meter SystemThe transmitter for the CO
2/H
2 purity meter
system on the gas valve rack is also of anexplosion proof design. The meter systemoperates on the thermal conductivity method. Themeter system measures the H
2 content of the gas
in the generator as well as the composition ofgas mixtures (CO
2/air and H
2/CO
2) during filling
and emptying of the generator.
5.4 Mechanical Purity Meter SystemThe second puri ty meter system is a
mechanical type and uses the physicalrelationships between the hydrogen pressure, thespeed of the generator fan, and the specificgravity of the medium. This meter system,therefore, functions only at rated speed.
5.5 Gas AnalysisIn addition, facilities are provided for gas
sampling for chemical analysis of the gas in thegenerator.
6. Gas DryerA small amount of the hydrogen circulating
in the generator for cooling is passed through agas arier. The gas inlet and gas outlet pipes ofthe gas dryer are connected at points of thegenerator with different static heads(differentialfan pressure), so that the gas is forced throughthe dryer by the differential pressure only.
The gas dryer is a pressure- resistantchamber filled with moisture absorbent material.The absorbent material can be reactived at anytime when the generator is running by means ofa heater, a fan and changeover valves.
7. Nitrogen(N2 ) SupplyOn a water-cooled turbine generator an
additional nitrogen supply is required for:
* Removing the air above the water level in theprimary water tank during initial operation of
the primary water system.* Removing the oxygen dissolved in the
primary water during filling of the primarywater system.
* Removing the hydrogen gas above the waterlevel in the primary water tank duringshutdown of the primary water system
* Removing the hydrogen gas dissolved in theprimary water during shutdown of the primarywater system.
The N2 purge during initial operation ensures
a complete removal of the oxygen from theprimary water circuit, thus eliminating the risk ofcorrosion attack.
The N2 purge during shutdown prevents the
formation of an explosive hydrogen-air mixtureDuring operation hydrogen may enter into theprimary water tank by diffusion at the insulatinghoses.
The nitrogen available from a bottle is passedto a pressure reducer for expansion and admittedinto the primary water tank via the N
2 supply line.
BHEL, Hardwar
BHEL, Hardwar
BHEL, Hardwar
Gas Diagram
List of Valves for Primary Water System
Turbo Generators
Description
2.1-7211-379/1 0197E
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
1 MKG 05 Globe Valve 15 4.0 CR SC To Mechnaical H2 Purity Pipe LineAA 501 Meter
2 MKG 05 Globe Valve 15 4.0 CR SC To Mechnaical H2 Purity Pipe LineAA 502 Meter
3 MKG 09 Globe Valve 15 4.0 CR SC To Core Monitor Pipe LineAA 520
4 MKG 09 Globe Valve 15 4.0 CR SC To Core Monitor Pipe LineAA 521
5 MKG 11 Globe Valve 8 25.0 CR SC Shut Off at Inlet to H2 DistributerAA 561 MKG 11/AA001
6 MKG 11 Monifold Valve 8 25.0 CR SC H2 Distributer Manifold H2 DistributerAA 531
7 MKG 12 Globe Valve 8 25.0 CR SC Shut Off at Inlet to H2 DistributerAA 501 MKG 12/AA001
8 MKG 15 Globe Valve 25 2.5 CR SC Shut Off at Inlet to Gas UnitAA 502 MKG 19/AA001
9 MKG 15 Globe Valve 25 2.5 CS SC For Connecting H2 Duistri Gas UnitAA 504 buter to Gas Unit
10 MKG 15 Globe Valve 25 2.5 CR SC Shut Off at Outlet From H2 DistributerAA 501 MKG 12/AA001
11 MKG 16 Globe Valve 25 2.5 CR SC Shut Off at Outlet From H2 DistributerAA 501 MKG 12/AA001
12 MKG 17 Globe Valve 25 2.5 CR SC For Connecting Gas Unit to Gas UnitAA 504 Station H2 Plant
13 MKG 17 Globe Valve 25 2.5 CR SC Shut Off at Inlet to Gas UnitAA 506 MKG 19/AA002
14 MKG 19 Globe Valve 25 2.5 CR SC Shut Off at Inlet From Gas UnitAA 501 MKG 19/AA001
15 MKG 19 Globe Valve 25 2.5 CR SC Shut Off at Inlet From Gas UnitAA 502 MKG 19/AA002
16 MKG 25 3-Way Valve 50 1.6 CR FL Shut Off to H2 Supply to Gas UnitAA 519
17 MKG 25 Globe Valve 50 2.5 CR FL Exhaust Gas UnitAA 502
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
18 MKG 25 Globe Valve 25 2.5 CR SC Shut Off at Inlet to AF Gas UnitAA 501
19 MKG 25 Globe Valve 8 25.0 CR SC Shut Off at Inlet to Gas Gas UnitAA 511 Analyser Cabinet
20 MKG 25 Globe Valve 8 25.0 CR SC For Taking Sample of Gas Gas UnitAA 512 Analyser Cabinet
21 MKG 25 3-Way Valve 50 1.6 CR FL Shut Off CO2 Supply to Gas UnitAA 518 Exhaust From TG
22 MKG 25 3-Way Valve 12 1.6 CR SC For Calibration of Gas Gas UnitAA 507 Analyser
23 MKG 25 Globe Valve 25 2.5 CS SC Shut Off at Outlet to AF Gas UnitAA 509
24 MKG 31 Gate Valve 8 25.0 CR SC Inlet to Pressure N2 DistributerAA 503 Regulator
25 MKG 31 Globe Valve 8 25.0 CR SC N2 Distributer Manifold N2 DistributerAA 502
26 MKG 35 Globe Valve 8 25.0 CR SC Outlet of Pressure N2 DistributerAA 501
27 MKG 31 Globe Valve 8 25.0 CR SC CO2 Distributer Manifold CO2 DistributerAA 531
28 MKG 51 Globe Valve 10 25.5 CR SC Shut Off at Inlet to CO2 CO2 VapouralserAA 561 Vapouralser
29 MKG 51 Sefety Relief 6 17.5 CS SC To Release Excess CO2 CO2 VapouralserAA 011 Valve Pressure at Inlet to
CO2 Vapouralser
30 MKG 59 Safety Relief 32 0.6 CS FL To Release Excess Co2 CO2 DistributerAA 001 Valve Pressure at CO2 Vapouriser
Outlet
31 MKG 69 Gas Valve 50 1.6 CS FL Shut Off at Inlet to Gas Pipe LineAA 501 Drier
32 MKG 69 Gas Valve 50 1.6 CS FL Shut Off at Intlet to Gas Pipe LineAA 504 Drier
33 MKG 69 Gas Valve 50 1.6 CS FL Shut Off at Outlet to Gas Pipe LineAA 505 Saparator in Gas Drier
Inlet Line
34 MKG 69 Gas Valve 15 1.6 CS SC Shut Off in Saparator Pipe LineAA 502 Drain
35 MKG 69 Globle Valve 8 25.0 CR SC Sampling Gas at Drier Gas UnitAA 503 Inlet Line
36 MKG 69 Non Return 50 1.6 CS FL Non Return in Air Line to Gas UnitAA 527 Valve Drying Tower
2.1-7211-379/2 0197E
BHEL, Hardwar
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO.DESG BORE PRESS MATL CONN
MM MPA
37 MKG 69 3-Way Double 50 1.6 CS FL Shut Off at Intlet to Gas Pipe LineAA 502 C/O Valve Drier
38 MKG 69 3-Way Double 50 1.6 CS FL Shut Off at Intlet to Gas Pipe LineAA 529 C/O Valve Drier
2.1-7211-379/3 0197E
Legend
FL = Flanged RT = Room TemperatureSC = ScrewedCS = Carbon SteelCR = Cromium SteelGM = Gun Metal
BHEL, Hardwar 2.1-7230-0011/1
C02 Flash Evaporator
1 General
C02 is used to displace air from the generator
before hydraogen filling and to displace hydrogen
from the generator before filling the generator with
air.
Since the C02 is available in the liquid state, it
must be expanded into a gas before use. The C02 is
expanded in a C02
flash evaporator located on the
gas va lve rack .To p reven t i c ing o f the f lash
evaporeator it is electrically heated.
2 Design features and mode of operation
The C02
flash evaporator consists of a tubular
housing closed by flanges at both ends. One flange
carr ies electreical heat ing elements which are
connected to terminals in the terminal box mounted
external to the flange. The opposite flange contains
the inlet and outlet to the cooled copper pipe of the
evaporator. The horizonntally arranged housing is
filled with heat transmitting liquid to ensure a better
heat trasfer to the copper pipe coil and thus to the
C02 flowing through the pipe coil.
The heat transmitting liquid is filled into the C02
f lash evaporator through the expansion vessel
mounted on top of the housing. For protection against
excessive heating a thermostat maintaining a constant
temperature is arranged in the housing holding the
heat t ransmit t ing l iquid. For protect ion against
excessive pressures in the C02
line, one relief valve
is arranged before and after the C02 flash evaporator.
The orifice at the C02
out let of the expansion
vessel provides for an expansioin of the C02 obtained
from the bottles to a pressure of 25 to 7 psig. Heating
of the C02 in the copper pipe coil is sufficient to prevent
icing of the expansion device at the prevailling flow
velocities.
2.1-7230-0011/1
C02 Flash Evaporator
1 Thermometer 8 Shutoff valve before C0 2 flash evaporator2 Vent for heat transmitting liquid 9 C0
2 inlet
3 Copper pipe coil 10 C02 outlet
4 Insulation 11 Housing5 Expansioin vessel 12 Heating element6 Relief valve before C02 flash evaporator 13 Drain for heat transmitting liquid7 Thermostat 14 Terminal box
Fig.1 C02 flash evaporator
BHEL, Hardwar 2.1-7260-0019/1
Gas Dryer
Any possible moisture contained in the hydrogen
in the generator is removed by a gas dryer. A gas
f low, set up by the dif ferential pressure of the
generator fan, circulates hydrogen through the gas
dryer chamber which is filled with absorbent material.
The absorben t mate r ia l i s p rov ided w i th a
humidicator. A change in color (blue/pink) as seen
through the sight glass tells the operator when it is
necessary to change over the cock from the drying
to the heating position. The absorbent material can
be reactivated at any time by heated air which is
supplied by a heater and fan. The changeover valves
are coupled so as to avoid incorrect operation and
provided with a limit switch which activates the heater
and fan.
To waste gas system
1 Multi-way valve
2 Pressure large
3 Gas dryer chamber
with absorbent material
4 Gas dryer heater
5 Gas dryer fan
6 Air filter
Fig.1 Gas Dryer Schematic
An in termediate pressure re l ie f pos i t ion is
provided for changeover from the drying position to
the heating position. When the changeover valve is
moved to the pressure relief position, the hydrogen
gauge pressure is allowed to go the zero. Via a
pressure re l ie f ho le commun ica t ing w i th the
atmosphere.
A pressure gauge shows when the gas dryer is
depessurized. The changeover valve should then be
moved to the heating position.
Position of four-way valve during drying
BHEL, Hardwar
Pressure Equalizing Control Valve
2.1-7262-0001/1
1 Gas dryer heater2 Gas dryer fan3 Temperature transmitter, heater4 Connectionto atmosphere5 Pessure garge6 Gas outlet7 Changeover lever8 Gas inlet9 Temperature gauge10 Gas inlet11 Filter for hot inlet air12 Fan motor13 Sight glass with cover
Gas Dryer Type: 8.70
BHEL, Hardwar
1 General
The losses occurring in the
stator winding,
terminal bushings and
phase connectors
are dissipated through direct water cooling. Since
the cooling water is the primary coolant to dissipate
the losses, it is designated as primary water.
The primary water is circulated in a closed circuit
by centrifugal pumps.
The primary water system basically consists of
the following components:
Primary water supply unit
Primary water coolers
Primary water valve rack
Primary water tank
The primary water supply unit combines the following
components fo r p r imary wate r supp ly to the
generator:
Primary water pumps
Primary water filters
Conductivity transmitter
Water treatment system
Volume flow, pressure and temperature transmitters.
The complete primary water system, its components and
their relationship are shown in the Primary Water Diagram.
2 Primary Water Quality
The primary water system may be fi l led with
oxygen free, mechanically clean
Primary Water System
2.1-7300-0009/1
distilled water
fully demineralized water from boiler feed water
treatment plant
condensate
Since the primary water comes into direct contact
with the high-voltage stator winding, it must have an
electrical conductivity of 0.5 to 1 µmho/cm. The water
in the primary water circuit is therefore treated in a
water treatment system. Fully demineralized water
f rom the boi ler feed water t reatment p lant and
condensate may only be used if no chemicals. Such
as ammonia, hydrazine, phosphate, etc. were added
to the water or condensate.
3 Primary Water Circuit
Fig. 1 shows a simplified schematic of the primary
water system. Note that the diagram shows that the
external port ion of the system may be operated
through a bypass line, with no primary water flowing
through the water-cooled generator components.
The primary water is circulated by one of the two
pumps on the primary water supply unit. Both primary
water pumps are of full-capacity type. The electric
control circuit of the pumps is arranged so that either
pump may be selected for normal service.
The primary water is drawn from the primary water
tank and passes to a primary water manifold (inlet)
via coolers and filters and from there to the stator
bars via teflon hoses. The primary water leaving the
stator winding is passed through similar teflon hoses
to another primary water manifold (outlet) and is then
returned to the primary water tank. A separate flow
path from a point before the stator winding inlet cools
the bushings and phase connectors.
4 Primary Water Tank
The primary water tank is mounted on the stator
frame on antivibration pads and is covered by the
generator lagging. The purpose of the primary water
water tank is to remove the hydrogen in the primary
water after is leaves the stator winding. The hydrogen
occurs in the primary water due to diffusion through
the telflon hoses which connect the stator winding to
inlet and outlet manifolds.
Since the primary water tank is the lowest pressure
point in the system, has a relat ively high water
temperature, a large water surface and sufficient
retention time, intensive degassing of the primary
water is ensured. The hydrogen gas in the primary
water tank is vesnted to atmosphere via the primary
water valve rack and a pressure regulator. The
pressure regulator can be adjusted to set the gas
pressure in the primary water tank.
The water level in the primary water tank can be
read a t a wate r leve l gauge. Add i t iona l l y , a
capatitance type measuring system is provide for
activating an alarm at minimum and maximum water
level.
BHEL, Hardwar
BHEL, Hardwar
BHEL, Hardwar
Primary Water DiagramList of Valve for Primary System
2.1-7311-7422/1 0197 E
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO. DESG BORE PRESS MATL CONN
MM MPA
1 MKF 01 Water Vallve 20 1.6 SS FL Shut off Valve Before P.W.TankAA 321 Water Level Gauge, Top
2 MKF 01 Water Valve 20 1.6 SS FL Vent Valve at Level P.W.TankAA 251 Transmitter
3 MKF 01 Globe Valve 10 2.5 SS SC Drain Valve at Level P.W. TankAA 210 Trainsmitter
4 MkF 01 Water Valve 20 1.6 SS FL Shut off Valve Before P.W.TankAA 311 Water Level Gauge, Bottom
5 MKF 01 Water Valve 20 1.6 SS FL Shut off Valve Before P.W.TankAA 326 Level Transmitter, Top
6 MKF 01 Water Valve 20 1.6 SS FL Shutt off For Oulet From P.W.TankAA 301 Level Transmitter
7 MKF o1 Water Valve 20 1.6 SS FL Shutt off Valve For Inlet P.W. TankAA 316 Level Transmitter
8 MKF 01 Water Valve 20 1.6 SS FL Shutt off Valve For Inlet P.W.TankAA 306 tp Level Transmitter
9 MKF 12 Needle Valve 10 2.5 SS SC Drain Valve Before Pump-1 P&F UnitAA 502
10 MKF 12 Globe Valve 100 2.5 SS FL Outlet of Stator Water P&F UnitAA 504 Pump-1
11 MKF 12 Globe Valve 100 2.5 SS FL Inlet to Stator Water P&F UnitAA 501 Pump-1 MKF 12/AP001
12 MKF 12 Non Return 100 1.6 SS FL Non Return at Outlet of P&F UnitAA 001 Valve Stator Water Pump-1
13 MKF 22 Non Return 100 1.6 SS FL Non Return at Outlet of P&F UnitAA 001 Valve Stator Water Pump-2
14 MKF 22 Globe Valve 100 2.5 SS FL Inlet to Stator Water P&F UnitAA 501 Pump-2 MKF 22/AP001
15 MKF 22 Needle Valve 10 2.5 SS FL Drain Valve Before Pump-2 P&F UnitAA 502
16 MKF 22 Globe Valve 100 2.5 SS FL Outlet of Stator Water P&F UnitAA 504 Pump-2
17 MKF 52 Needle Valve 10 2.5 SS SC Primary Water Vent Valve Pipe LineAA 531 For Cooler-1
18 MKF 52 Needle Valve 15 2.5 SS SC Primary Water Vent Valve Pipe LineAA 541 Before Coolers
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO. DESG BORE PRESS MATL CONN
MM MPA
19 MKF 52 Needle Valve 15 2.5 SS SC Drain Valve at Filter-1 P&F UnitAA 581
20 MKF 52 Globe Valve 100 2.5 SS FL Primart Water Shut Off Pipe LineAA 512 Valve After Cooler-2
21 MKF 52 Needle Valve 10 2.5 SS SC Vent Valve at Filter-1 P&F UnitAA 582
22 MkF 52 Needle Valve 15 25.0 SS SC Cooleing Water Drain Valve Pipe LineAA 552 Cooler-2
23 MKF 52 Globe Valve 100 2.5 SS FL Primary Water Shut Off Pipe LineAA 502 Valve Before Cooler-2
24 MKF 52 Needle Valve 10 2.5 SS SC Cooleing Water Vent Valve Pipe LineAA 562 at Cooler-2
25 MKF 52 Needle Valve 15 2.5 SS SC Primary Water Drain Valve Pipe LineAA 544 (Manifold)
26 MKF 52 Globe Valve 100 2.5 SS FL Primary Water Shut Off Pipe LineAA 511 Valve Before Cooler-1
27 MKF 52 Needle Valve 10 2.5 SS SC Cooleing Water Vent Valve Pipe LineAA 561 at Cooler-1
28 MKF 52 Needle Valve 10 2.5 SS SC Primary Water Vent Valve Pipe LineAA 532 For Cooler-2
29 MKF 52 Globe Valve 100 2.5 SS FL Inlet to Water Filter-2 P&F UnitAA 590
30 MKF 52 Needle Valve 15 2.5 SS SC Drain Valve at Filter-2 P&F UnitAA 591
31 MKF 52 Needle Valve 10 2.5 SS SC Vent Valve at Filter-2 P&F UnitAA 592
32 MKF 52 Globe Valve 100 2.5 SS FL Outlet From Water Filter-2 P&F UnitAA 593
33 MKF 52 Globe Valve 100 2.5 SS FL Primary Water Shut Off Pipe LineAA 501 value Before Cooler -1
34 MKF 52 Needle Valve 15 2.5 SS SC Primary Water Drain Valve Pipe LineAA 522 For Cooler-2
35 MKF 52 Needle Valve 15 2.5 SS SC Primary Water Drain Valve Pipe LineAA 521 For Cooler-1
36 MKF 52 Needle Valve 15 2.5 SS SC Vent Valve After PW Pipe LineAA 578 Coolers
37 MKF 52 Globe Valve 100 2.5 SS FL Inlet to Water Filter-1 P&F UnitAA 580
38 MKF 52 Needle Valve 10 2.5 SS SC Primary Water Vent Valve Pipe LineAA 545 (Manifold)
39 MKF 52 Needle Valve 15 2.5 SS SC Cooling Water Drain Valve Pipe LineAA 551 at Cooler-1
2.1-7311-7422/2 0197 E
BHEL, Hardwar
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO. DESG BORE PRESS MATL CONN
MM MPA
40 MKF 52 Globe Vallve 100 2.5 SS FL Outlet From Water Filter-1 P&F UnitAA 583
41 MKF 60 Needle Valve 10 2.5 SS SC Drain Primary Water P&F UnitAA 522 Make UP Line
42 MKF 60 Needle Valve 10 2.5 SS SC Drain Valve After P&F UnitAA 510 ION-Exchanger
43 MkF 60 Globe Valve 25 2.5 SS FL Shut Off Valve in Make Up P&F UnitAA 506 Line
44 MKF 60 Needle Valve 10 2.5 SS SC Vent Valve at Fine Filter P&F UnitAA 512
45 MKF 60 Needle Valve 10 2.5 SS SC Vent Valve Before P&F UnitAA 503 ION-Exchanger
46 MKF 60 Needle Valve 10 2.5 SS SC Drain Valve For Water P&F UnitAA 517 Treatment System
47 MKF 60 Globe Valve 25 2.5 SS FL By Pass Valve in Make Up P&F UnitAA 520 Line
48 MKF 60 Needle Valve 10 2.5 SS SC Drain Velve After P&F UnitAA 511
49 MKF 60 Globe Valve 25 2.5 SS FL Shut Off Valve After P&F UnitAA 509 ION-Exchanger
50 MKF 60 Globe Valve 25 2.5 SS FL Shut Off Valve After Water P&F UnitAA 519 Treatment System
51 MKF 60 Regulating 25 2.5 SS SC Control Valve For Water P&F UnitAA 502 Valve Treatment System
52 MKF 60 Globe Valve 25 2.5 SS FL Make Up Drain Valve Pipe LineAA 201
53 MKF 60 Regulating 25 2.5 SS FL Make Up Drain Valve Pipe LineAA 501 Valve
54 MKF 60 Non Return 25 1.6 SS FL Check Valve in Make Up P&F UnitAA 003 Valve Line
55 MKF 60 Relief Valve 25 2.5 SS FL Relief Valve in Make Up P&F UnitAA 001 Line
56 MKF 60 Globe Valve 25 2.5 SS FL Shut Off Vavle After Fine P&F UnitAA 513 Filter
57 MKF 80 Globe Valve 100 2.5 SS FL Shut Off Vavle For Gen. P.W.TankAA 504 By Pass
58 MKF 80 Globe Valve 100 2.5 SS FL Shut Off in Main Circuit P.W.TankAA 503 Discharge Line
59 MKF 80 Globe Valve 100 2.5 SS FL Shut Off at Inlet to Gen. P.W.TankAA 121
2.1-7311-7422/3 0197 E
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO. DESG BORE PRESS MATL CONN
MM MPA
61 MKF 82 Globe Vallve 100 1.6 SS FL Shut Off Valve in Primary P.W.TankAA 001 Water Outlet of Stator
Winding62 MKF 82 Regulating 100 1.6 SS FL Regulating Valve Befofe Pipe Line
AA 501 Valve Stator Winding
63 MKF 82 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 504 Transmitter at Stator Outlet
64 MKF 82 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 505 Transmitter at Stator Outlet
65 MKF 82 Needle Valve 15 2.5 SS SC Shut Off Valve For Press. Pipe LineAA 506 Measurement Before Stator
Outlet Winding
66 MKF 82 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 507 Transmitter at Stator Outlet
67 MKF 82 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 508 Transmitter at Stator Outlet
68 MKF 82 Needle Valve 10 2.5 SS SC Isolation Valve For GeneratorAA 512 D.P. Gauge
69 MKF 82 Needle Valve 10 2.5 SS SC Isolation Valve For GeneratorAA 513 D.P. Gauge
70 MKF 83 Regulating 40 1.6 SS FL Regulating Valve Before Pipe LineAA 501 Valve Bushing
71 MKF 83 Globes Valve 40 1.6 SS SC Shut Off Valve After Pipe LineAA 502 Bushing
72 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 503 Trainsmitter MKF83/CF001A
73 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 515 Trainsmitter MKF83/CF001B
74 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 504 Trainsmitter MKF83/CF001A
75 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 516 Trainsmitter MKF83/CF011B
76 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 506 Trainsmitter MKF83/CF011A
77 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 517 Trainsmitter MKF83/CF021B
78 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 508 Trainsmitter MKF83/CF021A
79 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 514 Trainsmitter MKF83/CF001B
80 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 505 Trainsmitter MKF83/CF011A
81 MKF 83 Needle Valve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 507 Trainsmitter MKF83/CF021A
2.1-7311-7422/4 0197 E
BHEL, Hardwar
SL. VLV TYPE OF VALVE NOM. NOM. BODY END FUNCTION LOCATIOIN REMARKNO. DESG BORE PRESS MATL CONN
MM MPA
82 MKF 83 Needle Vallve 15 2.5 SS SC Shut Off Valve Before Flow Pipe LineAA 513 Transmitter MK83/CF001B
83 MKF 83 Needle Vallve 15 2.5 SS SC Shut Off Valve After Flow Pipe LineAA 518 Transmitter MK83/CF021B
84 PGB 71 Gate Vallve 250 1.6 CS FL Cooling Water Inlet of Pipe LineAA 501 Cooler-1
85 PGB 71 Gate Vallve 250 1.6 CS FL Cooling Water Inlet of Pipe LineAA 502 Cooler-2
86 PGB 72 Gate Vallve 250 1.6 CS FL Cooling Water Outlet of Pipe LineAA 501 Cooler-1
87 PGB 72 Gate Vallve 250 1.6 CS FL Cooling Water Outlet of Pipe LineAA 502 Cooler-2
Legend
FL = FlangedSC = ScrewedCS = Carbon SteelSS = Stainless SteelSS = Stainless SteelCA = Cast Steel
2.1-7311-7422/5 0197 E
BHEL, Hardwar
Design Features of Primary Water Pumps
The primary water for cooling the stator winding,
phase connectors and terminal bushings circulated
in a closed system. To insure uninterrupted generator
operation, two full-capacity primary water pump sets
are provided. Either pump can be in service with
other acting as the standby. The state by pump is
ready for service and is automatically started without
interrupting the primary water circulat ion i f the
operating pump fails.
The primary water pumps are of a single-stage
centrifugal type with spiral and overhung implore.
Primary Water Pumps
2.1-7320-0009/1
Fig.1 Sliding-Ring Gland
The pump suction is arranged axially. While the
discharge is directed radially upwards. The spiral
casing is flanged to the bearing housing. The pump
imperil is provided with relief holes close to the hub
so that no axial thrust is carried by the bearings. The
point where the pump shaft passes through the pump
casing is sealed by means of a water-cooler sliding-
ring gland. The cooling water is supplied to the sliding-
ring gland through a by pass line from the pump
discharge. The pump shaft is supported in o i l -
lubricated antifrictioin bearings. The oil level in the
bearing housing can be checked at an oil sight glass.
The pump is connected to the three-phase ac motor
by a flexible coupling covered by a coupling guard.
The sliding-ring gland consists of a stationary part,
which is rigidly connected to the pump casing, and
rotating part attached to the shaft. The contact face
between the two parts is the seal ing face. The
stationary part is connected to the pump insert and is
composed of the seal ring and the Z-ring. The ceramic
Z-ring face toward the rotating part is lapped. The
sliding ring of the rotating part is made of resin-
impregnated graphite. The face of the sliding ring is
likewise lapped. The saft rotation is transmitted to the
sliding ring through a bellows connected to the sliding
ring. Shaft sealing is accomplished by the rear portion
of the bellow which is fitted tightly on the shaft. The
shaft rotation is transmitted to the sliding ring by the
bellows catch ring and catch sleeve. The bellows is
pressed against the sliding ring by the compression
ring, and the sliding ring is pressed against the Z-
ring through a spring supported on the shaft collar.
The design of this sliding-ring gland permits a free
movement of the rotating sliding ring relative to the
Z-ring.
BHEL, Hardwar 2.1-7330-0008/1
Primary Water Cooler
The primary water cooler is of a straight tube
type. One tubesheet is stationary, while the other
tubesheet is a floating type. The floating tubesheet
is sealed by O-Ring.
Tube bundle is free to move in response to
temperature change.
The water channel at glands can be removed
without draining the primary water.
The tube bund le cons is ts o f round tubes
expanded into the tubesheets. Baffles installed on
the tube bundle result in a transverse flow of cooling
water across the tubes. This achieves a more
efficient heat exchange and protects the tubes from
vibrations and bending.
The cooler shell is stainless steel with welded
flanges for connection to the flanges on the water
channels. The pipe nozzles for the primary water inlet
and outlet are welded to the shell. Each cooler shell
has vent and drain connection.
To vent and drain the tube side of the primary
water coolers, the water channels are equipped with
vent and drain connections.
Tube bundle, cooler shell and water channels are
bolted together. The larger tubesheet is mounted
between the shell flange and the water channel.
The p r imary wate r coo le r sec t ions a re
inlerconnected on their primary water sides via valves.
BHEL, Hardwar
Primary Water Treatment SystemTurbo Generators
Description
2.1-7340-0002/10999E
The water treatment system serves tomaintain a low electrical conductivity of theprimary water. The water treatment system isconnected in parallel to main circuit and containsa mixed-bed ion exchanger with series connectedfine filter, an integrating flow meter and aconductivity transmitter.
1. Mixed-Bed Ion ExchangerThe mixed-bed ion exchanger consists of a
tank filled with anion and cation exchanger tankprevent the escape of the resins into the pipingsystem. A fine filter after the ion exchangerretains any resin particles. An alarm is initiatedwhen the filter is contaminated.
The water flow passing through the ionexchanger is measured by means of anintegrating flow meter after the filter. After theion exchanger part of the flow is passed througha conductivity transmitter for checking the resinactivity.
2. Ion Exchanger ResinsThe ion exchangers consist of chemically and
highly active synthetic resins.The base substances of the exchanger resins
are polymers. The polymer in the cat ionexchanger contains highly acid groups, while thepolymer in the anion exchanger is composed ofhighly basic groups.
The exchanger resins are thus capable ofaccepting ions from the primary water whilesimultaneously releasing equivalent amounts ofother ions(hydrogen ions from the cationexchanger and hydroxyl ions from the exchanger)to the primary water. This process takes placethrough the ion exchanger.
The combination of highly acid cationexchangers and highly basic cation exchangersforms a multitude of small demineralization units,resulting in a high-purity deionate.
The capacity of the mixed- bed of the ionexchanger is limited by the number of ion it canexchange. This capacity is primarily determinedby the type of exchanger used, but also dependson the quantity of reactivating agent, the rate offlow and the water temperature.
When the resins are exhausted, they mustbe replaced by new resins.
After removal from the primary watertreatment system, the resins can be reactivated.
3. Adding Make-up Water to the PrimaryWater Circuit
Any loss of primary water in the total circuitcan be compensated for by introducing make-upwater upstream of the mixed-bed ion exchanger.The quantity of make -up water is totaled at avolumetric water meter and is indicative of thetightness of the primary water system.
BHEL, Hardwar
1 GeneralEven with the use of oxygen-poor water, copper
corrosion in the primary water circuit water circuit ofwater-cooled windings cannot be completely avoided;in isolated cases the corrosion products reduce thecross-sectional flow area of the water distributionsystem. Bes ides, the format ion of conduct ivedesposite can occur in the rotating water inlet andoutlet hoses of water-cooled rotor windings.
The severity of the corrosion attack can be largelyreduced by alkalizing the oxygen-poor water. Also,the system becomes less susceptible to disturbancesresulting from air in-leakage.
Operating the generator with alkaline water at pH8 to 9 improves its reliability land availability.
Operation at alkaline pH is ensured by a self-regulating alkalizer unit for feeding dilute sodiumhydroxide solution (NaOH).
2 Mode of OperationDilute sodium hydroxide solution is injected into
the low-conductivity primary water circuit where itremain as dissolved, dissociated sodium hydroxidesolution. OH ion connectration determines the pHvalue.
The ion exchanger in the water treatment system,i.e. mixedbed filters with H+ cation exchangers andO H – an ion exchangers , rema ins in se rv icecontinuously. It removes all copper, iron, chloringe,carbon dioxide ions, etc. from the water, However, italso removes the Na+ ions from the sodium hydroxidesolut ion. This e l iminat ion of sodium, which isproportional both to the volumetric flow rate throughthe ion exchanger and the NaOH concentration, mustbe compensated by continuous feeding of dilutesodium hydroxide solution.
Alkalizer Unitfor Primary Water Circuit
2.1-7341-0009/1
The alkalizer unit is arranged in the treatmentcircuit Sodium hydroxide solution is injected into thetreatment circuit where it is mixed with the water inthe treatment circuit and raises its conductivity. Thewater has the h ighest pur i ty a t the feed po in tdownstream of the ion exchangers. The conductivityo f the mixed water i s on ly de termined by theconcentration of the sodium hydroxide solution andprovides a reference quantity for the pH valve. Therelationship between pH and conductivity under idealconditions is illustrated in Fig.1
Following the admission on alkaline water, theconductivity in the treatment circuit is monitored.Conductivity must be maintained constant as requiredfor obtaining the specified alkalinity. Conductivity inprimary water circuit likewise approaches a constantvalue after several hours.3 Hydraulic Circuit
The hydraul ic circuit of the alkal izer units isillustrated in Fig.2
The diaphragm pump extracts the NaOH solutionfrom the NaOH tank and delivers it to the treatmentcircuit via a spring-loaded feed valve. The treatmentcircuit and especially the fine filter down steam of thetreatment circuit homogenize the concentration of thesolution injected into the circuit by shot feeding. Thevolume flow meter in the treatment circuit stops thediaphragm pump via a limit switch when the volumetricflow rate drops below a predetermined limit value. Avent on the diaphragm pump enables starting withoutback pressure and venting of the unit for activation.Low NaOH level in the tank is sensed with a leveldetector to activate an alarm. A soda lime filter in thetank vent binds the carbon dioxide contained in theinlet air and prevents the formation of carbonates inthe NaOH solution.
1 Diaphragm pump 4 Level detector2 NaOH tank 5 Soda lime filter in tank vent3 Feed valve 6 Vent
(check valve) 7 Treatment circuitFig.2 Schematic Diagram of Alkalizer Unit
The tank has a capacity to store the sodium
hydroxide solution required for a service period of several
months.
4 Control and Monitoring
An interlock using the volumetric flow rate in the
treatment circuit as a criterion prevents starting of the
diaphragm pump and NaOH feeding into the treatment
circuit under no-flow or empty conditions. The feed rate of
the diaphragm pump is controlled by changing the stroking
rate dependent on the conductivity in the treatment circuit
using a controller and stroking rate transducer.
The diaphragm pump is stopped as soon as the
conductivity in treatment circuit or
conductivity in primary water circuit
exceeds a predetermined maximum valve, or as soon as
the
conductivity in treatment circuit or
volumetric flow rate in treatment circuit drops below a
minimum valve.
This avoids over feeding due to faults or incorrect
operation of the alkalizer unit. After the pump has been
stopped the conductivity of the water is promptly decreased
by ion exchanger in the mixed-bed filter.
The alkalizer unit provides warning limits for
low conductivity in primary water circuit
low conductivity in leakage water circuit
low level in NaOH tank.
which are displayed in the control cabinet.
Via potential-isolated contacts the following alarm
conditions can be signalled to the control room either as
single alarm or as group alarm:
low conductivity in leakage water circuit
low conductivity in primary water circuit
low NaOH level in tank
loss of supply voltage.
1 NaOH tank
2 NaOH tank cap
3 Diaphragm pump
4 NaOH tank vent with lime filter
5 Feed valve (check valve)
6 Alarm and operating control
panel
7 Cable fracture is signalling
device
8 Analog/digital converter
9 Tale perm D con verger
10 Signal transmitter
Fig. 3 Alkalizer Unit
2.1-7341-0009/2
BHEL, Hardwar 2.1-7343-0002/1
Primary Water Filters
1 Main Filter
The primary water system includes a strainer-
type main filter with magnet bars. The filter screen
of the strainer has a mesh size of 75 µm (3 mils)
and is supported by a per forated sheet-meta l
cylinder. The magnet bars consist of a magnet carrier
and a number of permanent magnets. The high-grade
permanent magnets have an unlimited useful service
life. The magnet bars are arranged so that a strong
magnetic field is set up between them. The primary
water must pass through this magnetic field so that
al l i ron part ic les come within the range of the
magnetic bars, and are thus attracted and retained.
The magnet bar are protected by stainless steel
sleeves from which they can be removed with the
aid of eyebolts. On contamination of the strainer-type
filter, which is indicated by an alarm initiated at
excessive differential pressure, the filter should be
cleaned.
2 Fine Filter
A fine filed with one-way filter element giving a
degree of filtration of 5 µm (0.2 mils) is installed after
the mixed-bed ion exchanger in the primary water
treatment system.
The fi l ter element consist of cellulose fibbers
bonded with synthetic resin to achieve stability. The
fibres are distributed in the element in such a way
tha t the i r poros i t y i s h ighes t on the cu te r
c i rcumference o f the e lement and decreases
continuously towards the filer interior. Therefore,
filtration takes place in depth, and the solid matter is
his in the entire volume of the element. The coarser
particles are removed at the highly porous outer
surface, while the smaller particles are arrested in the
element body at varying depth, depending on their
size. On contamination of the filter, which is indicated
by an a larm in i t ia ted a t excess ive d i f fe rent ia l
pressure, the filter element should be removed and
replaced with new one.
BHEL, Hardwar 2.1-7131-0003/1
Seal Oil Cooler
1. Upper tubesheet2. Support plate3. Return water channel4. Partition ring5. Inspection port6. Tubel bundle7. Cooler shell
8. Cooling water connection9. Cooler base10. Water channel11. Lower tubesheet12. Oil outlet13. Oil inlet
BHEL, Hardwar 2.1-7344-0001/1
Primary Water Main Filter
BHEL, Hardwar 2.1-7345-0002/1
Primary Water Fine Filter
BHEL, Hardwar 2.1-7349-0003/1
Protective Screens atPrimary Water Inlet and OutletTHDF Series
BHEL, Hardwar
Coolant Temperature Control
2.1-8010-0002/1
Due to load variations during operation and the resulting
thermal expansions and contractions, the generator is
subjected to stresses.
In order to reduce these stresses, the hydrogen cooling
circuit and the primary water cooling are each provided
with a temperature control system to control the cooling
gas and primary water temperatures so that the active
generator components are maintained at the proper
temperature level.
The requirements for the temperature control systems
are described below :
ϑ cold = Cold gas temperature or cold primary water
temperature
ϑhot
= Hot gas temperature or hot primary water
temperature
ϑmean
= Mean temperature of hot and cold gas or of
hot and cold primary water
∆ϑ = hot - cold with generator carrying full load.
The temperature rise ∆ϑ at full load is the temperature
difference between the hot and cold hydrogen gas as given
in the hydrogen cooler design data or between the hot and
cold primary water as given in the design data of the primary
water cooler.
After startup and runup to rated speed, the cooling water
supply to the hydrogen coolers should be opened only when
the temperature of the hydrogen gas has reached the preset
cold gas reference. The temperature difference between
cold gas and hot gas is determined by the no-load losses.
The cooling water supply to the primary water coolers
should be opened only when the generator is carrying load,
since only then current-dependent heat losses will have to
be dissipated.
The temperature control systems are cold coolant
temperature control schemes with variable set point as a
function of the stator current. Set point adjustment is
selectable between I and I2 or with an exponent between
one and two. With rising stator current, the set point is
reduced, so that the mean value (ϑmean
) of hot and cold
coolant temperatures assumes a nearly constant value,
as shown in Fig. 1.
The difference between the setting values of the two
set points corresponds to half the temperature rise of the
hydrogen cooling gas at no-load, with 5-10 K (9-180F) to
be taken as a guiding value.
2.1-8010-0002/2
In order to maintain a low temperature level in the
generator, the reference should be set at the lowest
possible value, ensuring that the cold coolant temperature
will not drop the minimum level of 100 C (50
0F) even when
the generator is carrying full load.
Parallel shifting of the curves shown in Fig. 1 is possible
by adjustment of the cold coolant references. The
temperature of the cold primary water must, however,
always be higher than the temperature of the cold hydrogen
cooling has over the entire load range of the generator in
order to avoid any condensation of moisture contained in
the gas on the generator components carrying primary
water.
The control valve must be absolutely tight when in the
closed position to ensure that the coolant temperature will
not drop while the generator is being shut down.
For details on the operation and technical features of
this equipment, see equipment supplier’s operating
instructions.
The required temperatures for setting the coolant
temperature control system must be observed.
BHEL, Hardwar
Safety Equipment
for Hydrogen Operation
2.1-8310-0001/1
Turbo Generators
Operation
The use of hydrogen as coolant in the generator calls
for special safety equipment to ensure that hazardous
operating conditions which might endanger personnel or
the plant will not occur.
The safety and protective measures provided for the
generator are described in detail in this section. The
required measuring and alarm equipment is discussed
elsewhere in this manual [1].
During normal operation, leaks may develop which
result in a continuous escape of hydrogen. Long-time
experience has shown that no operational restrictions are
required as long as the hydrogen losses do not exceed 12
m3 (s.t.p.) during any 24-hour period. The surroundings of
the generator and the hydrogen supply system should not
be endangered if should engineering principles were
followed in plant design and provision is made for ample
ventilation of these areas so that the formation of localized
hydrogen pockets or explosive hydrogen-air mixtures is
precluded.
particular precautions are taken with respect to a failure
of the seal oil system. A special vapor exhauster creates a
slight vaccum in the generator bearing compartments to
prevent the escape of oil vapor from the bearing
compartments along the shaft. Any hydrogen collecting in
the bearing compartment will be drawn off by the exhauster
and vented.
Operation of the exhauster is monitored by a flow
transmitter with limit switch. If the exhauster fails, the
second exhauster on standby is automatically started.
To prevent the hydrogen which enters the bearing
compartment from escaping via the oil drain pipes, the drain
oil is returned to the turbine oil tank via the seal oil storage
tank and a loop seal. This loop seal is permanantly filled
with oil to prevent the escape of gas. The loop is designed
to withstand momentary pressure surges.
The bearing oil circuit and the seal oil circuit are
seperated from each other.
The seal oil drained from the seal oil tank (hydrogen
side circuit) passes into the seal oil storage tank. After
remaining in this tank for a predetermined time, the
degassed oil is admitted to the turbine oil tank together
with the bearing oil via a loop seal.
The measures outlined above have the following
effects:
The bearing compartments and the oil drain pipes are
vantilated continuously so that no explosive hazard will
arise during normal operation.
During normal operation, practically no hydrogen will
enter the turbine lube oil tank via the loop seal together
with the seal oil drained from the shaft seals, since the
hydrogen is already extracted in the seal oil storage
tank.
The isolating action of the loop seal prevents the
hydrogen escaping due to small leakages from flowing
into the turbine through the only partly filled oil drain
pipe.
The seal oil storage tank is continuously vented via the
vapor exhauster provided for the bearing compartments.
The exhauster creats a slight vaccum in the seal oil storage
tank so that the oil saturated with hydrogen is degassed.
After remaining in this tank for a predetermined time, the
degassed oil is admitted to the turbine oil tank together
with the bearing oil via a loop seal.
This continuous vantilation of the seal oil storage tank
prevents the formation of any explosive hydrogen-air-
mixture.
To avoid anydanger to the unit to the hydrogen supply,
only two hydrogen bottles should be opened if the bottle
supply is used.
BHEL, Hardwar
List of Valves
For vent Gas System
2.1-8311-7379/1
Turbo Generators
Operation
SL. VLV TYPE OF VALVE NOM. NOM BODY END FUNCTION LOCATION REMARKS
NO. DESG BORE PRESS MATL CONN
1 MKF 91 Safety Valve 6 2.5 CS SC Shut Off at PW Tank Pipe Line
AA 003
2 MKF 91 Globe Valve 20 2.5 CS SC PW Tank Gas Exhaust Pipe Line
AA 506
3 MKF 91 Globe Valve 20 2.5 CS SC PW Tank Gas Exhaust Pipe Line
AA 513
4 MKF 91 Globe Valve 20 2.5 CS SC PW Tank Gas Exhaust Pipe Line
AA 505
5 MKQ 31 Globe Valve 8 2.5 CS SC Isolating Valve Pipe Line
AA 301
6 MKQ 31 Disphragm valve 80 2.5 GM FL Shut Off at inlet of Pipe Line
AA 501 Vapour Exhauster
7 MKQ 32 Disphragm valve 80 2.5 GM FL Shut Off at inlet of Pipe Line
AA 501 Vapour Exhauster
8 MKQ 31 Non-Return valve 80 2.5 CS FL Shut Off at Outlet of Pipe Line
AA 001 Vapour Exhauster
9 MKQ 32 Non-Return valve 80 2.5 CS FL Shut Off at Outlet of Pipe Line
AA 001 Vapour Exhauster
Legend
FL = Flanged
SC = Screwed
CS = Carbon Steel
CR = Cromium Steel
GM = Gun Metal
RT = Room Temperature
BHEL, Hardwar
Generator Mechanical Equipment
Protectoin
2.1-8320-0002/1
Turbo Generators
Operation
1 Tripping Criteria
Turbogenerators require comprehensive safety and
supervisory devices to prevent damage and long forced
outages.
The protective equipment detects dangerous operation
conditions at an early stage and prevents them from
developing into damaging conditions. The protection
relieves the operating personnel from making the necessary
fast decisions.
The following criteria are sensed by the generator
mechanical equipment protection and processed by the
generator protection circuits:
1.1 High Cold Gas Temperature in Generator
1.2 Liquid in Generator Terminal Box
1.3 High Hot Air Temperature in Exciser Unit
1.4 High Seal Oil Inlet Temperatures
1.5 High Primary Water Inlet Temeperature
1.6 Low Primary Water Flow Rate at Sector Outlet
1.7 Low Primary Water Flow Rate at Bushing Outlets
Each of these criteria activates a turbine trip. The
generator is disconnected from the system and de-excited
through the two-channel reverse power relay.
2 Protection Circuits
2.1 Generators Protection Against Overheating byHigh
Cold Gas Temperature
The protection circuit covering criterion 1.1 prevents
insufficient cooling and thus overheating of the hydrogen-
cooled components in case of high cooling gas
temperature.
2.2 Generator Protection Against Internal Ground Fault
or Terminal Short-Circuit
The generator may be damaged by loaks in
components through which primary or secondary cooling
water or seal oil flows inside the generator.
Primary water flows through the stator winding, terminal
bushing and phase connectors. Secondary cooling water
flows through the hydrogen coolers located in the stator
end shields. Generator operation will only be endangered
by these coolants in the event of large leakages. As a result
of the high hydrogen pressure. Little water will emerge from
a small leak. Hydrogen will, however, enter into the water
circuit. The hydrogen loss can be derived from the hydrogen
consumption of the generator.
Operation of the generator will be seriously endangered
in the event of a major ingress of water which will collect in
the generator terminal box. Due to the restricted volume of
the compartment the liquid ca rise quickly, resulting in a
terminal short-circuit or ground fault. In order to prevent
such a failure, two level detectors are conected to the
generator terminal box to activate the generator mechanical
equipment protection before a critical level is reached.
2.3 Exciter Unit Protection Against Overheating
The protection circuit covering criterion 1.3 prevents
overheating of the exciter in case of insufficient cooling
(failure of exciter coolers).
2.4 Shaft Seal protection Against High Seal Oil Inlet
Temperature
High seal oil inlet temperature endangers proper sealing
performance of the shaft seals. High seal oil temperature,
as may, for instance, be experienced on failure of the seal
oil coolers, results in a reduction of oil viscosity. The gas
may penetrate the seal oil film at the shaft seal contact
face and allow the hydrogen to enter the bearing
compartment.
2.5 Protecting of Water-Cooled Components Against
Overheating
The protection circuit covering criterian 1.5 prevents
insufficient cooling and thus overheating of the water-cooled
components in case of high primary water inlet temperature.
2.7/2.7 Protection of Water-Cooled Components
Against Insufficient primary Water Supply
The protection circuits covering criteria 1.6 to 1.7
prevent overheating and damage to the stator winding,
phase connectors and bushing in case of insufficient
primary water supply.
BHEL, Hardwar
Tripping Scheme for Generator
Mechanical Equipment Protection
2.1-8321-0002/1
Lequid in generator teminal box
High cold has temperature
High got air temperature
in main exciter
High seal oil temperature
downstream of cooler
High primary water flow rate
at stator outlet
Low primary water flow rate
at bushing outlet
Alarm is initiated when the electrical generator protection system is tripped. Individual alarms for each criterion are proveded.
BHEL, Hardwar 2.1-8323-0001/1
Generator Mechanical Equipemtn Protection
Two-out-or-Two Protection CircuitWith Functional Test
BHEL, Hardwar
Electrical Generators Protection
2.1-8330-0002/1
Turbo Generators
Operation
Generators are high-quality mechines for securing the
best possible continuity of power supply. In addition to a
suitable techinical design and responsible mode of
operation, provision must therefore be made for automatic
protection facilities. This protectron must ensure a fast and
selective detection of any faults in order to minimize their
dangerous effects.
The protective equipment must be designed so that
anyserious fault will result in an immediate disconection
and de-excitation of the generator. Faults which do not
cause any direct damage must be brought to the attention
of the operating staff, enabling them to operate the unit
ioutside the critical range or to take precautionary measures
for shutdown.
Generators may be endangered by short-circuits,
ground faults, overvoltages, underexcitation and excessive
thermal stresses.
The folliowing protective equipment is recommended:
1 Differential protection
Breakdown of insulation between different stator phase
windings results in an internal short-circuit. The fault is
detected by a differential relay which initiates immediate
isolation and de-excitation of the generator. In order to
obtain a high sensitivity, the protected area should include
the generator only.
Operaing value: 0.2-0.4/NRelay time: < 60 ms
In certain cases, the generator may also be included in
the differential protection for the main transformer and
station service feeder. Generator faults are then detected
by two differential protection devices.
2 Stator Ground Fault Protection
Breakdown of insulation between the stator winding and
frame results in a stator ground fault. If possible, the stator
ground fault protection should cover the complete winding.
including the neutral point of the generator. The protection
is to initiate immediate isolation and de-excitation of the
generator.
Relay time: <1 s
The load resistance of a fround transformer and any
required boost to raise the neutral point potential should
be selected so that ground current due to a fault will amount
to less than 15 A.
3 Rotor Ground Fault Protection
Rapid fault detectioon is required for the following
reasons:
An interruption of the field circuit with arcing releases
high amounts of energy in the form of heat which may
cause severe burning.
A one-line-to-ground fault may develop to a double
ground fault, resulting in dangerous magnetic
unbalances, especially on four-pole generators.
To minimize the consequential damage, it is
recommended to provide two=pole and four-pole
generators with a protection circuit featuring a delayed
response. In the core of four-pole generators, the rotor
ground fault protection must always operate of avoid the
hazard of sudden, esxtremely high vibrations due to
magnetic unbalances.
Relay time: approximately 1 s
4 Underexcitation Protection
Failure of the voltage regulator, maloperation of the
generator or transformer control system and generator
operation in a system with capacitive load may result in a
reduction of the excitation required to ensure system
stability below a predetermined minimum value. Short-
circuits or interruptions in the field circuit result in a complete
loss of field and thus in instability of the generator. This
causes higher temperature rises in the rotor and core end
end portions, rotor overvoltage, system swims and torisional
vibrations of the shaft.
A momentary excursion beyond the steady-state
stability limit must not necessarily result in a loss of stability.
Therefore it is advisable to design the under-excitation
protection so that a warning will be given when the steady-
state stability limit is reached. The generator will be shut
down after a few seconds only.
The protection must operate instantaneously if a loss
of field occurs when the steady-state stability limit is
reached.
If the loss of field cannot be detected directly (e.g.
exciters with rotating diodes), it is recommended to
introduce a second stator criterion covering the range of
the permeance values 1/xd and 1/x’d and to provide for
instantaneous tripping when this criterion is exceeded.
5 Overcurrent Protection
System faults may result in inadmissible thermal
stressing of the generator. For this reason, an overcurrent
protection should be provided which operates on failure of
the system protection.
A definite-time delay overcurrent relay may be used
for this purpose,however, its relay time should longer than
that of the system protection.
Operating value: 1.3/NRelay time: 6-8 s maximum
To avoid long relay times, it is recommended to equip
large generators with an inverse-time-delay (impedence0
relay. This relay is energized by overcurrent and operates
with long or short-time setting, dependent on the location
of the short-circuit.
If connected to the generator neutral point, the over-
current protection serves as back-up protection for the
differential protection.
6 Load Unbalance Protection
Generators operating in an interconected system are
normally subjected to small load unbalnced only. However,
all one-and two-line-to-ground faults occuring in the system,
phase breakages or circuit breaker failures are in fact load
unbalances which may result in unduly high thermal
stressing of the rotor.
It is recommended to provide a two-stage load
unbalance protection. When the continuously permissible
load unbalance is reached, an alarm is given, whereas a
time-dependent isolation from the system occurs when this
value is exceeded.
In case of large units, it is recommended to provide a
protection with unbalanced load/time characteristic.
Operating value and relay time should be matched to the
load unbalanced/time characteristic applicable to the
particular generator.
7 Rise-in-voltage Protection
Rejection of partial or complete system loads causes a
voltage rise, followed byan increase in the prime mover
speed. This may result in the generator and the apparatus
conected to it being endangered by undully high voltages.
Maloperation during manual voltage regulation of the
generator may also result in inadmissible voltage stressing
of these devices. Due ot the sudden voltage variations
resulting from switching operations, it is advisable, at least
in the case of large units, to provide a two-stage rise-in
voltageprotection,i.e.:
with high (1.45 × UN) operaing value and instaneous
tripping;
with low (1.2 × UN) operaing value and delayed tripping.
8 Under-Frequency Protection
Major disturbances in an interconected system may
result in operation of the generator at under-frequency. At
rated voltage, the generator can be continuously operated
at rated k VA up to 95% of rated frequency.
To avoid excessive magnetic and thermal stressing, it
is recommended to provide an under-frequency protection.
Since the frequency deviation due to a system
disturbance is normally accompanied by a voltage
deviation, the protection should be designed on the basis
of the permissible load characteristic of the generator on
frequency and voltage deviations.
9 Reverse Power Protection
A rise in system frequency for any reason whatsoever
result in closing of the control valves, and the turbine is
driven by the motoring generator. Since the turbine is then
no longer supplied with cooling steam, the unit must be
disconected from the system. The relay must be provided
with a time delay of approximately 20s to prevent undesired
response to system swings (long time setting).
Specific faults in the turbine-generator interior initiate
emergency tripping. The steam supply to the turbine is
interrupted. A reliable criterion og perfectly tight closure of
the emergency stop valves is the flow of power from the
system back into the generator.
Disconnection of the unit from the system by the
generator circuit breaker with a time delay of 4s is only
permissible after the reverse power has been drawn by
the generator (short-time setting).
Operating value: about 50-80& of revese power
Relay time: long-time setting: approximately 20 s
short-time setting: approximately 4s
10 Overvoltage Protection
The use of surge duverters on the high-voltage side of
the unit transformer is considered sufficient for protecting
the generator against stmospheric overvolatage and
switching surges in the system.
With a view to a possible flashover from the high-voltage
winding to the low-voltage winding inthe unit tranformer, it
is, however, advisable to proide surge diverters for the
generator too, which shoud be connected between the
phases and ground.
Normally, the surge diverters are installed inthe direct
vicinity of the unit transformer. It is assumed that switching
surges due to a load isolator or circuit breaker connected
between the generator and transformer will not endanger
the generator.
Care should be taken toprovide exlosion-proof suge
diverters or suitable constructional measures in order to
avoid danger to persons or nearby pnat components.
Design priciple:
Reseal voltage: approximately 1.2-1.4 × UN(allowing for power-frequency
overvoltage on load rejection)
Power-frequncy
sparkover voltage:approximately 2 × UN(<test voltage for stator winding,
e.g. VDE 0530,
UP = 2 UN + 1 kV)
Impulse sparkover
voltage <4 × UN
2.1-8320-0002/2
BHEL, Hardwar
Tripping Scheme for
Electrical Generator Protection
2.1-8331-0001/1
Differential protection
Stator ground fault protection
Rotor ground fault protection
inderexcitation protection
without loss of field
with loss of field
Overcurrent protection
Unbalance load protection
Rise-in-voltage protection
Under-frequency protection
Reverse power protection
Long time
Short time (operates only at TT)
TT = Turbine trip
GCB = Generator circuit breaker
FB = Field breaker
BHEL, Hardwar 2.1-8351-0002/1
Arrangement of Brush Holders for
Rotor Grounding System
BHEL, Hardwar
Measuring Devices andSupervisory EquipmentIntroduction
2.1-8400-0002/1
Turbo Generators
Operation
The supervisory equipment consists of alarms and
measuring devices. The measuring devices give a visual
indication of the system parameters, the alarm devices
initiate visual or sudible signals in the event of a controlled
quantity falling below or exceeding the predetermined limit
values. In many cases, the measuring and alarm devices
are combined to form one supervisory.
Closely associated with the supervisory equipment are
regulating systems, automatic controls and protective
devices which provide for a reduction of the manual
supervisory work.
BHEL, Hardwar
Temperature TranducersResistance Temperature Detectorsand Thermocouples
2.1-8410-0004/1
1 Resistance Temperature Detectors (RTD’s)
RTD’s are used for temperature measurements on the
generator, e.g. to measure the slot temperatures and the
cold gas and hot gas temperatures. Both RTD’s with four-
wire connection and double-element RTD’s with eight-wire
conection are used.
When making measurements with RTD’s the resistance
element is exposed to the temperature to be measured.
The RTS works on the change in electrical resistance of a
conductor by the following formula:
R = Ro. (1+a.T)
where
Ro = reference resistance at O0c
a = temperature coefficient and
T = tempreature in 0c
The standard reference resistance of the platinum
resistance element is 100 ohmsl. The temperature
coefficient amounts to a=3.85×10-3 deg-1. this mean value
for the range O -100 0c.
1.1Circuit Connections
The two-wire connections to far commonly used involes
errors in case of leads. Long leads are exposed to different
temperatures, and the lead resistances then reach values
in the order of the resistance of the RTD element.
1.1.1 Three-Wire Connection
If a third lead is connected to the element in addition to
the two element leads, automatic compensation for lead
wire resistance including its changes can be achieved by
resistance of the two leads forming the pair to the element
are always the same.
1.1.2 Four-Wire Connection
If the two element leads are not alike or if the three-
wire method of compensation would be too costly a foru-
wire circuit should be used. Fig.2 shows the circuit diagram
of the foru-wire method.
Leads RL 1
and RL2
form the pair of lead wires to the
RTD Pt 100, while the other set of lead wires RL3
and RL4
from the RTD are connected to amplifier V. Being a normal
differential amplifier, it amplifies only the voltage drop
across the RTD to the required output voltage level.
Due to the mostly very high input resistance of amplifier
V, the resistance of lead wires RL3 RL4 from the RTD to
the amplifier is negligible, even if it would be substantially
in-creased be the provision of a safety barrier (explosion
protection).
2 Thermocouples
Thermocouples are used for temperature
measurements on generator, e.g.to measure the generator
and exciter bearing temperatures. Thermocouples are
mainly employed where small constants require fast
temperature indication.
2.1 Principle
Temperature measurement with thermocouples is
carried out as follows:
Two conductors of dissimilar materials,i.e.the positive
and the negative conductor (thremoelectric elements) are
joined at one end (hot junction) so as to produce an
electromotive force (emf), i.e.a thermoelectric emf(inmV).
The magnitude of the emf is dependent upon the
temperature difference betweenthe temperature to be
measured and that of the other two ends of the conductors.
To use the thermoelectric emf for temperature
measurement the free ends of the conductors are exposed
to a constant temperature (cold juction temperature) and
connected to a millivoltemeter calibrated in 0c.
2.2 Compensating Leads
The compensating leads serve to extend the
thermocouple up to the cold junction. When exposed to a
temperature up to 200 0C they produce the same
jthermoelectric emf as the associated thermocouple.See
DIN 43710 for calibration data and limits of error of
compensating leads.
The compensating leads used for the different
thermocouples are identified by colors:
cu-cuNi brown
Fe-CuNi blue
NiCr-Ni green
PtRh-Pt white
NiCr-Constantan red
The insulating sleeve of the positive lead is provided
withe a red mark in addition to the color code.
2.3 Cold Junction
For measureing a temperature by mean of a
thermocouple, the cold junction temperature must be know.
A cold junction at a temperature of 00c can be very earily
proeuced by melting tures of 20 0C and 500C ia also
possible. Note that in these cases certain corrections must
be added to the calibration 00C.To do this, add the
thermoelectric emf due to the cold junction temperature to
the obtain the total thermoelectric emf.
2.1-8410-0004/2
BHEL, Hardwar 2.1-8410-0004/3
The cold junction can, however, also implemented by
using a Pt100 RTD for determination of the actual
temperature. The temperature is referred to the calibration
figure for o0C by electronic means. The electronic cold
junction also avoids the temperature error due to the
junction between the compensating leads and the copper
leads.
To obtain a simpler circuit, the large number of
thermocouples used on the generator can be connected
to a doublepole measuring point selector switch enabling
the resective thermocouple to be connected to a
compensator for measurement.
BHEL, Hardwar
Temperature Tranducers
Rod-Type Thermostats
2.1-8410-0005/1
TurboGenerators
Description
Rod-Type thermostats are used for detecting
temperature limits. These instruments utilize the coefficients
of thermal expansion of two dissimilar metals.
Whene exposed to a temperature rise a rod arranged
inside a tube and fitted to one of it feature a lliner expansion
different from that of the surrounding tube. As a result of
this, a movements initiated in a switching head at the other
end of the detector tube which in turn actuates a
changeover contact. This changeover contact operates on
rising and falling temperature when the set value is reached.
The contacts are connected to the detector tube through a
mechanism providing for sudden changeover. Since the
rod-type thermostats are employed for temperature
detection in pressurized surroundings, they must alwas be
used in connection with protective tubes.
BHEL, Hardwar
Supervision of Generator
2.1-842 0-0003/1
TurboGenerators
Description
The most essential measuring and supervisory devices
at the generator serve for:
temperature monitoring
detection of liquid in generator interior.
1 Temperature Monitoring
1.1 Stator Slot Monitoring
The slot tempreture are measure withe resistance
temperature detectors (RTD’S). This platinum measuring
wire is embedded in a molded plastic body which provides
for insulation and pressure relief.
The RTD’S are embedded directly in the stator slots
between the bottom and top bars at points where the
highest temperature are expected.
The RTD’S are characterized by a constant temperature
vs. resistance characteristic, high mechanical strengh and
insensitivity to electrical and magnetic fields.
1.2 Cold and Hot Gas Temperatures
The temperatue of the hot and cold gases are
measured by RTD’S upstream and downstream of the
hydrogen coolers, and the limit values are sinsed
downsteam of the coolers for use with the hydrogen
temperature control system.
Temperature detectors located in the generator interior
are mounted in gastight protective tubes welded to the
stator frame.
1.3 primary Water Temperatures
The temperature of the hot primary water in the turbine-
end water manifold of the stator winding is measured withe
manifold of the stator winding is measured with resistance
temperature detectors. The temperature detectors are
welded to the water manifold in protective tubes exposed
to the primary water.
2 Stator Liquid Detection
Liquid (cooling water from hydrogen coolers, primary
water or seal oil) entering the generator housing is sensed
by level detectors assembled in gastigh housing located
on the seal oil valve rack. See Figs.2 and 3.
When pipes from several low-level points of the generator
are connected to a common level detector, sight glasses
are provided in the inlet pipe to identify the source of the
liquid.
BHEL, Hardwar
The generator terminal box has two leakage detection
pipes acting on the generator protectors. The two pipes
extend serval inches above the bottom of the generator
terminal box and are interconnected so that both detectors
will respond if the box should be in an inclined position.
These detectors are utilized as tripping criteria for the
generator mechanical equipment protection, whereas all
other detectors initiate only alarms.
2.1-8420-0003/20984E
BHEL, Hardwar
List of Valves
For Generator system
2.1-8423-0001/1
Turbo Generators
Operation
SL. VLV TYPE OF VALVE NOM. NOM BODY END FUNCTION LOCATION REMARKS
NO. DESG BORE PRESS MATL CONN
1 MKA 24 Globe Valve 50 2.5 CS FL By-Pass of Valve Sela Oil Valve Rack
AA 511 MKA 24/AA 501
2 MKA 24 Globe Valve 15 25.0 CS SC Outlet of Sight Glass Sela Oil Valve Rack
AA 502 MKA 24/BR 506
3 MKA 24 Globe Valve 50 2.5 CS SC Inlet of Sight Glass Sela Oil Valve Rack
AA 501 MKA 24/BR 506
4 MKA 23 Globe Valve 15 25.0 CS SC Outlet of Sight Glass Sela Oil Valve Rack
AA 512 MKA 23/BR 516
5 MKA 23 Globe Valve 50 2.5 CS FL Inlet of Sight Glass Sela Oil Valve Rack
AA 511 MKA 23/BR 516
6 MKA 23 Globe Valve 15 25.0 CS SC Outlet of Sight Glass Sela Oil Valve Rack
AA 502 MKA 23/BR 506
7 MKA 23 Globe Valve 50 2.5 CS FL Inlet of Sight Glass Sela Oil Valve Rack
AA 501 MKA 23/BR 506
8 MKA 22 Globe Valve 15 25.0 CS SC Outlet of Sight Glass Sela Oil Valve Rack
AA 502 MKA 22/BR 506
9 MKA 22 Globe Valve 50 2.5 CS FL Inlet of Sight Glass Sela Oil Valve Rack
AA 501 MKA 22/BR 506
10 MKA 21 Globe Valve 15 25.0 CS SC Outlet of Sight Glass Sela Oil Valve Rack
AA 502 MKA 21/BR 506
11 MKA 21 Globe Valve 50 2.5 CS FL Inlet of Sight Glass Sela Oil Valve Rack
AA 501 MKA 21/BR 506
12 PGB 31 Globe Valve 25 1.6 CS FL Cooler-D Inlet Pipe Line
AA 574 Ventilation
13 PGB 32 Globe Valve 25 1.6 CS FL Cooler-A Outlet Pipe Line
AA 571 Ventilation
14 PGB 32 Globe Valve 25 1.6 CS FL Cooler-B Outlet Pipe Line
AA 572 Ventilation
15 PGB 31 Globe Valve 25 1.6 CS FL Cooler-C Inlet Pipe Line
AA 572 Ventilation
16 PGB 31 Globe Valve 25 1.6 CS FL Cooler-C Outlet Pipe Line
AA 573 Ventilation
17 PGB 31 Globe Valve 10 2.5 CS SC Cooler-A Drain Pipe Line
AA 551
18 PGB 31 Needle Valve 10 2.5 CS SC Cooler-B Drain Pipe Line
AA 551
SL. VLV TYPE OF VALVE NOM. NOM BODY END FUNCTION LOCATION REMARKS
NO. DESG BORE PRESS MATL CONN
19 PGB 31 Needle Valve 10 2.5 CS SC Cooler-C Drain Pipe Line
AA 553
20 PGB 31 Needle Valve 10 2.5 CS SC Cooler-D Drain Pipe Line
AA 554
21 PGB 31 Globe Valve 25 1.6 CS FL Cooler-C Drain Pipe Line
AA 571
21 PGB 31 Globe Valve 25 1.6 CS FL Cooler-A Inlet Pipe Line
AA 571 Ventilation
22 PGB 32 Globe Valve 200 1.6 CS FL Shut off at Outlet of Pipe Line
AA 504 Cooler-D
23 PGB 32 Globe Valve 200 1.6 CS FL Shut off at Outlet of Pipe Line
AA 503 Cooler-C
24 PGB 32 Globe Valve 200 1.6 CS FL Shut off at Outlet of Pipe Line
AA 502 Cooler-B
25 PGB 32 Globe Valve 200 1.6 CS FL Shut off at Outlet of Pipe Line
AA 501 Cooler-A
26 PGB 31 Globe Valve 200 1.6 CS FL Shut off at Inlet of Pipe Line
AA 504 Cooler-D
27 PGB 31 Globe Valve 200 1.6 CS FL Shut off at Inlet of Pipe Line
AA 503 Cooler-C
28 PGB 31 Globe Valve 200 1.6 CS FL Shut off at Inlet of Pipe Line
AA 502 Cooler-B
29 PGB 31 Globe Valve 200 1.6 CS FL Shut off at Inlet of Pipe Line
AA 501 Cooler-A
30 PGB 32 Globe Valve 25 1.6 CS FL Cooler-C Outlet Pipe Line
AA 573 Ventilation
31 PGB 32 Globe Valve 25 1.6 CS FL Cooler-D Outlet Pipe Line
AA 574 Ventilation
Legend
FL = Flaged
SC = Screwed
CS = Carbon Steel
SS = Stainless Steel
CA = Cast Steel
2.1-8423-0001/2
BHEL, Hardwar
Supervision of Bearings
2.1-8440-0004/1
1 Generator Bearing Temperatures
The generator bearing temperatures are measured with
thermocouples located in the bearing lower hawer. The
actual measuring point is located at the babbitt/sleeve
interface. Measurement and recording of the temperatures
are performed in conjuction with the turbine supervision.
The overall turbine protection is tripped when the maximum
permissible temperature is exceeded.
2 Vibration Monitoring
The generator and exciter rotes are manufacured with
high precision and carefully balanced.
The unavoidable residual unbalance will, however,
result in vibrations during opertion, which are transmitted
to be stator frame and foundation via the bearings.
To permit a reliable assesment of the running condition,
vibration pickups are located at the bearubgs. Measurement
and recording of the vibrations are performed in conjunction
with the turbine supervision. The overall turbine protection
is tripped when a predetermined amplitude is exceeded.
Turbo Generators
Description
BHEL, Hardwar
Supervision of Seal Oil SystemTurbo Generators
Description
2.1-8450-0005/10999E
The location of the transmitters of the measuring
and supervisory equipment in the seal oil system is
shown in the seal oil Diagram[1].
The most essential measuring and supervisory
devices in the seal oil are:
Level detectors
Pressure and differential pressure gauges
Temperature detectors
Volume flow measuring devices
1 Level Detectors
Within the seal oil system
the oil levels in the TE and EE prechambers
the oil levels in the seal oil tank
the oil levels in the seal oil storage tank
are supervised.
A high oil level in the generator prechambers, due
to an increase in the amount of seal oil on the hydrogen
side of the shaft seal, results in an alarm is initiated when
the probe is immersed in oil.
A low oil level in the seal oil tank is monitored such
that an alarm takes place when the probe is no longer
covered with oil. This prevents dry running of the
hydrogen side seal oil pump.
A low oil level in the seal oil storage tank-only
feasible during the startup phase- results in an alarm for
protection of the air side pumps. The alarm is initiated
when the probe is no longer covered with oil.
2 Pressure and Differential Pressure Gauges
The following pressure measuring points are
provided:
Pressure downstream of air side seal oil pump 1
On failure of seal oil pump 1, a pressure switch
activates air side seal oil pump2, If the latter is not ready
for operation, air side oil pump 3 is automatically started.
Local indication is required for pressure setting of
the A1 valve and for valve and for visual examination.
Pressure downstream of air side seal oil pump 2
On failure of seal oil pump2, a pressure switch
activates air side seal oil pump1. If the latter is not ready
for operation, air side seal oil pump 3 is automatically
started.
Local indication is required for pressure setting of
the A1 valve and for visual examination.
Pressure downstream of air side seal oil pump 3
A pressure switch signals the takeover of the sealoil supply by seal oil pump 3.
Local indication is required for pressure setting ofthe A2 valve and for visual examination.
Pressure downstream of air side seal oil pumps
Readings from this pressure gauge are required forpressure setting of the A1 and A2 valves.
H2 casing pressure
This pressure gauge reading is required for settingthe pressure differential between the air side seal oilpressure and the H
2 casing pressure.
Seal oil pressure downstream of oil orifice
At this pressure gauge the seal oil pressure, set bymeans of the control orifice, can be observed.
Seal oil pump 3 is activated via a differentialpressure transducer, which detects the pressuredifferential between the generator casing pressure andthe air side seal oil, and a pressure switch when pressurefalls below the preset setpoint value. An additionalpressure switch initiates miscellaneous alarms and isused for Off control the hydrogen side seal oil pump.
TE and EE ring relief pressure
The pressure gauges indicate the relief pressure sitby means of the manual control valves.
In addition, pressure transmitters are provided forfurther processing of the pressure signals.
Pressure downstream of hydrogen side seal oil pump
A pressure switch signals a failure of the oil supply.The reading is required for setting of the C valve
and for visual examination.
Pressure in hydrogen side seal oil circuit of shaft seal
This pressure gauge serves for local observation ofthe set seal oil pressure at the shaft seal.
Pressure Differentials are Sensed at the Following Points:Pressure differential between the air side seal oil
before TE and EE shaft seals and the generator casingpressure is sensed by transducers which initiate an alarmon falling pressure differential, Local indication is providefor manual adjustment of the pressure regulating valvesand for visual examination.
2.1-8450-0005/20999E
Also refer to the following section[1] 2.1-7111 Seal Oil Diagram
Differential Pressure Indication at Air - Cooled
Hydrogen Side Seal Oil Filters
The indicators display the degree of f i l ter
contamination and activate an alarm at present pressure
differentials.
3. Temperature Detectors
The following temperatures are measured locally
with thermometers :
Seal oil temperature upstream and downstream of
air side seal oil coolers.
Seal oil temperature upstream and downstream of
hydrogen side seal oil coolers.
Cool ing water temperature upstream and
downstream of air side and hydrogen side seal oil
coolers.
In addition, the following temperatures are measured
by means of resistance temperature detectors for
remotes indication :
Seal oil temperature in hydrogen side seal oil drain,
TE and EE.
Seal oil temperature upstream and downstream of
air side and hydrogen side seal oil coolers.
The following temperature are also monitored with
rod type thermostats, which activate an alarm for high
seal oil temperature.
Seal oil temperature downstream of air side and
hydrogen side seal oil coolers.
4. Volume Flow Meter System
The following volume flows are measured for
comparison measurements :
Volume flow of EE sea ring relief oil
Volume flow of TE sea ring relief oil
Volume flow of air side seal oil, EE
Volume flow of air side seal oil, TE
Volume flow of hydrogen side seal oil, EE
Volume flow of hydrogen side seal oil, TE
BHEL, Hardwar
The location of the transmitters of the measuring and
wupervisory equipment in the gas system is shown in the
Gas Diagram [1].
The essential measuring and supervisory devices in
the gas system are :
Purity meter systems
Volume flow meter system
Pressure gauge
Temperature detectors
1 Electrical Gas Purity Meter System
The electrical gas purity meter system measures the
purity of the hydrogen gas in the generator as well as the
composition of the gas mixtures (CO2/air and H
2/CO
2)
during filling of the generator. The electrical gas purity meter
system is also used when removing the hydrogen from the
generator, where the hydrogen is replaced with carbon
dioxide and the carbon dioxide in turn with air. The gas
required for the measurement is taken from the generator
or from the filling lines, respectively, and, on completion of
the measurement, is discharged to the atmosphere through
a vent line.
For details on the electrical gas purity meter system,
see separate description [2].
The electrical gas purity meter system is equipped with
a limit switch which provides a signal to initiate an alarm
when the purity drops below a preset value.
2 Mechanical Gas Purity Meter System
A mechanical gas purity meter system is supplied to
operate independently of the electrical gas purity meter
system.
This meter system is a mechanical type and utilizes
the physical relationship between the H2 casing pressure
and the differential fan pressure, which in turn depends on
the fan speed (constant) and the density of the medium
handled the fan.
For details on the mechanical gas purity meter system
see separate description [3].
3 Volume Flow System
Measuring gas volume flow
For comparison measurement, a precisely defined
measuring gas flow must be admitted to the electrical gas
purity meter system. The measuring gas volume flow can
be read locally at the flow meter.
4 Pressure Gauges
The following measuring points are provided :
CO2 bottle pressure
The bottle pressure during CO2 filling can be obseved
at a local pressure gauge.
H2 bottle pressure
The bottle pressure can be read at the pressure gauge.
The pressure switch activates a signal at low H2 pressure.
In addition, the pressure is sensed with a pressure
transmitter, the electrical signal being used for remote
control and supervision.
N2 bottle pressure
The bottle pressure can be read at a local pressure
gauge.
H2 pressure at pressure reducers.
For observation of the pressure settings.
Defferential pressure at rotor fan
The differential pressure at the rotor fan can be
observed at a local pressure gauge.
H2 cssing pressure
The pressure is sensed by pressure transmitters, the
electrical signal of one pressure transmitter being used for
remote control and supervision. The signals of the
remaining two transmitters are converted into alarm and
control signals.
The H2 casing pressure dan be read at a local pressure
gauge.
Pressure in gas dryer chamber
The pressure in the gas dryer circuits can be observed
at local pressure gauges.
For aetails on the pressure transmitters, see separate
description [4].
5 Temperature detectors
Within the gas system, temperature detectors are used
for supervision of the gas dryer and CO2 flash evaporator.
The temperatures of the gas dryer heater and of the
heat transfer liquid in the CO2 flash evaporator are detected
by means of thermostats and used for control functions. In
addition, the temperature of the heat transfer liquid in the
CO2 flash evaporator is indicated locally by a thermometer.
For details of the thermostats, see separate description
[5].
Also refer to the following sections
[1] 2.1-7211Gas Diagram
[2] 2.1-7240Electrical Gas Purity Meter System
[3] 2.1-7250Mechanical Gas Purity Meter System
[4] 2.1-8412Pressure Transmitters
[5] 2.1-8410Temperature Detectors
Supervision of Gas System
2.1-8460-0009/1
TurboGenerators
Description
BHEL, Hardwar
Supervision of Primary Water SystemTurbo Generators
Description
2.1-8470-0003/10999E
The location of the transmitters of the measuringand supervisory equipment in the primary water systemis shown in the Primary Water Diagram[1].
The essential measuring and supervisory devicesin the primary water system are:
Conductivity meter systemLevel monitoring systemVolume flow metersPressure gaugesTemperature detectors
1 Conductivity Meter SystemThe conductivity of the primary water is monitored:
Downstream of ion exchangerUpstream of primary water inlet of generator
The measuring point downstream of the ionexchanger checks the ion exchanger for properperformance.
The measuring point in the primary water inlet ofthe generator permits the conductivity of the entirecooling system to be assessed.
Both measuring devices are equipped for indicationand alarm.
2 Level Monitoring SystemThe water level in the primary water tank by
capacitive method, a high or low water level initiating analarm.
A local water level gauge is located in parallel tothe electrical monitoring system.
3 Volume Flow Meter SystemThe primary water volume flows of the
stator winding andbushings
are measured and indicated by a differential pressureflow meter system. If the flow falls below a minimumvalue, an alarm is activated. If the flow continues to fall,the generator mechanical equipment protection istripped.
The amount of primary water flowing though the ionexchanger is monitored by a local flow meter. Theamount of water added to the system during operationis determined by of a water meter.
4 Pressure GaugesPressure or pressure differentials are sensed at the
following measuring point in the primary water coolingcircuit:
Pressure downstream of primary water pump 1Pressure downstream of primary water pump 2
The two pressure measuring points are equippedwith pressure switches and required for automatic controlof the two primary water pumps.
in addi t ion, a pressure gauge is provideddownstream of each pump for local observation of thepressure.
Pressure upstream of stator winding
This pressure measuring point is equipped withpressure switches and a local pressure gauge. Thepressure switches initiate an alarm at rising primary waterpressure.
The pressure gauge is provided for localobservation.
Gas pressure in primary water tank
A pressure switch activates an alarm at rising gaspressure in the primary water tank.
In addition, a pressure gauge is provided for localobservation of the tank gas pressure.
Differential pressure across main filterDifferential pressure across fine filter
Barton cells with switches display the degree of filtercontamination on a dial. In addition, contactsactivate an alarm on filter contamination at presetdifferential pressure.
5 Temperature DetectorsThe following temperatures are measured locally bymeans of thermometers:
Primary water temperature downstream of coolersCool ing water temperature upstream anddownstream of coolersPrimary water temperature downstream of bushings
Resistance temperature detectors are used tomeasure the followings temperatures for furtherprocessing according to different methods:
Pr imary water temperature upstream anddownstream of coolersPrimary water temperature downstream of statorwindingPrimary water temperature downstream of bushings
In addition, a rod-type thermostat monitors thefollowing temperature:
Primary water temperature downstream of coolers
Also refer to the following section[1] 2.1-7311 Primary Water Diagram
BHEL, Hardwar
Supervision of ExciterTurbo Generators
Description
The most essent ial measuring andsupervisory devices at the exciter are:
Temperature monitoring systemFuse monitoring systemGround fault detection systemExcitation current measuring device
1 Temperature Monitoring SystemThe exciter is provided with devices for
monitoring the temperatures of the cold air afterthe exciter cooler and the hot air leaving therectifier wheels and hot air leaving the rectifierwheels and main exciter.
2 Fuse Monitoring SystemThe indicator flags of the fuses on the
rectifier wheels may be checked during operation
with the built-in stroboscope.
3 Ground Fault Detection SystemTwo sliprings are installed on the shaft
between the main exciter and bearing. One isconnected to the star point of the three-phasewinding of the main exciter and the other to theframe. These sliprings permit ground faultdetection.
4 Excitation Current Measuring DeviceThe excitation current is measured indirectly
through a coil arranged between two poles of themain exciter. The voltage induced in this coil isproportional to the excitation current thusenabling a determination of the excitation current.
2.1-8490-0001/10999E
BHEL, Hardwar
BHEL, Hardwar
1 Design Feature
The exciter consists of
Rectifier wheels
Three-phase pilot exciter
Cooler
Metering and supervisory equipment
1 Automatic voltage regulator
2 Pemanent magnet pilot exciter
3 Sliprings for field groung fault detection
4 Qualdrature-axis measuring coil
5 Three-phse main exciter
6 Diode rectifier set
7 Three-phase lead
8 Multikontakt conector
9 Rotor winding of turbogenerator
10 Stator winding of tubogenerator
Fig. 1 Basic Arrangement of Brushless Excitation System
With Rotating Diodes
Exciter
2.1-9100-0021/1
Fig. 1 Shows the basic arrangement of the exciter. The
three-phase pilot exciter has a revolving held with
permanent magnet poles. The three-phase ac generated
by the permanent-magnet pilot exciter is rectified and
controlled by the TVR to provide a varable dc current for
exciting the main exciter The three-phase ac induced in
the rotor of the main exciter. The three-phase ac induced
in hte rotor of the main exciter is rectified by the rotating
rectifier bridge and fed to the field winding of the generator
rotor of the main exciter is rectified by the rotating rectifier
bridge and fed to the field winding of the generator rotor
through the dc leads in the rotor shaft.
Fig. 2 Exciter Rotor
The exciter shown in fig. 2 corresponds to ht basicarrangement described above.A common shaft carries the rectifier wheels, the rotor ofthe main exciter and the permanent-magnet rotor of thepilot exciter. The shaft is rigidly coupled to the genratorrotor. The exciter shaft is supported on a bearing betweenthe main and pilot exciters. The generator and exciter totorsare thus supported on total of three bearings.
Mechanical coupling of the two shaft assemblies resultsin simultaneous coupling of the dc leads in the central shaftbore through the Multikontakt electrical contact systemconsisting of plug-in bolts and sockets. This contact systemis also designed to compensate for length variations of theleads due to thermal expansion.
2 Rectifier WheelsThe main-components of the rectifier wheels are the
silicon diodes which are araanged in the rectifier wheels ina three-phase bridge circuit. The internal arrangement ofa diode is illustrated in Fig. 3. The contact pressure for thesilicon wafer is produced by a plate spring assembly. Thearrangement of the diods is such that this contact pressureiis increased by the cintrifugal force during rotation.
Fig. 3 Silicon Diods
Fig. 4 shows additional components contained in the
rectifier wheels. Two diodes each are mounted in each
aluminum alloy heat sink and thus connected in parallel.
Associated with each heat sink is a fuse which serves to
switch off the two diodes if one diods fails (loss of reverse
blocking capability).
Fig. 4 Rectifier Wheel
For suppression of the momentary voltage peaks arising
from commutation, each wheel is provided with six RC
network consisting of one capacitor and one damping
resistor each, which are combined in a single resin-
encapsulated unit.
The insulated and shrunken rectifier wheels seve as
dc buses for the negative and positive side of the rectifier
bridge. This arrangement ensures good accessibility to all
components and a minimum of circuit connections. The
two wheels are identical in their mechanical design and
dffer only in the forward direcitons of the diods.
The direct current from the rectifier wheels is fed to
these leads arrnaged in the center bore of the shaft via
radial bolts.
The three-phase alternating currents is obtained via
copper conductors arranged on the shaft circumference
between the rectifier wheels and the three-phase main
exiciter. The conductors are attached by means of banding
clips and equipped with screw-on lugs for the internal diode
connections. One three-phase conductor each is provided
for the four diodes of a heat sink set.
3 Three-Phase Main Exciter
Fig. 5 Main Exciter
The three-phase main exciter is a six-pole revolving-armature unit. Arranged in the stator frame are the poleseith the field and damper winding. The field winding isarranged on the laminated magnetic poles. At the pole shoebars are provided. Their ends being conected so as to forma damaper winding Between two poles a quadrature-axiscoil is fitted for inductive measurement of the exditercurrent.
The rotor consists of stacked laminations, which arecompressed by through bolts over compression rings. Thethree-phase winding is inserted in the slots of the laminatedrotor. The winding conductors are transposed within thecore lengt, and the end turns of the roteor winding aresecured with steal bands. The connections are made onthe side facing the rectifier wheels. The winding ends arerun to a bus ring system to which the three-phase leads tothe rectif ier wheels are also conected. After fullimpregnation with synthetic resin and curing, the completerotor is shrunk onto the shaft. A journal bearing is arrangedbetween main exciter and pilot exciter and has forced oillubrication from the turbine oil supply.
2.1-9100-0021/2
BHEL, Hardwar
4 Three-Phase Pilot Exciter
The three-phase pilotexciter is a 16 pole revolving-field
unit. The frame accommodates the laminated core with the
three-phase winding. The rotor consists of a hub with
mounted poles. Each pole consists of 12 separate
permanent magnets which are housed in a non-magnetic
metalic enclosure. The magnets are braced between the
hub and the external pole shoe with bolts. the rotor hub is
shrunk onto the free shaft end.
Fig. 6 Stator of Main Exciter
5 Cooling of Exciter
The is air cooled. The cooling air is cirvulated in a closed
circuit and recooled in two cooler sections arranged
alongside the exciter.
The complete exciter is housed in an enclosure draw
the cool air in at both ends and expel the warned air to the
compartment beneath the base plate.
The main exciter enclosure receives cool air from the
fan after it passes over the pilot exciter. The air enters the
main exciter from both ends and is passed into ducts below
the rotor body and discharged through radial slots in the
rotor core to the lower compartment. The wrm air is then
returned to the main enclosure via the cooler sections.
Fig. 7 Permanent-Magnet Pilot Exciter
6 Replacement of Air Inside Exciter Enclosure
When the generator is filled with hydrogen (operation
or standstill) an adequate replacement of the air inside the
exciter enclosure must be ensured. The air volume inside
the exciter enclosure requires an air change rate of 125m3/h.
While the generator is running, the air leving the exciter
enclosure via the bearing vapor exhaust system and the
leakage air outlet in the foundation provides for a pull-
through system. The volume of air extracted from the
cooling air circuit is replaced via the filters located at the
top of the enclosure.
When the generator is at rest, the air dryer of the exciter
unit discharges dry air inside the exciter enclosure. The air
leaves the exciter enclosure via the leakage air filter and
the leakage air oulet at the shaft as well as via the bearing
vapor exhaust system if this system is in sevice.
2.1-9100-0021/3
BHEL, Hardwar 2.1-9102-0002/1
Rectifier Wheels
ELR Series (More Than 60 Diodes)
BHEL, Hardwar 2.1-9103-0003/1
Rectifier Wheels and Coupling
ELR Series (Up to 120 Diodes)
BHEL, Hardwar 2.1-9104-0002/1
Permanent-Magnet
Pilot Exciter Rotor and Fan
BHEL, Hardwar 2.1-9110-0029/1
Exciter Cross Section
BHEL, Hardwar
BHEL, Hardwar 2.1-9140-0002/1
Stroboscope for Fuse Monitoring
The fuses on the rectifier wheels may be checked during
operation with the stroboscope. A separate flash tube is
provided for each wheel (A and B). The tubes, which are
supplied through a common control unit, are permanently
installed in the rectifier wheel enclosure. This permits easy
monitoring whithout any adjustment outside the exciter
enclosure being required.
Fig. 1 shows the basic arrangement of a fully
transistorized stroboscope The electronics required for
montrol of the light singals are contained in the control unit
and in the tubular lamps. The tubular lamps are connected
to the control unit by cables.
The stroboscope is located in the rectifier wheel and
exciter enclosure so that the fuses may be observed from
outside the exciter enclosure while controlling the
stroboscope.
To synchronize the sequence of flashes with the generator
rotation, the system frequency is utilized to activate the
flashes. A doyuble synchronous motor, controlled through
two pushbuttons and connected to two potentiometers and
IC's, causes the flash to be timed so that a slow-motion
observation of the fuse becomes possible.
The Observation period for one full revolution of the
rectifiier wheel (3600) is approximately 25 seconds. At
approximately 4500, the flash is reset to its initial rate, and
the observation can be repeated. The continuous sequence
of flshes can be interrupted at any time by actuating the
Feed of Return pushbutton. Following this, a stationry
image is obtained which ensures accurate checking of a
single fuse. After approximately two minutes, the
stroboscope is automatically switched off. If this period
should not be sufficient for fuse checking, switching on the
stroboscope for another two minutes without delay can be
repeated for any desired number of times by depressing
the On pushbutton.
The stroboscope contains four plug-in printed circuit
boards which can be readily replaced in order to remedy
any faults.
The capacitor and high-voltage transformer required
to produce the firing pulses for the flash tubes are located
on a printed circuit board which is accommodated in the
handle of the flash lamp.
The operating elements are located on the front panel
of the control unit for ease of operation. A depressed
pushbutton is indicated by an illuminated dot in the
pushbutton head.
Tthe line connector, the two connectors for the flash
lamps and the fuse are located on the back of the control
unit.
All connectors have a mechanical lock and are
protected agaist dust and splashwater. The cables are run
in flexible metal hoses for protection against mechanical
damage.
1 2 3 4 5 6 7 8 9 10
1 Flash tube 1 (A wheel)2 Control unit3 Pushbutton for flash tube 14 Pushbutton for flash tube 2
5 Feed pushbutton6 Pilot lamp for control voltage7 Return pushbutton
8 On pushbutton9 Off pushbutton10 Flash tube 2 (B wheel)
Fig.1 Components and Operating Elements of Stroboscope
BHEL, Hardwar
1 General
A dryer (dehumidifier) and an anicondensation heating
system are provided to avoid the formation of moisture
condensate inside the exciter with the turbine-generator at
rest or on turning gear.
Fig. 1 Exciter Dryer
2 Mode of Operation
The dryer dehumidifies the air within the exciter
enclosure. The dryer wheel is made of a nonflammable
material. On its inlet side, the wheel is provided with a
system of tubular ducts, the surfaces of which are
impregnated with a highly hygroscopic material.
The tubular ducts are dimensioned so that a laminar
flow with low pressure loss is obtained even at high air
velocity.
The moisture absorbed by the dryer wheel is removed
in a regeneration section by a stream of hot air derected
through the wheel in the opposite direction of the inlet air
and then discharged to the atmosphere.
After regeneration, the dryer wheel material is again
capable of absorbing moishture.
The adsorption of moisture and regeneration of the
dryer wheel material take place simultaneously, using
separate air streams, which ensures a continous drying of
the air.
Exciter Drying
2.1-9150-0003/1
TurboGenerators
Description
2.1 Operating Principle of Adsorption Dryer
The dehumidification takes place in a slowly rotating
dryer wheel (approximately 7 revolutions per hour). The
honeycomb dryer wheel consists of a magnesium silica
alloy containing crystalline lithium chloride. The inlet side
of the dryer wheel is subdivided so that 1/4 is available for
regeneration and 3/4 for the adsorption section.
2.1.1 Adsorption Section
The air to be dehumidified passes throungh the
adsorption section of the dryer wheel, with part of the
moisture contained in the air being removed by the
adsorbent material, i.e. lithium chloride. The moisture is
Fig. 2 Schematic Diagram
removed as a result of the pratial pressure drop existing
between the air and the adsorbent material.
2.1.2 Regeneration Section
In the regeneration section of the dryer wheel, the
accumulated moisture is removed from the dryer wheel by
the heated regeneratiion air.
Continuous rotation of the dryer wheel ensures
continuous dehumidification of the air within the exciter.
3 Anticondensation Heating System
An anticondensation heating system to support the
dryer is installed in the exciter baseframe. The heaters are
rated and arrgned so that the temperature in the exciter
interior.
BHEL, Hardwar
The field ground fault detection system detects high-
resistance and low-resistance ground faults in the exciter
field circuit. It is very important for safe operation of a
generatork, because a double fault causes magnetic
unbalances with very high currents flowing through the
faulted part, resulting in its destruction within a very short
time. It is therefore an essential requirement that even simle
ground faults should activate an alarm and protective
measures be initiated, if possible, before the fault can fully
Ground Fault Detection Systemfor Exciter Field Circuit
2.1-9180-0001/1
TurboGenerators
Description
develop. For this reason, the field ground fault detection
system consists of two stages and operates continuously.
Ifthe field ground fault detection system detects a
ground fault, an alarm is activated at RE < 80 kΩ (1st stage).
If the insulation resistance between the exciter field civuit
and ground either suddenly or slowly drops to RE < 5 kΩthe generator electrical protection is tripped (2nd stage).
The generator is thus automatically disconected from
the system and de-excited.
BHEL, Hardwar 2.1-9181-0002/1
Measuring Brush Holder for
Ground Fault Detection
BHEL, Hardwar 2.1-9182-0001/1
Brush Holders for
Ground-Fault Detection System
BHEL, Hardwar
Operating ans Setting Values
General
2.3-4000-0005/1
Turbo Generators
Operation
Strict observance of the operating and setting values
is a prerequiste for reliable operation of the turbogenerator.
Separate tables are provided for the various design
groups of the generator and its auxiliaries. They show the
transmitters activating the controls and alarms as well as
the transmitters acting on the generator protection circuits.
The Remark column contains additional information
on controls, temperatures and pressures.
All operating and setting values refer to rated output
of generator and maximum colling water temperatures
under steady-state conditions.
The operating ans setting values initially specified in
this manual are based on experience under due
consideration of the specific site conditions, such as static
head in case of pressure measuing points or thermal
characteristics in case of temperature measuring points.
These calculated values are intended as guiding values
for making the preliminary settings during init ial
commissionning of the unit.
These settings require certain corrections to account
for the actual conditions. The final settings obtained after
startup and initial load operation are to be entered in the
Operating Value column.
BHEL, Hardwar
Gas Quantities
2.3-4010-0001/11083E
Turbo Generators
Operation
BHEL, Hardwar
Measuring Point List of Generator
2.3-4030-0001/10197E
Turbo Generators
Operation
2.3-4030-0001/20197E
BHEL, Hardwar 2.3-4030-0001/30197E
2.3-4030-0001/40197E
BHEL, Hardwar 2.3-4030-0001/50197E
2.3-4030-0001/60197E
BHEL, Hardwar 2.3-4030-0001/70197E
2.3-4030-0001/80197E
BHEL, Hardwar 2.3-4030-0001/90197E
2.3-4030-0001/100197E
BHEL, Hardwar 2.3-4030-0001/110197E
2.3-4030-0001/120197E2.3-4030-0001/10
0197E
BHEL, Hardwar 2.3-4030-0001/130197E
2.3-4030-0001/140197E
BHEL, Hardwar 2.3-4030-0001/150197E
2.3-4030-0001/160197E
BHEL, Hardwar 2.3-4030-0001/170197E
2.3-4030-0001/180197E
BHEL, Hardwar 2.3-4030-0001/190197E
2.3-4030-0001/200197E
BHEL, Hardwar 2.3-4030-0001/210197E
2.3-4030-0001/220197E
BHEL, Hardwar 2.3-4030-0001/230197E
2.3-4030-0001/240197E
BHEL, Hardwar 2.3-4030-0001/250197E
2.3-4030-0001/260197E
BHEL, Hardwar
BHEL, Hardwar
1. Operating Log
During initial startup and during normal operation, the
hydrogen-colled turbogenerator, auxiliaries and all
instruments and controls should be monitored to assure
continuous reliable operation. The observations and
readings should be recorded. A typical operating log is
contained in these operating instructions.This table will, of
course, have to be adapted to the particular conditions of
the plant. The important requirement is that all checks and
readings be made at certain predetermined intervals and
preferably at the same load point. Any special conditions
regarding the operation of the hydrogen-cooled
Running Routine
General
2.3-4100-0002/1
Turbo Generators
Operation
turbogenerator should be noted separately. Such notes may
be useful in determining the cause of any subsequent
trouble and speeding up corrections.
2. Normal and Special Operating Conditions
The Generator should be continuously monitored from
startup ton shutdown. During initial startup, all checks
should be made at frequent intervals. Hourly readings may
be taken after completion of the initial period.
A generator at standstill is considered to have been
taken into service and must be continuously monitored after
one supply system was placed in operation.
BHEL, Hardwar
Operating values* Unit Tag Date
Number
Active power MW
Reactive power Mvar
Stator current kA
Stator voltage kV
Rotor current A
Speed s-1
Generator gas pressure kg/cm2
Slot 10C
20C
Slot temperature 30C
40C
50C
60C
Primary water Measuring point 10C
outlet temperature Measuring point 20C
TE water manifold measuring point 30C
Measuring point 10C
TE Measuring point 20C
Stator core Measuring point 30C
temperature Measuring point 10C
EE Measuring point 20C
Measuring point 30C
Coolers a/b cold0C
Coolers c/d cold0C
Gas temperature Coolers a/b hot0C
Coolers c/d hot0C
EE After coolers a/b0C
EE After coolers c/d0C
Inlet0C
Bearing oil TE0C
temperatureOutlet
EE0C
Generator bearing TE0C
temperatures EE0C
TE kg/cm2
Shaft lift oil pressureEE kg/cm
2
Generator bearing vibrationTE ahv µm
EE ahv µm
Job name ............................................................ Sl. No. ............................................ Remark .............................................
* Data should be recorded during steady-state conditions after constant operation for several hours.
2.3-4120-7347/1
Operating Log
Generator Supervision
Turbo Generators
Operation
BHEL, Hardwar
Operating values* Unit Tag Date
Number
Air side pressure after seal oil pumps kg/cm2
Hydrogen side pressure after seal oil pump kg/cm2
Air side seal oil pressure after orifice kg/cm2
TE kg/cm2
Air side seal oil pressureEE kg/cm
2
TE kg/cm2
Hydrogen side seal oil pressureEE kg/cm
2
TE mbarSeal oil differential pressure
EE mbar
TE kg/cm2
Ring relief oil pressureEE kg/cm
2
TE kg/sAir side seal oil volume flow
EE kg/s
TE kg/sHydrogen side seal oil volume flow
EE kg/s
TE kg/sRing relief oil volume flow
EE kg/s
Seal oil temperatures, Inlet0C
hydrogen side seal oil cooler Outlet0C
Hydrogen side seal TE0C
oil drain temperature EE0C
Seal oil temperatures, Inlet0C
air side seal oil coolers Outlet0C
Inlet0C
Outlet, H2 side cooler 10C
Cooling water Outlet, H2 side cooler 2
0C
temperaturesOutlet, air side cooler 1
0C
Outlet, air side cooler 20C
Job name ............................................................ Sl. No. ............................................ Remark .............................................
* Data should be recorded during steady-state conditions after constant operation for several hours.
2.3-4150-7347/1
Operation Log
Seal Oil System
Turbogenerators
Operation
BHEL, Hardwar
Operating values* Unit Tag. Date
Number
H2 boottle pressure kg/cm2
CO2 boottle pressure kg/cm2
N2 boottle pressure kg/cm2
H2 purity (elec. purity meter system) % H2
H2 purity (mech. purity meter system)** % H
2
Gas flow for measuring H2 purity I/h
H2 casing pressure kg/cm2
Temperature before gas dryer 0C
Pressure before gas dryer 0C
Job name ............................................................ Sl. No. ............................................ Remark .............................................
* Data should be recorded during steady-state conditions after constant operation several hours.
** To be recordced only on failure of electrical purity meter system.
2.3-4160-7347/1
Operation Log
Gas System
Turbogenerators
Operation
BHEL, Hardwar
Operating values* Unit Tag. Date
Number
Generator inlet 0C
Stator winding outlet 0C
Bushing outlet 0C
Before coolers 0C
After collers 0C
Stator winding oulet dm3/s
Bushing outlet U dm3/s
Prinary water flow Bushing outlet V dm3/s
Bushing outlet W dm3/s
Treated water dm3/s
Primary waterStator winding inlet kg/cm2
pressure After PW pumps 1/2 kg/cm2
Primary water After main filter µS/cm
conductivity After ion exchanges µS/cm
Primary water level in primary water tank %
Gas pressure in primary water tank kg/cm2
Job name ............................................................ Sl. No. ............................................ Remark .............................................Job name ............................................................ Sl. No. ............................................ Remark .............................................
2.3-4170-7347/1
Operation Log
Primary Water System
Turbogenerators
Operation
BHEL, Hardwar
Operating values* Unit Tag Date
Number
Cold air0C
Cooling air Main exciterHot air
0Ctemperature
Rectifier wheels Hot air0C
Cooling water Coolers e/f Inlet
0C
temperature Cooler e Outlet0C
Cooler f Outlet0C
Measuring Point 10C
Exciter bearing twmperatureMeasuring point 2
0C
Bearing oil outlet temperature0C
Exciter shaft vibration Relative µm
Exciter bearing vibration Absolute µm
Shaft lift oil pressure kg
Job name ............................................................ Sl. No. ............................................ Remark .............................................
* Data should be recorded during steady-state conditions after constant operation several hours.
2.3-4190-7347/1
Operation Log
Exciter Supervision
Turbogenerators
Operation