gas engine

Upload: cesar-orlando-barria-vera

Post on 06-Jan-2016

39 views

Category:

Documents


1 download

DESCRIPTION

CHILLER A GAS

TRANSCRIPT

  • Gui

    delin

    e Gas Engine-DrivenChillersSouthern California Gas Company

    New Buildings Institute

    Advanced Design Guideline Series

    New Buildings InstituteNovember, 1998

  • II SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Acknowledgments

    This Advanced Design Guideline was developed by the NewBuildings Institute for the Southern California Gas Company,contract P13311, part of SoCalGas Third Party InitiativesProgram for 1998. Project managers for SoCalGas includedTaimin Tang, Lilia Villarreal and James Green.

    This project was managed by the New Buildings Institute,Douglas Mahone, Executive Director.

    Subcontractors on this project were:

    Heschong Mahone Group:Catherine Chappell, Project Manager,Jon McHugh, Nehemiah Stone and Kalpana Kuttaiah

    GARD Analytics:Robert Henninger, Jason Glazer, and Mike Witte

    Eskinder Berhanu Associates

    The Expert Advisory Panel, which reviewed and advised theproject, included: Gary Nowakowski, Gas Research Institute;William Saulino, American Gas Cooling Center, Inc.; DavidGoldstein, Natural Resources Defense Council; Tamy Ben-Ezra; Peter Schwartz, LAS & Assoc.; Jeffrey Johnson, NewBuildings Institute

    New Buildings Institute11626 Fair Oaks Blvd. #302Fair Oaks CA 95628 (Sacramento area)(916) 966-9916 Fax: (916) 962-0101E-mail: [email protected]: www.newbuildings.org

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE III

    Table of Contents

    CHAPTER 1: PREFACE...................................................1

    CHAPTER 2: DESCRIPTION............................................3A. Applications.........................................................3B. Sizes.....................................................................4C. Benefits................................................................4D. Limitations...........................................................5E. Maintenance.........................................................5F. Installation Issues.................................................7

    Engine Room Ventilation ....................................7Exhaust System ...................................................7

    G. Heat Recovery .....................................................7H. Hybrid Systems....................................................9

    CHAPTER 3: HISTORY AND STATUS.............................11A. History ...............................................................11B. Current Market Share ........................................11C. Standards and Ratings........................................11

    Coefficient of Performance (COP) ....................12Integrated Part Load Value (IPLV) ...................12Applied Part Load Value (APLV).....................13

    D. Economics/Cost Effectiveness...........................13Energy Rates and Billing Structure ...................13Performance Characteristics ..............................14Operating Characteristics ..................................14Estimating Annual Energy Savings ...................14

    E. Equipment Manufacturers..................................15F. Equipment Installations .....................................15

    A.M. Best Company, Oldwick, New Jersey ......15J.C. Penny Department Store, Atlanta, GA ......16Carpenter's Home Church, Lakeland, Florida ...16Peachtree Tower, Atlanta, GA...........................17Boston YMCA, Residential/Hotel Facility........17

    CHAPTER 4: ANALYSIS ................................................19A. Overview ...........................................................19B. Energy Savings ..................................................20C. Cost Effectiveness .............................................20

    CHAPTER 5: DESIGN ANALYSIS GRAPHS.....................23A. Using the Graphs ...............................................23

    Annual Energy Cost Savings Graphs.................23Cost Effectiveness Graphs.................................23

    B. Energy Savings Graphs......................................25Gas Engine-Driven Chiller vs. Standard

    Efficiency Electric Chiller ......................25Gas Engine-Driven Chiller vs. High Efficiency

    Electric Chiller .......................................32Gas Engine-Driven Chiller vs. Single Effect

    Absorption Chiller ..................................39C. Cost Effectiveness Graphs .................................44

    Gas Engine-Driven Chiller vs. StandardEfficiency Electric Chiller ......................44

    Gas Engine-Driven Chiller vs. High EfficiencyChiller .................................................... 60

    Gas Engine-Driven Chiller vs. Single EffectAbsorption Chiller ................................. 76

    CHAPTER 6: BIBLIOGRAPHY....................................... 85

    CHAPTER 7: APPENDIX............................................... 87A. Building Type Descriptions .............................. 87B. Summary of Utility Rates.................................. 89C. Equipment First Cost......................................... 92D. Scalar Ratio and SIR......................................... 93

    Scalar Ratios Simplified ................................... 93Selecting a Scalar Ratio .................................... 94Savings to Investment Ratios (SIRs)................. 94Advanced Economic Analysis .......................... 94

  • IV SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    List of Figures

    Figure 1 - Gas Engine-Driven Chiller........................... 3Figure 2 - Site vs. Resource COP.................................. 4Figure 3 - Typical Gas Engine Service Schedule .......... 6Figure 4 - Good Engine Room Design .......................... 7Figure 5 - Engine Heat Recovery Schematic................. 8Figure 6 - Engine Heat Balance and Recovery ............. 9Figure 7 - Gas Engine-Driven Sales............................ 11Figure 8 - COP of Gas Engine-driven Chiller............. 12Figure 9 - IPVL Calculation Assumptions................... 13Figure 10 - Cities used for Cooling Analysis............... 19Figure 11 - Building Type and Size ............................. 19Figure 12 - Cooling Equipment Type Based on Size ... 20Figure 13 - Cooling Equipment Efficiencies ............... 21Figure 14 - Energy Cost Savings for Gas

    Engine-Driven vs. Standard EfficiencyChiller for Medium Office.......................... 25

    Figure 15 - Energy Cost Savings forGas Engine-Driven vs. StandardEfficiency Chiller for Large Office ............ 26

    Figure 16 - Energy Cost Savings forGas Engine-Driven vs. Standard Efficiency Chiller for Hospital.................. 27

    Figure 17 - Energy Cost Savings forGas Engine-Driven vs. StandardEfficiency Chiller for Hotel........................ 28

    Figure 18 - Energy Cost Savings forGas Engine-Driven vs. Standard Efficiency Chiller for Clinic...................... 29

    Figure 19 - Energy Cost Savings forGas Engine-Driven vs. StandardEfficiency Chiller for School...................... 30

    Figure 20 - Energy Cost Savings for GasEngine-Driven vs. Standard EfficiencyChiller for Large Retail ............................. 31

    Figure 21 - Energy Cost Savings for GasEngine-Driven vs. High EfficiencyChiller for Medium Office.......................... 32

    Figure 22 - Energy Cost Savings for GasEngine-Driven vs. High EfficiencyChiller for Large Office ............................. 33

    Figure 23 - Energy Cost Savings for GasEngine-Driven vs. High EfficiencyChiller for Hospital.................................... 34

    Figure 24 - Energy Cost Savings for GasEngine-Driven vs. High EfficiencyChiller for Hotel......................................... 35

    Figure 25 - Energy Cost Savings for GasEngine-Driven vs. High EfficiencyChiller for Clinic........................................ 36

    Figure 26 - Energy Cost Savings for Gas

    Engine-Driven vs. High EfficiencyChiller for School .......................................37

    Figure 27 - Energy Cost Savings for GasEngine-Driven vs. High EfficiencyChiller for Large Retail..............................38

    Figure 28- Energy Cost Savings for GasEngine-Driven vs Absorption Chillerfor Medium Office ......................................39

    Figure 29 - Energy Cost Savings for GasEngine-Driven vs Absorption Chiller for Large Office.........................................39

    Figure 30 - Energy Cost Savings for GasEngine-Driven vs. Absorption Chillerfor Hospital ................................................40

    Figure 31 - Energy Cost Savings for GasEngine-Driven vs. Absorption Chillerfor Hotel .....................................................40

    Figure 32 - Energy Cost Savings for GasEngine-Driven vs. Absorption Chillerfor Clinic ....................................................41

    Figure 33 - Energy Cost Savings for GasEngine-Driven vs. Absorption Chillerfor School ...................................................41

    Figure 34 - Energy Cost Savings for GasEngine-Driven vs. Absorption Chillerfor Large Retail ..........................................42

    Figure 35 - SIR for Gas Engine-Driven vs.Std. Eff. Elec. Chillers ................................44

    Figure 36 - SIR for various marginal gas costs forMedium Office, Gas Engine-Driven vs.Std. Eff. Chiller...........................................46

    Figure 37 - SIR for various marginal electric costs for Medium Office, Gas Engine-Drivenvs. Std. Eff. Chiller .....................................47

    Figure 38 - SIR for various marginal gas costs forLarge Office, Gas Engine-Driven vs.Std. Eff. Chiller...........................................48

    Figure 39 - SIR for various marginal electric costsfor Large Office, Gas Engine-Driven vs.Std. Eff. Chiller...........................................49

    Figure 40 - SIR for various marginal gas costs forHospital, Gas Engine-Driven vs.Std. Eff. Chiller...........................................50

    Figure 41 - SIR for various marginal electric costsfor Hospital, Gas Engine-Driven vs.Std. Eff. Chiller...........................................51

    Figure 42 - SIR for various marginal gas costs forHotel, Gas Engine-Driven vs.Std. Eff. Chiller...........................................52

    Figure 43 - SIR for various marginal electric costsfor Hotel, Gas Engine-Driven vs.Std. Eff. Chiller...........................................53

    Figure 44 - SIR for various marginal gas costs forClinic, Gas Engine-Driven vs.Std. Eff. Chiller...........................................54

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE V

    Figure 45 - SIR for various marginal electric costs forClinic, Gas Engine-Driven vs.Std. Eff. Chiller...........................................55

    Figure 46 - SIR for various marginal gas costs forSchool, Gas Engine-Driven vs.Std. Eff. Chiller...........................................56

    Figure 47 - SIR for various marginal electric costs forSchool, Gas Engine-Driven vs.Std. Eff. Chiller...........................................57

    Figure 48 - SIR for various marginal gas costs forLarge Retail, Gas Engine-Driven vs.Std. Eff. Chiller...........................................58

    Figure 49 - SIR for various marginal electric costs forLarge Retail, Gas Engine-Driven vs.Std. Eff. Chiller...........................................59

    Figure 50 - SIR for Gas Engine-Driven vs.Std. Eff. Elec. Chillers ................................60

    Figure 51 - SIR for various marginal gas costs forMedium Office, Gas Engine-Driven vs.High Eff. Chiller.........................................62

    Figure 52 - SIR for various marginal electric costs forMedium Office, Gas Engine-Driven vs.High Eff. Chiller.........................................63

    Figure 53 - SIR for various marginal gas costs forLarge Office, Gas Engine-Driven vs.High Eff. Chiller.........................................64

    Figure 54 - SIR for various marginal electric costs forLarge Office, Gas Engine-Driven vs.High Eff. Chiller.........................................65

    Figure 55 - SIR for various marginal gas costs forHospital, Gas Engine-Driven vs.High Eff. Chiller.........................................66

    Figure 56 - SIR for various marginal electric costs forHospital, Gas Engine-Driven vs.High Eff. Chiller.........................................67

    Figure 57 - SIR for various marginal gas costs forHotel, Gas Engine-Driven vs.High Eff. Chiller.........................................68

    Figure 58 - SIR for various marginal electric costs forHotel, Gas Engine-Driven vs.High Eff. Chiller.........................................69

    Figure 59 - SIR for various marginal gas costs forClinic, Gas Engine-Driven vs.High Eff. Chiller.........................................70

    Figure 60 - SIR for various marginal electric costs forClinic, Gas Engine-Driven vs.High Eff. Chiller.........................................71

    Figure 61 - SIR for various marginal gas costs forSchool, Gas Engine-Driven vs.High Eff. Chiller.........................................72

    Figure 62 - SIR for various marginal electric costs forSchool, Gas Engine-Driven vs.High Eff. Chiller.........................................73

    Figure 63 - SIR for various marginal gas costs forLarge Retail, Gas Engine-Driven vs.

    High Eff. Chiller ........................................ 74Figure 64 - SIR for various marginal electric costs for

    Large Retail, Gas Engine-Driven vs.High Eff. Chiller ........................................ 75

    Figure 65 - SIR for Gas Engine-Driven vs.Single Effect Absorption Chillers .............. 76

    Figure 66 - SIR for various marginal gas costs forMedium Office, .......................................... 78

    Figure 67 - SIR for various marginal gas costs forLarge Office, .............................................. 79

    Figure 68 - SIR for various marginal gas costs forHospital, .................................................... 80

    Figure 69 - SIR for various marginal gas costs forHotel, ......................................................... 81

    Figure 70 - SIR for various marginal gas costs forClinic, ........................................................ 82

    Figure 71 - SIR for various marginal gas costs forSchool, ....................................................... 83

    Figure 72 - SIR for various marginal gas costs forLarge Retail, .............................................. 84

    Figure 73 - Example Present Worth Calculation ........ 94Figure 74 - Range of Typical Scalars.......................... 96Figure 75 - Variable Effects on Scalar........................ 96

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE 1

    These Advanced Design Guidelines have been devel-oped by the New Buildings Institute in cooperation withSouthern California Gas Company to assist designers,program planners, and evaluators to make informeddecisions on the application and cost-effectiveness ofgas engine-driven cooling. There are two basic types ofgas chillers: engine-driven systems and absorptionsystems. This Guideline deals specifically with gasengine-driven systems. These Guidelines are intended tobe a step toward a comprehensive approach to designspecifications, which encompasses the full range ofefficiency options for a building.

    This Advanced Design Guideline is based on carefulevaluation and analysis of gas engine-driven cooling todetermine when it is appropriate, how it is best imple-mented, how cost effective it is, and how its energysavings are described. These Guidelines describeefficiency measures that are more advanced thanstandard practice, yet still cost effective in appropriateapplications. Design Guidelines are used by individualsand organizations interested in making buildings moreenergy efficient. They provide the technical basis fordefining efficiency measures used in individual buildingprojects, in voluntary energy efficiency programs, and inmarket transformation programs.

    It should be remembered that this Guideline documentdeals primarily with the comparison of a single effi-ciency measure and its baseline. This means that theanalysis assumes that all other features of the buildingare fixed. This is done primarily for clarity of theanalysis, and allows one to focus on the advantages andeconomics of the single measure.

    In reality, most new building design situations involvemultiple energy efficiency options. The cost effective-ness of one measure is often influenced by othermeasures. For example, increases in building envelopeinsulation can often reduce HVAC loads enough toreduce the sizing requirements for the heating andcooling equipment. It is not uncommon for the costsavings from smaller equipment to offset increasedinsulation costs.

    It is beyond the scope of this Guideline to attempt toaddress the interactions between measures, especiallybecause these interactions can cover a huge range ofoptions depending on the climate, the local energy costs,the building, and its systems. Nevertheless, the NewBuildings Institute recommends that building designersgive careful consideration to measure interactions and tointegrated systems design. This Guideline can provide

    the starting point by providing insight into the perform-ance of one measure.

    CHAPTER 1: PREFACE

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE 3

    Gas engine-driven chillers offer a unique and veryattractive opportunity for commercial building owners toshave electric demand charges and reduce operatingexpenses. Engine-driven systems have several potentialadvantages over electric motor-driven units. Amongthem are variable speed operation, high part loadefficiency, high temperature waste heat recovery fromthe engine, and reduced annual operating costs.

    Gas engine-driven systems use the same refrigerantcompression cooling process as conventional electric-powered systems. The only difference is that thecompressor is powered by a natural gas engine ratherthan an electric motor. Gas engine-driven chillers areavailable with reciprocating, screw and centrifugalcompressors. A Tecogen gas engine-driven chiller isshown in Figure 1.

    Source: AGCC

    Figure 1 - Gas Engine-Driven Chiller

    Although gas engine-driven chillers have been in usesince the 1960s, current research is resulting in betterperformance, lower maintenance requirements, andlonger operating lifetimes. Research and developmentefforts have also resulted in improved serviceability dueto the use of microprocessor controls, which facilitatepreventive maintenance, and allow remote monitoringand troubleshooting, and on-board diagnostics.

    Gas engine-driven chillers are more expensive topurchase than comparable electric motor-driven chillers,but they typically cost less to operate. Operating costsavings are primarily driven by electric demand charges.Operating costs are dominated by fuel costs, but alsoinclude maintenance costs. The reliability of gas cooling

    equipment has improved in the last few years andmaintenance requirements have decreased.

    A very important feature of engine-driven chillers isvariable speed control of chiller output. Engines aredesigned to operate over a wide range of speeds.Reducing the capacity of a compressor by slowing theshaft speed is the most efficient way to retain a highcoefficient of performance. By varying engine speedalone, partial cooling load capacities, down to approxi-mately 35%-65%, can be achieved efficiently withoutresorting to less efficient compressor capacity controlmechanisms.

    A. ApplicationsGas engine-driven chillers are used for space condi-tioning for a variety of building types, including

    hospitals,

    schools, universities and colleges,

    office,

    retail,

    manufacturing, and

    hotels.

    Gas engine-driven chillers can also be used for otherapplications such as process cooling, commercial andindustrial refrigeration and ice making. Governmentbuildings have been the top market segment for enginechillers. They typically have high energy costs and aremore willing to accept longer payback periods and lifecycle cost arguments than other building types. Theyalso often have internal staff familiar with and able tomaintain and service the equipment.

    The primary variable that drives the economics of gasengine-driven chillers is the electric demand charge.Ideal candidates for engine chiller applications are thosewhere the peak demand charge is high. Since cooling isgenerally the primary cause of sharp spikes in abuildings electric load profile, it is advantageous toinvestigate alternatives that can reduce this peak. Gascooling minimizes or flattens the electric peaks in abuildings electric load.

    The gas engine-driven chiller should be operated tomaximize electric peak-shaving in areas with highdemand charges or extended ratchet electricity rates.Base-loading the gas chiller is an attractive option inregions with high electric costs. This can be achieved

    CHAPTER 2: DESCRIPTION

  • CHAPTER 2: DESCRIPTION

    4 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    with a hybrid system, which uses an electric chiller forbase load, and the gas engine-driven chiller for peakloads.

    Engine-driven chillers can be economically installedsimply as a chiller or as part of an integrated cooling andheating facility. In many parts of the country, the costdifference between electricity and natural gas issufficient to justify engine-driven chillers. Additionalcost savings can be realized through the use of heatrecovery, since engine-driven chillers represent anexcellent opportunity to more fully utilize the energycontent of the fuel. Energy utilization efficiencies canexceed 75% by recovering heat from the engine as wellas generating chilled water.

    In summary, good applications for engine chillers havethe following characteristics:

    High demand charges

    Coincident need for air conditioning andheating

    Maintenance and service requirements areacceptable to building owner

    Payback period of 2 to 5 years is acceptable

    Other system design considerations include natural gasengine technology, heat recovery options, part-loadoperation and integration of engine-driven chillers tooptimize the energy efficiency of a facilitys cooling andheating plant.

    B. SizesGas engine-driven chillers are available for reciprocat-ing, screw and centrifugal compressors. Reciprocatingchillers, both air-cooled and water-cooled, are availableup to 200 tons. Air-cooled screw chillers are available inthe 100 to 400 ton size range, while water-cooled screwchillers are available up to 1,000 tons. Water-cooledcentrifugal chillers are available in sizes from 400 tonsup to 6,000 tons. Further detail of available equipmentis provided in Chapter 4, Section D, EquipmentManufacturers.

    C. BenefitsThe ability to vary engine speed to control chiller outputis the predominant advantage when considering the partload operation of the engine-driven chiller. From anefficiency perspective, reducing engine speed to achievebetter part load performance is advantageous both forthe engine and the compressor. Engine efficiency

    increases as shaft speed decreases, which positivelyaffects the COP.

    Gas engine-driven chillers have the following additionalfeatures:

    high temperature exhaust valves and seats

    water cooled exhaust manifolds

    low pressure natural gas fuel system

    optimum compression ratio design

    electronic ignition systems

    low emission package

    Microprocessor controls

    COPs up to 2.0

    They have considerably higher COPs than comparablegas-fired absorption cooling systems. The electricity useof the condenser water pumping and cooling tower fansis not as high, allowing them to be more competitivewith electric chillers. Due to the higher gas COPs ofengine-driven chillers, they are generally the best gascooling alternative in areas with high natural gas rates($0.70 to $1.00 per therm) such as the Northeast.

    The COP metric is also applied to electric chillers.However, since COP is based on site energy, it is notappropriate for comparing gas and electric chillerefficiencies.

    A better metric is the Resource COP, which accounts forthe source to site efficiency of the fuel, accounting forelectricity generation and transmission losses. Figure 2shows typical values for both electric chillers andabsorption chillers.

    Chiller Site COP Source-to-SiteFactor

    ResourceCOP

    Electric 2.0 - 6.1 0.27 0.54 - 1.65

    Engine 1.3 - 2.2 0.91 1.2 - 2.0

    Figure 2 - Site vs. Resource COP

    An advantage of engine-driven cooling equipment overelectric motor-driven is the ability to use the heatrejected from the engine during operation. Duringheating operation, the recovered heat can be used tosupplement the refrigeration cycle or to supply otherspace heating or process loads. The use of the enginewaste heat results in greater operating efficiencycompared to similar electric motor-driven units.

  • CHAPTER 2: DESCRIPTION

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 5

    D. LimitationsDespite the many benefits of gas engine-driven systems,there are some limitations and drawbacks.

    Gas engine-driven equipment requires more frequentmaintenance by knowledgeable technicians thanconventional electric motor-driven equipment. However,if properly serviced, engine-driven chillers haveextremely high reliability. The key to widespreadcommercialization of these systems will be the devel-opment of a maintenance infrastructure to provide low-cost service and retain high availability. Maintenanceissues are discussed in further detail in the followingsection.

    Additionally, gas systems can use significant amounts ofelectricity. For all central systems, both gas and electric,there is auxiliary energy use by the cooling towers,condenser water pumps and chilled-water pumps.Although the electricity use of these components in agas system is no different from an electric system, theelectric energy consumption must be included in theanalysis of the system.

    E. MaintenanceMaintenance of the refrigeration subsystem of anengine-driven chiller is the same as for electric chillers.The gas engine that drives the compressor requires dailychecks of engine oil and coolant levels. Long-termmaintenance includes oil and filter changes, replacingcoolant and spark plugs, testing batteries, checkingtiming, and making valve adjustments.

    Improvements in engine construction and reducedoperating speeds have reduced maintenance require-ments. Improvements include longer-lasting materialsfor spark plugs, valve and valve seat materials, andimproved oils and bearing materials.

    Many manufacturers provide maintenance contracts thatinclude routine maintenance and major overhaulsperformed by trained mechanics. Other than majoroverhauls, engine service is comprised of routineinspections/adjustments and periodic replacement ofengine oil, coolant and spark plugs. To ensure thatmaintenance is performed in timely manner, detailedoperating records should be kept.

    Figure 3 indicates typical recommended serviceintervals for natural gas engines including lubrication,cooling, ignition/electrical and fuel systems. Theseservice intervals assume that the chiller is installed in arelatively clean, dry environment, typical of mostapplications.

  • CHAPTER 2: DESCRIPTION

    6 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    SERVICE AT CALENDAR OR HOUR INTERVAL**Daily Monthly or 6 Months or 12,000 - 24,000 -

    750 hr* 4,000 hr* 15,000 hr* 30,000 hr*Engine Lubrication System

    Oil (engine/auxiliary) check level test replace - -Oil filter check P - replace - -Crankcase breather - check - -Oil Cooler - - - clean -

    Engine Cooling SystemCoolant check level check additives - replace -Coolant pump - - check - -Thermostats - - - replace -

    Ignition/Electrical SystemBatteries - check level - - -Spark plugs - check gap replace - -Timing - check - - -Alternator - - check - -Starting motor - - check - -

    Fuel SystemAir cleaner check - replace - -Air-fuel ratio - check - - -Control linkages - check - - -Gas regulator - check - - -Aftercooler - check - clean -Carburetor - - check rebuild -Turbocharger - - check rebuild -

    Engine MechanicalValve lash - check - - -Exhaust valve blow-by - check - - -Vibration damper - check - - -Crankshaft/camshaft - - - check -Cylinder heads - - - rebuild rebuildCrankshaft bearings/seals - - - - replacePiston rings/cylinder liners - - - - replaceEngine mounts - check - - -

    Engine AuxiliariesBelts and hoses - check - - -Safety controls - check - - -Driven equipment - - check - -

    ** Whichever comes first* Full load hours

    Source: ACCC Applications Engineering Manual for Engine-Driven Chillers

    Figure 3 - Typical Gas Engine Service Schedule

  • CHAPTER 2: DESCRIPTION

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 7

    F. Installation IssuesThe following issues need to be considered wheninstalling gas cooling equipment:

    engine room ventilation

    fuel supply system, and

    exhaust system

    Engine Room VentilationVentilation air must be supplied to the engine-drivenchiller for proper combustion and to remove heatradiated from the engine and exhaust piping surfaces.Approximately 3% to 6% of the energy input to theengine is lost to the surroundings from the enginesurface. The heat lost from piping and other sources candouble the amount of heat loss to the engine room.Because engine power is adversely affected by high inletair temperatures, sufficient air flow must be provided tothe engine so that the temperature rise in the engineroom does not exceed 15 - 20F. The engine roomtemperature should be less than 110F. Engine roomventilation is also required to protect electrical compo-nents and equipment from excessive temperatures thatcould negatively impact performance.

    Engine room ventilation must meet ASHRAE Standard1, Safety Code for Mechanical Refrigeration. Addition-ally, ventilation air must flow properly through themechanical room to provide effective cooling of theengine-driven chiller. To do so, the air should flow sothat it does not bypass the chiller, as shown in Figure 4.

    Chiller Unit

    Chiller Unit

    Chiller Unit

    Figure 4 - Good Engine Room Design

    Consideration must be given to the fuel supply pipingsystem. Gas piping to the building should be black iron.A flexible connector should be installed between the gasengine and the gas supply line.

    As part of the safety features built into the fuel supplysystem, a fuel shut-off valve should be installed thatautomatically ensures that the fuel flow to the engine isstopped when the engine is shut down either normally orin an emergency.

    Exhaust SystemThe primary function of the exhaust system is to removeproducts of combustion from the engine. The exhaustsystem is also designed to reduce engine exhaust noisethrough the use of mufflers and silencers. Proper exhaustsystem sizing and layout is crucial to minimize pressuredrop in the piping. Excessive back pressure causesengine power loss, poor fuel economy and high exhaustvalve temperatures. Allowable back pressure typicallyranges from 12 to 27 inches of water column, dependingon design engine speed, engine type and exhaust heatrecovery options. The exhaust system must vent to anappropriate outdoor location, away from air intakes,windows, or outdoor use areas.

    G. Heat RecoveryThe gas engine produces a substantial amount of thermalenergy that can easily be recovered from the enginecooling jacket and the engine exhaust. Effectiverecovery of this heat is an important consideration infully utilizing the fuel input energy to the engine. Byrecovering heat in the jacket water and exhaust,approximately 75-80% of the fuels energy can beeffectively utilized. The schematic in Figure 5 illustratesthe engine-driven chiller heat recovery system.

    As shown in Figure 6, heat recovered from the enginejacket accounts for up to 30% of the energy input and iscapable of producing 200F hot water. Almost all of theheat transferred to the engine coolant can be recovered,limited only by the efficiency of the heat exchange, andassuming that there is a demand for the heat.

    The other major source of heat is the engine exhaust.Exhaust temperatures of 850F - 1200F are typical.Only a portion of the exhaust heat can be recoveredsince exhaust gas temperatures are generally kept abovecondensation thresholds. Most heat recovery units aredesigned for a 300F - 350F exhaust outlet temperatureto avoid the corrosive effects of condensation in theexhaust piping. Exhaust gas can generate hot water toabout 230F or low-pressure steam (15 psig). There is

  • CHAPTER 2: DESCRIPTION

    8 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    up to 21% non-recoverable exhaust heat, assuming anexhaust stack temperature of approximately 300F -350F. For applications using condensing heat recoverysystems, additional heat can be recovered.

    Closed-loop systems are the most common configurationfor removing engine heat. They are designed to cool theengine by circulating coolant through engine passageswith an engine coolant pump. Most engine-drivenchillers are provided with an excess heat exchanger thattransfers engine heat to a cooling tower or radiator (aircooled). In heat recovery configurations, the excessheat exchanger is used to provide a secondary heat sinkin the event that demand for hot water is reduced whilethe chiller is operating.

    Another type of cooling system is the ebullient coolingsystem. An ebullient cooling system is designed to coolthe engine by natural circulation of the coolant without ajacket water pump. It is typically used in conjunctionwith exhaust heat recovery for production of low-pressure steam. Cooling water is introduced at thebottom of the engine where the transferred heat beginsto boil the coolant generating two-phase flow. Theformation of bubbles lowers the density of the coolant,causing a natural circulation to the top of the engine.The coolant at the engine outlet is maintained atsaturated steam conditions and is usually limited to250F and a maximum of 15psig. Inlet cooling water isalso near saturation condition and is generally 2 - 3Fbelow the outlet temperature. Uniform temperature

    throughout the coolant circuit helps to extend enginelife. The uniform temperature also contributes toimproved combustion efficiencies and reduced frictionin the engine.

    The recovered heat can be used to generate steam or hotwater, or it can be used directly in certain industrialapplications. Recovered heat is typically used for spaceheating, reheat, domestic hot water and absorptionchilling. The thermal energy can be used for domestichot water heating or steam generation without additionalfuel consumption.

    Shaft Power (30%)to drive chiller

    compressor

    Exhaust (15%)

    Jacket Coolant (30%)

    Exhaust (21%)Not Recovered

    Radiation (4%)

    Fu

    el I

    npu

    t E

    ner

    gy (

    100%

    )

    Rec

    over

    able

    E

    ner

    gy (

    75%

    )

    Figure 6 - Engine Heat Balance and Recovery

    HeatRecovery

    Engine

    Evaporator

    Condenser

    Compressor

    Exhaust GasHeat Exchanger

    Engine Dump Heat ExchangerDriveline Cooling Manifold

    GearBox

    Chilled W ater

    Hot W ater

    Source: AGCC

    Figure 5 - Engine Heat Recovery Schematic

  • CHAPTER 2: DESCRIPTION

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 9

    H. Hybrid SystemsA hybrid system includes a gas chiller and an electricchiller. A hybrid system allows for preferential loadingof either the gas or electric chiller. Typically, the gaschiller is used during peak electric demand periods,when the cost of electricity is high. The control of ahybrid system allows the operator to select the mostcost-effective and appropriate fuel source based on bothcost and availability.

    The restructuring of the utility industry adds significantcomplexity and uncertainty to the economics of chillersystem design and operation. It is expected that therewill be greater variety in electric rates includingseasonal and time-of-use rates, and real-time pricing.The key is operational flexibility. The use of gasengine-driven chillers eliminates the high incrementalcost of electricity, while a hybrid systems maximizes theflexibility of an all-energy plant.

    With restructuring of the electric utility industry,demand for hybrid gas/electric cooling systems willlikely increase. According to Gary Nowakowski, of theGas Research Institute (GRI), a hybrid system allows theuser to hedge against future energy rate uncertaintiesand choose the most economical energy source fromhour to hour. The move toward real-time pricing willfavor those customers, both gas and electric, that haverelatively flat energy load profiles. Gas cooling repre-sents an efficient way to level the energy profiles andgain leverage when purchasing energy.

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE 11

    A. HistoryDuring the 1930s and 1940s, gas engine-driven coolingsystems dominated the U.S. market. In the 1950s and1960s electric equipment began competing with gasequipment due to increased electric chiller efficienciesand the growing electric utility infrastructure.

    Engine-driven chillers still were successfully marketedby the gas utilities and manufacturers in the 1960s. Thegas companies used promotional rates and subsidiesprograms to entice buyers. The outstanding operatingeconomics were sufficient to place nearly 2,000 units inthe field between 1962 and 1970. The majority of thesewere located in Texas, presumably due to higher coolingloads and the availability of cheap gas. Counteractingthis, innovations in compressors, electric motors, andcontrols increased the performance and decreased thecost of electric cooling systems.

    In the 1970s, price controls and other governmentrestrictions helped push electric chiller sales ahead ofgas chillers. The gas crunch of the seventies curtailedgas cooling promotion and forced prospective buyers toselect conventional electric systems.

    The Gas Research Institute (GRI) initiated a program in1984 to develop commercial chillers using the engine-driven concept. GRI is a not-for-profit organization thatmanages R&D programs for the benefit of gas consum-ers and the natural gas industry. As part of the program,an extensive study was conducted to evaluate theproblems of past systems, the potential impact ofengine-driven chillers on the HVAC market, and thedesign considerations, which would lead to favorableeconomics and commercialization potential.

    B. Current Market Share

    The potential for the gas engine-driven chiller isattractive in regions with high electric demand charges.The gas engine chillers capability to operate efficientlyat part load makes it an ideal peaking unit.

    According to GRI, sales of natural gas engine-drivenchillers in the commercial market quadrupled between1994 and 1995, from about 7,000 tons of cooling tomore than 30,000 tons per year. By the end of 1996,sales were almost 50,000 tons per year. During 1997,engine chiller sales increased by about 20%, to an

    estimated 60,000 tons from 1996's 50,000-ton record.The fast growth rate is due to the market entry of majorHVAC manufacturers, a growing awareness of gascooling benefits, and a relentless business trend towardreducing costs, including energy bills. At current energyrates, about 50% of all U.S. commercial energy userscould realize more than a 20% return on investment witha gas-powered chiller.

    Natural gas equipment including both absorption andengine-driven units accounts for 8 to 10 percent of themarket for larger chillers. Gas engine-driven chillersrepresent about 2% of the total market. This number isexpected to grow, however, as a result of increasedefficiency, reliability, and accessibility of gas equip-ment. Figure 7 shows gas engine-driven chiller sales for1994 through 1997. The y-axis is the number of unitssold in rated tons times 1,000. For example, in 1994approximately 7,000 tons were sold. In 1997, approxi-mately 70,000 tons were sold. This indicates a tenfoldincrease in sales.

    Sca

    les

    (To

    ns

    of

    Co

    olin

    g)

    0

    10

    20

    30

    40

    50

    60

    70

    94 95 96 97

    Year

    Figure 7 - Gas Engine-Driven Sales

    C. Standards and RatingsCurrently there are no state or federal standards thatregulate gas engine-driven cooling systems. However,there are several metrics that are used to define engine-driven chiller efficiency, including:

    COP

    IPLV

    APLV

    Coefficient of Performance (COP)The performance of gas cooling equipment is usuallyrated in terms of COP, defined as cooling output, or

    CHAPTER 3: HISTORY AND STATUS

  • CHAPTER 3: HISTORY AND STATUS

    12 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    refrigeration effect, in Btu, divided by energy input, inBtu. This same metric is applied to electric chillers, butsince it is based on site energy, it is not appropriate forcomparing gas and electric chiller efficiencies.

    Engine-driven chillers have the highest coefficient ofperformance of any gas cooling product. This perform-ance advantage enables engine-driven chillers tocompete very effectively with electric chillers in manyparts of the country.

    Engine-driven chillers, as well as electric chillers, arerated to Air Conditioning and Refrigeration InstituteARI-550-92 conditions as listed below:

    Chilled Water Conditions:

    44F chilled water supply temperature

    54F chilled water return temperature

    2.4 gpm/ton chilled water flow

    Water Cooled Condensers:

    85F condenser water supply temperature

    95F condenser water return temperature

    3.0 gpm/ton condenser water flow

    Air Cooled Condensers:

    95F air supply temperature

    20F temperature differential between air sup-ply and condensing refrigerant

    2F refrigeration system loss to the condenser

    Figure 8 provides a typical range of engine-drivenchiller COPs with and without heat recovery.

    Heat Recovery Option COP at Full Load

    No Heat Recovery 1.2-2.0

    Jacket Water HeatRecovery

    1.5-2.25

    Jacket Water and Ex-haust Heat Recovery

    1.7-2.4

    Figure 8 - COP of Gas Engine-driven Chiller

    Heat recovery from the jacket coolant and exhaust gaswill boost overall energy utilization. The COP of anengine-driven chiller can reflect this heat recoverybenefit as shown in the following equation:

    COP = System Cooling Load + Recovered HeatEngine Fuel Input

    The heat recovered is added to the cooling loadproduced by the engine-driven chiller, thereby increas-ing useful thermal output and the COP.

    There is no industry standard on how to calculate theCOP of an engine-driven chiller when considering heatrecovery partly because the economic value of therecovered heat is so variable. Some manufacturerscalculate COP assuming that the recovered heat is fullyutilized for domestic hot water, space heat or processneeds. Others assume that the recoverable heat is usedto produce additional cooling in a single-effect absorber.The former definition is generally preferred andprovides a higher calculated COP since the efficiency ofthe absorber does not deduct from the value of therecovered energy.

    Integrated Part Load Value (IPLV)Another measurement of chiller efficiency is IntegratedPart Load Value, IPLV. IPLV is an industry standardfor calculating an annual COP based on a typical loadprofile and the part load characteristics of chillers. Itwas originally conceived as part of ANSI/ASHRAEStandard 90.1 (Standard for Energy Efficient Design ofNew Nonresidential and High-Rise Residential Build-ings) in response to a need for directly comparingmanufacturers part load data. The method assumes thatthe chiller operates at a specific part load for a specificnumber of hours during the year, according to thefollowing equation:

    IPLV = 1 0.17 + 0.39 + 0.33 + 0.11

    A B C D

  • CHAPTER 3: HISTORY AND STATUS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 13

    Figure 9 provides the assumption and appropriate valuesfor the equation.

    ChillerLoad(%)

    ChilledWaterReturn

    Temp (F)

    Mfgr.RatedCOP

    Part LoadHours (%)

    100 85 A 17

    75 78.75 B 39

    50 72.5 C 33

    25 66.25 D 11

    Figure 9 - IPVL Calculation Assumptions

    COP ratings A, B, C and D at each part load conditionare obtained from the chiller manufacturer and should bederived from actual chiller tests. Note that the calcula-tion allows for a 2.5F reduction in the entering coolingwater temperature for every 10% drop in cooling load.A lower entering cooling water temperature correspondsto part load (reduced) cooling demand, which resultsfrom a drop in ambient temperature.

    Engine driven chillers have excellent IPLV ratings. Partload operation of an engine driven chiller means thatengine speed is reduced to slow the compressor speed inresponse to a reduced cooling load. Reducing enginespeed means that the engine is operating at greaterefficiency which contributes to a higher IPLV. For thisreason, engine driven chillers have better part loadperformance gains than constant speed electric motordriven chillers (hermetic or open drive).

    Although IPLV is a useful way to compare differentmanufacturers chiller models, it probably doesntrepresent actual operating conditions. For applicationswhere cooling load is not significantly affected byambient temperature conditions, (e.g., cooling load isdominated by internal gains) this estimate of part loadperformance may not provide accurate results. Chillerperformance should be modeled to actual building loadprofiles tailored to site-specific ambient conditions.

    Applied Part Load Value (APLV)The Applied Part Load Value, APLV is calculated usingthe same IPLV formula, except that actual chilled andcondenser water temperatures and flow rates are used.The advantage of using the APLV over the IPLV, is thatthis rating more closely approximates actual operatingconditions imposed on the chiller. The disadvantage is

    the additional performance data that needs to becollected.

    D. Economics/Cost EffectivenessThe economics of gas-fueled cooling systems vs.electric chillers are driven by the additional investmentcost and several factors influencing operating cost,including:

    relative costs of the electricity and gas, andtheir billing structures,

    relative performance characteristics,

    operating characteristics, and

    relative maintenance costs.

    The first three factors are discussed in the followingsections and combined to produce estimates of AnnualEnergy Savings. Annual operating savings include anenergy component and a comparison of O&M costs.

    Energy Rates and Billing StructureEnergy rates and billing structure have a major impacton economic evaluations of gas versus electric coolingequipment. Energy rates include:

    Electric demand, $/kW

    Electric energy, /kWh

    Gas energy rate, $/MMBtu (or therms)

    It is essential that the complete utility rates and ratestructures are used for an accurate economic analysis.Utility rate structures may include one or more of thefollowing:

    Block Rates - The electric block rates maybe in termsof kWh, with different rates for various levels of energyconsumption. It may also be stated in kWh per kW ofdemand. In this case the kWh rate is a function ofdemand. A lower demand typically results in a largeamount of kWh at a lower rate. A high demand resultsin a small amount of kWh at a lower rate. Typically,although not always, the unit price per kWh increases asdemand increases.

    Time-of Use Rates - the electric rate may vary depend-ing on the time of day. The time-of-use rate is typicallydescribed in terms of on-peak and off-peak, andsometimes partial peak.

    Ratchets - the electric rate may include a demandratchet, which allows for a variation on how the demandkW is defined.

  • CHAPTER 3: HISTORY AND STATUS

    14 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Seasons - some utilities have different summer andwinter rates.

    Taxes - applicable taxes and franchise fees, which canbe over 10% in many areas.

    Special Rates - for gas cooling equipment or specialload-management electric rates are sometimes available.

    Using average electric and gas costs is rarely adequateto capture the cost of operating cooling equipment,especially when the rate structure includes demandcharges or declining blocks. The marginal electric pricefor cooling has a larger demand component relative tousage, which drives up the unit price. The details of theactual electric rates must be considered in the totalanalysis of chiller system operating costs.

    Performance CharacteristicsWhen comparing gas and electric cooling options thereare several equipment performance characteristics thatmust be considered:

    Electric chiller seasonal COP and peak loadCOP,

    Gas cooling equipment seasonal COP,

    Gas and electric differential auxiliary powerrequirements, seasonal and peak, and

    Gas and electric differential O&M costrequirements, $/ton hour.

    Miscellaneous electric loads, such as the engine coolantand oil pumps, should be included in the calculation ofannual savings. The energy required to reject excessengine heat to a radiator or a cooling tower should alsobe included. In practice, however, these parasitic lossesare a small percentage (typically less than 3%) of thesavings achieved by the gas engine-driven chiller.

    Operating CharacteristicsOperating schedules for building types vary. Forexample, HVAC equipment for office buildingsgenerally are operated approximately 10 12 hours perday, five days per week. Equipment in hospitals willoperate near full load for much of the day and atreduced, but still significant load for the remainder ofthe day. The descriptions of the building types used inthe analysis, provided in the appendix, include theassumed operating schedules.

    Annual energy savings need to be large enough toovercome higher initial costs and potentially highermaintenance costs for gas-engine driven chillers to becost-effective. Annual energy savings will be a function

    of the operating schedule. An operating schedule thathas a significant number of hours where the equipmentruns at part load, favors gas engine-driven chillersbecause of their excellent part load performance.However, operating schedules that require equipment torun at full load for relatively few hours and not at all formost hours will result in too little annual energy savingsto realize an acceptable payback for most businessrequirements.

    Estimating Annual Energy SavingsTo estimate annual energy savings, the performancecharacteristics of each chiller alternative must becarefully compared. Part load performance characteris-tics are essential for predicting energy savings ade-quately. It is part load operation that distinguishesengine-driven chiller performance, significantlycontributing to energy efficiency.

    The customary approach to analyzing chiller economicshas been to employ equivalent full load hour method-ology. Equivalent Full Load Hours (EFLH) are definedas the total cooling load supplied over the cooling load(ton/hours) divided by the cooling equipment capacity(tons). Part load operation is modified to obtain theequivalent of running at full load. While this methoddoes not reflect the efficiency of part load operation, itdoes simplify economic comparison. Because theengine chiller has superior part load performance, itdoes not benefit from this approach and the results areconsequently conservative. Longer hours of operation atpart load conditions will increase the energy savingsbenefit of engine-driven chillers.

    Since the economics of gas cooling are highly dependenton operating hours, accurate analysis requires a detailedbuilding simulation. A comprehensive analysis shouldbe done with an hourly simulation model, such as DOE-2, HAP, or TRACE, which predicts when, where andhow much cooling is required for the building.

    The current publicly available version of DOE-2.1Econtains performance simulation modules for:

    direct-fired absorption chillers,

    natural gas engine-driven chillers, and

    gas engine-driven air conditioners and heatpumps.

    These models accurately adjust for the part loadperformance and variable speed operation of gas coolingequipment as well as electric options.

  • CHAPTER 3: HISTORY AND STATUS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 15

    E. Equipment ManufacturersThere are several manufacturers and packagers ofengine-driven chillers.

    Caterpillar and Waukesha actively promote theuse of their engines in cooling configurationswith Carrier, York, Trane, Vilter, Bell & Gos-sett, Ingersoll Rand, Frick, and Dunham Bushcompressor packages.

    Napps Technology offers split system units inthe 15 to 25 ton range.

    Cummins Southwest offers built-up gas chillersystems from 55 to 200 tons.

    Tecogen makes air-cooled units in the 50-120ton size range, water-cooled units in the 125-350 ton range and industrial engines between500 and 1,000 tons

    York International makes engine chillers rang-ing from 400 tons up to 2,100 tons.

    Alturdyne Energy Systems offers an extensiveproduct line of engine chillers ranging from 25tons up to 3,500 tons.

    The Trane gas Powered CentraTraVac GPC iscomposed of centrifugal chiller driven by aWaukesha engine.

    Industrial Heat Recovery Equipment (IHRE),make 100 to 1,100 ton engine chillers.

    Tecogen and York Intl. currently have the largest marketshare for gas engine-driven chillers.

    F. Equipment Installations

    Installations of gas engine-driven chillers include avariety of building types including, hotels, hospitals,schools, office buildings, shopping centers, apartmentbuildings, industrial plants, and ice rinks. Following areseveral examples of gas engine-driven chiller installa-tions:

    A.M. Best Company, Oldwick, New Jersey

    In the spring of 1995, three new Alturdyne engine-driven chillers were installed in the A.M. Best Com-panys 105,000 sq. ft. office. Two 100-ton and one 130-ton engine-driven chillers replaced two existing 150-tonelectric centrifugal chillers. The company realizes a netenergy cost savings during the cooling season, fromApril to October, of approximately $42,800.

    "We knew it was time to replace the aging chillers,"explains C. Burton Kellogg, II, senior vice president forA.M. Best. "After learning about all the environmentaland economic advantages of the Alturdyne chillers, wedecided to go the natural gas route."

  • CHAPTER 3: HISTORY AND STATUS

    16 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    J.C. Penny Department Store,Atlanta, GA

    The installation at the 16,500 sq. ft. Cumberland MallJ.C.Penney store in December 1994, consisted of a 250ton engine-driven chiller. The store saves nearly$55,000 in energy costs annually.

    Carpenter's Home Church,Lakeland, Florida

    The 167,000 sq. ft. church, completed in January 1985,includes a bookstore, child care center, wedding chapel,offices, and a radio station. In July 1987, two 150-tonTecochill chillers were installed in an old boiler room.

    "When we were building the church, the electric utilitygave us an estimate on what we could expect to pay forcooling the facility," says Church Comptroller JoePerez, "They quoted figures around $22,000 per month.Our highest bill with the Tecochill chillers has been$12,000.

    "We've always performed our own maintenance on thechillers," says Facilities Engineer Jack Collins. Oneengine has run for 24,000 hours and the other unit for22,000 hours. The life span is supposed to be 20,000hours before a complete overhaul is required.

  • CHAPTER 3: HISTORY AND STATUS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 17

    Peachtree Tower, Atlanta, GA

    Three 150 ton engine-driven chillers were installed inthe 418,000 sq. ft. high rise condominium complex in1993, replacing an aging electric chiller. The complex,which has 335 units, saves around $65,000 annuallythrough reduced demand charges and an additional$5,000 from engine heat recovery which is used fordomestic hot water heating.

    Boston YMCA, Residential/Hotel Facility

    The 106,000 sq. ft. YMCA building, built in 1992, has apool, exercise room, saunas, basketball court, and 140living quarters, some with kitchenettes. The 150 tonengine chiller operates 12 months per year. Waste heatis used to heat the swimming pool, and to provide hotwater for the laundry. Savings are estimated at $25,000per year over an electric chiller.

    The system is tied by modem back to the manufacturer.The technicians are constantly monitoring our system.Theyre able to see any potential difficulty before it everhas a chance to happen, says Lou Falzarano, Mainte-nance Director at the YMCA.

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE 19

    A. OverviewGas engine-driven chillers were compared to thefollowing chiller options:

    Standard efficiency electric screw orcentrifugal

    High efficiency electric screw or centrifugal

    Indirect-fired single effect absorption

    The analysis is structured to provide typical valuesthat can be used as a screening tool during schematicdesign of a building or as guidance on equipmentefficiency issues for voluntary programs or energy codebodies. The results of a detailed energy and ratesanalysis, for seven building types in ten cities, have beendistilled down to a series of graphs.

    The cities and buildings are representative of the rangeof climates and building occupancies where gas coolingoptions would be used. The list of cities, sorted byCooling Degree Day (CDD) is provided in Figure 10.Information on building type and size are provided inFigure 11. The economic analysis is of course dependentupon gas and electric rates. Building descriptions andcity specific utility rates are provided in the Appendix.

    The results are graphed for various gas rates and variouselectric rates. Due to the complexities of the interactionsbetween fuel type usage and utility rates, it was notpossible to develop typical gas-to-electric cost results.These graphs can be used, as will be shown by examplein the following chapter, to determine relative increasein gas consumption and relative decrease in electricconsumption, when comparing a gas chiller to anelectric chiller. The results of separate fuel type analysiscan then be combined to provide a complete picture ofthe savings opportunities.

    City CDD50

    San Francisco 2,883

    Chicago 2,941

    Washington DC 3,734

    Los Angeles 4,777

    Atlanta 5,038

    San Diego 5,223

    Riverside 5,295

    Fort Worth 6,557

    Phoenix 8,425

    Miami 9,474

    Figure 10 - Cities used for Cooling Analysis

    Figure 11 shows the building types included in theanalysis, along with the building size in square feet, andthe cooling equipment size in tons. The range ofequipment sizes represents the variation in cooling loadfor the cities analyzed. The sizing of the cooling plantfollows ASHRAE 90.1R ECB guidelines with a 20 %oversizing margin.

    Type Size(Sq Ft)

    Cooling(tons)*

    Medium Office 49,000 100 - 143

    Large Office 160,000 408 - 573

    Hospital 272,000 384 - 519

    Hotel 315,000 645 - 891

    Out-PatientClinic

    49,000 90 - 111

    SecondarySchool

    50,000 90 - 205

    Large Retail 164,000 165 - 393

    *Cooling plant capacity includes 20% additional oversizing

    Figure 11 - Building Type and Size

    CHAPTER 4: ANALYSIS

  • CHAPTER 4: ANALYSIS

    20 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    As shown in Figure 12, the type of electric equipment,either screw or centrifugal, used as a comparison, wasdependent on the size. Figure 13 shows the standard andhigh efficiencies assumed for the various types ofchillers.

    Size (tons) Type

    100 - 300 Screw

    >300 - 600 Screw

    >600 Centrifugal

    Figure 12 - Cooling Equipment Type Based on Size

    Because of the complexities and individual nature ofhybrid systems, results of any hybrid systems analysiscannot be generalized. They were therefore intentionallynot included in this analysis. However, if the resultsindicate that a gas engine-driven chiller is cost-effective,or even marginally not cost-effective, a hybrid systemunder the same conditions, will typically be cost-effective.

    B. Energy SavingsEnergy savings were calculated using detailed DOE-2.1E building simulation models. The models providecomprehensive data on energy use and savings. Themodeling included a complete comparison of systemcomponents, including auxiliary equipment such ascooling towers, fans and pumps.

    The graphs in the following chapter present the energysavings for each of the cities for a range of marginal gasand electrical prices. The graphs present the annualenergy cost savings, in dollars per year, versus themarginal cost of gas, in dollars per therm, or themarginal cost of electricity in dollars per kWh. Themarginal energy cost, gas or electric, is calculated asenergy cost savings, in dollars, divided by energysavings in therms or kWh. The marginal cost accountsfor varying rates that may apply based on total usage.

    C. Cost EffectivenessCost effectiveness is based on the calculation of theSavings to Investment Ratio (SIR). SIR is defined as theLife Cycle Cost (LCC) savings, in dollars, divided bythe incremental measure cost per unit capacity, indollars per ton capacity, as shown in the followingequation:

    SIRLCC Savings

    Incremental Cost=

    The SIR uses an investment model over the life of theequipment rather than the simplistic and short rangeperspective of simple payback.

    The LCC savings describe the present worth of theenergy cost savings over the life of the investment. If theLCC savings are greater than the incremental cost, thenthe SIR will be greater than one and the measure isassumed to be cost effective.

    Savings to Investment Ratios (SIRs) indicate the costeffectiveness of the equipment selection depending uponseveral factors including:

    building type,

    equipment,

    climate,

    utility rate, and

    scalar ratio.

    Specific equipment cost information is provided in theAppendix. Additional first cost and maintenance costswere applied to the cost-effectiveness model, including:

    additional cooling tower capacity for engine-driven chiller adds $15-$20/ton to first cost.

    additional boiler capacity for single effect ab-sorption adds $50-$150/ton to first cost.

    the maintenance cost premium for engine-driven versus electric chiller reduces operatingcost savings by $10-$20/ton/yr. This numberwill be higher for buildings with long runhours, which require maintenance at shortertime intervals.

    Another element of the cost for gas engine-drivenchillers is the potential savings from interactions withother building elements. For example, installing a gasengine-driven chiller may reduce the buildings electricload enough to allow for downsizing of the electricservice drop and load center. These savings could besignificant but are not included due to the variabilitybetween installations.

    The scalar ratio is a single term that combines discountrate, period of analysis, and fuel escalation. A scalarratio is a mathematical simplification of life cyclecosting (LCC) analysis. The first year savings aremultiplied by the scalar to arrive at the life cyclesavings. In technical terms, the scalar ratio representsthe series present worth multiplier. A more detaileddescription of the scalar ratio is provided in theAppendix.

  • CHAPTER 4: ANALYSIS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 21

    Different scalars have been used to evaluate the cost-effectiveness based on different economic assumptions.Typical values of the scalar are in the 8 to 16 range.This approach has the virtue that different life cyclecosting criteria, and different scalars may be applied tothe results.

    Standard Efficiency High EfficiencyEquipment Type & Size

    COP kW/ton COP kW/ton

    Electric Screw, 150 to 300 4.2 0.84 4.90 0.72

    Electric Centrifugal, >300 5.2 0.68 6.01 0.58

    Single Effect Absorption - - 0.60 5.86

    Engine-Driven Screw - - 1.30 2.70

    Engine-Driven Centrifugal - - 1.85 1.90

    Reference: ASHRAE 90.1R Minimum Efficiency and Efficiency as of Jan, 2000

    Figure 13 - Cooling Equipment Efficiencies

  • GAS ENGINE-DRIVEN CHILLERS GUIDELINE 23

    A. Using the GraphsThe following pages contain families of graphs thatdescribe the performance of gas engine-driven chillersin a variety of cities and building types. As described inChapter 4, these graphs were developed from DOE-2.1Eruns done for representative prototype buildings usingthe actual utility rate structures currently published foreach of the cities. The graphs can save the reader agreat deal of analysis work, and can provide goodinformation about when and where of gas engine-drivenchillers can be cost effective.

    Each of the lines on the graphs represents the energysavings potential of the prototype building in one of theten cities studied. Markers on each line indicate currentlocal gas and electric rates for each city. By followingthe line on the graph, the results can be extrapolated todifferent utility rates.

    Annual Energy Cost Savings GraphsTwo sets of energy cost savings are calculated for eachbuilding type. One is for a range of marginal gas costsand a fixed marginal electric cost. The other is for arange of marginal electric costs based on a fixedmarginal gas cost.

    The top graph in Figure 14 is typical of the annualenergy cost savings vs. marginal gas cost graphs. Thebottom graph is for the same conditions showing theenergy cost savings vs. marginal electric costs. Theseparticular results are for the medium office buildingprototype. The comparison is between a gas engine-driven chiller and a standard efficiency electric screwchiller.

    The horizontal x-axis of these graphs is the marginalcost of gas, in dollars per therm, or the marginal cost ofelectricity, in dollars per kWh. Marginal cost is the costcharged, under the local utility rate structure, for thosekilo-Watt/hours that are saved by the use of the gaschiller. For the case of gas rates, marginal cost repre-sents the costs charged per therm for the increase in gasconsumption. The marginal cost does not include theutility basic service charges or other charges that arecommon to both equipment scenarios.

    The vertical y-axis shows the annual energy costsavings, in dollars per year, between the base equipmentand the gas engine-driven chiller.

    As shown on the top graph, as gas prices increase, theenergy savings associated with an engine-driven chillerdecrease. Conversely, as electric prices increase, savingsfrom the gas chiller increase, as shown in the bottomgraph.

    For example, as shown in Figure 22, Chicago isrepresented by a solid diamond marker. In this example,the prototype large office building in Chicago has amarginal gas cost of approximately $0.37 per therm, anda marginal electric cost of approximately $0.11 kWh.The gas engine-driven chiller would save approximately$14,000/year compared to a high efficiency screwchiller.

    The slope of the line represents the rate of change inannual energy cost savings for each increment ordecrement in the marginal cost of energy. In theChicago example, if gas were to increase to $0.45 pertherm, a 20% increase, the energy cost savings woulddecrease to approximately $12,000 per year. Con-versely, if the electric rate increased to $0.20, thesavings would increase to $32,000 per year.

    The cases shown on this graph can also be used toestimate savings for other cities with comparableclimates. For example, the Chicago line would also bereasonably representative of Milwaukee or Detroit orOmaha. The gas costs in these other locations may bedifferent than Chicago, but by entering the graph at thex-axis value that represents the costs in the otherlocation, an estimate of the savings can be obtained.

    Cost Effectiveness GraphsThis section presents the cost effectiveness graphsdeveloped for various utility rates and locations.

    The SIR is used as the figure of merit for cost effective-ness, as described in Chapter 4. It is the ratio of the lifecycle cost (LCC) savings to the incremental first cost, asshown in the following equation:

    SIRLCC Savings

    Incremental Cost=

    If the LCC savings are greater than the incremental cost,then the SIR will be greater than one and the investmentis a sound one. Thus, any point on the graph that isabove the 1.00 point on the vertical axis is a goodinvestment.

    CHAPTER 5: DESIGN ANALYSIS GRAPHS

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    24 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Calculating the LCC savings can seem complicated toanybody unfamiliar with present worth analysisprinciples. It involves several variables, including thelifetime of the investment, the rate of increase in energycosts, and the rate of economic inflation. These factorshave been combined into a single numeric parametercalled the scalar ratio, or scalar, as described inChapter 4.

    The graphs in Figure 36 are typical of the savings-to-investment ratio (SIR) as a function of marginal gascosts graphs for scalars of 8, 12, and 16. Figure 37 isan example of the SIR as a function of marginalelectric costs graphs. For each of the SIR graphs,particular scalar and incremental equipment values areused. The top graph in Figure 36 is for a scalar of 8,and the incremental equipment cost is $369/ton ofchiller capacity. There are different sets of graphs foreach of the different building types studied.

    Each graph enables one to quickly determine the citieswhere the gas engine-driven chiller is currently costeffective. If the marker for the city is above the 1.00SIR line, its cost effective. If the marker is not quiteover the 1.00 line, then one can see how much of anincrease in marginal gas cost would be needed to bring itover the line.

    For example, if one were comparing a gas engine-drivenchiller to a high efficiency chiller for a large office for ascalar of 8, in Miami (marked with an X in Figure 53),the SIR would be 0.80, which is not cost effective.However, if the marginal gas rate were approximately$0.55, the gas cooling option would be cost-effective.

    As with the previous graphs, one can also apply thesegraphs to other cities by selecting one of the ten citieswhose climate conditions are most similar and movingto the point on that line, which corresponds to the gas orelectric costs in the other city.

    These graphs can be adjusted for different incrementalequipment costs. For example, the SIR for a scalar of 8for Miami, shown in the graph in Figure 54, is based onan incremental cost of $369/ton. This value is thedenominator of the SIR values plotted on this graph. Ifthe incremental cost for a particular installation wasinstead $450/ton, then the SIR value from the graphwould be adjusted to reflect the new cost. In this case,an SIR value of 0.80 from the graph would be multipliedby 369/450 to arrive at an adjusted SIR of 0.66. If,instead, the incremental cost was $225/ton, the adjust-ment factor would be 369/225, for an adjusted SIR of1.31, which makes the gas option cost effective. Theadjustment factor will always have a numerator of 369and a denominator of the new incremental equipment

    cost, in dollars per ton capacity, as shown in thefollowing equation:

    Further review of the Cost-Effectiveness, or SIR graphs,shows that for a large office, Figure 53, an engine-drivenchiller compared to a high efficiency electric chiller iscost-effective based on a scalar of 8 for all cities exceptMiami. Using a scalar of 12, gas cooling also becomescost-effective in Miami. The cost-effectiveness resultscan be obtained from either the gas or the electric basedgraphs.

    The following pages contain the full set of graphscomparing gas engine-driven chillers to other coolingoptions. For each comparison there are different energyand equipment costs, and different economic criteria.

    Some of the graphs have no or almost no savings curveson them, while others are apparently missing curves forone or two cities. In these cases the energy savings areso great that the curves are literally off the scale. Forexample, in Figure 37, the graph for SIR comparing gasengine driven chillers against standard efficiencychillers with a scalar of 12, shows curves for only fourcities, and only one of them, Miami, has the markershowing (above 1.0). This technology can be assumedto be cost effective for these conditions.

    A singular exception to the above discussion is thegraph showing gas driven chillers versus high efficiencychillers in hospitals (Figure 55). In this case, gas ratesare high enough and electric rates low enough in Miamithat there are no energy savings for the technology.Savings/Incremental Equipment Cost is a negativenumber, and the marker for Miami is below the x-axis ofthe graph.

    In any case where the marker for a city does not appearon the line, you can simply estimate where the marketwould be based on the local marginal cost of gas and anextension of the citys SIR curve.

    Actual

    graphgraphActual Cost

    CostSIRSIR =

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 25

    B. Energy Savings Graphs

    Gas Engine-Driven Chiller vs.Standard Efficiency Electric Chiller

    Figure 14 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for Medium Office

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Medium Office

    $0

    $2,000

    $4,000

    $6,000

    $8,000

    $10,000

    $12,000

    $14,000

    $16,000

    $18,000

    $20,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therm)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Medium Office

    $0

    $10,000

    $20,000

    $30,000

    $40,000

    $50,000

    $60,000

    $70,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    26 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Figure 15 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for Large Office

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Large Office

    $0

    $10,000

    $20,000

    $30,000

    $40,000

    $50,000

    $60,000

    $70,000

    $80,000

    $90,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therms)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas-Engine Driven vs. Std. Eff. Elec. Chiller - Large Office

    $0

    $50,000

    $100,000

    $150,000

    $200,000

    $250,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 27

    Figure 16 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for Hospital

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Hospital

    $0

    $100,000

    $200,000

    $300,000

    $400,000

    $500,000

    $600,000

    $700,000

    $800,000

    $900,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Hospital

    $0

    $20,000

    $40,000

    $60,000

    $80,000

    $100,000

    $120,000

    $140,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therms)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    28 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Figure 17 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for Hotel

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Hotel

    $0

    $50,000

    $100,000

    $150,000

    $200,000

    $250,000

    $300,000

    $350,000

    $400,000

    $450,000

    $500,000

    $550,000

    $600,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Hotel

    $0

    $10,000

    $20,000

    $30,000

    $40,000

    $50,000

    $60,000

    $70,000

    $80,000

    $90,000

    $100,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therms)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 29

    Figure 18 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for Clinic

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Clinic

    $0

    $20,000

    $40,000

    $60,000

    $80,000

    $100,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Clinic

    $0

    $5,000

    $10,000

    $15,000

    $20,000

    $25,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therms)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    30 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Figure 19 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for School

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - School

    $0

    $5,000

    $10,000

    $15,000

    $20,000

    $25,000

    $30,000

    $35,000

    $40,000

    $45,000

    $50,000

    $55,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - School

    $0

    $2,000

    $4,000

    $6,000

    $8,000

    $10,000

    $12,000

    $14,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therms)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 31

    Figure 20 - Energy Cost Savings for Gas Engine-Driven vs. Standard Efficiency Chiller for Large Retail

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Large Retail

    $0

    $50,000

    $100,000

    $150,000

    $200,000

    $250,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. Std. Eff. Elec. Chiller - Large Retail

    $0

    $5,000

    $10,000

    $15,000

    $20,000

    $25,000

    $30,000

    $35,000

    $40,000

    $45,000

    $50,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therms)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    32 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Gas Engine-Driven Chiller vs.High Efficiency Electric Chiller

    Figure 21 - Energy Cost Savings for Gas Engine-Driven vs. High Efficiency Chiller for Medium Office

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Medium Office

    $0

    $2,000

    $4,000

    $6,000

    $8,000

    $10,000

    $12,000

    $14,000

    $16,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therm)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Medium Office

    $0

    $5,000

    $10,000

    $15,000

    $20,000

    $25,000

    $30,000

    $35,000

    $40,000

    $45,000

    $50,000

    $55,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 33

    Figure 22 - Energy Cost Savings for Gas Engine-Driven vs. High Efficiency Chiller for Large Office

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Large Office

    $0

    $10,000

    $20,000

    $30,000

    $40,000

    $50,000

    $60,000

    $70,000

    $80,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therm)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Marginal Electric Costs and fixed Gas Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Large Office

    $0

    $50,000

    $100,000

    $150,000

    $200,000

    $250,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    ) Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    34 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Figure 23 - Energy Cost Savings for Gas Engine-Driven vs. High Efficiency Chiller for Hospital

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Hospital

    $0

    $100,000

    $200,000

    $300,000

    $400,000

    $500,000

    $600,000

    $700,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Hospital

    $0

    $20,000

    $40,000

    $60,000

    $80,000

    $100,000

    $120,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therm)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    GAS ENGINE-DRIVEN CHILLERS GUIDELINE 35

    Figure 24 - Energy Cost Savings for Gas Engine-Driven vs. High Efficiency Chiller for Hotel

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Hotel

    $0

    $50,000

    $100,000

    $150,000

    $200,000

    $250,000

    $300,000

    $350,000

    $400,000

    $450,000

    $500,000

    0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40

    Marginal Elec Costs ($/kWh)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

    Energy Cost Savings for various Gas Costs and fixed Electric Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller - Hotel

    $0

    $10,000

    $20,000

    $30,000

    $40,000

    $50,000

    $60,000

    $70,000

    $80,000

    0.20 0.30 0.40 0.50 0.60 0.70 0.80

    Marginal Gas Costs ($/therm)

    En

    erg

    y C

    ost

    Sav

    ing

    s ($

    )

    Chicago

    Atlanta

    Ft. Worth

    Miami

    Wash DC

    LA City

    Riverside

    Phoenix

    San Diego

    San Francisco

  • CHAPTER 5: DESIGN ANALYSIS GRAPHS

    36 SOCALGAS/NBI ADVANCED DESIGN GUIDELINES

    Figure 25 - Energy Cost Savings for Gas Engine-Driven vs. High Efficiency Chiller for Clinic

    Energy Cost Savings for various Marginal Electric Costs, and fixed Gas Costs - Gas Engine-Driven vs. High Eff. Elec. Chiller -