CW250 SERIES CURTAIN WALL SYSTEM - AAMA 507 SIMULATIONS TO DETERMINE U-
FACTOR, SOLAR HEAT GAIN COEFFICIENT, AND VISIBLE TRANSMITTANCE RATINGS
RECORD RETENTION END DATE
COMPUTERSIMULATIONREPORT
TEST DATE10/05/18
ISSUE DATE
SCOPE OF WORK
REPORT NUMBERI9462.01-116-45 R0
22
DOCUMENT CONTROL NUMBERRT-R-AMER-Test-3754 (02/20/18)©2017 INTERTEK
GAMCOCORPORATION
PAGES
10/05/23
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
SERIES/MODEL: CW250 Series Curtain Wall System
For INTERTEK B&C:
SIGNATURE: SIGNATURE:DATE: 10/05/18 DATE: 10/05/18
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client.
Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any
party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the
Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in
writing by Intertek. The observations and test results in this report are relevant only to the sample(s) tested. This report by itself
does not imply that the material, product, or service is or has ever been under an Intertek certification program.
This report does not constitute certification of this product nor an opinion orendorsement by this laboratory.
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
Project Engineer
Simulation Technician
Team Leader, SIRC
REPORT ISSUED TOGAMCO CORPORATION131-10 Maple AvenueFlushing, New York 11355
SECTION 1
Intertek B&C is an NFRC accredited simulation laboratory and all simulations wereconducted in full compliance with NFRC approved procedures and specifications.
Berkeley National Laboratory (LBNL). Results obtained are simulated values and were
SUMMARY
Intertek Building & Construction (Intertek B&C) was contracted to AAMA 507 computersimulations utilizing thermal modeling computer software developed by Lawrence
secured using the designated test methods.
Jonathan P. Spencer REVIEWED BY:COMPLETED BY: Eric S. Leitner
TITLE:TITLE:
JPS;jps
Version: 02/20/18 Page 2 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
ANSI/NFRC 100-2017, Procedure for Determining Fenestration Product U-Factors
Modeling Assumptions / Technical Interpretations
WINDOW 7.4.14
TEST METHODS
The products were evaluated in accordance with the following:
ANSI/NFRC 200-2017, Procedure for Determining Fenestration Product Solar Heat Gain
Coefficient and Visible Transmittance at Normal Incidence
SECTION 3TEST PROCEDURE
Any modeling assumptions and technical interpretations required to model this product
TOTAL PRODUCT CALCULATIONS WINDOW 7.4.14SPECTRAL DATA LIBRARY IGDB 62.0
AAMA 507-15, Standard Practice for Determining the Thermal Performance
Characteristics of Fenestration Systems Installed in Commercial Buildings
THERM 7.4.4CENTER-OF-GLASS MODELING
are listed below.1) To prevent air infiltration, tape was applied to all interior sash crack locations.
intermediate for the head and sill members and the vertical intermediate for thejambs. This procedure is outlined in the NFRC Simulation Manual, Section 8.9.
2) The center-line modeling approach was conducted using the horizontal
SECTION 2
The total product, including specific frame, spacer, and glass details, was modeled usingNFRC approved software.FRAME AND EDGE MODELING
Version: 02/20/18 Page 3 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
SASH MATERIAL NA - Not Applicable
SPACER OPTIONSTYPE PRIMARY SEAL
PRODUCT TYPE Glazed Wall System
SECTION 4SIMULATION SPECIMEN DESCRIPTION
A1-D
Exterior Air Temperature -0.4°FExterior Wind Velocity 12.3 mph (Perpendicular Flow)
Interior Air Temperature 69.8°F
CW250 Series Curtain Wall System
GLAZING OPTIONSOUTER PANE
1/4"1/4"
Generic Aluminum Dual Seal Spacer Butyl Rubber Butyl RubberCODE
GL1GL2
FRAME MATERIAL AU - Thermally Improved
SERIES/MODEL
1/4"1/4"
GAP SIZES0.500"0.250"
IG OVERALL1"1"
MIDDLE PANEN/A
Heat Mirror
INNER PANE
SECONDARY SEAL
GL1: Dual glazed IG unit (COG=0.48 - COG=0.20)GL2: Dual glazed IG unit w/ heat mirror (COG=0.18 - COG=0.10)
U-FACTOR CALCULATIONS
SECTION 5MEASURED SIMULATION DATA
Version: 02/20/18 Page 4 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
Vision Area / Total Area (%)
SECTION 6SIMULATION RESULTS
U-FACTOR CALCULATIONS: System U-Factor vs. Percentage of Vision Area
0.48
0.46
0.44
0.42
0.40
0.38
0.36
0.34
0.32
0.30
0.28
0.26
0.24
0.22
0.20
0.18
0.16
0.14
0.12
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
0.90
0.95
707580859095
COGU-Factor
Version: 02/20/18 Page 5 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
SECTION 6SIMULATION RESULTS
SHGC CALCULATIONS: System SHGC vs. Percentage of Vision Area
VT CALCULATIONS: System VT vs. Percentage of Vision Area
Vision Area / Total Area (%)
Vision Area / Total Area (%)
0.75
0.70
0.65
0.60
0.55
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
707580859095
COG SHGC
0.75
0.70
0.65
0.60
0.55
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
707580859095
COG VT
Version: 02/20/18 Page 6 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
*The size specific U-Factor matrix is based on the Glazed Wall System NFRC specimen size of
2000mm x 2000mm (78.75 in x 78.75 in). This represents 90.7% Vision Area / Total Area.
20 0.10 0.30
Size Specific U-Factor Matrix*
17 0.16 0.3518 0.14 0.3319 0.12 0.31
14 0.22 0.4015 0.20
7 0.36 0.51
0.3816 0.18 0.36
0.4711 0.28 0.4512 0.26 0.4313 0.24 0.42
0.612 0.46 0.60
5 0.40 0.556 0.38 0.53
SECTION 6SIMULATION RESULTS
U-FACTOR CALCULATIONS (CW250 Series Curtain Wall System)
8 0.34 0.50
Glazing Option Center-of-Glass U-Factor Overall U-Factor1 0.48
0.560.42
9 0.32 0.4810 0.30
3 0.44 0.584
Version: 02/20/18 Page 7 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
0.20 0.180.15 0.140.10 0.090.05 0.05
*The size specific SHGC and VT matrices are based on the Glazed Wall System NFRC specimen
size of 2000mm x 2000mm (78.75 in x 78.75 in). This represents 90.7% Vision Area / Total
Area.
0.110.06
0.200.150.100.05
Size Specific VT Matrix*Center-of-Glass VT Overall VT
0.75 0.680.70 0.630.65 0.59
Overall SHGC0.700.650.610.560.510.470.420.380.40
0.350.300.25
0.60 0.540.55 0.500.50 0.450.45 0.410.40 0.36
0.500.45
0.330.290.240.200.15
SIMULATION RESULTS
SHGC/VT CALCULATIONS (CW250 Series Curtain Wall System)Size Specific SHGC Matrix*
Center-of-Glass SHGC0.750.700.650.600.55
0.35 0.320.30 0.270.25 0.23
SECTION 6
Version: 02/20/18 Page 8 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
0.5476 0.4693
6 0.38 48.9°F 0.8839 0.5312 0.45230.40210.40200.40200.4030
0.41510.41610.4030
2.02742.0060
1.25011.25011.25011.2501
MullionSill
2.50021.2501
0.41610.41510.4151
2.50021.2501 0.4296
0.8949
L. JambR. JambMullion
Sill
2.02752.02782.0276
2.0275R. Jamb
0.9172 0.5803
0.4428
0.5033
4 0.42 46.8°F 0.9061 0.5640 0.4864
0.42970.42870.42870.4287
2.00622.02772.02802.02782.00652.0059
2.0062
1.25011.2501
45.8°FMullion
SillHead
0.44180.44190.44290.45640.4554
Mullion 2.5002 2.0284 0.4690
2 0.46 44.8°F 0.9285 0.5967 0.5203
3 0.440.4419
1
0.4700
CO
G U
-Fac
tor
Total Product U-Factor
Edge
U-F
acto
r
Fram
e
U-F
acto
r
Fram
e H
eig
ht
Cro
ss S
ecti
on
CO
G T
emp
erat
ure
0.6131 0.53730.93982.02832.0068 0.4700
2.0286
2.0071
0.48
HeadL. JambR. Jamb
Sill
1.2501
5 0.40 47.9°F
2.00612.00562.0272
HeadL. JambR. JambMullion
SillHead
L. Jamb
1.25011.25011.25012.5002
2.00582.02732.02762.0275
1.25011.25011.2501
0.46900.4690
2.02802.0283
2.0065
2.5002
1.25011.2501
1.25010.45640.45540.4554
1.25011.25011.25011.25012.50021.25011.2501
2.02812.0068
SECTION 6SIMULATION RESULTS
TOTAL PRODUCT CALCULATIONS (CW250 Series Curtain Wall System)
Op
tio
n N
um
ber
43.7°F
HeadL. JambR. JambMullion
SillHead
L. JambR. Jamb
NFRC
100-2017
70.00%
Vision Area
95.00%
Vision Area
Version: 02/20/18 Page 9 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
SECTION 6SIMULATION RESULTS
TOTAL PRODUCT CALCULATIONS (CW250 Series Curtain Wall System)
Op
tio
n N
um
ber
CO
G U
-Fac
tor
Fram
e H
eig
ht
Fram
e
U-F
acto
r
Edge
U-F
acto
r
Total Product U-FactorC
ross
Sec
tio
n
CO
G T
emp
erat
ure
70.00% NFRC 95.00%
Vision Area 100-2017 Vision Area
HeadL. JambR. JambMullion
1.2501 2.0056
7 0.36 50.0°F1.2501 2.0272 0.38891.2501 2.0275 0.38882.5002 2.0273 0.3889
0.3898
0.8728 0.5149 0.4352
SillHead
L. JambR. Jamb
1.2501 2.0059
8 0.34 51.0°F
1.2501 2.0056 0.37661.2501 2.0272 0.37571.2501 2.0275 0.3756
0.3898
0.8619 0.4984 0.4179Mullion
SillHead
L. Jamb
2.5002 2.0274
9 0.32 52.0°F
1.2501 2.0060 0.37661.2501 2.0057 0.36351.2501 2.0273 0.3626
0.3757
0.8509 0.4821 0.4008R. JambMullion
SillHead
1.2501 2.0276
10 0.30 53.1°F
2.5002 2.0274 0.36261.2501 2.0060 0.36351.2501 2.0058 0.3505
0.3626
0.8401 0.4656 0.3833L. JambR. JambMullion
Sill
1.2501 2.02741.2501 2.0277 0.34962.5002 2.0275 0.34961.2501 2.0061 0.3505
0.3496
HeadL. JambR. JambMullion
1.2501 2.0059
11 0.28 54.2°F1.2501 2.0275 0.33671.2501 2.0279 0.33662.5002 2.0277 0.3367
0.3376
0.8293 0.4492 0.3660
SillHead
L. JambR. Jamb
1.2501 2.0063
12 0.26 55.2°F
1.2501 2.0061 0.32461.2501 2.0278 0.32371.2501 2.0281 0.3237
0.3375
0.8185 0.4326 0.3484Mullion
Sill2.5002 2.02791.2501 2.0065 0.3246
0.3237
Version: 02/20/18 Page 10 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
0.2407L. Jamb 1.2501 2.0002 0.2364R. Jamb 1.2501 2.0005 0.2364Mullion 2.5002 2.0003 0.2364
Sill 1.2501 1.9782 0.2370
18 0.14 61.6°F
Head 1.2501 1.9779 0.2370
0.7406 0.3290
0.2585L. Jamb 1.2501 1.9983 0.2502R. Jamb 1.2501 1.9987 0.2502Mullion 2.5002 1.9985 0.2502
Sill 1.2501 1.9764 0.2508
17 0.16 60.6°F
Head 1.2501 1.9761 0.2509
0.7513 0.3456
0.8077 0.4162 0.3311
1.2501 2.0064
TOTAL PRODUCT CALCULATIONS (CW250 Series Curtain Wall System)
Op
tio
n N
um
ber
CO
G U
-Fac
tor
Fram
e H
eig
ht
Fram
e
U-F
acto
r
Edge
U-F
acto
r
Total Product U-Factor
CO
G T
emp
erat
ure
Cro
ss S
ecti
on
70.00% NFRC 95.00%
Vision Area 100-2017 Vision Area
SIMULATION RESULTSSECTION 6
0.3117HeadL. JambR. JambMullion
1.2501 2.0280 0.31081.2501 2.0284 0.31082.5002 2.0282 0.3108
SillHead
L. JambR. Jamb14 0.22 57.3°F
13 0.24 56.3°F
1.2501 2.0284 0.29811.2501 2.0287 0.2980
1.2501 2.0067 0.3117
0.31372.5002 2.0285 0.2980Mullion
SillHead
L. Jamb15 0.20 58.4°F 0.7864 0.3833
1.2501 2.0070 0.29891.2501 2.0071 0.28611.2501 2.0288 0.2853
0.29621.2501
16 0.18 59.5°F
2.5002 2.0289 0.28531.2501 2.0074 0.2861
Mullion 2.5002 1.9982 0.2632Sill 1.2501 1.9761 0.2638
0.7620 0.3623L. Jamb 1.2501 1.9981 0.2632R. Jamb 1.2501 1.9983
1.2501 1.9758 0.2638
2.0291 0.2852R. JambMullion
SillHead
0.7970 0.3998
1.2501 2.0067 0.2989
0.27640.2632
Version: 02/20/18 Page 11 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
0.2047L. Jamb 1.2501 2.0010 0.2103R. Jamb 1.2501 2.0013 0.2103Mullion 2.5002 2.0012 0.2103
Sill 1.2501 1.9789 0.2109
20 0.10 63.9°F
Head 1.2501 1.9786 0.2109
0.7198 0.2955
0.2227L. Jamb 1.2501 2.0005 0.2234R. Jamb 1.2501 2.0009 0.2234Mullion 2.5002 2.0007 0.2234
Sill 1.2501 1.9785 0.2240
19 0.12 62.7°F
Head 1.2501 1.9782 0.2240
0.7299 0.3123
SECTION 6SIMULATION RESULTS
TOTAL PRODUCT CALCULATIONS (CW250 Series Curtain Wall System)
Op
tio
n N
um
ber
CO
G U
-Fac
tor
CO
G T
emp
erat
ure
Cro
ss S
ecti
on
Fram
e H
eig
ht
Fram
e
U-F
acto
r
Edge
U-F
acto
r
Total Product U-Factor
70.00% NFRC 95.00%
Vision Area 100-2017 Vision Area
Version: 02/20/18 Page 12 of 22 RT-R-AMER-Test-3754
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
DRAWINGS / BILL OF MATERIALSSECTION 7
The drawings which follow have been reviewed by Intertek B&C and are representative of the
simulation result(s) reported herein. Any deviations are documented herein or on the
drawings.
Version: 02/20/18 Page 13 of 22 RT-R-AMER-Test-3754
CW250 SERIES
CURTAIN WALL SYSTEM
HEAD
JAMB
3
JAMB
1
MULLION
2
2
4
1
3
1
1/4" : 1"
Revisions
Project :
Scale:
Date:
Checked by:
SHEET #
DateNo. Description
CustomerDrawn by:
MANUFACTURERS OF FENESTRATION PRODUCTS
GAMCO CORPORATION
TEL: (718)359-8833 FAX: (718)359-8661
[email protected] www.gamcocorp.com
131-10 MAPLE AVE. FLUSHING, N.Y.11355GAMCO
SILL
4
JAMB
1
Q. ZHANG
C. CHAN
THERMAL SIMULATION
FOR CURTAIN WALL
INTERIOR
N.T.S.
EXTERIOR
EXTERIOR
K
THE DESIGN OF THE GASKET SHOWN HEREIN IS THE PRODUCT OF TREMCO, INC. NO REPRODUCTION OR USE OF THIS DESIGN IS AUTHORIZED WITHOUT THE CONSENT OF TREMCO.
R
Telephone:
TEST REPORT FOR GAMCO CORPORATIONReport No.: I9462.01-116-45 R0Date: 10/05/18
130 Derry CourtYork, PA, 17406
717-764-7700Facsimile: 717-764-4129
www.intertek.com/building
.01R0 10/05/18 N/A
SECTION 8REVISION LOG
REVISION # DATE PAGES REVISION
Original Report Issued to Gamco Corporation.
Version: 02/20/18 Page 22 of 22 RT-R-AMER-Test-3754