ED34-862 Specifications

FXUQ-MA 383

12

2. Specifications

Ceiling Suspended Cassette Type

Notes:★1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.★2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.

3 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.★4 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These values are normally somewhat higher

during actual operation as a result of ambient conditions.5 Refer to page 391 for Fan Motor Input.

ModelIndoor Unit FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1

Connection Unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE

★1 Cooling Capacity (19.5°CWB)

kcal/h 7,100 10,000 12,500

Btu/h 28,300 39,600 49,500

kW 8.3 11.6 14.5

★2 Cooling Capacity (19.0°CWB) kW 8.0 11.2 14.0

Casing Color White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)

Dimensions: (H×W×D) mm 165×895×895 230×895×895 230×895×895

Coil (Cross Fin Coil)

Rows×Stages×Fin Pitch mm 3×6×1.5 3×8×1.5 3×8×1.5

Face Area m² 0.265 0.353 0.353

Fan

Model QTS48A10M QTS50B15M QTS50B15M

Type Turbo Fan Turbo Fan Turbo Fan

Motor Output × Number of Units W 45×1 90×1 90×1

Air Flow Rate (H/L)m³/min 19/14 29/21 32/23

cfm 671/494 1,024/741 1,130/812

Drive Direct Drive Direct Drive Direct Drive

Temperature Control Microprocessor Thermostat forCooling and Heating

Microprocessor Thermostat for Cooling and Heating

Microprocessor Thermostat for Cooling and Heating

Sound Absorbing Thermal Insulation Material Heat Resistant Foamed Polyethylene, Regular Foamed Polyethylene

Heat Resistant Foamed Polyethylene, Regular Foamed Polyethylene

Heat Resistant Foamed Polyethylene, Regular Foamed Polyethylene

Piping Connections

Liquid Pipes mm φ9.5 (Flare Connection) φ9.5 (Flare Connection) φ9.5 (Flare Connection)

Gas Pipes mm φ15.9 (Flare Connection) φ15.9 (Flare Connection) φ15.9 (Flare Connection)

Drain Pipe mm VP20(External Dia. 26 Internal Dia. 20)

VP20(External Dia. 26 Internal Dia. 20)

VP20(External Dia. 26 Internal Dia. 20)

Machine Weight kg 25 31 31

★4 Sound Level (H/L) (230V) dBA 40/35 43/38 44/39

Safety Devices Thermal Protector for Fan Motor Thermal Protector for Fan Motor Thermal Protector for Fan Motor

Standard Accessories

Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws, Washers, Holding Plate.

Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws, Washers, Holding Plate.

Operation Manual, Installation Manual, Drain Hose, Clamp Metal, Insulation for Fitting, Sealing Pads, Clamps, Screws, Washers, Holding Plate.

Drawing No. C : 4D045395A

Conversion Formulae

kcal/h=kW×860Btu/h=kW×3412

cfm=m³/min×35.3

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

Page 2: Fxuq

Specifications ED34-862

384 FXUQ-MA

BEV Units

Connection Example

Model BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE

Power Supply 1 Phase 50Hz 220~240V 1 Phase 50Hz 220~240V 1 Phase 50Hz 220~240V

Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate

Dimensions: (H×W×D) mm 100×350×225 100×350×225 100×350×225

Sound Absorbing Thermal Insulation Material

Flame and Heat Resistant Foamed Polyethylene

Flame and Heat Resistant Foamed Polyethylene

Flame and Heat Resistant Foamed Polyethylene

Piping Connection

Indoor Unit

Liquid Pipes 9.5mm (Flare Connection) 9.5mm (Flare Connection) 9.5mm (Flare Connection)

Gas Pipes 15.9mm (Flare Connection) 15.9mm (Flare Connection) 15.9mm (Flare Connection)

Outdoor Unit

Liquid Pipes 9.5mm (Flare Connection) 9.5mm (Flare Connection) 9.5mm (Flare Connection)

Suction Gas Pipes 15.9mm (Flare Connection) 15.9mm (Flare Connection) 15.9mm (Flare Connection)

Machine Weight (Mass) kg 3.0 3.0 3.5

Standard AccessoriesInstallation manual, Gas piping

connections, Insulation for fitting, Sealing material, Clamps

Installation manual, Gas piping connections, Insulation for fitting,

Sealing material, Clamps

Installation manual, Gas piping connections, Insulation for fitting,

Sealing material, Clamps

Drawing No. 4D045387A 4D045387A 4D045388A

BRC1C62

PowerPowersupplysupply

lineline

TransmissionTransmissionlineline

ControlWiringControlWiring

1. Wiring Work•The connecting line between SkyAir Indoor Unit

– BEV Unit : 3 cores…like a Transmission Line•BEV Unit’s power supply line; Single phase 2 line…like a VRV Indoor unit•BEV Unit – other VRV indoor unit or outdoor unit – : 2 cores…DIII network wiring (super wiring)2. Piping work SkyAir side,Outdoor Unit Side,They are both flare connection.

-When connecting centralized-control device, it is necessary to install an interfaceadaptor for SkyAir series in an indoor unit.

-Distance between indoor unit and –BEV unit must be within 5m.

Consideration matter

Installation pattern / maintenance

Outline figure

Gas pipe (With Thermistor,

Liquid pipe

Insulation pipe cover)

Electric valve drive part

Hanger

PC board

Terminal block

SW.BOX cover

Piping part cover

(Wall surface attachment is also possible)

1. Level installation (It hangs by two hangers) 2. Vertical Installation (Wall Surface Mounted)

Service space*1

*1; Service space for switch box. (Service access panel is required for the bottom side. When there is nothing, 350 or more spaces are required. )*2; For electric valve drive part’s maintenance. (a control box is removed)

Installation space

150 or more

Service space*2100 or more

Gas pipe

Screw fixed(x2 Screws x2 place)

Hanger bolt Liquid pipe

Service access panel (450 x 450 )