e3
CO - CrownEnergy Recovery Unit > Technical Catalogue
Compact & Self-regulated
High Efficiency Plate Exchanger up to 95%
Plug & Play Controls
Indoor or Outdoor Installation
Side-by-side or Double Deck Formats
Up to 1.33 m3/s (4800 m3/h)
Full BMS Communication
EC Motors
-
7/28/2019 FW e3co Crown Technical Catalogue UK
2/13
2
Application
High efficiency, high performance self regulating ventilation and energy recovery for office and industrial applications.
Thermal efficiency up to 95 % (EN308), in compliance with ErP 2009/125/EC directive
Air filtration and temperature control included
Compact, plug n play units complete with BMS communications in accordance with (EN 15232)
Range
Available in 6 models, the e3co Crownrange covers flow rates from 200 to 4,800 m3/h (0.05 to 1.33m3/s).
Every e3co Crownmodel has two programmable air flow rates (VAV & CAV control options)
e3co Crownrange is available in 3 variants:
e3ssential : self regulating air handling unit dedicated to use in temperate climate area
e3nhanced : self regulating air handling unit fitted with an electric or a hot water coil for external temperatures down to -10C e3lite : same as the e3nhanced series but includes an electric pre-heater for external temperatures down to -20C
Construction
Aluminium penta-post framework incorporates anti thermal bridging feature (polyamide sections) which offers class TB2
thermal performance in accordance with EN1886
Corners are manufactured from reinforced polyamide
Double skin panels have steel inner and outer skins that are 1mm in thickness (class 2 in accordance with EN 1886)
- Insulation: high density 50 mm MO wool mineral (class T2 and class A for air leakage in accordance with EN1886)
- External face : Pre-painted sheet (RAL 7035)
- Internal face: galvanized steel
Circular spigot connections with lip seals to guarantee that systems are airtight
Brackets are clamped to unit framework for fixing to the ground or ceiling
Integrated controls compartment is included to house electrical components and regulation system.
Lockable, removable, hinged access panels include integrated IP65 control panel with LCD display and pad lockable local
electrical isolator
Access to internal components via lockable panels.
Integral condensate tray and condensate pipework and connection
100% internal bypass, damper, motorized and self-regulating
Fans and Motors
Complete with high efficiency centrifugal plug fans
Direct driven via EC (Electronically Cumulated) motors with high-performance, thermal protection and built in speed control.
The EC technology is an ecological solution guaranteeing low energy consumption and better management and control of
the operating point (air flows can be control led from 10 to 100 %). Low sound levels
Controls
User friendly interface
Fast and easy commissioning
Pre-configured controls. Constant Air Volume, Variable Air Volume and Constant Pressure options.
Plug and play solution
Full BMS capability as standard, using a MODBUS protocol. Other protocol options
available on request
Heat Exchanger
Static high-performance counter-flow heat exchanger core with aluminium plates (EUROVENT certified)
Efficiency greater than 90 % (EN 308) under operating conditions as stated below:
Fresh air : -10C/90 % RH Return air 20C/50 % RH
Automatic defrost function by opening the bypass damper and modulation of the fresh air flow if necessary - e3ssential and
e3nhanced series. The e3lite series, includes an extra integrated electric pre-heater (frost heater)
Filters
Filters are included to provide protection to other components (ie, exchanger/fans)
Media frames are mounted on runners fitted with lip seals to ensure effective air tightness
The e3co Crownunit is equipped with a high efficiency F7 grade filter fitted to the fresh air intake and a G4 grade filter to
the extracted air intake. The F7 grade filter has vee form media to deliver a high surface area and low pressur e drop
Benefits and Features
Integrated ventilation control is provided by an IP65 rated display panel, suitable for either outdoor or indoor installation,
BMS communication using MODBUS is via an RS485 port. TCP/IP communication is available on request
100 % bypass, internal to the central unit, fitted with servomotors controlled automatically by built-in controls which
provides FREE-COOLING and NIGHT-COOLING functions
Wide choice of flow modulations to optimise energy consumption (EN 15232)
Temperature probes (x4) are included to monitor supply air, exhaust air and external temperature There is also a probe
to control the defrost function. An additional probe is fitted to the e3lite BE version for control of the pre-heater.
An integrated de-icing sensor is included to protect the hot water coil fitted into the e3nhanced/e3lite BC versions.
e3nhanced/e3lite BE versions are complete with a manual reset safety thermostat to protect the electric heater
elements
Programmable on board time clocks are included
Weekly clock and public holiday clock functions
Supply air filter pressure switch provides a dirty filter alarm
Press ure switches are used within the control of air flows of each fan, and provide fan ail alarms
Lockable local electrical isolator mounted on unit casing
Installation
Double Deck or Side-by-Side options (excepte3co Crown90-6)
Indoor or outdoor (with weather roof and rain canopy accessories fitted)
Low profile - suitable for mounting in ceiling voids
Specification Specification
ENERGY
EXPERTISE
ENVIRONME
-
7/28/2019 FW e3co Crown Technical Catalogue UK
3/13
4
With any system it is always important to have the right product and application to maximise efficiency, with
Flkt Woods new e3co Crown ERU units we have a variety of applications which benefit from our new range.
The applications below give an indication of where the new e3co Crown ERU units can be installed and used to
minimise energy consumption and provide precise air volume control.
Environmental Assessment Schemes
It is now very common for new build projects to try and achieve environmental standards such as those set
out in LEED and BREEAM programs. Flkt Woods, with its market leading knowledge and products in energy
recovery, has helped many projects achieve the very highest levels in both of these schemes.
Energy using Products Directive (EuP)
The various lots within the EuP directive dictates the eco design requirements for minimum efficiency grades and
labelling. Efficiency grades for fans from 125W to 500W are already published, and e3co Crown products are
expected to be included in the near future. The efficiency requirement is the combination of the fan and drive
efficiency, so EC technology will offer the end user or the designer a solution that is better than the minimum
eco design standards.
Energy Performance of Buildings Directive (EPBD)
The Commission of the European Union has recently proposed a revision of the EPBD (Energy Performance
in Buildings Directive, 2002/91/EC). The objective is to further strengthen the effectiveness and impact of the
existing Directive.
The background to this initiative is to optimise energy usage. It was noted that even in member states where the
existing Directive has been successfully implemented, the Commission still identified an untapped potential for
improvements that could further reduce the energy consumption and CO2
emissions from buildings.
Building Regulations - Part L2 for New (A) and Existing Buildings (B)
Effective from October 2010, Building Regulations Part L and F outline the need for a healthier working/indoor
environment, with the target to decrease CO2
emissions by a further 25% from the initial reduction stated
within the 2006 document. The eco design of our e3co Crown range will allow specifiers to create designs
which incorporate the necessary energy usage reductions, whilst still providing precise control of mechanical
ventilation.
European Energy Related Products Directive (ErP)
Not only does the e3co-Crown meet the requirements of the ErP 2009/125/EC, but also EN15232. In addition,
at the heart of the product, its heat exchanger core is Eurovent Certificated.
LEGISLATION
In Europe, all countries now have to design their new buildings to meet energy targets that
are set out in the Energy Performance in Buildings Directive (EPBD). All Flkt Woods Energy
Performance of Buildings Directive solutions are designed to enable full compliance with this
and other directives regarding ventilation and air conditioning.
Being a global manufacturer and supplier makes meeting legislation easier for Flkt Woods. It means that
Flkt Woods must produce solutions at standards that equal the most stringent legislation and guidelines around.
Only by doing this can we ensure that we meet relevant standards within every market.
Applications Legislation
OFFICES
Flkt Woods offer a highperformance product rangecovering all key elements ofthe overall ventilation system.Our products are designedto secure the best overallperformance of the system as a
whole, considering parameterssuch as health and air quality,energy efficiency, noise, firesafety and ease of installation.
EDUCATION
High occupancy levels
during teaching periodsrequire energy-efficient andcontrollable demand-basedmanagement of air quality andtemperature. The comfort,health and alertness ofstaff and pupils is ensuredduring the learning process,but operating costs can beminimised when these facilitiesare unoccupied.
GYMNASIUM/INDOOR SPORTS
Differing types of activityand occupancy mean abroad spectrum of functionalrequirements to ensure efficientremoval of used air and theintroduction of fresh supplies.Systems need to contain and
control the periodic build upof high humidity levels andtemperature.
HEALTHCARE
For a hospital to operate atits maximum potential, it has tohave all systems workingat the optimum. This notonly applies to staff,communications and lifesupport systems, but also
to pipework, cleaning andventilation systems.
RETAIL/SHOPPING AREAS
With high activity levelsduring the working week andweekends, its important tomake sure that all areas ofventilation are maintained and
Flkt Woods has the systemsto achieve all requirements.
RESIDENTIAL
The purpose of ventilation is to
provide clean good quality airby removing the stale, pollutedair from our homes. The maintask is of course to ensure thatthe indoor air is healthy andsafe to breathe. Ventilationtoday is also about energy andsaving energy costs by addingheat recovery to the ventilationsystem.
TOILETS
Fast, efficient removal ofodours and air-borne pollutantscontribute to the maintenance
of cleanliness and anacceptable environment in
communal sanitary areas.
INDUSTRY
Flkt Woods technologyis used widely in industrialprocessing plants and factoriesfor ventilation of work spaces,as vital components in hightech manufacturing facilities,and for maintaining delicateenvironments within high
tolerance levels inpetro-chemical andpharmaceutical plants.
-
7/28/2019 FW e3co Crown Technical Catalogue UK
4/13
6
Fresh air
Configurations and Electrical Information
Configuration W Configuration Y
Configuration L
Excepte3co Crown 90-6
Configuration P
Excepte3co Crown 90-6
Side-by-side format (air flows side-by-side) (view rom above)
Double Decked format (air flows one above the other) (side access view)
ElectrovalveKit Type
Application Water Coil
HOT WATER COIL: Include in PREMIUM/INFINITE BC CHILLED WATER COIL:Add a COMBIBOX CBF BF module
HOT WATER CHILLED WATER
DN/Kvs - 90/7 0 8 0/ 60 6 0/ 50 4 5/ 50 7/12 6/11
10/1,6 - 3/8 M - IP54
90-1 90-1 90-1 90-1 - -
90-2 90-2 90-2 90-2 - -
90-3 90-3 90-3 90-3 - -
15/2,5 - 1/2 M - IP54 90-4 90-4 90-4 90-4 90-1-90-2 + CBX 1-2 BF 9008-9010+ CBX 1-2 BF
20/4 - 1/2 F - IP54 90-5 90-5 90-5 90-5 90-3 + CBX 3 BF 9016 + CB X 3 B F
25/6,3 - 3/4 F - IP54 90-6 90-6 90-6 90-6 90-4 + CBX 4 BF 9023 + CB X 4 B F
25/10 - 1 F - IP54 - - - - 90-5 + CBX 5 BF 9035 + CB X 5 B F
32/16 - 1 1/4 F - IP41 - - - - 90-6 + CBX 6 BF 9048 + CBX 6 BF
Electro valve kit consists 1 off 3-wayvalve, 3 connectors, servomotorsuitable for control via a 0-10vsignal.
Servomotors fitted to valves areavailable with either an IP41enclosure (indoor installation) orIP54 rated, suitable for outdoor
installation.
CrownModel
FanMotorpower(W)
TempRangeC/C(min/max)
IP.
Rating
Overheat
Protection*
e3ssentiale3nhanced BC
e3lite BC e3nhanced BE e3-lite BE
VoltageV
FLCAmpRating
**
VoltageV
FLCAmpRating
**
VoltageV
Model
FLCAmpRating
**
VoltageV
Model
FLCAmpRating
**
90-1 2 x 220 -20 / 60 IP44 PTI 230/1/50 3.4 230/1/50 14.3 230/1/50 BE 025 14.3 230/1/50 BE 025 25.2
90-2 2 x 485 -20 / 60 IP54 PTO 230/1/50 6.2 230/1/50 22.5 230/1/50 BE 025 17.1 230/1/50 BE 025 33.4
90-3 2 x 900 -20 / 40 IP54 PTO 230/1/50 7.8 400/3/50 15.42 30 /1 /5 0 B E 0 37 2 4. 1
4 00 /3 /5 0 B E 0 52 2 3. 04 00 /3 /5 0 B E 0 52 1 5. 4
90-4 2 x 900 -20 / 40 IP54 PTO 230/1/50 7.8 400/3/50 17.52 30 /1 /5 0 B E 0 37 2 4. 1
4 00 /3 /5 0 B E 0 67 2 7. 24 00 /3 /5 0 B E 0 67 1 7. 5
90-5 2 x 2500 -20 / 40 IP54 PTO 400/3N/50 8.0 400/3/50 19.9 400/3/50B E 0 67 1 7.7
400/3/50B E 0 67 2 9.6
BE 135 27.5 BE 135 39.4
90-6 2 x 2500 -20 / 40 IP54 PTO 400/3N/50 8.0 400/3/50 34.0 400/3/50B E 0 67 1 7.7
400/3/50B E 0 67 4 3.7
BE 135 27.5 BE 135 53.5
* PTO: Overheat protection opening (output on terminal block) / PTI: built-in overheat protection (in series with the windings).** SC is the same as the FLC as EC motors use a soft start function.
Extract air
F resh a ir Ext ract a ir
Drawing and Dimensions
* Available in double deck configuration only.
Double Deck format - 90-1 To 90-6
Model A B C D E F F1 F2 G J K Te3ssential
kge3nhanced
kge3litekg
90-1 315 1915 915 505 255 405 1097 362 456 465 245 540 1/2 215 218 220
90-2 315 1915 915 505 255 405 1097 362 456 465 245 540 1/2 215 218 220
90-3 400 2230 1115 605 305 505 1261 362 607 565 345 690 1/2 310 315 318
90-4 450 2345 1315 705 355 605 1376 362 607 565 445 690 3/4 400 407 412
90-5 500 2625 1515 805 405 705 1520 450 655 640 545 740 3/4 550 560 564
90-6* 630 2970 1715 1030 455 805 1677 535 758 685 645 840 1 710 725 732
Dimensions Table
ModelRC Weight
kgK
mmH
mmJ
mmMD Weight
kg
90-1 4 340 362 362 8
90-2 4 340 362 362 8
90-3 5 440 462 462 10
90-4 7 540 562 562 13
90-5 10 640 662 662 15
90-6* 13 740 762 762 17
Optional Extras
Option RC Option MD
RC - Rain
Canopy
MD - Motorised
Damper
Integrated Exchanger
Side-by-Side format - 90-1 To 90-5
Integrated Exchanger
-
7/28/2019 FW e3co Crown Technical Catalogue UK
5/13
8
Returnair20C/50%
-5C / 90% HR
-10C / 90% HR
300Pa
250Pa
200Pa
150Pa
300Pa
250Pa 200Pa 150Pa
0C / 90% HR
+5C / 90% HR
Efficiency(%)-EN308
perfan
Powerconsumption(W)
Staticpressure(Pa)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
100%90%
80%70%60%50%40%
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m3/s)
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m3/s)
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28
Flow rate (m3/s)
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m3/s)
Performance curves shown are based on the e 3nhanced or e3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e3nhanced or e3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.
Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.
Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.
NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up
Performance - 90-1 Heating Data - 90-1
BC for e3nhanced and e3lite versions - Hot Water Coil
Watertemp
(C/C)
Coilair onTemp(C)
Flow rate (m/h)(m/s)
300(0.08)
400(0.11)
500(0.14)
600(0.17)
700(0.19)
800(0.22)
82/71
11Power (kW)/Air supply temp. (C) 5.1/60 6.3/56 7.3/53 8.3/51 9.2/49 10/47
Water flow rate (l/h)/DP water (kPa) 410/11 510/17 590/22 670/28 740/34 800/41
15Power (kW)/Air supply temp. (C) 4.8/61 5.8/58 6.8/55 7.7/52 8.5/51 9.33/49
Water flow rate (l/h)/DP water (kPa) 380/10 470/14 550/20 620/24 690/31 750/35
90/70
11Power (kW)/Air supply temp. (C) 5.3/62 6.5/58 7.5/55 8.5/52 9.4/50 10.2/48
Water flow rate (l/h)/DP water (kPa) 240/4 290/6 340/8 380/10 420/12 450 /12
15Power (kW)/Air supply temp. (C) 4.9/63.9 6.1/59 7.05/56 7.9/54 8.7/52 9.5/50.4
Water flow rate (l/h)/DP water (kPa) 220/3 270/5 310/6 350/8 390 /10 420 /11
45/40
11Power (kW)/Air supply temp. (C) 2.4/34 3/32.7 3.5/31 3.9/30.1 4.3/29 4.7/28
Water flow rate (l/h)/DP water (kPa) 430/13 520/19 610/24 680/30 760/37 820/43
15Power (kW)/Air supply temp. (C) 2.1/35.6 2.5/34 3/32 3.3/31.8 3.7/30.9 4/30.1
Water flow rate (l/h)/DP water (kPa) 370/10 450/14 520/18 590/23 650/27 710/32
60/50
11Power (kW)/Air supply temp. (C) 3.4/43.7 4.2/41 4.8/39 5.4/37.5 6/36 6.5/34.9
Water flow rate (l/h)/DP water (kPa) 300/6 360/9 420/12 480/15 530/18 570 /20
15Power (kW)/Air supply temp. (C) 3/44 3.7/42 4.3/40 4.9/39.3 5.4/37 5.8/36.8
Water flow rate (l/h)/DP water (kPa) 270/5 330/8 380/10 430/12 470/14 510/17
BE for e3nhanced and e3lite versions - Electric Heater
Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH
or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.
2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.
Fresh Air 0C 0C -5C -10C -15C -20CQv (m/h) 800 800 800 800 800 800
Versione3ssential e3nhanced BE 025 e3lite BE 025
Electric Heater Pre-heater + Post Heater
Total power (kW) - 2.5 2.5 2.5 2.5 + 2.5 2.5 + 2.5
Air supply Temp. (C) 16.8 26.2 25.6 20.8 24.6 19.7
Typical Plate Heat Exchanger Core Performance data
Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH
ModelAir fow rate
RecoveredkW
Air O temp C / RHThermal
Eiciency %m3/h m3/s
Crown 90-1 450 0.13 3.7 19.3C 16.1%RH 90.1
Watertemp
(C/C)
New airtemp(C)
Flow rate (m/h) 400 600 800 1000
7/12
32/40
Power ( kW)/A ir suppl y t em p. ( C-%HR) 3 .4/14. 5-82 4.4/16.4 -79 5.1/17. 7-77 5.7/18. 8-75
Water flow rate (l/h)/DP water (kPa) 580/5 750/8 880/10 970/12
27/50
Power ( kW)/A ir suppl y t em p. ( C-%HR) 2 .6/13. 9-86 3.3/15. 4-83 3.8/16. 5-82 4.2/17. 3-81
Water flow rate (l/h)/DP water (kPa) 440/3 560/5 650/6 720/7
25/50
Power (kW)/A ir suppl y t em p. ( C-%HR) 2 .0/13. 6-85 2.5/15-83 2.9/15. 9-82 3.1/16. 6-81
Water flow rate (l/h)/DP water (kPa) 350/2 430/3 490/4 530/4
6/11
32/40
Power ( kW)/A ir suppl y t em p. ( C-%HR) 3 .6/13. 8-82 4.7/15. 7-79 5.5/17. 1-77 6.2/18. 2-75
Water flow rate (l/h)/DP water (kPa) 620/5 800/9 940/11 1050/14
27/50
Power ( kW)/A ir suppl y t em p. ( C-%HR) 2 .8/13. 2-86 3.6/14. 7-84 4.2/15.8 -82 4.7/16. 7-81
Water flow rate (l/h)/DP water (kPa) 480/4 620/5 720/7 810/9
25/50
Power ( kW )/Ai r supp ly t em p. ( C -%HR) 2 .3/12. 9-85 2.9/14. 3-83 3.3/15.2 -82 3.6/16-81
Water flow rate (l/h)/DP water (kPa) 390/2 490/4 560/5 620/5
CBX 1-2 BF for Chilled Water Module
-
7/28/2019 FW e3co Crown Technical Catalogue UK
6/13
10
Performance - 90-2 Heating Data - 90-2
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28
-5C / 90% HR
+5C / 90% HR
0C / 90% HR
-10C / 90% HR
300Pa250Pa
150Pa
300Pa
250Pa
200Pa 150Pa
200Pa150Pa
Returnair20C/50%
Efficiency(%)-EN308
perfan
Powerconsumption(W)
Staticpressure(Pa)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/s)
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m3/s)
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28
Flow rate (m3/s)
0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m3/s)
80%
70%
60%
50%
40%
Performance curves shown are based on the e 3nhanced or e3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e3nhanced or e3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.
Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.
Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.
BC for e3nhanced and e3lite versions - Hot Water Coil
Watertemp
(C/C)
Coilair onTemp(C)
Flow rate (m/h)
(m/s)
400(0.11)
500(0.14)
600(0.17)
700(0.19)
800(0.22
900(0.25)
82/71
11Power (kW)/Air supply temp. (C) 6.3/56 7.3/53 8.3/51 9.2/49 10/47 10.8/45
Water ow rate (l/h)/DP water (kPa) 510/17 590/22 670/28 740/34 800/41 870/47
15Power (kW)/Air supply temp. (C) 5.8/58 6.8/55 7.7/52 8.5/51 9.33/49 10.1/47.8
Water ow rate (l/h)/DP water (kPa) 470/14 550/20 620/24 690/31 750/35 810/41
90/70
11Power (kW)/Air supply temp. (C) 6.5/58 7.5/55 8.5/52 9.4/50 10.2/48 11/46.8
Water ow rate (l/h)/DP water (kPa) 290/6 340/8 380/10 420/12 450 /12 490/15
15Power (kW)/Air supply temp. (C) 6.1/59 7.05/56 7.9/54 8.7/52 9.5/50.4 10.3/48.8
Water ow rate (l/h)/DP water (kPa) 270/5 310/6 350/8 390 /10 420 /11 450/13
45/40
11Power (kW)/Air supply temp. (C) 3/32.7 3.5/31 3.9/30.1 4.3/29 4.7/28 5.1/27.5
Water ow rate (l/h)/DP water (kPa) 520/19 610/24 680/30 760/37 820/43 890/51
15Power (kW)/Air supply temp. (C) 2.5/34 3/32 3.3/31.8 3.7/30.9 4/30.1 4.4/29.5
Water ow rate (l/h)/DP water (kPa) 450/14 520/18 590/23 650/27 710/32 760/38
60/50
11Power (kW)/Air supply temp. (C) 4.2/41 4.8/39 5.4/37.5 6/36 6.5/34.9 7/33
Water ow rate (l/h)/DP water (kPa) 360/9 420/12 480/15 530/18 570 /20 620/24
15Power (kW)/Air supply temp. (C) 3.7/42 4.3/40 4.9/39.3 5.4/37 5.8/36.8 6.4/35.9
Water ow rate (l/h)/DP water (kPa) 330/8 380/10 430/12 470/14 510/17 550/20
BE for e3nhanced and e3lite versions - Electric HeaterFresh Air 0C 0C -5C -10C -15C -20CQv (m/h) 980 980 980 980 980 980
Versione3ssential e3nhanced BE 025 e3lite BE 025
Electric Heater Pre-heater + Post Heater
Total power (kW) - 2.5 2.5 2.5 3.75 + 2.5 3.75 + 2.5
Air supply Temp. (C) 16.7 24.4 23.8 19 24.6 19.7
Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH
or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.
2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.
Typical Plate Heat Exchanger Core Performance data
Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:
External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH
ModelAir fow rate
RecoveredkW
Air O temp C / RHThermal
Eiciency %m3/h m3/s
Crown 90-2 600 0.17 4.8 19.0C 16.4%RH 89.0
NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up
Watertemp
(C/C)
New airtemp(C)
Flow rate (m/h) 400 600 800 1000
7/12
32/40
Power ( kW)/A ir suppl y t em p. ( C-%HR) 3 .4/14. 5-82 4.4/16.4 -79 5.1/17. 7-77 5.7/18. 8-75
Water flow rate (l/h)/DP water (kPa) 580/5 750/8 880/10 970/12
27/50
Power ( kW)/A ir suppl y t em p. ( C-%HR) 2 .6/13. 9-86 3.3/15. 4-83 3.8/16. 5-82 4.2/17. 3-81
Water flow rate (l/h)/DP water (kPa) 440/3 560/5 650/6 720/7
25/50
Power (kW)/A ir suppl y t em p. ( C-%HR) 2 .0/13. 6-85 2.5/15-83 2.9/15. 9-82 3.1/16. 6-81
Water flow rate (l/h)/DP water (kPa) 350/2 430/3 490/4 530/4
6/11
32/40
Power ( kW)/A ir suppl y t em p. ( C-%HR) 3 .6/13. 8-82 4.7/15. 7-79 5.5/17. 1-77 6.2/18. 2-75
Water flow rate (l/h)/DP water (kPa) 620/5 800/9 940/11 1050/14
27/50
Power ( kW)/A ir suppl y t em p. ( C-%HR) 2 .8/13. 2-86 3.6/14. 7-84 4.2/15.8 -82 4.7/16. 7-81
Water flow rate (l/h)/DP water (kPa) 480/4 620/5 720/7 810/9
25/50
Power ( kW )/Ai r supp ly t em p. ( C -%HR) 2 .3/12. 9-85 2.9/14. 3-83 3.3/15.2 -82 3.6/16-81
Water flow rate (l/h)/DP water (kPa) 390/2 490/4 560/5 620/5
CBX 1-2 BF for Chilled Water Module
-
7/28/2019 FW e3co Crown Technical Catalogue UK
7/13
12
Performance - 90-3 Heating Data - 90-3
BC for e3nhanced and e3lite versions - Hot Water Coil
Watertemp
(C/C)
Coilair onTemp(C)
Flow rate (m/h)(m/s)
600(0.17)
800(0.22)
1000(0.28)
1200(0.33)
1400(0.39)
1500(0.42)
82/71
11Power (kW)/Air supply temp. (C ) 10.1/59.7 12.4/55.8 14.4/52 16/50 18/48 18.8/47.3
Water ow rate (l/h) /DP water (kPa) 810/18 990/27 1150/36 1310/46 1440/55 1510/60
15P owe r ( kW )/A ir s up pl y t em p. ( C ) 9. 4/6 1 11 .5/ 57. 4 1 3. 4/ 54 .5 15 .2 /5 2. 2 1 6. 7/5 0 17 .5 /4 9.3
Water ow rate (l/h)/DP water (kPa) 750/16 920/24 1070/31 1220/40 1340/48 1400/52
90/70
11P owe r ( kW )/A ir s u pp ly t e mp . ( C) 1 0. 5/6 2. 1 1 3/5 7.8 1 4. 9/ 54 .4 16 .7 /5 1. 7 1 8.5 /49 .5 19 .3 /4 8.6
Water ow rate (l/h)/DP water (kPa) 460/6 570/9 660/12 740/15 820/18 850/20
15Power ( kW)/Air s upply t emp. ( C ) 9.8/63.4 12/59 13.9/56.2 15.6/53.7 17.2/51.5 18/50.7
Water ow rate (l/h)/DP water (kPa) 430/6 530/8 610/10 690/13 760/16 800/18
45/40
11P owe r ( kW )/A ir s up pl y t em p. ( C ) 4. 8/ 34 .2 5 .8 /3 2. 4 6 .8 /30 .9 7 .7 /2 9.7 8 .5/ 28 .7 8. 91 /2 8. 3
Wa te r ow r at e ( l/h )/ DP w at er ( kP a) 83 0/2 0 1 020 /30 1 19 0/4 0 13 40/ 49. 1 1 48 0/6 0 15 50/ 68
15Power (kW)/Air supply temp . (C) 4.1/35.4 5/33.8 5.88/32.5 6.6/31.4 7.3/30.6 7.6/30.2
Water ow rate (l/h)/DP water (kPa) 720/15 880/22 1020/30 1160/37.3 1280/45 1330/51
60/50
11Power ( kW)/Air s upply t emp. ( C) 6.6/43.4 8.1/40.8 9.4/38.7 10.7/37 11.8/35.6 12.3/35
Water ow rate (l/h)/DP water (kPa) 580/10 710/14 830/20 940/24 1030/30 1080/33
15P owe r ( kW )/A ir s up pl y t emp . ( C ) 5. 9/4 4. 6 7 .3 /4 2. 2 8 .5 /40 .3 9 .6 /3 8. 8 1 0. 6/ 37 .5 11 .1 /3 6. 9
Water ow rate (l/h)/DP water (kPa) 520/8 640/12 750/16 840/20 930/25 970/27
BE for e3nhanced and e3lite versions - Electric HeaterFresh Air 0C 0C -5C -10C -15C -20CQv (m/h) 1550 1550 1550 1550 1550 1550
Versione3ssential e3nhanced BE 025 e3lite BE 025
Electric Heater Pre-Heater + Post Heater
Total power (kW) - 3.75 3.75 3.75 5.25 + 3.75 5.25 + 5.25
Air supply Temp. (C) 16.7 24 23.5 21.5 23.7 21.6
-5C / 90% HR
+5C / 90% HR
0C / 90% HR
-10C / 90% HR
300Pa250Pa200Pa
300Pa
250Pa
200Pa 150Pa
150Pa
300Pa
150Pa
250Pa200Pa150Pa
Returnair20C/50%
Efficiency(%)-EN308
perfan
Powerconsumption(W)
Staticpressure(Pa)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
80%
70%
60%
50%
40%
0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m3/s)
0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m3/s)
0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44
Flow rate (m3/s)
0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m3/s)
Performance curves shown are based on the e 3nhanced or e3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e3nhanced or e3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.
Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.
Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.
30%
Notes:
1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RHor 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.
2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.
Typical Plate Heat Exchanger Core Performance data
Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH
ModelAir fow rate
RecoveredkW
Air O temp C / RHThermal
Eiciency %m3/h m3/s
Crown 90-3 950 0.26 7.7 19.0C 16.4%RH 89.0
NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up
Watertemp
(C/C)
New airtemp(C)
Flow rate (m/h) 1000 1200 1400 1600
7/12
32/40
Power (kW)/A ir suppl y t em p. ( C-%HR) 7 .3/16. 4-78 8.1/17.2 -77 8.8/18-76 9.4/18. 6-75
Water flow rate (l/h)/DP w ater (kPa) 17 1/4 21 10/19 24 2/1 1 26
27/50
Power ( kW )/Ai r suppl y t em p. ( C -%HR) 5 .6/15. 3-83 6.2/16-82 6.7/16. 6-81 7.1/17-81
Water flow rate (l/h)/DP water (kPa) 960/10 6 11 10/13 15
25/50
Power (kW)/A ir suppl y t em p. ( C-%HR) 4 .3/15 -82 4.6/15.6 -82 4.9/16. 1-81 5.1/16. 5-80
Water flow rate (l/h)/DP water (kPa) 730/6 790/7 840/8 880/8
6/11
32/40
Power ( kW)/A ir suppl y t em p. ( C-%HR) 7 .7/15. 9-78 8.6/16.8 -77 9.3/17. 5-76 9.9/18. 2-75
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 32 0/ 17 1 47 0/ 20 1 59 0/2 3 1 70 0/2 6
27/50
Power ( kW)/A ir suppl y t em p. ( C-%HR) 6 .0/14. 8-83 6.7/15. 5-82 7.2/16. 1-81 7.7/16. 6-81
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 03 0/ 11 1 14 0/ 13 1 23 0/1 5 1 31 0/1 7
25/50
Power ( kW)/A ir suppl y t em p. ( C-%HR) 4 .8/14. 3-83 5.2/14. 9-82 5.6/15. 5-81 5.9/15. 9-80
Water flow rate (l/h)/DP water (kPa) 820/7 900/9 960/10 1010/11
CBX 3 BF for Chilled Water Module
-
7/28/2019 FW e3co Crown Technical Catalogue UK
8/13
14
Performance - 90-4 Heating Data - 90-4
BC for e3nhanced and e3lite versions - Hot Water Coil
Watertemp
(C/C)
Coilair onTemp(C)
Flow rate (m/h)(m/s)
1000(0.28)
1250(0.35)
1500(0.42)
1750(0.49)
2000(0.56)
2250(0.63)
82/71
11Power (kW)/Air supply temp. (C) 16/58 19.4/55 22/53 24.3/51.3 26/49.5 28/47
Water ow rate (l/h) /DP water (kPa) 1320/16 1560/22 1760/28 1950/34 2130/41 2300/47
15Power (kW)/Air supply temp. (C) 15.4/60.3 18/57 20.5/55 22.7/53 24.7/51 26/50
Water ow rate (l/h)/DP water (kPa) 1240/14 1440/19 1640/24 1820/30 1980/35 2140/41
90/70
11Pow er ( kW )/ Ai r suppl y t emp. ( C ) 17.2/ 61 .1 20.1/ 57 .8 22.7/ 55 .1 25.1/ 52 .9 27.3/ 50 .9 29.4/ 49 .2
Water ow rate (l/h)/DP water (kPa) 760/6 890/8 1000/10 1110/12 1210/14 1300/16
15P owe r ( kW )/A ir s u pp ly t e mp . ( C) 16 /62 .5 18 .7/ 59. 5 2 1. 2/ 56 .9 23 .4 /5 4. 7 2 5.5 /52 .9 27 .5 /5 1.3
Water ow rate (l/h)/DP water (kPa) 710/5 830/7 940/9 1030/10 1130/13 1210/14
45/40
11Pow er ( kW )/ Ai r suppl y t emp. ( C ) 7 .83/ 33 .8 9 .2/32.4 10.4/ 31 .2 11.5/ 30 .2 12.6/ 29 .4 13.6/ 28 .6
Water ow rate (l/h)/DP water (kPa) 1360 /19 1600/26 1810/32 2000/38 2190/46 2370/54
15Pow er ( kW )/ Ai r suppl y t emp. ( C ) 6 .75/ 35 7 .9/33.8 8 .97/ 32 .8 10/ 31 .9 10.8/ 31 .1 11.7/ 30 .4
Water ow rate (l/h)/DP water (kPa) 1180/14 1380/20 1560/24 1730/30 1880/35 2040/41
60/50
11P owe r ( kW )/A ir s u pp ly t e mp . ( C ) 1 0. 9/4 2. 9 1 2. 8/ 40. 8 1 4. 4/3 9. 1 1 6/3 7.7 1 7. 4/ 36 .5 18 .8 /3 5. 4
Water ow rate (l/h)/DP water (kPa) 950/10 1120/13 1260/16 1400/19 1520/22 1650/26
15P owe r ( kW )/A ir su pp ly te mp . ( C ) 9. 8/4 4. 1 1 1. 5/ 42. 2 13 /40 .7 14 .4/ 39. 4 1 5. 7/ 38 .3 16 .9 /3 7. 3
Water ow rate (l/h)/DP water (kPa) 860/8 1010/10 1140/13 1260 /16 1370/19 1480/22
BE for e3nhanced and e3lite versions - Electric HeaterFresh Air 0C 0C -5C -10C -15C -20CQv (m/h) 2300 2300 2300 2300 2300 2300
Versione3ssential e3nhanced BE 025 e3lite BE 025
Electric Heater Pre-Heater + Post-Heater
Total power (kW) - 3.75 3.75 6.75 6.75 + 3.75 6.75 + 6.75
Air supply Temp. (C) 16.6 21.5 21 20.1 20.1 19.1
-5C / 90% HR
+5C / 90% HR
0C / 90% HR
-10C / 90% HR
300Pa
250Pa 200Pa
300Pa
200Pa250Pa
150Pa
150Pa
200Pa
200Pa 150Pa
Returnair20C/50%
Efficiency(%)-EN308
perfan
Powerconsumption(W)
Staticpressure(Pa)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
100%90%
80%
70%
60%
50%
40%
0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67Flow rate (m3/s)
0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67Flow rate (m3/s)
0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67
Flow rate (m3/s)
0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67Flow rate (m3/s)
Performance curves shown are based on the e3nhanced or e3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e3nhanced or e3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.
Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.
Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.
Notes:
1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RHor 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.
2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.
Typical Plate Heat Exchanger Core Performance data
Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH
ModelAir fow rate
RecoveredkW
Air O temp C / RHThermal
Eiciency %m3/h m3/s
Crown 90-4 1450 0.40 11.9 19.5C 16 %RH 90.7
NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up
Watertemp
(C/C)
New airtemp(C)
Flow rate (m/h) 1400 1800 2200 2600
7/12
32/40Power (kW)/Air supply temp. (C-%HR) 10.7/15.9-79 12.4/17.1-77 13.7/18.0-76 14.8/18.8-75
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 83 0/ 14 2 12 0/ 18 2 35 0/2 1 2 53 0/2 4
27/50Power (kW)/Air supply temp. (C-%HR) 8.2/15.0-84 9.4/15.9-82 10.4/16.6-81 11.1/17.2-80
Water flow rate (l/h)/DP water (kPa) 140 0/8 1610/11 1 770/1 3 1910 /15
25/50Power (kW)/A ir suppl y t em p. ( C-%HR) 6 .4/14. 5-83 7.2/15. 3-82 7.9/16-81 8.3/16. 5-80
Water flow rate (l/h)/DP water (kPa) 1090/6 1240/7 1350/8 1430/9
6/11
32/40Power (kW)/Air supply temp. (C-%HR) 11.4/15.2-79 13.3/16.4-77 14.8/17.4-76 16.0/18.2-75
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 96 0/ 15 2 27 0/ 20 2 53 0/ 24 2 75 0/2 8
27/50Power (kW)/Air supply temp. (C-%HR) 8.9/14.3-84 10.3/15.2-82 11.5/16-81 12.4/16.6-81
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 53 0/ 10 1 77 0/ 13 1 96 0/ 15 2 12 0/1 8
25/50Power ( kW)/A ir suppl y t em p. ( C-%HR) 7 .2/13. 8-83 8.2/14. 7-82 9.0/15.4 -81 9.6/15. 9-80
Water flow rate (l /h)/DP water (kPa) 12 20/7 1400/9 1 530/10 1640 /11
CBX 4 BF for Chilled Water Module
-
7/28/2019 FW e3co Crown Technical Catalogue UK
9/13
16
Performance - 90-5 Heating Data - 90-5
BC for e3nhanced and e3lite versions - Hot Water Coil
Watertemp
(C/C)
Coilair onTemp(C)
Flow rate (m/h)(m/s)
1500(0.42)
1900(0.53)
2300(0.64)
2700(0.75)
3100(0.86)
3500(0.97)
82/71
11Power (kW)/Air supply temp. (C ) 24.8/58 29.3/55 33.5/53.1 37.2/50.9 40.7/49 44/47.4
Wa te r ow r at e ( l/h )/ DP wa te r ( kP a) 1 99 0/4 2 2 350 /58 2 69 0/7 4 29 80/ 91 3 260 /1 08 35 30/ 125
15P owe r ( kW )/A ir su pp ly te mp . ( C ) 2 3. 1/6 0. 3 27 .4/ 57. 3 3 1. 2/ 54 .8 34 .7 /5 2. 8 3 7. 9/5 1 41 /4 9. 4
Wa te r ow ra te (l /h )/ DP wa te r ( kP a) 1 85 0/3 7 2 200 /51 2 50 0/6 5 2 78 0/ 80 3 040 /94 .7 32 90/ 110
90/70
11Pow er ( kW )/ Ai r suppl y t emp. ( C ) 25.3/ 60 .2 29.7/ 56 .7 33.8/ 53 .9 37.5/ 51 .5 40.9/ 49 .5 44.1/ 47 .8
Water ow rate (l/h)/DP water (kPa) 1120/4 1310/6 1490/8 1660/9 1810/11 1950/13
15Pow er ( kW )/ Ai r suppl y t emp. ( C ) 23.5/ 61 .6 27.7/ 58 .3 31.5/ 55 .6 34.9/ 53 .4 38.1/ 51 .5 41.1/ 49 .9
Water ow rate (l/h)/DP water (kPa) 1040/4 1220/5 1390/7 1540/8 1680/10 1820/11
45/40
11P owe r ( kW )/A ir su pp ly te mp . ( C ) 1 1. 5/3 3. 5 1 3.6 /32 1 5. 5/3 0. 7 17 .3/ 29. 7 1 8.9 /28 .8 2 0. 4/ 28
Water ow rate (l/h)/DP water (kPa) 2000/14 2370/20 2700/25 3010/10 3290/36 3550/41
15P owe r ( kW )/A ir s u pp ly t e mp . ( C ) 10 /34 .7 1 1. 7/ 33. 4 1 3. 4/3 2. 3 14 .9/ 31. 3 1 6. 3/ 30 .6 17 .6 /2 9. 9
Water ow rate (l/h)/DP water (kPa) 1730/11 2040/15 2330 /19 2600/23 2840/27 3070/32
60/50
11P owe r ( kW )/A ir s u pp ly t e mp . ( C ) 16 /42 .3 1 8. 9/ 40. 1 2 1. 5/3 8. 3 23 .9/ 36. 9 2 6. 1/ 35 .6 28 .2 /3 4. 5
Water ow rate (l/h)/DP water (kPa) 1410/7 1650/9.4 1880/12 2090/15 2280/18 2470/20
15P owe r ( kW )/A ir su pp ly te mp . ( C ) 1 4. 4/4 3. 6 1 7/4 1. 6 19 .3 /4 0 21 .5/ 38. 6 2 3. 5/ 37 .5 25 .3 /3 6. 5
Water ow rate (l/h)/DP water (kPa) 1260/6 1490/8 1690/10 1880 /12 2060/15 2210/17
BE for e3nhanced and e3lite versions - Electric HeaterFresh Air 0C 0C -5C -10C -15C -20CQv (m/h) 3500 3500 3500 3500 3500 3500
Versione3ssential e3nhanced BE 025 e3lite BE 025
Electric Heater Pre-Heater + Post-Heater
Total power (kW) - 6.75 6.75 13.5 8.25 + 6.75 8.25 + 13.5
Air supply Temp. (C) 16.7 22.5 22 20.2 19.5 20.5
-5C / 90% HR
+5C / 90% HR
0C / 90% HR
300Pa
250Pa
250Pa200Pa
200Pa
150Pa
150Pa
300Pa
-10C / 90% HR
200Pa
200Pa
150Pa
150Pa
Returnair20C/50%
Efficiency(%)-EN308
perfan
Powerconsumption(W)
Staticpressure(Pa)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
70%
60%
50%
40%
30%
0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m3/s)
0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m3/s)
0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00
Flow rate (m3/s)
0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m3/s)
Performance curves shown are based on the e 3nhanced or e3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e3nhanced or e3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.
Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.
Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.
Notes:
1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RHor 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.
2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.
Typical Plate Heat Exchanger Core Performance data
Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH
ModelAir fow rate
RecoveredkW
Air O temp C / RHThermal
Eiciency %m3/h m3/s
Crown 90-5 2100 0.58 17.0 19.1C 16.4%RH 89.2
NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up
Watertemp
(C/C)
New airtemp(C)
Flow rate (m/h) 2000 2500 3000 3500
7/12
32/40
Power (kW)/Air supply temp. (C-%HR) 19.2/12.7-84 22.4/13.8-83 25.2/14.7-81 27.7/15.4-80
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 3 30 0/ 14 3 84 0/ 18 4 32 0/2 2 4 74 0/2 6
27/50
Power (kW)/Air supply temp. (C-%HR) 14.9/12.5-88 17.3/13.3-86 19.4/14-85 21.2/14.6-84
Water flow rate (l/h)/DP water (kPa) 256 0/9 2960/11 33 20/1 4 3630 /16
25/50
Power (kW)/Air supply temp. (C-%HR) 12.0/12.3-87 13.8/13-86 15.3/13.7-85 16.6/14.2-84
Water flow rate (l/h)/DP water (kPa) 205 0/6 2360/8 2620/9 2850 /10
6/11
32/40
Power (kW)/Air supply temp. (C-%HR) 20.4/11.9-85 23.8/13-83 26.8/13.9-82 29.5/14.7-80
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 3 49 0/ 15 4 07 0/ 20 4 59 0/2 4 5 06 0/2 9
27/50
Power (kW)/Air supply temp. (C-%HR) 16.1/11.6-88 18.7/12.5-87 21.0/13.3-86 23.1/13.9-85
W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 2 76 0/ 10 3 20 0/ 13 3 60 0/1 6 3 95 0/1 9
25/50
Power (kW)/Air supply temp. (C-%HR) 13.2/11.4-87 15.2/12.2-86 17.0/12.9-85 18.6/13.5-84
Water flow rate (l /h)/DP water (kPa) 22 60/7 2610/9 2 910/11 3180 /13
CBX 5 BF for Chilled Water Module
-
7/28/2019 FW e3co Crown Technical Catalogue UK
10/13
18
Performance - 90-6 Heating Data - 90-6
BC for e3nhanced and e3lite versions - Hot Water Coil
Watertemp
(C/C)
Coilair onTemp(C)
Flow rate (m/h)(m/s)
2200(0.61)
2700(0.75)
3200(0.89)
3700(1.03)
4200(1.17)
4700(1.31)
82/71
11Power (kW)/Air supply temp. (C) 36/59 42/56 47.8/54.2 52.7/52.3 57.3/50 61/49
Wa te r ow ra te (l /h )/D P wa te r ( kP a) 29 40/ 8 3 41 0/ 11 3 830 /1 3. 3 42 30/ 16 4 600 /18 .7 49 50/ 22
15Power (kW)/Air supply temp. (C ) 34/60.6 39/58 44.5/55.8 49.1/54 53.4/52.4 57.4/50.9
Wa te r ow r at e ( l/h )/D P wa te r ( kP a) 27 30/ 7 31 70/ 9. 3 3 570 /1 1. 6 39 40/ 14 4 28 0/1 6 46 00/ 19
90/70
11Pow er (kW)/A ir supp ly temp . ( C ) 37.9/ 61 .3 43.7/ 58 .3 49.1/ 55 .8 54.1/ 53 .7 58.7 / 51 .8 63.1/ 50 .2
Water ow rate (l/h)/DP water (kPa) 1670/3 1930/4 2170/5 2390/6 2590/7 2790/8
15Pow er ( kW )/ Ai r suppl y t emp. ( C ) 35.3/ 62 .7 40.8/ 59 .8 45.8/ 57 .5 50.4/ 55 .4 54.7/ 53 .7 58.8/ 52 .2
Water ow rate (l/h)/DP water (kPa) 1560/3 1800/4 2020/4 2230/5 2420/6 2600/7
45/40
11P owe r ( kW )/A ir s u pp ly t e mp . ( C) 17 .3 /3 4 20 .1/ 32. 7 2 2. 6/ 31 .6 24 .9 /3 0. 6 2 7.1 /29 .8 29 .1 /2 9.1
Water ow rate (l/h)/DP water (kPa) 3010/10 3500/12 3940/15 4340/18 4720/22 5070/24
15P owe r ( kW )/A ir su pp ly te mp . ( C ) 1 4. 9/3 5. 1 1 7. 3/ 34 1 9. 4/3 3 21 .4 /3 2. 2 2 3.3 /31 .5 25 .1 /3 0.8
Water ow rate (l/h)/DP water (kPa) 2600/7 3010/10 3380 /11 3730/14 4060/16 4370/19
60/50
11P owe r ( kW )/A ir s up pl y t em p. ( C ) 24 /4 3 27 .9/ 41. 1 3 1. 3/ 39 .5 34 .5 /3 8. 2 3 3.6 /38 .8 40 .3/ 36
Water ow rate (l/h)/DP water (kPa) 2110/5 2440/6 2740/8 3020/9 2940/9 3530/12
15P owe r ( kW )/A ir s u pp ly t e mp . ( C) 2 1. 6/4 4. 2 2 5/4 2.5 2 8. 1/4 1. 1 30 .9 /3 9. 8 3 7.5 /37 .1 36 .2 /3 7. 9
Water ow rate (l/h)/DP water (kPa) 1890/4 2190/5 2460/6 2700/8 3280/11 3170/10
BE for e3nhanced and e3lite versions - Electric HeaterFresh Air 0C 0C -5C -10C -15C -20CQv (m/h) 4800 4800 4800 4800 4800 4800
Versione3ssential e3nhanced BE 025 e3lite BE 025
Electric Heater Pre-Heater + Post-Heater
Total power (kW) - 6.75 6.75 13.5 18 + 6.75 18 + 13.5
Air supply Temp. (C) 16.6 20.8 20.3 19.7 20.9 20.9
-5C / 90% HR
+5C / 90% HR
0C / 90% HR
-10C / 90% HR
300Pa
250Pa
250Pa
200Pa
300Pa200Pa150Pa
150Pa
300Pa200Pa
200Pa
Returnair20C/50%
Efficiency(%)-EN308
perfan
Powerconsumption(W)
Staticpressure(Pa)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
Flow rate (m3/h)
80%
70%
60%
50%
40%30%
Performance curves shown are based on the e3nhanced or e3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e3nhanced or e3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.
Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.
Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.
0.39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39Flow rate (m3/s)
0.39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39Flow rate (m3/s)
0.39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39
Flow rate (m
3
/s)
0.39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39Flow rate (m3/s)
Notes:
1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RHor 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.
2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.
Typical Plate Heat Exchanger Core Performance data
Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH
ModelAir fow rate
RecoveredkW
Air O temp C / RHThermal
Eiciency %m3/h m3/s
Crown 90-6 3000 0.83 24.3 19.1C 16.4%RH 89.1
NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up
Watertemp
(C/C)
New airtemp(C)
Flow rate (m/h) 2000 3000 4000 5000
7/12
32/40Power (kW)/Air supply temp. (C-%HR) 17.1/12.5-100 28.9/12.7-84 35.1/14.1-82 40.4/15.2-81
Water flow rate (l/h)/DP water (kPa) 293 0/4 4950/10 60 20/1 4 6920 /17
27/50Power (kW)/Air supply temp. (C-%HR) 13.0/12.5-100 22.3/12.5-88 27.0/13.5-88 30.9/14.4-85
Water flow rate (l/h)/DP water (kPa) 223 0/3 3830/6 4620/9 5290 /11
25/50Power (kW)/Air supply temp. (C-%HR) 9.9/12.3-100 17.9/12.3-87 21.4/13.3-85 24.2/14-84
Water flow rate (l/h)/DP water (kPa) 1710/2 3070/4 3660/6 4150/7
6/11
32/40Power (kW)/Air supply temp. (C-%HR) 18.3/11.8-100 30.6/11.9-85 37.3/13.3-83 43.1/14.4-81
Water flow rate (l /h)/DP water (kPa) 31 40/5 5230/11 6 390/15 7380 /20
27/50Power (kW)/Air supply temp. (C-%HR) 14.2/11.7-100 24.1/11.6-88 29.3/12.8-86 33.6/13.7-85
Water flow rate (l /h)/DP water (kPa) 24 40/3 4130/7 5 010/10 576 0/13
25/50Power (kW)/Air supply temp. (C-%HR) 11.4/11.4-100 19.7/11.4-87 23.7/12.5-86 27.0/13.3-84
Water flow rate (l/h)/DP water (kPa) 1950/2 3380/5 4060/7 4630/9
CBX 6 BF for Chilled Water Module
-
7/28/2019 FW e3co Crown Technical Catalogue UK
11/13
20
Modulation Solutions Flow Rate Modulation
HS air flow
LS air flow
Air flow
HS constant air flow
LS constant air flow
Air flow
CAV ECConstant Air Volume2 Constant Air flow Options
VAV TB ECVariable Air Volume - Trickle & Boost Strategy2 Air flow rates - Low Speed/High Speed
View of access to technica l compartment
Access door to technical compartment
features integral display and user interface.
Remote control unit (optional)
HS air flow
LS air flow
Air flow
HS constant air flow
Air flow
LS constant air flow
COP ECConstant Pressure Control
All control options use EC motor technology
VAV AQ ECVariable Air Volume/CO2 sensor & EC FansProportional air flow control via CO2 sensor
CAV AQ ECConstant Air Volume/CO2 sensor2 Constant Air flow options controlled byCO2 sensor
The e3co Crown unit has a factory-programmable controller as standard, which can be used to configure how the air
flow can be modulated:
Constant pressure
Air flow
The e3co Crown ERU product includes an integral control panel with LCD displaymounted on the unit casing, and can be used to adjust time clocks, air flow rates,
temperatures (proportional control of the internal bypass, internal hot water coil for BC
version or electric heater for BE version, Night cooling). Fault alarms are also displayed.
Stop HS Stop LS HS Stop LS+ LS HS
Forced Stop
e3co-Crown VAV TB EC
Variable Air Volume control (2
air flows) - Trickle and Boost
Functions
Clock Clock Clock + VF Contact #1Easy LCD display or
remote control
or or or or
VF Contact #1 VF Contact #1 VF Contact #1 + VF Contact #1 VF Contact #1
e3co-Crown CAV EC
Constant Air Volume control (1 or
2 air flows). EC Fans Fitted
Clock Clock Clock + VF Contact #1Easy LCD display or remote
control
or or or or
VF Contact #1 VF Contact #1 VF Contact #1 + VF Contact #1 VF Contact #1
e3co-Crown COP EC
Constant Pressure control at
Variable Air flows. EC Fans Fitted
ClockEasy LCD display or remote
control
or or
VF Contact #1 VF Contact #1
e3co-Crown VAV AQ EC
PROPORTIONAL Variable Air
Volume control via CO2
Sensor,
between 2 adjustable air flows. EC
Fans Fitted.
Clock + 0-10V CO2
ProbesEasy LCD display or remote
control
or or
0-10V CO2
Probes VF Contact #1
e3co-Crown CAV AQ EC
PROPORTIONAL control via CO2Sensor, between 2 Constant Air
Volumes (adjustable #2). EC Fans
Fitted.
Clock + 0-10V CO2
ProbesEasy LCD display or remote
control
or or
0-10V CO2
Probes VF Contact #1
Notes:
#1: Volt Free Contact can be either : Remote ON-OFF /
ON-OFF CO2 Probe / ON-OFF Humidity Probe
#2 Except e3co-Crown 90-1
Control Function Options:
Standard Function Optional Function
-
7/28/2019 FW e3co Crown Technical Catalogue UK
12/13
22
Sound Data Product Codes
As standard, integrated controls can manage one or several heaters
(depending on the unit version selected : e3ssential, e3nhanced or e3lite)
Climate Solutions
Integrated Coil
CrownType
Pre-Heating Heating
Electric coil Electric coil Water water coil
e3ssential - - -
e3nhanced BC - -
e3nhanced BE - -
e3lite BC -
e3lite BE -
1 2 3 4 5
e3co-CROWN 90-1 L - P - W - Y e3ssential Controlse3nhanced BC/BE xxx
e3lite BC/BE xxx
1 - High Thermal Efficiency unit (90%) - complete with automatic control and Counter Flow Plate Heat Exchanger
2 - Unit Model Code Examples:
90-1 Efficiency = 90%, Unit size = 1 (0.22 m 3/s)
90-5 Efficiency = 90%, Unit size = 5 (1.00 m 3/s)
3 - Unit Configuration Options:
L & P: Side-by-Side format (except unit model 90-6)
W & Y: Double Deck format
4 - Unit Version Options:
e3ssential Unit with NO coils fitted
e3nhanced BC Hot water coil (POST Heater) plus appropriate controls fitted
e3nhanced BE xxx Electric heater (POST Heater) plus appropriate controls fitted
e3lite BC Unit with Electric PRE-Heater and hot water POST Heater plus controls
e3lite BE xxx Unit with Electric PRE-Heater and Electric POST heater plus controls
For BE versions, the xxx relates to the power rating of the electrical heater. Options shown below:
BE 025 = 2.50 (single phase)
BE 037 = 3.70 (single phase)
BE 052 = 5.25 (three phase)
BE 067 = 6.75 (three phase)
BE 082 = 8.25 (three phase)
BE 105 = 10.5 (three phase)
BE 135 = 13.5 (three phase)
5 - Controls:
VAV TB EC (Std) - Variable Air Volume Trickle and Boost
VAV AQ EC - Variable Air Volume and CO2
Sensor
CAV EC - Constant Air Volume
CAV AQ EC - Constant Air Volume and CO2
Sensor
COP EC - Constant Pressure - All motors are EC Type
All units feature EC motors
Accessory Options
Weather Roof
Code: WR
For Outdoor installation.Pre-Painted Steel
(RAL 7035)
Motorized Damper
Code: MD
For Unit shut-off andFrost protection.
Features Opposed blades
Rain Cowl
Code: RC
Complete with safety grille
(bird guard)
Constructed from
Galvanised Steel
Support Legs (set of 4)
Code: SLK
Can be used instead of
Integral mounting brackets
Flexible Connectors
Code: FC MO
Circular: 315 to 630mm
ElectroValve Kit
Code: EVK
0-10V motorized 3 way valve
for used with e3nhanced
and e3lite BC
Available IP 41 or IP 54
Damper Motor
Code: DA
Open / Closed 24V
Servo Motor to control
Fresh air damper and to
provide Frost protection
Remote Control
Code: RC-10ML
Additional LCD display
Can be used local to Easy
Control compartment
or remote (10m) from unit
BMS Controller Unit
Code: BCU
Controller with LON or
TCP/IP BMS protocol
Control Repeater Unit
Code: CRU
Repeater unit used to
Booster control signal
between 10m and 1km
from unit
Acoustic data has been obtained from tests based upon the EN 13053 standard
External Chilled water
Coil Section - Code: CBX-BF
or
External DX Coil Section
Code: CBX-DX
Summer/Winter Changeover
ThermoStat
For use with CBX-BF
Model
In-duct Sound Power Levels (Supply Air and Exhaust Air Connections) BreakoutdBA @
3mSFP
63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz Lw LwA
Crown 90-1 66 65 67 68 64 59 56 56 73 69 33 0.85
Crown 90-2 64 65 66 69 64 58 57 61 74 70 34 0.88
Crown 90-3 66 69 70 68 68 60 57 55 76 71 35 0.72
Crown 90-4 65 69 71 68 67 60 57 55 76 71 35 0.72
Crown 90-5 65 72 73 72 69 66 63 65 78 74 39 1.06
Crown 90-6 70 78 79 78 75 73 70 72 85 81 45 1.01
-
7/28/2019 FW e3co Crown Technical Catalogue UK
13/13
Flkt Woods Group SA18, avenue Louis Casa, CH-1209 Geneva, Switzerland
Tel. +41 22 309 3800
email [email protected] www.flaktwoods.com
Flkt Woods operates a policy of continuous improvement and reserves the right to supply products that may differ fromFlkt Woods operates a policy of continuous improvement and reserves the right to supply products that may differ from
Flkt Woods Group - Ventilation Solutions
The Flkt Woods Group is divided into three businesses:
Global Inrastructure and Industry (GII)A leader for Air Movement using fans to improve performance of equipment and industrialprocesses
Air Climate Solutions (ACS)A worldwide HVAC leader recognized by our customers as a provider of superior Air ClimateSolutions combining Indoor Air Quality and Energy Efciency applied to specied buildings
Ventilation Solutions (VS)A European Ventilation Specialist Servicing our customers with a complete range of
ventilation products focused on Non residential buildings. For more specic productinformation for Ventilation Solutions, please visit:
www.vsecatalogue.flaktwoods.com
Flkt Woods LimitedAxial Way, ColchesterEssex, C04 5ZDUNITED KINGDOMTel: +44 (0)1206 222 555
Fax: +44 (0)1206 222 777E-mail: [email protected]
Flkt Woods OyKalevantie 39FI-20520TurkuFINLANDTel: +358 20 442 3000Fax: +358 20 442 3018E-mail: [email protected]
Flkt Woods OyHmeentie 23FI-37800ToijalaFINLANDTel: +358 20 442 3500Fax: +358 20 442 3502E-mail: [email protected]
Flkt Woods ABGesllgatan 17745 39EnkpingSWEDENTel: +46 36 19 30 00Fax: +46 17 12 40 97E-mail: [email protected]
Flkt Woods ABKung Hans vg12 192 68, SollentunaSwedenTel: +46 (0)771 26 26 26
Fax: +46 (0)8 626 73 10E-mail: [email protected]
Flkt Woods ABFlktvgen 2, Box 84153 22JrnaSWEDENTel: +46 8-551795 00Fax: +46 8-551744 80E-mail: [email protected]
Flkt Woods4 Avenue LaurentCELY-Batiment C - Etage 3Asnieres Sur Seine92600 FRANCETel: +33 1 80 21 07 00Fax: +33 1 80 21 07 00E-mail: [email protected]
Flkt Woods Ventilatoren GmbHAm Sportplatz 4DE-40882RatingenGERMANYTel: +49 2012 61038 11Fax: +49 2102 61038 18E-mail: [email protected]
Flkt Woods SpAVia Pacinotti, 28IT-20092, Cinisello BalsamoITALYTel: +39 02 6186 6091
Fax: +39 02 6186 0947E-mail: [email protected]
Flkt Bovent Sp. z o.o.Panattoni Park Pruszkw IIul. Poudniowa 2, Otarzew05-850 Oarw MazowieckiPOLANDTel: +48 22 392 43 43Fax: +48 22 392 43 44E-mail: [email protected]
LLC Flkt Industrial& Building Systems23, ul. ProfsojuznayaRU-117418 MoscowRUSSIATel: +7 (495) 589-31-08Fax: +7 (495) 589-31-74E-mail: [email protected]
VS/ERU
TBG
ROUP-03/0312