Fundamentals of Fiber To The Office (FTTO)
P.R.Rajendranath, RCDD, OSP, CT, DCETopnet Distribution, Dubai
Dirk Herppich, Dipl.‐Ing.Microsens, Germany
![Page 2: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/2.jpg)
Agenda
• Introduction of FTTO• Design Guidelines• Installation Practices – Hardware & Configuration
• Management of FTTO’s• Q&A
7/27/2017 Microsens‐[email protected]‐2017 2
![Page 3: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/3.jpg)
Introduction
• HistoryFTTO Technology emerged in Germany at the start of the 1980s when fiber based connectivity was extensively explored and meet the following,‐ Ethernet based‐ Long Life Cycle‐ Redundancy‐ Security‐ Improved energy efficiency‐ Low maintenance‐ Less network hierarchy
7/27/2017 Microsens‐[email protected]‐2017 3
![Page 4: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/4.jpg)
Introduction
• FTTO (Fiber To The Office) is a future‐proof networking infrastructure for modern office environments
• A cost effective cabling infrastructure for modern office environments
• FTTO is a standards compliant and decentralized cabling concept
7/27/2017 Microsens‐[email protected]‐2017 4
![Page 5: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/5.jpg)
Introduction
• Highly efficient fiber optic technology with the flexibility of twisted pair cabling
• Networking infrastructure that offers flexibility, protects investments and reduces life cycle costs.
7/27/2017 Microsens‐[email protected]‐2017 5
![Page 7: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/7.jpg)
Fiber Optic Technology
• Fiber optic technology being the most future‐proof cabling technology currently available, its economic benefits are widely accepted, and used particularly in generic office environments, such as commercially‐used buildings.
7/27/2017 Microsens‐[email protected]‐2017 7
![Page 8: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/8.jpg)
Current Scenario
• In Local Area Networks (LANs), optical fiber is normally used for backbone cabling.
• Multi‐fiber multimode (OM3/OM4) or single‐mode fiber cables are used in backbone.
• For horizontal cabling for the individual floors, fiber optic cabling is quite rare, only copper cabling is used.
• Following a short boom at the end of the 90s, things have become very quiet again around Fiber to the Office (FTTO) and Fiber to the Desk (FTTD) solutions.
7/27/2017 Microsens‐[email protected]‐2017 8
![Page 9: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/9.jpg)
Long distances possible > 100 km
Almost unlimited bandwidth
Low space requirements
Longer Life time
No EMC issues and grounding problems
Higher Security (tapping)
Fiber optic cable less expensive than copper
Environmental friendly (green building)
Advantages of Fiber Optics
7/27/2017 Microsens‐[email protected]‐20179
![Page 10: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/10.jpg)
Physical Conditions Demand Fiber
For a large number of applications copper cabling cannot be used
–Physical restrictions • airports with extremely long cable routes• historically protected buildings need thinner cables and smaller pathways
– Electro‐magnetic considerations • e.g. industrial, hospitals
7/27/2017 Microsens‐[email protected]‐2017 10
![Page 11: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/11.jpg)
FTTO Reduces Cost
Others
Installation & termination
Passive Infrastructure (Fiber)
Passive Infrastructure (Copper)LAN Systems (active)
SCN –Copper
SCN –FTTO
FTTO Makes Gigabit Ethernet Cost-Effective for medium to large IT-Infrastructures• CAPEX (Capital expenditure)• OPEX (Operational
expenditure)• Flexibility
7/27/2017 Microsens‐[email protected]‐2017 11
![Page 12: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/12.jpg)
FTTO Green and Sustainable
SCN –Copper
SCN –FTTO
Energy Consumption / Costs
Typical > 200 ports
• FTTO saves up to 70% in energy costs
• FTTO is the greenest network solution• No need for energy hungry floor
distribution rooms– Less power consumed – Less active equipment also means less
CO2-Footprint and less impact on the environment
– Less technical rooms also means more useable area
7/27/2017 Microsens‐[email protected]‐2017 12
![Page 13: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/13.jpg)
Fiber Requires Less Energy
Due to fibre physics, less energy is required to transport data over fibre.
– Fibre transmission can halve energy requirements in comparison with traditional copper cabling solutions.
– Fibre optic cables can carry signals with much less energy loss than copper cable as copper wires lose signal energy as heat (P=I2R) due to their resistance.
7/27/2017 Microsens‐[email protected]‐2017 13
![Page 14: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/14.jpg)
FTTO Consumes Low Power
0.5‐1 W/port
3‐4 W/port
Micro FTTO switch consumes low power, i.e. 0.5 – 1 W per port for data transmission
– as against 3-4 W per port for traditional rack mounted switches
7/27/2017 Microsens‐[email protected]‐2017 14
![Page 15: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/15.jpg)
FTTO is Energy Efficient
FTTO micro-switches support “Eco-Mode” and Energy Efficient Ethernet (IEEE 802.3az)
7/27/2017 Microsens‐[email protected]‐2017 15
![Page 16: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/16.jpg)
Copper Structured Cabling Network
Strict length limitation (max. 90 m)
Floor distribution required
Additional energy consumption for air conditioning / UPS
For each end device one central switch port is required
Huge bundles of cabling (fire load / EMC)
Technology change requires complete change of horizontal cabling
7/27/2017 Microsens‐[email protected]‐201716
![Page 17: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/17.jpg)
Fiber To The Office
No length limitation
Gain more usable space – no floor distribution required
4 end devices share one central switch port
Up to 75% reduced cabling volume
At technology change the cabling can remain unchanged
Technical advantages of fibre
7/27/2017 Microsens‐[email protected]‐201717
![Page 18: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/18.jpg)
Cost Effectiveness
“Cost comparison of the FTTO‐concept with a standard structured cabling with floor distribution“•WIK = Wissenschaftliches Institutfür Kommunikationsdienste
•Founded by the ministry of economy andtechnology (BMWi)
•Analyses and evaluates the concept in terms ofbusiness and political economical aspects
•Main competence is the development of detailed cost models for different network architectures.
The comparison shows clearly the advantagesof the FTTO concept. Both, technology andeconomical wise fiber networks are the betterchoice. WIK‐Consults proves this with anexpertise and recommends clearly the useof fiber networks.
7/27/2017 Microsens‐[email protected]‐201718
![Page 21: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/21.jpg)
Cost Effectiveness
Number of workplaces 220 220 1040 1040
New building
Old building
Newbuilding
Oldbuilding
Costs of installation and operation after 10 years
Copper 429,860 € 437,294 € 1,668,005 € 1,731,980 €
FTTO 309,129 € 309,129 € 1,106,685 € 1,106,685 €
Related difference 28% 29% 34% 36%
Yearly costs per work place
Copper 265 € 270 € 218 € 226 €
FTTO 191 € 191 € 145 € 145 €
Related difference 28% 29% 34% 36%
– The total costs (first installation, operation, planned replacements) of the copper architecture are in all scenarios higher than the FTTO solution and the cost advantage increases if you increase the distances, the number of floors or the number of workspaces.
7/27/2017 Microsens‐[email protected]‐201721
![Page 23: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/23.jpg)
FTTO Concept
Standards‐compliant, decentralized networking concept
Combination of the advantages of fiber optics and copper cabling in an intelligent way
Standard interfaces (TP) at the workplace
One central building wiring closet for better scalability, migration, and redundancy
Investment protection and reliable planning due to long‐term periods of use
Low cable volume, no floor distribution units, reduction of investment and operational costs
7/27/2017 Microsens‐[email protected]‐2017 23
![Page 24: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/24.jpg)
• In classic structured cabling system, the horizontal cabling on each floor consists of copper cables linking the data ports in the offices to decentralisedEthernet switches located on each floor
Copper Structured Cabling System
Standard Phone
Standard Phone
PC
Printer
Notebook
PC
Wireless AP
Data
Voice
Wall Outlets
7/27/2017 Microsens‐[email protected]‐2017 24
![Page 25: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/25.jpg)
• The FTTO Concept implements fiber optic cables for the horizontal floor cabling, allowing the end users to connect their equipment directly up to copper Ethernet ports via 4‐port fiber micro switches / installation switches (Fast Ethernet or 1 Gb) located in the work areas.
FTTO Concept
Notebook
Printer
PC
Phone
Installation Switch
Data & Voice
7/27/2017 Microsens‐[email protected]‐2017 25
![Page 26: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/26.jpg)
Central Switch
FTTO Concept
Central Switch
FTTO Switch
7/27/2017 Microsens‐[email protected]‐2017 26
![Page 28: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/28.jpg)
FTTO Sub Systems
Work Area
• The horizontal cable can be terminated with a splice on connector or field connectors
7/27/2017 Microsens‐[email protected]‐2017 28
![Page 29: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/29.jpg)
FTTO Sub Systems
Horizontal Cables
For the horizontal links either Single Mode or Multi Mode cables can be used.
Preferably 2 core
7/27/2017 Microsens‐[email protected]‐2017 29
![Page 30: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/30.jpg)
FTTO Sub Systems
Backbone Cables
• For the backbone links, use higher count tight buffered cables
• Strands depends on the number of FTTO switches
7/27/2017 Microsens‐[email protected]‐2017 30
![Page 31: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/31.jpg)
FTTO Sub Systems
Backbone Hardware
Wall mount splice enclosures are used to join the backbone and horizontal cables.
7/27/2017 Microsens‐[email protected]‐2017 31
![Page 32: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/32.jpg)
Easy installation and operation
Compact dimensions, Universal 45x45 Design
Universal Snap‐In mounting into
Cable trunks, sub‐floor boxes, wall boxes
In wall
Desktop (Desktop box, laboratory unit)
Distribution racks (DIN‐rails)
Simple configuration and monitoring vianetwork management
Micro Switch / Installation Switch
7/27/2017 Microsens‐[email protected]‐201732
![Page 33: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/33.jpg)
FTTO Switch
Optimised compact and fanless design Full Gigabit Ethernet Performance on all ports 1x 1000Base‐X fiber uplink 4x 10/100/1000Base‐T Twisted Pair RJ‐45 ports 1x 10/100/1000Base‐T Twisted Pair RJ‐45 downlink (optional)
Power‐over‐Ethernet functionality on all RJ‐45 ports Integrated network management
7/27/2017 Microsens‐[email protected]‐2017 33
![Page 34: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/34.jpg)
Power Supply
•AC power supply (decentral) Local AC/DC power supply 230V AC to 54V DC, 65W
7/27/2017 Microsens‐[email protected]‐2017 34
![Page 35: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/35.jpg)
Power Supply
•iDC Power Supply (central) Central AC/DC power supply Protection with UPS possible Voltage drop to be considered
7/27/2017 Microsens‐[email protected]‐2017 35
![Page 36: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/36.jpg)
Power Supply
Power Design Tool Calculating cable length and diameter
7/27/2017 Microsens‐[email protected]‐2017 36
![Page 38: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/38.jpg)
Redunduncy
Dual SFP Uplink• Provides 2 slots for fiber uplink
• Downlink is removed
• Former Downlink port is used as Expansion Port (Terminal)
7/27/2017 Microsens‐[email protected]‐2017 38
![Page 39: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/39.jpg)
FTTO – Dual SFP
Data Center BData Center A
Micro Switch G6Dual SFP Uplink
Dual SFP Uplink ‐ Redundant Data Center
•Service is more critical than individual user•Maximum network service availability•Minimized downtime
7/27/2017 Microsens‐[email protected]‐2017 39
![Page 40: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/40.jpg)
FTTO – Dual SFP
Micro Switch G6Dual SFP Uplink
Micro Switch G6Dual SFP Uplink
Micro Switch G6Dual SFP Uplink
Dual SFP Uplink – Redundant Ring Structure
•Simplified network topology•Easy to install, easy to expand•Ring provides failure tolerance
7/27/2017 Microsens‐[email protected]‐2017 40
![Page 41: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/41.jpg)
FTTO – Dual SFP
Patch Panel
Micro Switch G6Dual SFP Uplink
Micro Switch G6Dual SFP Uplink
Micro Switch G6Dual SFP Uplink
Dual SFP Uplink –Ring structure with star topology
•Star cabling topology, patched for ring structure•Utilization of existing cabling•Ring provides failure tolerance7/27/2017 Microsens‐[email protected]‐2017 41
![Page 42: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/42.jpg)
FTTO – Ring Cabling
FTTO TopologyRing Structure•Ring structure for horizontal cabling•Ring structure for vertical cabling•Combination of PLM and Micro Switches•Simplified installation and expansion•Minimized cabling efforts
Profi LineModular
Profi LineModular
Profi LineModular
Micro Switch G 6Dual SFP Uplink
Micro Switch G 6Dual SFP Uplink
Micro Switch G 6Dual SFP Uplink
7/27/2017 Microsens‐[email protected]‐2017 42
![Page 43: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/43.jpg)
FTTO Expansion
Downlink Port
DownlinkPortsEnergyEfficientEthernetPoE+ (max. 30 W)
• For cascading up to 3 FTTO switches
• For locations where more than 4 ports are required
7/27/2017 Microsens‐[email protected]‐2017 43
![Page 45: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/45.jpg)
Cabling Requirement
• Usable space / floor ‐ 1,200 m2
• Number of floors ‐ 6• Total usable space ‐ 7,200 m2
• Number of work areas ‐ 720 • Work areas / floor ‐ 120• I/O per floor ‐ 120 dual
7/27/2017 Microsens‐[email protected]‐2017 45
![Page 47: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/47.jpg)
Copper Structured Cabling Information Outlets 1,440 Cat6 Patch Cords ‐ I/O 1,440 Cat6 Horizontal Cable (m) 72,000 Cat6 Patch Panel (24 port) 60 Cat6 Patch Cords ‐ TR 1,440 24‐port access switch 60 FO Patch Panel (6‐fiber) 5 FO Patch Panel (48‐fiber) 1 FO Patch Cords 126‐core FO cable (m) 150 42U Racks for Telecom Rooms 5 42U Racks for Equipment Room 4 Telecom Rooms 5 Equipment Room 1 Core Switch ports 60
7/27/2017 Microsens‐[email protected]‐2017 47
![Page 50: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/50.jpg)
FTTO Bill of Material
FTTO switch (4‐port) 360 Cat6 Patch Cords ‐ I/O 1,440 2‐core FO cable Horizontal (m) 18,000 FO termination box 360 FO Patch Cords (FTTO) 360 Splice enclosures 6 FO Patch Cords (ER) 360
FO Patch Panel (72‐fiber) 12 72‐core FO cable (m) 300 42U Racks for Equipment Room 4 Equipment Room 1 Core Switch ports 360
7/27/2017 Microsens‐[email protected]‐2017 50
![Page 51: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/51.jpg)
Copper and FTTO Bill of MaterialItem Copper FTTO
Information Outlets 1,440 FTTO switch (4‐port) 360 Cat6 Patch Cords ‐ I/O 1,440 1,440Cat6 Horizontal Cable (m) 72,000 2‐core FO cable Horizontal 18,000 FO termination 360 Cat6 Patch Panel (24 port) 60 Cat6 Patch Cords ‐ TR 1,440 24‐port access switch 60 FO Patch Panel (6‐port) 5 FO Patch Panel (48‐port) 1 FO Patch Panel (72‐fiber) 12 6‐core FO cable (m) 150 72‐core FO cable (m) 300 FO Patch Cords 12 360 42U Racks for Telecom Rooms 5 Splice enclosures 6 42U Racks for Equipment Room 4 4
Telecom Rooms 5
Equipment Room 1 1Core Switch ports 60 360
7/27/2017 Microsens‐[email protected]‐2017 51
![Page 52: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/52.jpg)
Design Advantages of FTTO Solution
![Page 53: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/53.jpg)
Saving Space on Telecom Rooms
Only 2 per floor(optional)
FTTO COPPER
• Saving on premium space• Reduced operations cost (Cooling, Power, maintenance, access control, fire safety)
7/27/2017 Microsens‐[email protected]‐2017 53
![Page 54: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/54.jpg)
Cable Trunking and Laying
2 core FO cable is only 4 mm diaand one cable for 4 users
Cat6A or Cat7 cable is 7 – 8 mm diaand 4 cables for 4 users
• Saving on cable trunking• Reduced installationcost
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 54
![Page 55: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/55.jpg)
Core and Access Switches
Only 3 core switches
60 nos. 24-port Gigabit switches with PoE and 1 Core switch
• Saving on hardware, space, power and cooling• Reduced maintenance and troubleshooting• Higher reliability and availability
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 55
![Page 56: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/56.jpg)
Bandwidth per User
1Gb/s
1Gb/s
4 users share 1 GbE link24 users share 1 GbE link
FTTO offers higher bandwidth per user
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 56
![Page 57: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/57.jpg)
Future Proof
All present and future datatransfer speeds will be supported
1
Gb/s1040100 ++
1
10 Gb/s
??
> 1 THz 500 MHz
FTTO is future proofed
Copper can not support morethan today’s 10 Gb/s
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 57
![Page 58: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/58.jpg)
Life Cycle Cost
Fiber networks have alonger useable lifetimebecause fiber networkscan be upgraded withoutpulling new cable:increased data rates areimplemented bychanging the electronics.
In a copper cabling network,increased data rates havehistorically required thatusers change cables,connectors and electronics [Cat5e, Cat6, Cat6A].
FTTO offers lowest TCO
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 58
![Page 59: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/59.jpg)
Costs
• Initial cost slightly less than copper
• Much less cost of space for only a few TRs
• Low operation cost• Low maintenance cost
• High initial cost for huge cabling, trunking and large quantity of hardware
• Huge cost for large number of TRs
• High operation cost• High maintenance cost
FTTO offers the least total cost of ownership
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 59
![Page 60: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/60.jpg)
Availability
When an SFP or fiber uplinkfails only 4 users will beaffected
When an SFP or fiber uplink fails all 24 users will be affected
FTTO offers high availability
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 60
![Page 61: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/61.jpg)
Reliability
FTTO is inherently morereliable because of itsresistance to electromagnetic interference (EMI), radio frequencyinterference (RFI) and crosstalk.
Copper cabling is highlysusceptible to EMI, RFI,crosstalk and return lossfailures.
FTTO is highly reliable, provides error‐free transfer
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 61
![Page 62: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/62.jpg)
Weight and Pulling Tension
• Weighs only 21 kg/km• Max pulling loading 660 N
• Weighs 75 kg/km• Max pulling loading 100 N
Fiber is lighter and stronger
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 62
![Page 63: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/63.jpg)
Cable Testing
Simplified testing, only afew parameters to betested :attenuation, polarity ,length and OTDR trace,On a much less numberof links 75% less than copper
Many parameters have tobe tested: length, wire map, return loss, Insertion loss, NEXT, PSELFEXT, delay skew. Even if one of them fails,the link will not work
FTTO is simpler to test and troubleshoot
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 63
![Page 64: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/64.jpg)
Safety
Fiber is dielectric (non‐metallic), so completely safe and presents no spark or fire hazard.
Copper conductselectricity, can causedamages to equipment ifcarries unwantedcurrents.
Fiber provides maximum safety
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 64
![Page 65: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/65.jpg)
Security
Fiber does not radiateany energy, so it isextremely difficult to tapinto it
Copper cable can betapped since it radiatesEMI
FTTO provides maximum security
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 65
![Page 66: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/66.jpg)
Environmental
Due to its size andweight, fiber optic cableuses less than one fifth of jacket material used by copper cables.
Large volume of coppercables used have large amount of jacket and Insulation material, which poses an environmental hazard.
FTTO is environmental friendly
FTTO COPPER
7/27/2017 Microsens‐[email protected]‐2017 66
![Page 67: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/67.jpg)
FTTO is Standard Compliant
• TIA/EIA 568C– Standardised as Fiber‐to‐the‐Enclosure (FTTE) – Centralized cabling – Singlemode cable can now be used in horizontal
• EN 50173– Recognized as collapsed backbone cabling
• ISO 11801– Recognized as FTTD and centralized optical architecture (COA)
7/27/2017 Microsens‐[email protected]‐2017 67
![Page 68: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/68.jpg)
Association for FTTO
• A non-profit organization • Composed of ICT professionals, consultants,
manufacturers, distributors, systems integrators, and users of ICT infrastructure who are actively involved in applications of fiber optic for ICT network infrastructure
• To support the growth and education of FTTO for its use in the industry
• Members are focussed on promoting the adoption of FTTO for modern data network infrastructure in premise applications
• www.ftto.us, www.ftto.me, www.ftto.in7/27/2017 Microsens‐[email protected]‐2017 68
![Page 69: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/69.jpg)
Why FTTO?
• Fiber optic technology is the most future‐proof cabling technology currently available– maximum achievable bandwidth – a range of other obvious advantages.
• Copper cabling is much less future‐proof from a long‐term perspective.
• Copper performance has its physical limitations and is clearly inferior to fiber optic networks.
7/27/2017 Microsens‐[email protected]‐2017 69
![Page 70: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/70.jpg)
Why FTTO?
• FTTO concept offers cost benefits for large projects, such as airports or hospitals
• FTTO can also achieve obvious cost savings for smaller projects
• For some buildings, FTTO may be the only solution
7/27/2017 Microsens‐[email protected]‐2017 70
![Page 71: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/71.jpg)
Installation Options
Floor Tank
Desktop BoxIn Wall
Distribution Rack
Wall Box
Pillar
Cable Trunk
TeLi-Tank
7/27/2017 Microsens‐[email protected]‐2017 71
![Page 72: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/72.jpg)
Installation Accessories
Micro Switch in cable ductwith 45 mm track
Adapter plate + E2 Socketin OBO BETTERMANN GEK BR-Duct
7/27/2017 Microsens‐[email protected]‐2017 72
![Page 73: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/73.jpg)
Installation Accessories
Insert switch
Apply cover frame
7/27/2017 Microsens‐[email protected]‐2017 73
![Page 74: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/74.jpg)
Installation Accessories
Power supply installed with C-rail
Power supply installed with front-locking mounting in duct
7/27/2017 Microsens‐[email protected]‐2017 74
![Page 75: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/75.jpg)
Installation Accessories
Power supply installed in a standard socket
7/27/2017 Microsens‐[email protected]‐2017 75
![Page 76: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/76.jpg)
Installation Accessories
• Floor service box installation
7/27/2017 Microsens‐[email protected]‐2017 76
![Page 77: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/77.jpg)
Installation Accessories
• Floor service box installation
7/27/2017 Microsens‐[email protected]‐2017 77
![Page 78: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/78.jpg)
Installation Accessories
• Switch with cover installed in an hollow wall socket
7/27/2017 Microsens‐[email protected]‐2017 78
![Page 79: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/79.jpg)
References
Dubai International Airport, UAEConcourse A
Dubai International Airport, UAEConcourse D
AIRPORTS
7/27/2017 Microsens‐[email protected]‐2017 79
![Page 80: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/80.jpg)
References
UNIVERSITIES
Munich University, Germany
College de l'oise, France
7/27/2017 Microsens‐[email protected]‐2017 80
![Page 81: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/81.jpg)
References
HOSPITALS
Det Nye Universitetshospital, Denmark
Cannes Hospital, France
7/27/2017 Microsens‐[email protected]‐2017 81
![Page 84: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/84.jpg)
Hardware Platform
•Hardware PlatformLatest Ethernet switch technology
Energy Efficient Ethernet (energy savings for copper ports) QoS – 4 Hardware Queues pro Port 256 VLANs
Power‐over‐Ethernet Plus (802.3at) on all copper ports (max. 30W per end device)Memory card for firmware and configuration (optional)Solid, shielded metal housing, clear structure of ports and displaysMounting in standard 45mm double frameHorizontal and vertical versions for cable ducts, columns and sub‐floor boxes
7/27/2017 Microsens‐[email protected]‐2017 84
![Page 85: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/85.jpg)
Switch Features
Uplink PortSFP/ Fixed/RJ-45 (PD)
Power54VDC/230VAC
Expansion PortTerminal
Local PortsEnergy Efficient EthernetPoE+ (max. 30 W)
Reset ButtonReset/Factory Defaut
Labelling FieldIntegrated
6GENERATION
LED DisplaySwitch/Port/PoE Status
7/27/2017 Microsens‐[email protected]‐2017 85
![Page 86: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/86.jpg)
Switch Features(Contd.)
Downlink PortsEnergy Efficient EthernetPoE+ (max. 30 W)
Memory CardConfiguration Storage(optional with G6+)Chamfer EdgeSimplified Installation
6GENERATION
7/27/2017 Microsens‐[email protected]‐2017 86
![Page 87: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/87.jpg)
Versions
Horizontal Mounting(Reference)- Cable ducts- Floor-boxes
Vertical Mounting- Cable ducts- Columns- Floor-boxes
7/27/2017 Microsens‐[email protected]‐2017 87
![Page 89: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/89.jpg)
Quality of Service
Port
Queue 3 - highest
Sch
edul
er
Cla
ssifi
er
Port
Strict
Weighted
Queue 0 - lowest
4 Priority levels4 queues per port
2 WeightingsStrict = Higher priority firstWeighted = queues weighted 8:4:2:1
Prioritization
7/27/2017 Microsens‐[email protected]‐2017 89
![Page 90: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/90.jpg)
Quality of Service
Port 2:Normal datalow priority
Port based prioritizationLayer 1: Hardware
7/27/2017 Microsens‐[email protected]‐2017 90
![Page 91: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/91.jpg)
Quality of Service
VoIP applicationhigh priority
Data applicationlow priority
Layer 2: IEEE 802.1p/Q (VLAN Tag)
Layer 3: DiffServ Codepoint (IP Header)
Protocol based prioritization
7/27/2017 Microsens‐[email protected]‐2017 91
![Page 97: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/97.jpg)
Enterprise Networks
PC
PC
MicroSwitch
VoIPphone
VoIPphone
VLAN Filtering (IEEE 802.1p/Q)
7/27/2017 Microsens‐[email protected]‐2017 97
![Page 98: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/98.jpg)
Enterprise Networks
VLAN ModesAccessOutgoing frames are sent untagged. Incoming frames receive the port’s default VLAN ID (PVID). This port mode is normally used for connecting end devices.
HybridOutgoing frames are sent tagged, except the frames of the default VLAN port. Incoming frames from the default port VLAN are expected to be untagged, frames from other VLANs are always expected to be tagged. This mode is normally used to connect a VoIP phone and a PC to share one port. In this setup the phone communicates tagged and the PC untagged.
TrunkOutgoing frames are always sent tagged. Incoming frames are expected to be received tagged. Incoming frames without a VLAN tag are processed using the port’s default VLAN ID (PVID). This mode is normally used as an inter-switch connection.
7/27/2017 Microsens‐[email protected]‐2017 98
![Page 99: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/99.jpg)
Enterprise NetworksPort VLANs
Egress packetsVLAN Tag is removed
Insert/removal of port VLAN ID/priorityProcessing of tagged/untagged packets (hybrid ports)
Ingress packets without tagPort VLAN tag is inserted
Ingress packets with tagVLAN tag remains unchanged
Trunk portVLAN tag remains unchanged
7/27/2017 Microsens‐[email protected]‐2017 99
![Page 100: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/100.jpg)
Smart Lighting/Office
![Page 101: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/101.jpg)
Smart Lighting/Office
Smart LightingSmart Lighting Smart OfficeSmart Office
• Light • GUI• Light switch
• Light • GUI• Light switch
• Public address• Intercom• Window blinds• Heating control• Wall thermostat• Air conditioning
• Public address• Intercom• Window blinds• Heating control• Wall thermostat• Air conditioning
7/27/2017 101
![Page 102: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/102.jpg)
Smart Sensor
Presence Intensity Temperature
7/27/2017 102
![Page 103: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/103.jpg)
Smart Lighting Controller
1 Controller for each light
• Powered via PoE+ • Input RJ‐45 (Ethernet)• Sensor input RJ‐45
• Output to light Phoenix contacts on the device back side
• Power output approx. 25 W
7/27/2017 103
![Page 104: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/104.jpg)
Micro Access Point
Extension Modulefor the Micro Switch G6
3 functions in one device:
• WLAN Access Point (802.11b/g/n)• Smart I/O (2x In Optokop./2x Out 230 VAC)• Wireless Gateway (868 MHz)
• Own Firmware based on OpenWRT (Linux)• Integrated FHEM Server as EQ3 Gateway• PoE power supply via Micro Switch• Configuration via Micro Switch firmware
7/27/2017 104
![Page 105: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/105.jpg)
LED Lights
Requirements for LED lights:
‐ max. 54 V DC‐ Power consumption approx. 30 W
7/27/2017 105
![Page 106: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/106.jpg)
Construction
7/27/2017 106
![Page 107: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/107.jpg)
Construction
7/27/2017 107
![Page 108: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/108.jpg)
Construction
DCAC
PE L N
NC+ +- -
Power Supp ly240 W
7/27/2017 108
![Page 109: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/109.jpg)
Construction
DCAC
PE L N
NC+ +- -
Power Supp ly240 W
7/27/2017 109
![Page 110: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/110.jpg)
Construction
DCAC
PE L N
NC+ +- -
Pow er Supp ly240 W
7/27/2017 110
![Page 111: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/111.jpg)
Construction
DCAC
PE L N
NC+ +- -
Pow er Supp ly240 W
7/27/2017 111
![Page 112: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/112.jpg)
Construction
DCAC
PE L N
NC+ +- -
Pow er Supp ly240 W
7/27/2017 112
![Page 113: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/113.jpg)
System Overview
7/27/2017 113
![Page 114: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/114.jpg)
Smart Office Showroom
LED ceiling panel
LED Downlight
Air conditioning
Roller Shutter
Micro SwitchMicro Access Point
VoIP Telefon
Smart Lighting Sensor
Smart Audio System
7/27/2017 114
![Page 115: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/115.jpg)
Smart Lighting Director – Decentral Control from the switch
LED ceiling panel
Smart Lighting Sensor
Smart Office Director App
7/27/2017 115
![Page 116: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/116.jpg)
Benefits Smart Lighting
• Open, decentral and IP based system• Roll‐Out office after office• Integration into a virtual central control system• Individual control by user• Apps on the Smart Director• High security with SNMP v3, etc. (compared to e.g. KNX)
• Simple planning• Reduced fire load in the building• Due to less cable more space in cable ducts• Reduced installation costs (quicker and less qualified persons)
• Energy savings up to 80%• Monitoring of the real power consumption at each controller• Extreme reduction of maintenance cycles by use of LEDs > 50000 h• Possibility for premaintenance• Detection of faulty lights from central management
7/27/2017 116
![Page 117: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/117.jpg)
Central Management Software
NetworkManagement Platform
7/27/2017 Microsens‐[email protected]‐2017 117
![Page 118: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/118.jpg)
Software Overview
Network Management Platform
FTTO IndustrialEthernet
AccessMetro
Strategic Product Groups
7/27/2017 Microsens‐[email protected]‐2017 118
![Page 119: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/119.jpg)
NMP Server
General facts• Based on Java language• Available for Windows and Linux• 32 and 64 Bit versions available• Three different versions available
• nmp standard• nmp professional• nmp server
• License key required• Unlimited number of devices
7/27/2017 Microsens‐[email protected]‐2017 119
![Page 120: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/120.jpg)
Overview of Licensing Models1 Redundant Server per LicenseUnlimited Number of User-Stations per SW-License and Enterprise
•NMP Standard
• Common Feature Set (Standard, Professional, Server)
Auto Discovery, Element Manager, Flexible Device Tree, Backup/Restore of Switch Configuration
NMP Server
• Multi User, Shared Database
• Server Redundancy• Northbound Interface for Data
Retrieval
• Single User/Single Station,Non‐Shared Database
NMP Professional
• Single User/Single Station, Non‐Shared Database
Common Feature Set (Professional, Server)• Topology Manager• Inventory List Generator • Device Search Tool• VLAN Change Tool• Link monitoring
• Task Scheduler • E‐Mail notifications • Automatic alarm list generation • Switch Password Changer • RMA Tool
7/27/2017 Microsens‐[email protected]‐2017 120
![Page 121: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/121.jpg)
Element Manager
Device List Tree
Device/Group/ChannelDetailed View
Device Graphical View
7/27/2017 Microsens‐[email protected]‐2017 121
![Page 123: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/123.jpg)
Feature Update
NetworkManagement Platform
Server 2010
7/27/2017 Microsens‐[email protected]‐2017 123
![Page 125: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/125.jpg)
NMP Standard
• Multi User, but• Decentralized• All data local
• Inconsistency in• Data storage• Data backup• User Management• Access Control
7/27/2017 Microsens‐[email protected]‐2017 125
![Page 126: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/126.jpg)
NMP Server
• Central Server• Data consistence• SQL Database• Central backup
• User Management• Access control
• Client Options• Web browser
– OS independent– No local application
• NMP Client
– Full functionality– Syncronisation to server
7/27/2017 Microsens‐[email protected]‐2017 126
![Page 127: Fundamentals of Fiber To The Office (FTTO) - BICSI of Fiber To The Office (FTTO) P.R.Rajendranath, RCDD, OSP, CT, DCE Topnet Distribution, Dubai Dirk Herppich, Dipl.‐Ing](https://reader031.vdocuments.us/reader031/viewer/2022021506/5b03b2e87f8b9aba168c3e1c/html5/thumbnails/127.jpg)
NMP ServerMotivation/BenefitsCentralized management platform
+ Single point of administration
• Dedicated user/access management+ Full control over network access+ Extended logging functionality
• Central database+ Simplified data protection/backup
• Access with Client or Browser+ NMP Client with full function set+ Web client requires only local browser7/27/2017 Microsens‐[email protected]‐2017 127