SEPTEMBER 2019 AN ISO 9001 : 2015 COMPANY Training Calendar Piyush Patel (M.D.) Techno-Talk Motor Control AN ISO 9001 : 2015 COMPANY Amtech Power Official News Letter of Amtech Electronics (India) Ltd., Gandhinagar, Gujarat (India) OT-iB Series OT-iB Series Customer’s Voice Energy saving in cooler fan From the Desk of Managing Director Customer’s Voice -AMTECH FAMILY Islamic New Year Happy Muharram -AMTECH FAMILY Once a King organized a competition of drawing- artists. The competitors were to bring a picture of the king. King personally was to give judgment about which picture is the best. First competitor showed the f rame holding the picture of the king. "Well, it is a good picture, but my eyes look better than those appearing in the picture", the king turned to next competitor. "This picture is excellent, but my nose is more beautiful than what it looks like in this picture". Like this the king went on rejecting the artists, nobody seemed to be worth for selection as a winner. Finally one artist came forward. The king looked at the picture. "Very good", the king remarked, "but my face is more handsome than this". "It can't be, Your Excellency", replied the artist, "It is not a picture, you are holding the mirror, My Lord, in your hands". The king, appeared embarrassed a bit, but then was very happy to know the wisdom of the artist and felicitated him as a winner! Moral of the story: You cannot be better than what you are, unless you really improve. A painting is made up of many different colors, each one important and necessary Redundant VFD Solution Mahakoshal Refractories Pvt. Ltd Benefits of Power Factor Correction

Upload: others

Post on 24-Aug-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

SEPTEMBER 2019

AN ISO 9001 : 2015 COMPANY

Training Calendar

Piyush Patel (M.D.)

Techno-Talk

Motor Control

AN ISO 9001 : 2015 COMPANY

Amtech Power

Official News Letter of Amtech Electronics (India) Ltd., Gandhinagar, Gujarat (India)

OT-iB Series

OT-iB Series

Electronics Soft-Starter

MODENORM

ESC UP

DOWN ENTER

GROUP

STOPRESET

FAULT

RUN

Electronics Soft-Starter

MODENORM

ESC UP

DOWN ENTER

GROUP

STOPRESET

FAULT

RUN

Customer’s Voice

Energy saving in cooler fan

From the Desk of Managing Director

Customer’s Voice

-AMTECH FAMILY

Islamic New Year

HappyMuharram

-AMTECH FAMILY

Once a King organized a competition of drawing- artists. The competitors were to bring a picture of the king. King personally was to give judgment about which picture is the best. First competitor showed the f rame holding the picture of the king. "Well, it is a good picture, but my eyes look better than those appearing in the picture", the king turned to next competitor. "This picture is excellent, but my nose is more beautiful than what it looks like in this picture". Like this the king went on rejecting the artists, nobody seemed to be worth for selection as a winner. Finally one artist came forward. The king looked at the picture. "Very good", the king remarked, "but my face is more handsome than this". "It can't be, Your Excellency", replied the artist, "It is not a picture, you are holding the mirror, My Lord, in your hands". The king, appeared embarrassed a bit, but then was very happy to know the wisdom of the artist and felicitated him as a winner!Moral of the story: You cannot be better than what you are, unless you really improve.

A painting is made up of many different colors,

each one important and

necessary

Redundant VFD Solution

Mahakoshal Refractories Pvt. Ltd

Benefits of Power Factor Correction

Page 2: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

TRAINING CALENDAR

201920192019201920192019201920192019202020202020

25-2623-2420-2125-2622-2319-2017-1821-2219-2023-2424-2519-20

+AXPERT-EAZYSERIES VFD

Active Static VAR Compensator

Active Front-end Converter

Active Harmonic Filter

Electronics Soft-Starter

MODENORM

ESC UP

DOWN ENTER

GROUP

STOPRESET

FAULT

RUN

OT-iB Series

Electronics Soft-Starter

MODENORM

ESC UP

DOWN ENTER

GROUP

STOPRESET

FAULT

RUN

OT-iB Series

Active Static VAR Compensator

AXPERT- Series ENGINEERED SYSTEMS

Active Harmonic FilterActive Front-end Converter

Product training module: About Amtech VFD and AC Motor fundamentals Physical familiarity of VFD and Soft Starter Understanding the specifications, different models, selecting the proper rating and options provided for VFD and Soft Starter Installation and Commissioning of VFD and Soft Starter Understanding of different applications of VFD and Soft Starter Trouble shooting of VFD and Soft Starter

TM Drive support software Axpert - Communicator for PC

Product Portfolio:

Page 3: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

3

CUSTOMER’S VOICE

Page 4: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

DOC. NO. CS-281TITLE: ENERGY SAVING IN COOLER FAN

Payback Period Approximately 4-5 Months

Industry : CementApplication : Cooler FanMotor rating : AC Induction Motor, 3-Phase 110 kW : 415 Volt : 2980 RPM : 50Hz : 178Amp :Previous system : Motor was running on Star Delta Starter.Problem observed : 1) High maintenance cost. 2) Energy losses due to flow control by damper.Present system : + AXPERT-EAZY 110 kW Variable Frequency Drive used. kW (Consumption) Damper PositionPrevious system (Without drive) : 106 kW 93 % OpenPresent system (With drive) : 89 kW 100 % OpenSystem block diagram :

Merits of new system : 1. Easy & smooth operation. 2. Energy saving due to flow control by VFD.Economical analysis :

Energy consumption without VFD - P1 = 106 kWEnergy consumption with VFD - P2 = 89 kWEnergy saving per day ((P1 - P2) x 24) = 408 UnitsSaving per day @ Rs. 5/- Unit = Rs. 2,040/-Saving per year (Approx. 320 Days) = Rs. 6,52,800/-

110 kW,178 A, 3-PHASE INDUCTION MOTOR+AXPERT-EAZY

3-PHASE, 415 V,AC SUPPLY

Model: AMT-0260A-4COOLER FAN

Page 5: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

AMTECH POWER CUSTOMER’S VOICE

Page 6: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

6

PRODUCT OVERVIEW

The new generation of control system, developed by Amtech Electronics (India) Ltd, integrates the operation of Redundant VFD for critical applications.This solution is used for critical applications where a single stoppage of VFD is not allowed as it results in huge loss of production and/or stoppage like in Power plant, Boiler, Spinning pump etc. Amtech has designed and successfully installed Redundant VFD solution in many critical applications with complete engineered system. Solution takes only motor connection and speed reference from the field and rest all are factory programmed. This gives plug and play installation.

At times, your process needs bump-less transfer in no time without any major change in speed. Our system solutions equipped with state-of-the-art technology monitors the health of the VFD all the time and in an abnormal situation, transfers the control to the hot standby VFD in no time. The transfer will be so smooth at times, that even your control room will not be able to diagnose the transfer.

FeaturesRedundant operation of VFDCold and Hot standby operationEqual speed referenceBump-less transfer with speed trackingFailsafe and reliable transfer operationSpeed reference loss detectionIntelligent monitoring and controlling of all operation

and interlocksOptional functionality for DOL running in case of both

VFD failuresMaintenance functionality by manually bump-less

transfer to take one VFD in maintenanceFactory tested solutionUser friendly system

BenefitsEliminates breakdown due to failure of one VFDBump-less transfer gives jerk free operation during transferEliminates breakdown due to speed reference lossReliable transfer with interlocksContinues energy saving, without any interruptionBetter reliability, almost 100% uptimeImproved process flow and excellent value for moneyLow operating costs & minimized maintenance costsQuick and safe commissioningQualified after-sales service by Amtech assistance

Major ApplicationBoiler Fans like PA Fan / ID Fan / FD FanProcess Pumps – Viscose / Oil PumpMining Application – Conveyor / CrusherExtruder Application – Aluminum / Plastic / POYPharmaceutical / Drug manufacturing equipment

REDUNDANT VFD SOLUTION

Page 7: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

TECHNO-TALKReduced Utility Bills:Power factor correction removes power factor penalties on your electricity bill.Electricity tariffs for industrial and commercial customers have energy and demand rates. Some of these tariffs are structured to increase the cost of electricity if your power factor does not meet a minimum threshold (often 90%). Regardless of how your utility bills you for power, power factor correction can save you money.Increased System Capacity:Power factor correction frees up capacity on your supply transformer. Improvement in Power Factor allows you to add additional load to your system without altering the kVA.Improved Voltage Conditions:Low voltage, resulting from excessive draw, causes motors to be sluggish and overheated. As power factor decreases, total line current increases, causing further voltage drop.By adding capacitors to your system and improving power factor, you will improve voltage and therefore get more efficient motor performance and longer motor life.Reduced Transmission Losses:Losses caused by poor power factor are due to reactive current flowing in the system. These are watt-related charges that can be eliminated through power factor correction.Reduced Carbon Footprint:Power factor correction reduces the total current drawn from an electrical distribution network (which affects systems such as the power stations, distribution grid, and supply transformers). In so doing, the heat or transmission losses incurred on these systems are reduced, which reduces your carbon footprint.What Is Power Factor and Power Factor Correction?Power factor is a measurement of how effectively your electrical system converts electric current (supplied by your power utility) into useful power output.You may be able to find your current power factor indicated on your electricity bill. A low power factor means you’re not fully using the electrical power you’re paying for, creating significant penalties on your electricity bill, overloading your electrical distribution system, and increasing your carbon footprint.Power factor can be improved. A high power factor of 90% or more will result in more efficient electrical consumption and a lower utility bill.Power Factor Formula:Power Factor (%) = Real Power (kW) OR kW Demand Apparent Power (kVA) (kVA) kVA Demand

Benefits of Power Factor Correction

Page 8: From the Desk of Managing Director - Amtech Electronics · eliminated through power factor correction. Reduced Carbon Footprint: Power factor correction reduces the total current

Gandhinagar

Atlanta

GandhinagarAhmedabad

Mumbai

Surat

MuzaffarnagarDelhi(Gurgaon)

VadodaraIndore

Jamnagar

Udaipur

Kolkata

Nagpur

Pune

Hyderabad

Vapi Raipur

Bhopal

Jamshedpur

JaipurLucknow

Vizag

Bangalore

Chennai

Belgaum

PondicherryTrichy

AurangabadNasik

Chandigarh

Veraval

M. D. Kamath

Paresh Patel

Regional OfficesContact Person Phone No. (O) Mobile No. E-mail

022-28846083Vrajesh Yadav 0981990050109108051977

09825042458

[email protected]@amtechelectronics.com

[email protected]

MumbaiBangaloreChennaiDelhi

T. S. Sridhar 09840618533 09940229955.

[email protected]

Umesh Bhatia 09589344318Indore / Raipur [email protected]

H.O. and Service CenterContact Person Phone No. (O) Mobile No. E-mailBhavana Thakkar 09909975944H.O. Gandhinagar [email protected] Moradiya 09909973780Amtech Service Center

[email protected]

G. Sateesh Kumar 09573900222Hyderabad [email protected] C. 09932820680Kolkata [email protected]

09825042458095893443180957390022209932820680

09108051977

Pankaj Gulati 09888748620Chandigarh [email protected]