from: cc - portal.cwingate.com · rfi transmittal date sent 7/19/2017 job # 2016940 project name...

4
RFI TRANSMITTAL Date Sent 7/19/2017 Job # 2016940 Project Name 787 11th Avenue Georgetown Core & ... Transmittal # LOT-2016940-R995 From: Michael Linde Cauldwell Wingate Company 380 Lexington Avenue, New York, NY 10168 Phone: 212-983-7150 Fax: 212-983-7275 Spec Section Scope Impact Ref. Drawings To: Rafael Vinoly Architects PC attn. Jim Herr- Project Director, Kevin Johns, Thomas ... 50 Vandam St., New York, NY 10013 Cc: ICOR Consulting Engineers(MEP) Response Requested By: 7/29/2017 RFI #: 247.1 SUBJECT: Support for 750 kW Generator INFORMATION REQUESTED: Please advise how water will drain from within the curb box-out should it collect under the generator. Refer to attached RFI #247.0 for generator curb layout. RESPONSE: RESPONSE DATE: FILE ATTACHMENTS: File Description of Contents LOT-2016940-R491- 247.0_SILMAN_RVA_2017_032 3 (2).pdf PDF File 3.94 MB

Upload: vanxuyen

Post on 25-Feb-2019

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: From: Cc - portal.cwingate.com · RFI TRANSMITTAL Date Sent 7/19/2017 Job # 2016940 Project Name 787 11th Avenue Georgetown Core & ... Transmittal # LOT -2016940 -R995 From:

 

RFI TRANSMITTAL

Date Sent 7/19/2017 Job # 2016940

Project Name 787 11th Avenue Georgetown Core & ...

Transmittal # LOT-2016940-R995

 

From:

Michael Linde

Cauldwell Wingate Company

380 Lexington Avenue, New York, NY 10168

Phone: 212-983-7150 Fax: 212-983-7275

Spec Section

Scope Impact

Ref. Drawings

To: 

Rafael Vinoly Architects PC

attn. Jim Herr- Project Director, Kevin Johns, Thomas ...

50 Vandam St., New York, NY 10013

  Cc:

ICOR Consulting Engineers(MEP)

Response Requested By: 7/29/2017

RFI #:   247.1

 

SUBJECT:

Support for 750 kW Generator

 

INFORMATION REQUESTED:

Please advise how water will drain from within the curb box-out should it collect under the generator. Refer to attached RFI #247.0 for generator curb layout.

RESPONSE: RESPONSE DATE:

 

 

 

 

 

 

 

 

 

FILE ATTACHMENTS:

File Description of Contents

LOT-2016940-R491-247.0_SILMAN_RVA_2017_0323 (2).pdf PDF File 3.94 MB

Page 2: From: Cc - portal.cwingate.com · RFI TRANSMITTAL Date Sent 7/19/2017 Job # 2016940 Project Name 787 11th Avenue Georgetown Core & ... Transmittal # LOT -2016940 -R995 From:

RFI TRANSMITTAL

Date Sent 12/22/2016 Job # 2016940

Project Name 787 11th Avenue Georgetown Core & ...

Transmittal # LOT-2016940-R491

 

From:

William J. Maher

Cauldwell Wingate Company

380 Lexington Avenue, New York, NY 10168

Phone: 212-983-7150 Fax: 212-983-7275

Spec Section

Scope Impact

Ref. Drawings

To: 

Silman-STRUCTURAL

attn. Jason Tipold, Russell Feathers, Paul Evans

32 Old Slip, 10th Floor, NY, NY 10005

  Cc:

ICOR Consulting Engineers(MEP)

Rafael Vinoly Architects PC

Response Requested By: 1/1/2017

RFI #:   247.0

 

SUBJECT:

Support for 750 kW Generator

 

INFORMATION REQUESTED:

It is unclear how the new 750 kW generator is attached to the building structure. We do not see any details for concrete pad nor steel dunnage to support the generator. Shall the generator be bolted directly to the new 12th floor level concrete slab on metal deck? Please advise.

RESPONSE: RESPONSE DATE:

 

 

 

 

 

 

 

 

 

FILE ATTACHMENTS:

File Description of Contents

16715 2016-07-17 BULLETIN #4.pdf PDF File 695 KB

SILMAN: Ownership has agreed to place this unit on cast in place concrete curbs, as recommended by ICOR. Seeattached.

JRT 2/27/17 UPDATED

ttumelty
Text Box
RVA response: We defer to SILMAN's professional judgment and see no negative impacts architecturally from the implementation of the solution proposed. Coordinate with all trades and coordinate curb layout based on unit specifications. 2017_0323_TT⤯䍲敡瑩潮䑡瑥⡄㨲〱㜰㌲㌰ㄵ㘱ㄭ〴✰〧⤯䑁⠰‰‱朠⽈敬瘠⁔�
Page 3: From: Cc - portal.cwingate.com · RFI TRANSMITTAL Date Sent 7/19/2017 Job # 2016940 Project Name 787 11th Avenue Georgetown Core & ... Transmittal # LOT -2016940 -R995 From:

750 kW Generator

Page 4: From: Cc - portal.cwingate.com · RFI TRANSMITTAL Date Sent 7/19/2017 Job # 2016940 Project Name 787 11th Avenue Georgetown Core & ... Transmittal # LOT -2016940 -R995 From:

4

6

7

1

L KJ H DEG

3

FF.1

5.2

2

J.2 J.1

4.2

5

MECH. PENTHOUSE

M04

UP

DN

UP

SE-1 EMR

M02

STAIR B

M03STAIR C

M01

CONTROLLER

TRANSFORMER

Governor

3

34

10

1

4

4"

GAL

DPL-R-GEN

4" 4" 4" 4"

DPL-R-GEN DPL-R-GEN DPL-R-GEN DPL-R-GEN

GAL GAL GAL GAL

3"

GAL

LOAD BANK

3.5"

GAL

DPL-R-EM

3.5"

GAL

3"

GAL

3"

GAL

3"

GAL

FIRE PUMP

3"

GAL

DPL-R-EM

41

10

1

4

11'-4"

10'-9"

6'-0

"

11'-8

"

H

20'-11"

6'-0

"4'-3

"

4'-10"CONCRETE PAD68"L x 62"W x 6"H

CONDUIT STUB UP AREA

3"

GAL

LOAD BANK

3"

GAL

3"

GAL

LOAD BANK LOAD BANK

22'-9"

9'-1

1"

H

LOAD BANK LOAD BANK FIRE PUMP

34

10

1

4

4"

GAL

DPL-R-GEN

4" 4" 4" 4"

DPL-R-GEN DPL-R-GEN DPL-R-GEN DPL-R-GEN

GAL GAL GAL GAL

3"

GAL

LOAD BANK

3.5"

GAL

DPL-R-EM

3.5"

GAL

3"

GAL

3"

GAL

3"

GAL

FIRE PUMP

3"

GAL

DPL-R-EM

41

10

1

4

11'-4"

10'-9"

6'-0

"

11

'-8"

H

LOAD BANK LOAD BANK FIRE PUMP

MECH. PENTHOUSE

3

6'-0

"

20'-11"

6'-0

"4'-3

"

4'-10"

CONDUIT STUB UP AREA

3"

GAL

LOAD BANK

3"

GAL

3"

GAL

LOAD BANK LOAD BANK

22'-9"

9'-1

1"

H

DOOLEY ELECTRIC

NI

O

TCAF

SITA

SLAC

ELECTR I

L

ZE

SO

BMYS

TAH

ES

EH T

TL

A

R

I

Q U A L I F I E DE L E C T R I C A L C O N T R A C T O R S

EL E

CTR I C

A LC O N TR A CTORS

AS

SO

CIATIONNATIONA

L

1/8"1/2"

1/4"

01"

2"

3"

LA NOITANRETNI

BROTHER

HOOD FO ELECTRICALWORKERS

FFO

TA

.

.P.S.U.GER

NACI RE MA

OFEDERATI

NFO L A BOR

&

CONGRESS FO NI DUSTRIAL ORGANIZATIO

NS&

NAIDANACRUOBAL

CONG

RESSHTIWDETAILIFFA

1981

,82.VONDEZINAGRO

55T

H S

TR

EE

T

54T

H S

TR

EE

T

11TH AVENUE

N

ELEVENTH AVE

787

NEW YORK, NY

787

1/4" = 1'-0"

GENERATOR LAYOUT- BULKHEAD LEVEL

1

3/8" = 1'-0"

GENERATOR STUB UP DETAIL - BULKHEAD LEVEL

2

P

R

E

L

I

M

I

N

A

R

Y

L

A

Y

O

U

T

N

O

T

F

O

R

C

O

N

S

T

R

U

C

T

I

O

N

3/8" = 1'-0"

LOAD BANK STUB UP DETAIL - BULKHEAD LEVEL

3

35,000 LBGENERATOR- SEE MEPDWGS

COORDINATE FINALCURB LOCATIONSWITH MECHANICALCONTRACTOR

GENERATOR CURB PART FRAMINGPLAN

NEW 6" TALL x 12" WIDE NWCONCRETE CURB UNDER UNITPERIMETER WITH 1-#4 CONT.AND #3 DOWELS INTO THE SLABBELOW @24" O/C WITH HILTIHY-200, 3" EMBED

C6x8.2

C6x

8.2

C6x8.2

C6x8.2

C6x

8.2

C6x8.2

SSK-29A - UPDATED RFI247 Response for GeneratorCurb and Penetrations2017-02-24JRT/RF

32 Old Slip, 10th Floor, New York, NY 10005 212 620 7970