foundation presentation .pptx

25
Simple Cycle Energy Center Core Engineering Consultant Arlington, Tx Dec 12, 2015 Team of Engineers Ali Shafikhani Haroon Rasheed Mohammed Muqtadar Chhokila Lama Sandeep Shah Tenzing Lama 1

Upload: haroon-rasheed-ahmed

Post on 22-Jan-2018

93 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Foundation Presentation .pptx

Simple Cycle Energy CenterCore Engineering Consultant

Arlington, Tx

Dec 12, 2015

Team of Engineers Ali Shafikhani

Haroon Rasheed

Mohammed Muqtadar

Chhokila Lama

Sandeep Shah

Tenzing Lama

1

Page 2: Foundation Presentation .pptx

Project Outline ● Project Introduction

● Scope: Foundation Design

● Conclusion and Recommendations

● References

➢Turbine

➢GSU Transformers and

Breakers

➢ Four Water Tank

2Speaker: Ali Shafikhani

Page 3: Foundation Presentation .pptx

IntroductionPlant Layout

3Speaker: Ali Shafikhani

543 megawatt simple cycle gas fired electric generating facility in

Maverick County, Texas

Water

Tanks

GSU Transformers &

Breakers

Turbines

Page 4: Foundation Presentation .pptx

Foundation Design

A TM2500 Gas Turbine

GSU Transformers and BreakersA Water Storage Tank 4

Speaker: Ali Shafikhani

Page 5: Foundation Presentation .pptx

Turbine Options

Speaker: Ali Shafikhani5

Page 6: Foundation Presentation .pptx

Mat Foundation Design(for 90% of loads)

● Strong sand layer over weak clay layerEliminating the top clay layer.

Speaker: Ali Shafikhani

Foundation dimension: 23*64 (ft) with huge safety factor

6

Page 7: Foundation Presentation .pptx

Mitigation of Turbine Vibration

loading EffectApplication of light weight high compressive strength geofoam blocks as structural

void fill material (Ɣ=0.7-2.85 pcf).

- To mitigate destructive vibration loading effect.

- In order to design a lightweight mat foundation to prevent subsequent

settlement.

- To make a cost effective design.

- To decrease construction time period.

Speaker: Ali Shafikhani

Resource:

(https://hayfieldhouse.wordpress.com/category/foundation/)Resource: (http://cenews.com/article/9649/geofoam-a-lightweight-fill-

alternative)

7

Page 8: Foundation Presentation .pptx

Lightweight foundation on expansive soil

8

Expansive soils:

- High settlement and swelling potential during seasonal rainfall.

- Load concentration motivates this settlement and swelling effect.

- differential settlement will occur.

Page 9: Foundation Presentation .pptx

Mitigation of Swelling effect of top

Clay layer

Speaker: Ali Shafikhani

Deep foundation dimension: 16*3*5 (ft)(Resource: Chen (1988), O’Nill (1988))

9

Page 10: Foundation Presentation .pptx

Combined Footing● Strong clay layer over weaker sand layer

Speaker: Ali Shafikhani

Foundation dimension: 4.5*10 (ft). F.S>4

10

Page 11: Foundation Presentation .pptx

Elastic Settlement Mat Foundation and Combined Footing:

● Sand layers:

● Clay layers:

● Mat Foundation: Se= 0.68 (in)● Combined Footing: Se= 0.36 (in)

Speaker: Ali Shafikhani

11

Page 12: Foundation Presentation .pptx

Elastic Settlement Drilled shaft:

● This case: Se= 0.48 inch

Speaker: Ali Shafikhani12

Page 13: Foundation Presentation .pptx

Storage TankWater 50,000 gal

Height of Steel Tank = 50 ft

Tank Thickness = 1.5 in

Structural load = Tank + Water

=

418 kips

Bore log 2

Speaker: Sandeep Shah 13

Page 14: Foundation Presentation .pptx

●2 X 2 Group Pile●Length of Piles= 20 ft ●Circular Concrete Pile●Diameter = 1.5 ft●Spacing (S) = 2.5 D

Dimensions

Speaker: Sandeep Shah14

Page 15: Foundation Presentation .pptx

Pile Capacity●Tip Resistance (Sand layer) Qp = 319 kips

(Meyerhof’s Method)●Skin Resistance (Clay+Sand) Qs = 74 kips

(Alpha & Meyerhof)●Ultimate bearing Capacity of 4 piles without the

group effect Qu = 1572 kips●Group efficiency = 1.11 (Piles behave individually)●Ultimate load bearing capacity of the group pile

Qg(u) = 1572 kips●F.S. = 3, Qall = 524 kips > 418 kips

Speaker: Sandeep Shah15

Page 16: Foundation Presentation .pptx

Settlements●Elastic Settlement

➢ Individual= 0.180 in

➢Group piles = 0.33 in

● Consolidation Settlement

➢ Group = 1.15 in

Total Settlement = 1.48in <1.5 in

● Pile Cap

➢ Dimension=6ft X 6ft

➢Thickness=3.3 ft.

➢Weight= 17.8kips

Group Pile Weight of 4 piles = 21.2 kips

Speaker: Sandeep Shah 16

Page 17: Foundation Presentation .pptx

GSU TRANSFORMERProperties of Transformer

Dimensions

Width : 65” = 5.41’

Length : 84” = 7’

Height : 96.625” = 8.05’

Weight

APPROX. WEIGHT:

CORE & COIL - 3832 lbs.

CASE - 3011 lbs.

LIQUID (343 gal.) -2744 lbs.

TOTAL - 9587 lbs.

17Speaker: Haroon Rasheed

Page 18: Foundation Presentation .pptx

GSU TRANSFORMERASSUMPTIONS:

● Pressure bulb reaches a depth of 2B (12’)

● The three layers from the depth of 4’ to 16’ are considered to be one sandy layer with a ᶲavg of 34⁰ and ϒavg of 115 psf

18

Speaker: Haroon Rasheed

Page 19: Foundation Presentation .pptx

FORMULAS

19Speaker: Haroon Rasheed

Page 20: Foundation Presentation .pptx

RESULTS● Qb = 13123.8 lbs● Qt = 22800 lbs● Qu = 21602.45 lbs● Qu < Qt Hence O.K.● Qall = 345639 lbs● Elastic Settlement = 0.6”● Elastic settlement is less than 1.5”

20

Speaker: Haroon Rasheed

Page 21: Foundation Presentation .pptx

GSU BREAKERProperties of GSU Breaker

Dimensions

•Length : 92” = 7.6’

•Width : 78” = 6.5’

Weight

•Weight with gas - 11180 lbs.

•Weight less gas - 10910 lbs.

21Speaker: Haroon Rasheed

Page 22: Foundation Presentation .pptx

GSU BREAKERASSUMPTIONS:

● Pressure bulb reaches a depth of 2B (12’)

● The three layers from the depth of 4’ to 16’ are considered to be one sandy layer with a ᶲavg of 34⁰ and ϒavg of 115 psf

22Speaker: Haroon Rasheed

Page 23: Foundation Presentation .pptx

RESULTS● Qb = 15311 lbs● Qt = 22800 lbs● Qu = 21289 lbs● Qu< Qt Hence O.K.● Qall = 745115 lbs● Elastic Settlement = 0.56”● Elastic settlement is less than 1.5”

23Speaker: Haroon Rasheed

Page 24: Foundation Presentation .pptx

Conclusion & Recommendation● Shallow Foundation is the best type of foundation to be considered for

the transformer

● The load of the transformer is less therefore foundations such as pile foundation and mat foundation are not recommended

● Geo form is used as an anticipate to fill the voids between reinforcing bars and a part of foundation as it increases compressive strength and absorbs the vibration of GSU

● For the water storage tank, Pile Foundation is Recommended

24Speaker: Haroon Rasheed

Turbine GSU Transformer &

Breaker

Water Storage Tank

Mat Foundation Shallow Foundation Pile Foundation

Page 25: Foundation Presentation .pptx

References●"Highland Tank - Steel Storage Tanks." Highland

Tank - Steel Storage Tanks. N.p., n.d. Web. 06 Dec. 2015.

●Das, Braja M. Principles of Foundation Engineering, SI, Stamford, CT: Cengage Learning, 2011, Print.

25Speaker: Haroon Rasheed