fm-200 (hfc-227ea) - toangiaphat.comtoangiaphat.com/files/news/1001/content/1434/fm200...
TRANSCRIPT
Model No.
Dimension
Agent
Cylinder Capacity
Protection Volumes
Control Circuit
Fire Alarm
Color
Cabinet Material
Cylinder Weight
Total Weight
MFP-050
50kg X 1unit
58m3
102kg
190kg
FM-200 PACKAGE
MFP-075
500W X 500D X 1900H
FM-200 GAS
75kg X 1unit
87m3
AC100V/220V
DC 24V
IC Control Circuit
SIREN & Sound Alarm
Pale yellow
SS400
143kg
230kg
0℃ ~ 40℃
MFP-100
100kg X 1unit
116m3
181kg
265kg
PowerMain Power
Back-up Power
>>> Details of FM-200 Package Composition
>>> FM-200 Package Spec.
[50kg]
Handle
Controlpanel
Speaker
DischargeHead
CopperTube
CopperTube
Agentmeasuningequipment
Cylindervalve
Cylinder
Tighteningband
EmergeneyBattery
PressureS/WFiexible
Tube
[75kg] [100kg]
FM-200 (HFC-227ea)
Recommended Temperature for use
http://www.naver.com/
■ Head Office Room 1009, ByeokSan Digital Valley 5, 60-73, Gasan-Dong, GuemCheon-Gu, Seoul, Korea (Zip Code : 153-801) Phone : 82-2-785-1301, Fax : 82-2-785-1313■ lst Factory 146BL-13LT, 715-12, Gojan-Dong, Namdong-Gu, Incheon, Korea (Zip Code : 405-821) Phone : 82-32-811-1301, Fax: 82-32-811-1305■ 2nd Factory 448-188, Hakun-Ri, Yangchon-Myeon, Gimpo-Si, Gyeonggi-Do, Korea (Zip Code : 415-843) Phone : 82-31-988-1306, Fax : 82-31-985-1808
The information contained herein is subject to change without prior notice to customers for manufacturer’s improvement of product quality.2013. 6. REV.2
>>> FM-200 Package Operation Sequence
FM-200 (HFC-227ea) Package System (Cabinet Type) is the high-technology firefighting extinguisher and can suppress the fire promptly by automatic and manual operation.
>>> Why FM-200 Clean Agent- The most reliable and effective extinguishant agent from HFC substitutes for Halon 1301
- Environment-friendly agent and Ozone Depletion Potential(ODP) is “zero” (0).
- Safe to humans and can be used for residential area
- Non-conductive agent and most suitable for the usage in the
expensive electronic equipment such as computer and communication device.
>>> Applicable Industries - data processing room, electricity equipment room, communication device room, electronic equipment
room, broadcasting equipment room, VTR room, central monitoring room, disaster prevention room,
boiler room, elevator machine room, garage, parking lot, printing house
- anechoic room, chemical laboratory, x-ray room, hospital, pharmacy, vault
- library, museum, art museum, antiquity gallery, jewelry depository
- The building or storage room that stores and handles quasi-dangerous article or special combustibles
Fire Occurrence
Fire detected by person
Fire Confirmation
Operation by manual
Detector No.2 actuation
Announce for escape
Closing of all the doors to the protected area
Closingof damper
“Discharge Lamp” is turned on
Fire Fighting
Announcefor escape
Discharge of FM-200
Fire Alarm
Detector No.1 actuation
Push the stop button in
case of false operation
FM-200 (HFC-227ea)
>>> FM-200 Agent Quantity Calculation Method
>>> FM-200 Package Operation Installation
W : Weight of extinguishing agent (kg)
V : Volume of the protected area (m3)
S : Linear Constant per extinguishing agent (K1 + K2t)
= 0.1269 + 0.0005t
C : Design concentration of extinguishing agent per volume (%)
t : Temperature of a protected area
▲Package Assembly ▲Smoke Detector ▲Heat Detector ▲Discharge Lamp ▲Manual Control Panel
※ Min. design concentration 8.45%, temperature 20℃ basis
※ Max. design concentration 10.5%, temperature 20℃ basis
8.45
10.5
0.674
0.857