fluke 1653 catalogue
DESCRIPTION
FlukeTRANSCRIPT
-
1651B 1652B
1653B
Fluke 1650B SeriesMultifunction Installation Testers
The installation testing solution for demanding environmentsThe Fluke 1650B Series testers, with new advanced features, are the perfect instal-lation testing tool for verifying the safety of electrical installations in domestic, com-mercial, and industrial applications. Ensure that fixed wiring is correctly installed and compliant with IEC 60364, HD 384 require-ments, and all relevant local standards. The 1650B Series is efficient to use by allowing
the user to measure loop impedance with-out tripping RCDs, eliminating the need to bypass them. Slim reach probes allow you to keep your eyes on the panel while probing hard to reach areas. With easy-to-operate controls, a large display with a wide viewing angle, padded neck strap, and a compact, ergonomic design, these testers are com-fortable enough to use for all day testing.
Extended Specifications
Compact,lightweightandcom-fortabletowear
Simpleoperationforfast,easytesting
Fasthighcurrentlooptest(highcurrentmode)
AdvancedlooptestingpreventsRCDsfromtripping
VariableRCDcurrentmodeforcustomizedsettings
Zeroadapterforeasytestleadcompensation
ThePASS/FAILindicatortakestheguessworkoutofRCDtesting
Insulationtestvoltages(1651:250V,500V,1000V),(1652:250V,500V,1000V),(1653:50V,100V,250V,500V,1000V)foravarietyofapplications
SelectvoltagemeasurementquicklyandeasilybetweenL-N,L-PE,andN-PE
Dualdisplaygivessimultaneousreadoutofmainsvoltageandfrequency
Autodischargeallowsfastandsafedischargeofelectricalenergyincapacitivecircuits
Addedsafetythroughlivecir-cuitdetection,tocheckandinhibittestifcircuitundertestislive
Wiringconnectioncheckindi-cationandlivecircuitdetectionforaddedsafety
Timesavingauto-nullfeaturesubtractsleadresistancefrommeasurements,andstoresitinmemoryevenafterpoweringdown
Highresolutionmeasurementsdownto0.01ohmforahighlevelofaccuracy
Userselectablesafetyvoltagelevelof50Vor25Vforvariedenvironments
Rotaryknoblabelingavailableinsixversions.English,French,German,Italian,Spanishandauser-friendlysymbolsversion
Performgroundtestswithaux-iliaryearthspikeseliminatingtheneedformultipleinstru-ments(1653only)
Downloadupto500storedresultswithIRportandadapterforprofessionalreporting(1653only)
Detachableleadsforeasyreplacement
EN-61557andVDE0413compliant
-
Measurement Function 1651B 1652B 1653B Voltage&Frequency Wiringpolaritychecker InsulationResistance Continuity&Resistance Loop&LineResistance ProspectiveEarthFaultCurrent(PEFC/IK)ProspectiveShort-Circuitcurrent(PSC/IK)
RCDswitchingtime RCDtrippinglevel ramptest ramptestRCDvariablecurrent AutomaticRCDtestsequence TestpulsecurrentsensitiveRCDs(TypeA) EarthResistance PhaseSequenceIndicator
Other Features Self-test IlluminatedDisplay
Memory, Interface Memory ComputerInterface Timeanddate(WhenusedwithFlukeViewsoftware) Software Optional
Included Accessories Hardcase Remotecontrolprobe[1] ZeroAdapter Note[1]Includedwithall165XBversionsexcept1651BUKVersion.
Specifications
Specification Characteristic Size 10cm(L)x25cm(W)x12.5cm(H)Weight(withbatteries) 1.5kgBatterysize,quantity TypeAA,6ea.Batterytype Alkalinesupplied.Usablewith1.2VNiCdorNiMHbatteries(not
supplied)Batterylife(typical) 200hoursidlingFuse T3.15A,500V,1.5kA6.3x32mm(PN2030852)OperatingTemperature -10Cto40CStorageTemperature -10Cto60Cindefinitely(to-40Cfor100hrs)RelativeHumidity Noncondensing
-
Electrical Measurement SpecificationsTheaccuracyspecificationisdefinedas(%reading+digitcounts)at23C5C,80%RH.Between-10Cand18Candbetween28Cand40C,accuracyspecificationsmaydegradeby0,1x(accuracyspecification)perC.Thefollowingtablescanbeusedforthedeterminationofmaximumorminimumdisplayvaluesconsideringmaximuminstrumentoperatinguncer-taintyperEN61557-1,5.2.4.
Insulation Resistance (RISO)
50 V 100 V 250 V 500 V 1000 V
Lim
it V
alue
Max
imum
D
ispl
ay V
alue
Lim
it V
alue
Max
imum
D
ispl
ay V
alue
Lim
it V
alue
Max
imum
D
ispl
ay V
alue
Lim
it V
alue
Max
imum
D
ispl
ay V
alue
Lim
it V
alue
Max
imum
D
ispl
ay V
alue
1 1.12 1 1.12 1 1.3 1 1.3 1 1.32 2.22 2 2.22 2 2.4 2 2.4 2 2.43 3.32 3 3.32 3 3.5 3 3.5 3 3.54 4.42 4 4.42 4 4.6 4 4.6 4 4.65 5.52 5 5.52 5 5.7 5 5.7 5 5.76 6.62 6 6.62 6 6.8 6 6.8 6 6.87 7.72 7 7.72 7 7.9 7 7.9 7 7.98 8.82 8 8.82 8 9.0 8 9.0 8 9.09 9.92 9 9.92 9 10.1 9 10.1 9 10.110 11.02 10 11.02 10 11.2 10 11.2 10 11.220 22.02 20 22.02 20 22.2 20 22.2 20 22.230 33.02 30 33.2 30 33.2 30 33.2 30 33.240 44.02 40 44.2 40 44.2 40 44.2 40 44.250 55.02 50 55.2 50 55.2 50 55.2 50 55.2
60 66.2 60 66.2 60 66.2 60 66.2
70 77.2 70 77.2 70 77.2 70 77.2
80 88.2 80 88.2 80 88.2 80 88.2
90 99.2 90 99.2 90 99.2 90 99.2
100 110.2 100 110.2 100 110.2 100 110.2
200 220.2 200 220.2 200 220.2
300 347 300 345400 462 400 460
500 577 500 575
600 690
700 805
800 920
900 1035
1000 1150
3FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
-
Continuity (RLO)
Loop Tests (ZI)
Limit Value Maximum Display Value 0.2 0.160.3 0.250.4 0.340.5 0.430.6 0.520.7 0.610.8 0.70.9 0.791 0.882 1.783 2.684 3.585 4.486 5.387 6.288 7.189 8.0810 8.9820 17.9830 26.8
Loop ZI Hi Current Loop ZI No Trip Loop ZI Loop RE
Limit Value Maximum Display Value
Limit Value Maximum Display Value
Limit Value Maximum Display Value
Limit Value Maximum Display Value
0.20 0.14 - - 3 2.53 3 2.720.30 0.23 - - 4 3.38 4 3.620.40 0.32 0.40 0.28 5 4.23 5 4.520.50 0.41 0.50 0.37 6 5.08 6 5.420.60 0.50 0.60 0.45 7 5.93 7 6.320.70 0.59 0.70 0.54 8 6.78 8 7.220.80 0.68 0.80 0.62 9 7.63 9 8.120.90 0.77 0.90 0.71 10 8.48 10 9.021.00 0.86 1.00 0.79 20 16.98 20 18.021.10 0.95 1.10 0.88 30 25.3 30 27.21.20 1.04 1.20 0.96 40 33.8 40 36.21.30 1.13 1.30 1.05 50 42.3 50 45.21.40 1.22 1.40 1.13 60 50.8 60 54.21.50 1.31 1.50 1.22 70 59.3 70 63.21.60 1.40 1.60 1.30 80 67.8 80 72.21.70 1.49 1.70 1.39 90 76.3 90 81.21.80 1.58 1.80 1.47 100 84.8 100 90.21.90 1.67 1.90 1.56 200 169.8 200 180.22.00 1.76 2.00 1.64 300 253 300 272- - - - 400 338 400 362- - - - 500 423 500 452- - - - 600 508 600 542- - - - 700 593 700 632- - - - 800 678 800 722- - - - 900 763 900 812- - - - 1000 848 1000 902
4FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
-
RCD/FI Tests (T, IN)
Earth Tests (RE)
RCD/FI Time RCD/FI Current
Limit Value Maximum Display
Value Limit Value
Maximum Display Value
20 18.1 0.5 0.4330 27.1 0.6 0.5240 36.1 0.7 0.6150 45.1 0.8 0.760 54.1 0.9 0.7970 63.1 1 0.8880 72.1 2 1.7890 81.1 3 2.68100 90.1 4 3.58200 180.1 5 4.48300 271 6 5.38400 361 7 6.28500 451 8 7.18600 541 9 8.08700 631 10 8.98800 721 20 17.98900 811 30 26.81000 901 40 35.82000 1801 50 44.8
60 53.8
70 62.8
80 71.8
90 80.8
100 89.8
200 179.8
300 268
400 358
500 448
Limit Value Maximum Display Value 10 8.820 17.830 26.840 35.850 44.860 53.870 62.880 71.890 80.8100 89.8200 179.8300 268.0400 358.0500 448.0600 538.0700 628.0800 718.0900 808.01000 898.02000 1798.0
5FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
-
Range Resolution Accuracy
50Hz - 60Hz Input Impedance
Overload Protection
500V 0.1V 0.8%+3 3.3M 660Vrms
AC Voltage Measurement (V)
Continuity Testing (RLO)
Insulation Resistance Measurement (RISO)
Range (Autoranging) Resolution Open Circuit Voltage Accuracy 20 0.01 >4V (1.5%+3digits)200 0.1 >4V (1.5%+3digits)2000 1 >4V (1.5%+3digits)
NoteThenumberofpossiblecontinuitytestswithafreshsetofbatteriesis3000.
Range RLO Test Current 7.5 210mA35 100mA240 20mA2000 2mA
Test Probe Zeroing Pressthe tozerothetestprobe.Cansubtractupto2ofleadresistance.Errormessagefor>2.
Live Circuit Detection Inhibitstestifterminalvoltage>10Vacdetectedpriortoinitiationoftest.
Test Voltages Accuracy of Test Voltage (at rated test
current) Model 1651B Model 1652B Model 1653B
250-500-1000V 250-500-1000V 50-100-250-500-1000V +10%,-0%
Test Voltage Insulation Resistance
Range Resolution Test Current Accuracy
50V 10kto50M 0.01M 1mA@50k (3%+3digits)
100V100kto20M 0.01M
1mA@100k (3%+3digits)20Mto100M 0.1M (3%+3digits)
250V10kto20M 0.01M
1mA@250k (1.5%+3digits)20Mto200M 0.1M (1.5%+3digits)
500V10kto20M 0.01M
1mA@500k(1.5%+3digits)
20Mto200M 0.1M (1.5%+3digits)200Mto500M 1M 10%
1000V100kto200M 0.1M
1mA@1M (1.5%+3digits)200Mto1000M 1M 10%
NoteThenumberofpossibleinsulationtestswithafreshsetofbatteriesis2000.
Auto Discharge Dischargetimeconstant30Vpriortoinitiationoftest.Maximum Capacitive Load: Operablewithupthe5Fload.
6FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
-
7FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
Loop and Line Impedance (ZI)No Trip and Hi Current Modes RCD/FI
Prospective Earth Fault Current Test (PSC/IK)
RCD Testing RCD Types Tested
Test Signals
Mains Input Voltage Range 100-500Vac(50/60Hz)Input Connection (soft key selection)
LoopImpedance:phasetoearthLineimpedance:phasetoneutral
Limit on Consecutive Tests Automaticshutdownwheninternalcomponentsaretoohot.ThereisalsoathermalshutdownforRCDtests.
Maximum Test Current @ 400 V 20Asinusoidalfor10msMaximum Test Current @ 230 V 12Asinusoidalfor10ms
Range Resolution Accuracy*
20 0.01 NoTripmode:(3%+6digits)HiCurrentmode:(2%4digits)
200 0.1 NoTripmode:(3%)HiCurrentmode:(2%)2000 1 6%**Notes* Validforresistanceofneutralcircuit200V.
Computation ProspectiveEarthFaultCurrent(PEFC/IK)orProspectiveShortCircuitCurrent(PSC/IK)determinedbydividingmeasuredmainsvoltagebymeasuredloop(L-PE)resistanceorline(L-N)resistance,respectively.
Range 0to10kAor0to50kA(SeePower-OnOptionsearlierinthismanual)Resolution and Units Resolution Units
IK1000A 0.1kA
Accuracy Determinedbyaccuracyofloopresistanceandmainsvoltagemeasurements.
RCD Type* Model 1651B Model 1652B Model 1653B AC1 G2 AC S3 A4 G A S
Notes1ACRespondstoAC2GGeneral,nodelay3STimedelay4ARespondstopulsedsignal*RCDtestinhibitedforV>265acRCDtestspermittedonlyifselectedcurrentxearthingresistanceis
-
8FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
Tripping Speed Test (T)
Maximum Trip TimeTheRCDsymbolswitchesonwhentestingtheRCDtriptimeifthetriptimemeetsthefollowingconditions:
RCD/FI-Tripping Current Measurement/Ramp Test (IN)Models1652Band1653B
Earth Resistance Test (RE) Model1653BOnly.Thisproductisintendedtobeusedtomeasureinstallationsinprocessplants,industrialinstallations,andresidentialapplications.
Current Settings[1] Multiplier Current Accuracy 10301003005001000mA-VAR x1/2 +0%,-10%oftestcurrent10301003005001000mA-VAR x1 +10%,-0%1030100mA x5 +10%,-0%Note[1]1000mAtypeAConly.700mAmaximumtypeAinVARmode.
Current Multiplier *RCD Type Measurement Range
Trip Time Accuracy Europe UKx1/2 G 310ms 2000ms (1%Reading+1ms)x1/2 S 510ms 2000ms (1%Reading+1ms)x1 G 310ms 310ms (1%Reading+1ms)x1 S 510ms 510ms (1%Reading+1ms)x5 G 50ms 50ms (1%Reading+1ms)x5 S 160ms 160ms (1%Reading+1ms)Notes*GGeneral,nodelay*STimedelay
RCD I N Trip time limitsAC,G x1 Lessthan300msAC,G-Stype x1 Between130msand500msA x1 Lessthan300msA-Stype x1 Between130msand500msAC,G x5 Lessthan40msAC,G-Stype x5 Between50msand150msA x5 Lessthan40msA-Stype x5 Between50msand150ms
Current Range Step Size Dwell Time Measurement
Accuracy Type G Type S*30%to110%ofRCDratedcurrent
10%ofIN 300ms/step 500ms/step 5%
Note30%to150%forTypeAIN>10mA,30%to210%forTypeAIN=10mASpecifiedtripcurrentrange:50%to100%forTypeAC,35%to140%forTypeA(>10mA),35%to200%forTypeA(10mA)
Range Resolution Accuracy 200 0.1 (2%+5digits)2000 1 (3.5%+10digits)
Range: RE + RPROBE Test Current 160 50mA1600 5mA16000 500A52000 150A
Frequency Output Voltage128Hz 25V
Live Circuit Detection Inhibitstestifterminalvoltage>10Vacisdetectedpriortostartoftest.
-
Phase Sequence IndicationModel1653BOnly
Mains Wiring TestIcons( )indicateifL-PEorL-Nterminalsarereversed.Instrumentoperationisinhib-itedandanerrorcodeisgeneratediftheinputvoltageisnotbetween100Vand500V.TheUKLoopandRCDtestsareinhibitediftheL-PEortheL-Nterminalsarereversed.
Operating Ranges and Uncertainties per EN 61557
Icon iconPhaseSequenceindicatorisactive.Display of Phase Sequence Displays1-2-3indigitaldisplayfieldforcorrect
sequence.Displays3-2-1forincorrectphase.Dashesinplaceofanumberindicateavaliddeterminationcouldnotbemade.
Mains Input Voltage Range (phase-to phase) 100to500V
Function Display Range EN 61557 Measurement
Range Operating Uncertainty
Nominal Values
VEN61557-1 0.0Vac500Vac 50Vac500Vac(2%+2dgt)UN=230/400Vacf=50/60Hz
RLOEN61557-4 0.00-2000 0.2-2000(10%+2dgt)4.0Vdc24VdcRLO2.00IN200mA
RISOEN61557-2 0.00M-1000M1M-200M(10%+2dgt)200M-1000M(15%+2dgt)
UN=50/100/250/500/1000VdcIN=1.0mA
ZIEN61557-3
ZI0.00-2000
2-1000(15%+2dgt)
UN=230/400Vacf=50/60HzIK=0A10.0kA
ZI(NoTrip)0.00-2000
0.4-2(15%+6dgt)
ZI(HiCurrent)0.00-2000
0.2-2(10%+4dgt)
RE0.00-2000
10-1000(10%+2dgt)
T,INEN61557-6
T0.0ms2000ms 25ms2000ms(10%+1dgt)T=10/30/100/300/500/1000mA
IN0.5mA550mA 0.5mA550mA(10%+1dgt)IN=10/30/100/300/500mA
REEN61557-5 0.0-2000 10-2000(10%+2dgt) f=128Hz
PhaseEN61557-7 1:2:3
9FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
-
Influence Quantity
Volt
s
RLo
EN
615
57-4
RIS
O
EN
615
57-2
Z I
EN
615
57-3
TE
N 6
1557
-6
IN
EN
615
57-6
RE
EN
615
57-5
E1-Position 0.00% 0.00% 0.00% 0.00% 0.00% 0.00% 0.00%E2-SupplyVoltage 0.50% 3.00% 3.00% 3.00% 3.00% 2.75% 2.25%E3-Temperature 0.50% 3.00% 3.00% 3.00% 3.00% 2.25% 2.75%E4-SeriesInterferencesVoltage - - - - - - 1.50%E5-Resistanceoftheprobesandauxiliaryearthelectrodes - - - - - - 4.00%
E6.2-Systemphaseangle - - - 1.00% - - -E7-Systemfrequency 0.50% - - 2.50% - - 0.00%E8-Systemvoltage - - - 2.50% 2.50% 2.50% 0.00%E9-Harmonics - - - 2.00% - - -E10-D.C.Quantity - - - 2.50% - - -
Fluke CorporationPOBox9090,Everett,WA98206U.S.A.
Fluke Europe B.V.POBox1186,5602BDEindhoven,TheNetherlands
For more information call:IntheU.S.A.(800)443-5853orFax(425)446-5116InEurope/M-East/Africa+31(0)402675200orFax+31(0)402675222InCanada(800)-36-FLUKEorFax(905)890-6866Fromothercountries+1(425)446-5500orFax+1(425)446-5116Webaccess:http://www.fluke.com
2008FlukeCorporation.Specificationssubjecttochangewithoutnotice.PrintedinU.S.A.11/20083367586D-EN-NRevAPub_ID:11518-eng
Modification of this document is not permitted without written permission from Fluke Corporation.
Fluke. Keeping your world up and running.
10FlukeCorporationFluke1650BSeriesMultifunctionInstallationTesters
Ordering information
1653B MultifunctionInstallationTester
1652B MultifunctionInstallationTester
1651B MultifunctionInstallationTester
Optional accessoriesMTC1363MainsTestCordMTC77MainsTestCordES165XEarthSpikeTestKit(1653only)
FVF-SC2FlukeViewSoftware(1653only)
Included with 1650B:TP165XRemoteControlProbe(1652Band1653Bonly)TL165/UKFusedtestleadsetTD07FPARTPtestcertificates(1651Bonly)C1600HardCarryingCaseMainstestcordZeroadapterPaddedcarryingstrapQuickreferenceguide6AAbatteries
Operating Uncertainties per EN 61557 TheOperatingUncertaintyshowsthemaximumpossibleuncertaintywhenallinfluencefactorsE1-E10arecounted.
Volt
s
RLo
EN
615
57-4
RIS
O
EN
615
57-2
Z I
EN
615
57-3
TE
N 6
1557
-6
IN
EN
615
57-6
RE
EN
615
57-5
IntrinsicUncertaintyA 0.80% 1.50% 10.00% 6.00% 1.00% 5.00% 3.50%